SCALE: NTS
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
-
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
DescriptionRev. Date By App’dChk’d
$DATE$ $TIME$ $FILE$
MELVYN THONG
N.T.S. JULI JULY 2007
L/ROAD/MES/SD/1001
LROADMES-SD1001-.dgn
NURLY
STANDARD INSTALLATION DETAILS
MALVIN HO
T
TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX
(POB/LINKWAY/TAXI STAND/BUS SHELTER)
TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX (POB / LINKWAY / TAXI STAND / BUS SHELTER)
NOTES:
1. CONTRACTOR IS RESPONSIBLE TO REPLACE ITEM * TO
A 32A RATING AND PROVIDE THE LINKWAY VICINITY
AS SHOWN IN SLD (B)
SCALE: NTS
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
-
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
DescriptionRev. Date By App’dChk’d
$DATE$ $TIME$ $FILE$
MELVYN THONG
N.T.S. JULI JULY 2007
L/ROAD/MES/SD/1002
LROADMES-SD1002-.dgn
NURLY
STANDARD INSTALLATION DETAILS
MALVIN HO
TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX
(BUS SHELTER/LINKWAY)
NOTES:
1. CONTRACTOR IS RESPONSIBLE TO REPLACE ITEM * TO
A 32A RATING AND PROVIDE THE LINKWAY VICINITY
AS SHOWN IN SLD(B)
TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX (BUS SHELTER / LINKWAY)
SCALE: NTS
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
-
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
DescriptionRev. Date By App’dChk’d
$DATE$ $TIME$ $FILE$
MELVYN THONG
N.T.S. JULI JULY 2007
L/ROAD/MES/SD/1003
LROADMES-SD1003-.dgn
NURLY
STANDARD INSTALLATION DETAILS
MALVIN HOTYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX (BUS SHELTER)
TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX
(BUS SHELTER)
NOTES:
1. CONTRACTOR IS RESPONSIBLE TO REPLACE ITEM * TO
A 32A RATING AND PROVIDE THE LINKWAY VICINITY
AS SHOWN IN SLD(B).
SCALE: NTS
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
-
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
DescriptionRev. Date By App’dChk’d
$DATE$ $TIME$ $FILE$
MELVYN THONG
N.T.S. JULI JULY 2007
L/ROAD/MES/SD/1004
LROADMES-SD1004-.dgn
NURLY
STANDARD INSTALLATION DETAILS
MALVIN HO
T
TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX
(DBO BUS SHELTER/POB/LINKWAY/TAXI STAND)
NOTES:
TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX (DBO BUS SHELTER / POB / LINKWAY / TAXI STAND)
1. CONTRACTOR IS RESPONSIBLE TO REPLACE ITEM * TO
A 32A RATING AND PROVIDE THE LINKWAY VICINITY
AS SHOWN IN SLD(B).
SCALE: NTS
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
-
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
DescriptionRev. Date By App’dChk’d
$DATE$ $TIME$ $FILE$
MELVYN THONG
N.T.S. JULI JULY 2007
L/ROAD/MES/SD/1005
LROADMES-SD1005-.dgn
NURLY
STANDARD INSTALLATION DETAILS
MALVIN HO
TYPICAL DETAIL OF POB OG-BOX
TYPICAL DETAIL OF OG-BOX
SIDE VIEW
NAME PLATE
LAND TRANSPORTAUTHORITYLOGO
NEOPRENE SEAL
UV RESISTANTWINDOW C/W
CABLE ENTRYOPENING FOR
PLINTH C/W
WEATHERPROOF TO IP 54
EXTERNAL VIEW
ABLOY MASTER KEY
FOR POWERGRID
FRONT INTERNAL VIEW
REMOVEABLE
PLATE
ABLOY MASTER KEYAS PER LTA’s
REQUIREMENTS
2 NOS. POWER GRID
KWH METER
LEAD IN C/W 90^ LONG BEND PIPES
FOR POWER GRID INCOMING CABLING
2 NOS Ø100mm HEAVY DUTY uPVC
2 NOS Ø50mm
HEAVY DUTY
UPVC PIPE FOR
POB ELECTRICAL
DISTRIBUTION
2 NOS Ø50mm HEAVY DUTY
uPVC PIPE FOR FUTURE
BUS SHELTER ELECTRICAL
DISTRIBUTION
SINGAPORE 498825SPANNERS BUILDING
SPANNERS INTERNATIONAL PTE LTD6 CHANGI NORTH STREET 1
Certified Company9002ISO
CONTRRACT NO:SERIAL NO:
YEAR MANUFACTURE:
LAND TRANSPORT
LOGOAUTHORITY
300
SCALE: NTS
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
-
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
DescriptionRev. Date By App’dChk’d
$DATE$ $TIME$ $FILE$
MELVYN THONG
N.T.S. JULI JULY 2007
L/ROAD/MES/SD/1006
LROADMES-SD1006-.dgn
NURLY
STANDARD INSTALLATION DETAILS
MALVIN HO
TYPICAL DETAIL OF POB OG-BOX
TYPICAL DETAIL OF OG-BOX
REMOVABLE PLATE
3273-A
ABLOY
FIX PLATE
70 70
REMOVABLE PLATE
70
27.5
82.5
REMOVABLE PLATE
27.5
82.5
1Ø KWH
METER
POWER
GRID
T’wood= 230
70
Std= 235
T’wood= 230
Std= 235
138138
T’wood= 230 T’wood= 230
560
1Ø KWH
METER
POWER
GRID
BI Supply
and Installed
By PG
3273-A
ABLOY
3273-A
ABLOY
EXTERNAL FRONT DOOR
PARTITION
FIX PLATE
Front
Back
EXTERNAL BACK DOOR
GLASS
EXTERNAL VIEW INTERNAL FRONT VIEW
PLAN VIEW
EXTERNAL BACK VIEW
BUS SHELTER
SIDE VIEWINTERNAL SIDE VIEW
SUPPORT FOR BREAKER
PARTITION
SUPPORTFOR BREAKER
EXTERNALFRONTDOOR
POB/LINKWAY
PARTITION
EXTERNAL FRONT DOOR
Ø100mm HEAVY DUTY UPVC PIPEFOR POB/LINKWAY ELECTRICAL DISTRIBUTION
GLASS GLASS
2 NOS Ø100mm HEAVY DUTY UPVCLEAD IN C/W 90^ LONG BEND PIPESFOR POWER GRID INCOMING CABLING
2 NOS Ø100mm HEAVY DUTY UPVCLEAD IN C/W 90^ LONG BEND PIPESFOR POWER GRID INCOMING CABLING
Ø100mm HEAVY DUTY UPVC PIPEFOR POB/LINKWAY ELECTRICAL DISTRIBUTION
Ø100mm HEAVY DUTY UPVC PIPEFOR BUS SHELTER ELECTRICAL DISTRIBUTION
PLINTH C/W OPENINGFOR CABLE ENTRY
Overall Length = min 1120mm
Overall Length = min 1120mm
420
Depth = min 450mm Depth = min 450mm
Ø50mm HEAVY DUTY UPVC PIPEFOR BUS SHELTER ADVERTISING PANEL
Ø100mm HEAVY DUTY UPVC PIPE FOR BUS SHELTER ELECTRICAL DISTRIBUTION
Ø50mm HEAVY DUTY UPVC PIPE FOR BUS SHELTER ADVERTISING PANEL
SCALE: NTS
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
-
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
DescriptionRev. Date By App’dChk’d
$DATE$ $TIME$ $FILE$
MELVYN THONG
N.T.S. JULI JULY 2007
L/ROAD/MES/SD/1007
LROADMES-SD1007-.dgn
NURLY
STANDARD INSTALLATION DETAILS
MALVIN HO
TYPICAL LIGHTING LAYOUT PLAN AND
LIGHTNING PROTECTION SYSTEM
FOR BUS SHELTER (WITH OR WITHOUT RAILING)
2 NOS. Ø50mm HEAVY DUTY
UPVC PIPE C/W PULL WIRE
2 NOS. Ø100mm HEAVY DUTY UPVC
HEAD-IN 90^ LONG BEND PIPES FOR
POWERGRID’S INCOMING CABLE
1 NO. Ø50mm HEAVY DUTY
UPVC PIPE C/W PULL WIRES
FROM 0G-BOX TO ADVERTISING PANEL
PVC CABLE IN
FLEXIBLE CONDUIT
PROPOSED 1 x 18W
(IP 65) LIGHT FITTING
TYPICAL LIGHTNING PROTECTION SYSTEM LAYOUT PLAN
TYPICAL LIGHTING LAYOUT PLANSCALE: NTS
EARTH PIT
(TOTAL RESISTANCE < 10ohm)
EARTH PIT
(TOTAL RESISTANCE < 10ohm)
NEW
OG BOX
WITHOUT RAILING
A
A
ROOF EAVES ABOVE
R O A D
CONC. SLAB TO ENGR’S DTLS COMPLETE WITH 20mm THK
GRANOLITHIC FINISHES TO SO’S APPROVAL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF
PANEL COMPLETE WITH MIN. 1 mm THK
TOP PANEL TO SO’S APPROVAL
1 2 3
1 2 3
7500
750 3000 3000 750
1400 100 1400
M.S. RHS POST UNDERNEATH TO ENGR’S DTL
ALUM. SEAT TO DTL
200 WIDE YELLOW LINE IN HOT APPLIED
THERMOPLASTIC ROAD MARKING MATERIALS
3
3
BUS STOP ADDRESS & NUMBER SIGN
PLATE TO FACE ONCOMING TRAFFIC IN
ACCORDANCE TO LTA STD DRAWING NO.
LTA/ARCH/CF/97/8/13 LATEST REVISION
LINE OF ROAD KERB OR ROAD RESERVE LINE
NOTICE BOARD WITH ALUM. FRAME C/W
10mm THK. TEMPERED GLASS
50 X 50 X 3 THK ALUM. ANGLE PLATE FOR
BUS STOP ADDRESS & NUMBER SIGN PLATE
MS ANGLE ROOF FASCIA TO ENGR’S DTL
ROOF CAPPING @ 1500mm C/C TO
MFR’S DTL
1 NO. ELECT. PIPE FOR ADVERTISEMENT
PANEL (AP) TO BE LOCATED AT THE
DOWNSTREAM EDGE OF BUS SHELTER
7500
750 3000 3000 750
1500 1500 1500 1500
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DTL
Ø600 REFUSE BIN
SCALE: NTS
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
-
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
DescriptionRev. Date By App’dChk’d
$DATE$ $TIME$ $FILE$
MELVYN THONG
N.T.S. JULI JULY 2007
L/ROAD/MES/SD/1008
LROADMES-SD1008-.dgn
NURLY
STANDARD INSTALLATION DETAILS
MALVIN HO
PROPOSED 1 x 18W (IP65) LIGHT FITTING
2 NOS Ø50mm HEAVY DUTY UPVC PIPES
2 NOS Ø100mm HEAVY DUTY UPVC
PIPES LEAD IN 90^ LONG BEND PIPES
FOR POWERGRID INCOMING CABLING
NEW OG BOX (IP55)
LOCATION SHALL BE SUBJECTED TO
SITE CONDITIONS AND POWERGRID’S APPROVAL
PROPOSED 1 x 18W (IP65) LIGHT FITTING
2 NOS Ø50mm HEAVY DUTY UPVC PIPES
BONDING TO ALUMINIUM SEAT
2 NOS Ø100mm HEAVY DUTY UPVC
PIPES LEAD IN 90^ LONG BEND PIPES
FOR POWERGRID INCOMING CABLING
NEW OG BOX (IP55)
LOCATION SHALL BE SUBJECTED TO
SITE CONDITIONS AND POWERGRID’S APPROVAL
6mÀ PVC EARTH BONDING CABLE IN
Ø25mm HEAVY DUTY UPVC PIPE
PVC CABLE IN PVC
FLEXIBLE CONDUIT
PVC CABLE IN PVC
FLEXIBLE CONDUIT
6mÀ PVC EARTH BONDING CABLE IN
Ø25mm HEAVY DUTY UPVC PIPE
LIGHT FITTING TO M&E SPECS & SHALL
NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING
BRACKET FOR LIGHT FITTING
CONDUIT
ENCASED IN
CONCRETE
CONDUIT
ENCASED IN
CONCRETE
LIGHT FITTING TO M&E SPECS & SHALL
NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING
BRACKET FOR LIGHT FITTING
TYPICAL FRONT ELEVATION OF BUS SHELTER (WITH RAILING)
SCALE: NTS
TYPICAL FRONT ELEVATION OF BUS SHELTER (WITHOUT RAILING) TYPICAL SECTION OF BUS SHELTER (WITHOUT RAILING)SCALE: NTS
SCALE: NTS
TYPICAL SECTION OF BUS SHELTER (WITH RAILING)
CABLE ENTRY
ACCESS PANEL
(REFER TO TYPICAL
SUPPORT POST DETAIL)
CABLE ENTRY
ACCESS PANEL
(REFER TO TYPICAL
SUPPORT POST DETAIL)
TYPICAL ELECTRICAL INSTALLATION DETAILS
FOR BUS SHELTER (WITH AND WITHOUT RAILING)
ELEVATION 1
FFL
1 2 3
ALUM. SEAT TO DTL
CONC. SLAB TO ENGR’S DTLS COMPLETE WITH
20mm THK GRANOLITHIC FINISHES TO SO’S APPROVAL
BUS STOP ADDRESS & NUMBER SIGN
PLATE TO FACE ONCOMING TRAFFIC IN
ACCORDANCE TO LTA STD DRAWING NO.
LTA/ARCH/CF/97/8/13 LATEST REVISION
(TO BE BOLTED TO ALUM. ANGLE PLATE)
NOTICE BOARD WITH ALUM. FRAME
C/W 10mm THK. TEMPERED GLASS
MS ANGLE ROOF FASCIA TO ENGR’S DTL
M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C
TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
7500
750 3000 3000 750
1000 1000
1500 1500 1500 1500
M.S. RHS TO ENGR’S DETAIL
LIGHT FITTING TO M&E SPECS
REFUSE BIN TO BE FIXED IN POSITION
FFL
SECTION A-A
A
3^ FALL
FOOTING TO ENGR’ S DETAIL
M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C
TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
ROAD
300
ALUM SEAT TO DETAIL
ELECTRICAL CABLE IN PVC
FLEXIBLE PIPE IN SUPPORT POST
(REFUSE BIN NOT SHOWN FOR CLARITY)
Scale 1 :20
REF. DWG. NO. L/STLBS/AR/STD/0002
MIN. 10mm THK. ALUM. HONEYCOMB ROOF
PANEL COMPLETE WITH MIN. 1 mm THK
TOP PANEL TO SO’S APPROVAL
CONC. SLAB TO ENGR’S DTL COMPLETE WITH 20mm THK
GRANOLITHIC FINISHES TO SO’S APPROVAL
3000 MIN. 600
300 2700
G.I. PIPE ALONG BACK OF M.S. FASCIA FOR
ELECT. CABLES TO M&E DWG. & SPEC.
LIGHT FITTING TO M&E SPECS & SHALL
NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING
BRACKET FOR LIGHT FITTING
CATCH BASIN AND UPVC PIPE IN
ACCORDANCE WITH THE CURRENT
LTA STANDARD DETAILS OF ROAD
ELEMENTS
ELEVATION 1
S/S RAILING TO BE PROVIDED WHERE THERE
IS SUDDEN GREAT DIFFERENCE IN LEVEL
FFL
1 2 3
ALUM. SEAT TO DTL
BUS STOP ADDRESS & NUMBER SIGN
PLATE TO FACE ONCOMING TRAFFIC IN
ACCORDANCE TO LTA STD DRAWING NO.
LTA/ARCH/CF/97/8/13 LATEST REVISION
(TO BE BOLTED TO ALUM. ANGLE PLATE)
NOTICE BOARD WITH ALUM. FRAME
C/W 10mm THK. TEMPERED GLASS
MS ANGLE ROOF FASCIA TO ENGR’S DTL
M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C
TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
7500
750 3000 3000 750
1000 1000
1500 1500 1500 1500
M.S. RHS TO ENGR’S DETAIL
LIGHT FITTING TO M&E SPECS
REFUSE BIN TO BE FIXED IN POSITION
FFL
SECTION A-A
A
3^ FALL
FOOTING TO ENGR’ S DETAIL
M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C
TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
300
ALUM SEAT TO DETAIL
ELECTRICAL CABLE IN PVC
FLEXIBLE PIPE IN SUPPORT POST
(REFUSE BIN NOT SHOWN FOR CLARITY)
Scale 1 :20
REF. DWG. NO. L/STLBS/AR/STD/0004
MIN. 10mm THK. ALUM. HONEYCOMB ROOF
PANEL COMPLETE WITH MIN. 1 mm THK
TOP PANEL TO SO’S APPROVAL
CONC. SLAB TO ENGR’S DTL COMPLETE WITH 20mm THK
GRANOLITHIC FINISHES TO SO’S APPROVAL
3000 MIN. 600
300 2700
G.I. PIPE ALONG BACK OF M.S. FASCIA FOR
ELECT. CABLES TO M&E DWG. & SPEC.
LIGHT FITTING TO M&E SPECS & SHALL
NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING
BRACKET FOR LIGHT FITTING
ROAD
CATCH BASIN AND UPVC PIPE IN
ACCORDANCE WITH THE CURRENT
LTA STANDARD DETAILS OF ROAD
ELEMENTS
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
-
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
DescriptionRev. Date By App’dChk’d
$DATE$ $TIME$ $FILE$
MELVYN THONG
N.T.S. JULI JULY 2007
L/ROAD/MES/SD/1009
LROADMES-SD1009-.dgn
NURLY
STANDARD INSTALLATION DETAILS
MALVIN HO
TEAKWOOD FOR MOUNTING
CABLE GLAND FOR ARMOURED CABLE
C1 WELDED ALL-ROUND TO
300x300x20 THK MS PLATE
10mm THK NON SHRINK GROUT
TERMINAL BLOCK CONNECTOR
MOUNTED ON TEAKWOOD BLOCK
25mm x 3mm COPPER TAPE
FLAT BAR TO SUPPORT TEAKWOOD BLOCK
ARMOURED CABLE IN UPVC PIPE
PVC CABLE + 2.5mÀ PVC EARTH CABLE
IN FLEXIBLE CONDUIT
FROM OG BOX TO FIRST LIGHTING POINT
SECTION K-K
SECTION B-B
SECTION C-C
DETAIL 2
DETAIL 1
LIGHT FITTING TO M&E SPECS & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
ELECTRICAL CABLE CONCEALED IN PVC
FLEXIBLE CONDUIT TO M&E DWG. & SPEC.
LIGHT FITTING TO M&E SPECS & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
EARTH PIT
(TOTAL EARTH
RESISTANCE
<10 ohms)
TYPICAL SUPPORT POST DETAIL
TYPICAL CABLE ENTRY DETAIL FOR BUS SHELTER
SEE DETAIL X
SECTION Y-Y
Y-
Y-
25mm x 3mm COPPER TAPE
ALUMINIUM OR
STEEL SUPPORT POST
M8 ALUMINIUM COPPER BOLT
TO STEEL SUPPORT POST
DETAIL X´
A
Scale 1:5
DETAIL 1
GASKET
SECTION K-KScale 1:5
S/S SCREW
´
Scale 1:5
3^ FALL
S/S SCREW
ISOLATOR / BONDING TAPE BETWEEN
ALUM. ROOF FRAME & M.S. MEMBER
ISOLATOR / BONDING TAPE BETWEEN
ALUM. ROOF FRAME & M.S. MEMBER
1500
DETAIL 2
ISOLATOR / BONDING TAPE BETWEEN
ALUM. ROOF FRAME & M.S. MEMBER
750
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
M.S. ANGLE ROOF FASCIA
TO ENGR’S DETAIL
FFL
Scale 1:5
B-
B-
SECTION B-BScale 1:5
´
´
OPENING FOR INCOMING CABLES COVERED
BY POST CAPPING
(TO BE PROVIDED AT 1ST & LAST POST ONLY)
MS BASE PLATE TO ENGR’S DETAIL
CONC. SLAB TO ENGR’S DTL COMPLETE WITH
20mm THK GRANOLITHIC FINISHES TO SO’S APPROVAL
TYPICAL SUPPORT POST DETAIL
RC FOOTING TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
Ø50 mm PVC FLEXIBLE CONDUIT
FOR INCOMING CABLES TO M&E DETAIL
K-
CENTRE LINE OF LIGHT FITTING
´
BUS STOP ADDRESS & NUMBER SIGN
PLATE TO FACE ONCOMING TRAFFIC IN
ACCORDANCE TO LTA STD DRAWING NO.
LTA/ARCH/CF/97/8/13 LATEST REVISION
(TO BE BOLTED TO ALUM. ANGLE PLATE)
MS RHS TO ENGR’S DETAIL
3000
300 2700
1500
MIN. 10mm THK. ALUM. HONEYCOMB ROOF
PANEL COMPLETE WITH MIN. 1mm THK.
TOP PANEL TO SO’S APPROVAL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL COMPLETE
WITH MIN. 1mm THK.TOP PANEL TO SO’S APPROVAL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
TO SO’S APPROVAL
K-
10
100 100
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
3%%d
40
40
G.I. PIPE ALONG BACK OF M.S. FASCIA
FOR ELECT. CABLES TO M&E DWG. & SPEC.
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C TO ENGR’S DETAIL
200
3%%d
ALUM. ROOF CAPPING FOR ROOF PANEL TO MFR’S DETAIL
C-
C-
SECTION C-CScale 1:5
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
TO SO’S APPROVAL
ALUM. ROOF CAPPING FOR ROOF PANEL
TO MFR’S DETAIL
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
G.I. PIPE ALONG BACK OF M.S. FASCIA
FOR ELECT. CABLES TO M&E DWG. & SPEC.
ELECTRICAL CABLE CONCEALED IN PVC
FLEXIBLE CONDUIT TO M&E DWG. & SPEC.
OPENING FOR INCOMING CABLES COVERED
BY POST CAPPING
(TO BE PROVIDED AT 1ST & LAST POST ONLY)
ELECTRICAL CABLE CONCEALED IN PVC
FLEXIBLE CONDUIT IN SUPPORT POST
LIGHT FITTING MOUNTING BRACKET TO CONTRACTOR PROPOSAL
LIGHT FITTING TO M&E SPECS & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
LIGHT FITTING TO M&E SPECS & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
-
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
DescriptionRev. Date By App’dChk’d
$DATE$ $TIME$ $FILE$
MELVYN THONG
N.T.S. JULI JULY 2007
L/ROAD/MES/SD/1010
LROADMES-SD1010-.dgn
NURLY
STANDARD INSTALLATION DETAILS
MALVIN HO
EARTH ROD
25mm x 3mm ALUMINIUM CONDUCTOR TAPE
ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE
25mm x 3mm COPPER CONDUCTOR TAPE
ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE
EARTH ROD
25mm x 3mm ALUMINIUM CONDUCTOR TAPE
ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE
25mm x 3mm COPPER CONDUCTOR TAPE
ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE
PIPE SLEEVE PIPE SLEEVE
PURPOSE MADE BOND
CONTRACTOR TO ENSURE THAT BONDED
IN ACCORDANCE TO CP33 REQUIREMENTS
PURPOSE MADE BOND
CONTRACTOR TO ENSURE THAT BONDED
IN ACCORDANCE TO CP33 REQUIREMENTS
EARTH PIT
(TOTAL EARTH RESISTANCE 10ohms)
EARTH PIT
(TOTAL EARTH RESISTANCE 10ohms)
TYPICAL LIGHTNING PROTECTION SYSTEM
FOR COVERED PEDESTRIAN OVERHEAD BRIDGE
FOR COVERED POB (EXPRESSWAY)
FOR COVERED POB (NON-EXPRESSWAY)
UPVC PIPE SEALED
WITH APPROVED
SEALANT TO PREVENT
WATER INGRESS
BI-METALLIC BOND/CLAMP AND
ALUMINIUM CONDUCTOR TAPE
BOLTED ON BEARING PLATE.
CONCRETE SURFACE PAINTED OVER
TO PREVENT ALUMINIUM TAPE
TO HAVE DIRECT CONTACT
WITH CONCRETE SURFACE
DETAIL X
BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE
BOLTED ON BEARING PLATE CONCRETE SURFACE
PAINTED OVER TO PREVENT ALUMINIUM TAPE
TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE
(SEE DETAIL X)
BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE
BOLTED ON BEARING PLATE CONCRETE SURFACE
PAINTED OVER TO PREVENT ALUMINIUM TAPE
TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE
(SEE DETAIL X)
ENCASED HEAVY
DUTY UPVC PIPES
STAINLESS STEEL
COVER PLATE
ENCASED HEAVY
DUTY UPVC PIPES
R.C. COLUMN25mm x 3mm
COPPER TAPE
BI-METALLIC
CONNECTOR
PROTECTION
TEST
BOX
LIGHTNING
NUT INSERTM5 COUNTERSUNK BOLT
Y-
Y-
STAINLESS STEEL
COVER PLATE
SECTION Y-Y
25mm x 3mm
ALUMINIUM TAPE
BI-METALLIC
CONNECTOR
25mm x 3mm
COPPER TAPE
25mm x 3mm
ALUMINIUM TAPE
TYPICAL LIGHTNING PROTECTIONTEST BOX AT POB
ELEVATION VIEW(WITH COVER)
ELEVATION VIEW(WITHOUT COVER)
150mm x 150mm TEST LINK BOX
AT 1500mm HEIGHT FROM
GROUND LEVEL (SURFACE MOUNT)
IN ACCORDANCE TO CP33 REQUIREMENTS
(SEE TYPICAL LIGHTNING PROTECTION
TEST BOX AT POB)
150mm x 150mm TEST LINK BOX
AT 1500mm HEIGHT FROM
GROUND LEVEL (SURFACE MOUNT)
IN ACCORDANCE TO CP33 REQUIREMENTS
(SEE TYPICAL LIGHTNING PROTECTION
TEST BOX AT POB)
10x10mm CHAMFER
TO ROADSIDE DRAIN
12%%d
PILE CAP TO ENGR’S DETAIL
R.C. GRATING
2800
3702060370
1800
MIN. 40 MIN. 40
EQ EQ
FALL
2200 700
75
675
625
´ OF POB DECK
AND ROOF
TYPICAL CROSS BEAM
TO ENGR’S DETAIL
RC COLUMN TO ENGR’S DETAIL WITH
20mm THK PRECASTED GRANOLITHIC
CHIPPING FINISHED TO S.O’S APPROVAL
10x10mm CHAMFER
TO ROADSIDE DRAIN
12%%d
PILE CAP TO ENGR’S DETAIL
2800
3702060370
1800
MIN. 40 MIN. 40
EQ EQ
FALL
2200 700
75
675
625
TYPICAL CROSS BEAM
TO ENGR’S DETAIL
RC COLUMN TO ENGR’S DETAIL WITH
20mm THK PRECASTED GRANOLITHIC
CHIPPING FINISHED TO S.O’S APPROVAL
Ø45mm S.S. RAILING Ø45mm S.S. RAILING
CHS HOT-DIPPED GALVANISED M.S. POST
TO ENGR’S DETAIL COMPLETE WITH SPRAY
COATING FINISH TO SO’S APPROVAL
CHS HOT-DIPPED GALVANISED M.S. MEMBER
TO ENGR’S DETAIL COMPLETE WITH SPRAY
COATING FINISH TO SO’S APPROVAL
´ OF POB DECK
AND ROOF
CHS HOT-DIPPED GALVANISED M.S. POST
TO ENGR’S DETAIL COMPLETE WITH SPRAY
COATING FINISH TO SO’S APPROVAL
CHS HOT-DIPPED GALVANISED M.S. MEMBER
TO ENGR’S DETAIL COMPLETE WITH SPRAY
COATING FINISH TO SO’S APPROVAL
FALL FALL
20mm THK PRECASTED GRANOLITHIC
CHIPPING FINISHED TO S.O’S APPROVAL
PLANTING TROUGH WITH WATERPROOFING
MEMBRANE TO SO’S APPROVAL
PLANTING TROUGH WITH WATERPROOFING
MEMBRANE TO SO’S APPROVAL
20mm THK PRECASTED GRANOLITHIC
CHIPPING FINISHED TO S.O’S APPROVAL
R.C. GRATING
Ø50mm PVC PIPE FOR LIGHTING CIRCUITS
TO OG BOX TO M&E SPECIFICATIONS
FFL OF
POB DECK
Ø15mm S.S. ROD AT NOT MORE THAN 100mm CLEAR Ø15mm S.S. ROD AT NOT MORE THAN 100mm CLEAR
FFL OF
POB DECK
FOOTPATH LEVEL
ROAD LEVEL
FOOTPATH LEVEL
ROAD LEVEL
MIN. 10mm THK. ALUM. HONEY COMB ROOF PANEL COMPLETE
WITH MIN. 1mm THK. TOP PANEL TO SO’S APPROVAL
MIN. 10mm THK. ALUM. HONEY COMB ROOF PANEL COMPLETE
WITH MIN. 1mm THK. TOP PANEL TO SO’S APPROVAL
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
-
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
DescriptionRev. Date By App’dChk’d
$DATE$ $TIME$ $FILE$
MELVYN THONG
N.T.S. JULI JULY 2007
L/ROAD/MES/SD/1011
LROADMES-SD1011-.dgn
NURLY
STANDARD INSTALLATION DETAILS
MALVIN HO
EARTH ROD
25mm x 3mm ALUMINIUM CONDUCTOR TAPE
ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE
25mm x 3mm COPPER CONDUCTOR TAPE
ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE
EARTH ROD
25mm x 3mm ALUMINIUM CONDUCTOR TAPE
ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE
25mm x 3mm COPPER CONDUCTOR TAPE
ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE
PIPE SLEEVE
EARTH PIT
(TOTAL EARTH RESISTANCE 10ohms)
EARTH PIT
(TOTAL EARTH RESISTANCE 10ohms)
TYPICAL LIGHTNING PROTECTION SYSTEM
FOR UNCOVERED PEDESTRIAN OVERHEAD BRIDGE
FOR UNCOVERED POB (EXPRESSWAY)
FOR UNCOVERED POB (NON-EXPRESSWAY)
25mm x 3mm ALUMINIUM CONDUCTOR TAPE
PIPE SLEEVE
25mm x 3mm ALUMINIUM CONDUCTOR TAPEUPVC PIPE SEALED
WITH APPROVED
SEALANT TO PREVENT
WATER INGRESS
BI-METALLIC BOND/CLAMP AND
ALUMINIUM CONDUCTOR TAPE
BOLTED ON BEARING PLATE.
CONCRETE SURFACE PAINTED OVER
TO PREVENT ALUMINIUM TAPE
TO HAVE DIRECT CONTACT
WITH CONCRETE SURFACE
DETAIL X
BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE
BOLTED ON BEARING PLATE CONCRETE SURFACE
PAINTED OVER TO PREVENT ALUMINIUM TAPE
TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE
(SEE DETAIL X)
BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE
BOLTED ON BEARING PLATE CONCRETE SURFACE
PAINTED OVER TO PREVENT ALUMINIUM TAPE
TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE
(SEE DETAIL X)
ENCASED HEAVY
DUTY UPVC PIPES
STAINLESS STEEL
COVER PLATE
ENCASED HEAVY
DUTY UPVC PIPES
R.C. COLUMN25mm x 3mm
COPPER TAPE
BI-METALLIC
CONNECTOR
PROTECTION
TEST
BOX
LIGHTNING
NUT INSERTM5 COUNTERSUNK BOLT
Y-
Y-
STAINLESS STEEL
COVER PLATE
SECTION Y-Y
25mm x 3mm
ALUMINIUM TAPE
BI-METALLIC
CONNECTOR
25mm x 3mm
COPPER TAPE
25mm x 3mm
ALUMINIUM TAPE
TYPICAL LIGHTNING PROTECTIONTEST BOX AT POB
ELEVATION VIEW(WITH COVER)
ELEVATION VIEW(WITHOUT COVER)
150mm x 150mm TEST LINK BOX
AT 1500mm HEIGHT FROM
GROUND LEVEL (SURFACE MOUNT)
IN ACCORDANCE TO CP33 REQUIREMENTS
(SEE TYPICAL LIGHTNING PROTECTION
TEST BOX AT POB)150mm x 150mm TEST LINK BOX
AT 1500mm HEIGHT FROM
GROUND LEVEL (SURFACE MOUNT)
IN ACCORDANCE TO CP33 REQUIREMENTS
(SEE TYPICAL LIGHTNING PROTECTION
TEST BOX AT POB)
S.S. LIGHTING ENCASEMENT TO DETAIL
TO ROADSIDE DRAIN
PILE CAP TO ENGR’S DETAIL
R.C. GRATING
1800
MIN. 40 MIN. 40
FALL
LIGHT FITTING TO M&E SPEC. & SO’S APPROVAL
2200 700
75
675
625
TYPICAL CROSS BEAM
TO ENGR’S DETAIL
RC COLUMN TO ENGR’S DETAIL WITH
20mm THK PRECASTED GRANOLITHIC
CHIPPING FINISHED TO S.O’S APPROVAL
S.S. LIGHTING ENCASEMENT TO DETAIL
TO ROADSIDE DRAIN
PILE CAP TO ENGR’S DETAIL
R.C. GRATING
1800
MIN. 40 MIN. 40
FALL
2200 700
75
675
625
TYPICAL CROSS BEAM
TO ENGR’S DETAIL
RC COLUMN TO ENGR’S DETAIL WITH
20mm THK PRECASTED GRANOLITHIC
CHIPPING FINISHED TO S.O’S APPROVAL
Ø45mm S.S. RAILING Ø45mm S.S. RAILING
LOCATION OF SUPPORT POST FOR FUTURE COVERLOCATION OF SUPPORT POST FOR FUTURE COVER
FALL FALL
20mm THK PRECASTED GRANOLITHIC
CHIPPING FINISHED TO S.O’S APPROVAL
PLANTING TROUGH WITH WATERPROOFING
MEMBRANE TO SO’S APPROVAL
Ø100mm PVC PIPE WITH Ø5mm HOLES
PERFORATION AT 100mm C/C ALL DIRECTIONS
PLANTING TROUGH WITH WATERPROOFING
MEMBRANE TO SO’S APPROVAL
Ø100mm PVC PIPE WITH Ø5mm HOLES
PERFORATION AT 100mm C/C ALL DIRECTIONS
20mm THK PRECASTED GRANOLITHIC
CHIPPING FINISHED TO S.O’S APPROVAL
FFL OF
POB DECK
FFL OF
POB DECK
Ø15mm S.S. ROD AT NOT MORE THAN 100mm CLEAR
FOOTPATH LEVEL
ROAD LEVEL
FOOTPATH LEVEL
ROAD LEVEL
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
-
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
DescriptionRev. Date By App’dChk’d
$DATE$ $TIME$ $FILE$
MELVYN THONG
N.T.S. JULI JULY 2007
L/ROAD/MES/SD/1012
LROADMES-SD1012-.dgn
NURLY
STANDARD INSTALLATION DETAILS
MALVIN HO
SECTION K-K
SECTION B-B
SECTION C-C
TEAKWOOD FOR MOUNTING
CABLE GLAND FOR ARMOURED CABLE
C1 WELDED ALL-ROUND TO
300x300x20 THK MS PLATE
10mm THK NON SHRINK GROUT
TERMINAL BLOCK CONNECTOR
MOUNTED ON TEAKWOOD BLOCK
FLAT BAR TO SUPPORT TEAKWOOD BLOCK
25mm x 3mm
COPPER TAPE
DETAIL 1
PVC CABLE + 2.5mÀ PVC EARTH CABLE
IN FLEXIBLE CONDUIT
ARMOURED CABLE IN UPVC PIPE
FROM OG BOX TO FIRST LIGHTING POINT
G.I. PIPE ALONG BACK OF M.S. FASCIA
FOR ELECT. CABLES TO M&E DWG. & SPEC.
EARTH PIT
(TOTAL EARTH
RESISTANCE
<10 ohms)
LIGHT FITTING TO M&E SPEC. & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
TYPICAL CROSS SECTION FOR SINGLE POST COVERED LINKWAY
LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING ELECTRICAL CABLE CONCEALED IN PVC
FLEXIBLE CONDUIT IN SUPPORT POST
LIGHT FITTING TO M&E SPEC
(DESIGN TO REFER TO ARCH DWG)
LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE
LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
TYPICAL CABLE ENTRY DETAIL
FOR SINGLE POST COVERED LINKWAY
SEE DETAIL X
SECTION Y-Y
Y-
Y-
25mm x 3mm COPPER TAPE
ALUMINIUM OR
STEEL SUPPORT POST
M8 ALUMINIUM COPPER BOLT
TO STEEL SUPPORT POST
DETAIL X
´
A
Scale 1:5
DETAIL 1
GASKET
SECTION K-K
S/S SCREW
´
Scale 1:5
3^ FALL
S/S SCREW
ISOLATOR / BONDING TAPE BETWEEN
ALUM. ROOF FRAME & M.S. MEMBER
ISOLATOR / BONDING TAPE BETWEEN
ALUM. ROOF FRAME & M.S. MEMBER
1500
SECTION J-J
TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE
DETAIL 2
ISOLATOR / BONDING TAPE BETWEEN
ALUM. ROOF FRAME & M.S. MEMBER
ELECTRICAL CABLE CONCEALED IN PVC
FLEXIBLE CONDUIT IN SUPPORT POST
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
M.S. ANGLE ROOF FASCIA
TO ENGR’S DETAIL
M.S. ANGLE ROOF FASCIA
TO ENGR’S DETAIL
40
FFL
Scale 1:5
B-
B-
SECTION B-BScale 1:5
´
´
MS BASE PLATE TO ENGR’S DETAIL
OPENING FOR INCOMING CABLES COVERED
BY POST CAPPING
(TO BE PROVIDED AT 1ST & LAST POST ONLY)
CONC. SLAB TO ENGR’S DTL COMPLETE WITH
20mm THK GRANOLITHIC FINISHES TO SO’S APPROVAL
TYPICAL SUPPORT POST DETAIL
RC FOOTING TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
Ø50 mm PVC FLEXIBLE CONDUIT
FOR INCOMING CABLES TO M&E DETAIL
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
50 x 50 x 3 ALUM ANGLE PLATE
MS RHS TO ENGR’S DETAIL
100 100
750
Scale 1:5
REF. DWG. NO. L/STLLW/AR/STD/1002
Scale 1:5
REF. DWG. NO. L/STLLW/AR/STD/1002
300
MIN. 10mm THK. ALUM. HONEYCOMB ROOF
PANEL COMPLETE WITH MIN. 1mm THK.
TOP PANEL TO SO’S APPROVAL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL COMPLETE
WITH MIN. 1mm THK.TOP PANEL TO SO’S APPROVAL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
TO SO’S APPROVAL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
TO SO’S APPROVAL
750
¨81
750
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
ALUM FLASHING PIECE BOLTED AT BOTH END
OPENING FOR INCOMING CABLES COVERED
BY POST CAPPING
(TO BE PROVIDED AT 1ST & LAST POST ONLY)
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
C-
C-
SECTION C-CScale 1:5
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
TO SO’S APPROVAL
ALUM. ROOF CAPPING FOR ROOF PANEL TO MFR’S DETAIL
ALUM. ROOF CAPPING FOR ROOF PANEL
TO MFR’S DETAIL
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
G.I. PIPE ALONG BACK OF M.S. FASCIA
FOR ELECT. CABLES TO M&E DWG. & SPEC.
ELECTRICAL CABLE CONCEALED IN PVC
FLEXIBLE CONDUIT TO M&E DWG. & SPEC.
G.I. PIPE ALONG BACK OF M.S. FASCIA
FOR ELECT. CABLES TO M&E DWG. & SPEC.
ALUM. ROOF CAPPING FOR ROOF PANEL
TO MFR’S DETAIL
M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C TO ENGR’S DETAIL
LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
LIGHT FITTING TO M&E SPEC. & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
LIGHT FITTING MOUNTING BRACKET TO CONTRACTOR PROPOSAL
LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
-
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
DescriptionRev. Date By App’dChk’d
$DATE$ $TIME$ $FILE$
MELVYN THONG
N.T.S. JULI JULY 2007
L/ROAD/MES/SD/1013
LROADMES-SD1013-.dgn
NURLY
STANDARD INSTALLATION DETAILS
MALVIN HO
SECTION D-D
SECTION C-C
TEAKWOOD FOR MOUNTING
CABLE GLAND FOR ARMOURED CABLE
C1 WELDED ALL-ROUND TO
300x300x20 THK MS PLATE
10mm THK NON SHRINK GROUT
TERMINAL BLOCK CONNECTOR
MOUNTED ON TEAKWOOD BLOCK
FLAT BAR TO SUPPORT TEAKWOOD BLOCK
25mm x 3mm
COPPER TAPE
PVC CABLE + 2.5mÀ PVC EARTH CABLE
IN FLEXIBLE CONDUIT
ARMOURED CABLE IN UPVC PIPE
FROM OG BOX TO FIRST LIGHTING POINT
EARTH PIT
(TOTAL EARTH
RESISTANCE
<10 ohms)
TYPICAL CROSS SECTION FOR DOUBLE POST COVERED LINKWAY
ELECTRICAL CABLE CONCEALED IN PVC
FLEXIBLE CONDUIT IN SUPPORT POST
LIGHT FITTING TO M&E SPEC
(DESIGN TO REFER TO ARCH DWG)
TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE
TYPICAL CABLE ENTRY DETAIL
FOR DOUBLE POST COVERED LINKWAY
LIGHT FITTING TO M&E SPEC. / CONTRACTOR TO
PROPOSE MOUNTING BRACKET FOR LIGHT FITTING
SECTION B-B
LIGHT FITTING TO M&E SPEC. / CONTRACTOR TO
PROPOSE MOUNTING BRACKET FOR LIGHT FITTING
SEE DETAIL X
SECTION Y-Y
Y-
Y-
25mm x 3mm COPPER TAPE
ALUMINIUM OR
STEEL SUPPORT POST
M8 ALUMINIUM COPPER BOLT
TO STEEL SUPPORT POST
DETAIL X
A B
FFL
Scale 1:5
B-
B-
CONC. SLAB TO ENGR’S DTL COMPLETE WITH
20mm THK GRANOLITHIC FINISHES TO SO’S APPROVAL
RC FOOTING TO ENGR’S DETAIL
3^ FALL
S/S SCREW
ISOLATOR / BONDING TAPE BETWEEN
ALUM. ROOF FRAME & M.S. MEMBER
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL COMPLETE
WITH MIN. 1mm THK.TOP PANEL TO SO’S APPROVAL
ELECTRICAL CABLE CONCEALED IN PVC
FLEXIBLE CONDUIT IN SUPPORT POST
2400
CENTRE OF LIGHT FITTING
1200
100 100
M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C TO ENGR’S DETAIL
TYPICAL CROSS SECTION
SECTION B-BScale 1:5
´
´
´
GASKET
SECTION D-D
´
1500
ISOLATOR / BONDING TAPE BETWEEN
ALUM. ROOF FRAME & M.S. MEMBER
M.S. ANGLE ROOF FASCIA
TO ENGR’S DETAIL
750
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
TO SO’S APPROVAL
ALUM. ROOF CAPPING FOR ROOF PANEL TO MFR’S DETAIL
Scale 1:5
300 1800 300
G.I. PIPE ALONG BACK OF M.S. FASCIA
FOR ELECT. CABLES TO M&E DWG. & SPEC.
PVC FLEXIBLE CONDUIT FOR
INCOMING CABLES TO M&E DETAIL
M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C TO ENGR’S DETAIL
SECTION C-CScale 1:5
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
TO SO’S APPROVAL
ALUM. ROOF CAPPING FOR ROOF PANEL
TO MFR’S DETAIL
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
G.I. PIPE ALONG BACK OF M.S. FASCIA
FOR ELECT. CABLES TO M&E DWG. & SPEC.
ELECTRICAL CABLE CONCEALED IN PVC
FLEXIBLE CONDUIT TO M&E DWG. & SPEC.
C-
C-
OPENING FOR INCOMING CABLES COVERED
BY POST CAPPING
(TO BE PROVIDED AT 1ST & LAST POST ONLY)
40
80
LIGHT FITTING MOUNTING BRACKET TO CONTRACTOR PROPOSAL100
40
LIGHT FITTING TO M&E SPEC. / CONTRACTOR TO
PROPOSE MOUNTING BRACKET FOR LIGHT FITTING
M.S. ANGLE ROOF FASCIA
TO ENGR’S DETAIL
1720 BOTTOM OPENING FOR INCOMING CABLES
COVERED BY POST CAPPING
(TO BE PROVIDED AT 1ST & LAST POST)
M.S. SUPPORT POST @ 3000 mm C/C TO ENGR’S DETAIL
M.S. SUPPORT POST @ 3000 mm C/C TO ENGR’S DETAIL
M.S. SUPPORT POST @ 3000 mm C/C
TO ENGR’S DETAIL
M.S. SUPPORT POST @ 3000 mm C/C TO ENGR’S DETAIL
M.S. BASE PLATE TO ENGR’S DETAIL
M.S. RHS TO ENGR’S DETAIL
LIGHT FITTING TO M&E SPEC. / CONTRACTOR TO
PROPOSE MOUNTING BRACKET FOR LIGHT FITTING
FFL
SECTION E-E
TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
50 X 50 X 3 ALUM ANGLE PLATE
Scale 1:5
REF. DWG. NO. L/STLLW/AR/STD/2002
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
TO SO’S APPROVAL
750
¨81
750
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
ALUM FLASHING PIECE BOLTED AT BOTH END
ALUM. ROOF CAPPING FOR ROOF PANEL
TO MFR’S DETAIL
M.S. SUPPORT POST @ 3000 mm C/C TO ENGR’S DETAIL
LIGHT FITTING TO M&E SPEC. / CONTRACTOR TO
PROPOSE MOUNTING BRACKET FOR LIGHT FITTING
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
-
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
DescriptionRev. Date By App’dChk’d
$DATE$ $TIME$ $FILE$
MELVYN THONG
N.T.S. JULI JULY 2007
L/ROAD/MES/SD/1014
LROADMES-SD1014-.dgn
NURLY
STANDARD INSTALLATION DETAILS
MALVIN HO
TYPICAL OG BOX POSITION FOR COVERED LINKWAY
EARTH
PIT
EARTH
PIT
BONDING DETAILS TO
ROOF SPECIALIST’S REQUIREMENTS
BONDING TO UPPER ROOF
LIGHTNING PROTECTION SYSTEM
(BONDING DETAILS TO ROOF
SPECIALIST’S REQUIREMENTS)
BONDING TO UPPER ROOF
LIGHTNING PROTECTION SYSTEM
(BONDING DETAILS TO ROOF
SPECIALIST’S REQUIREMENTS)
BONDING DETAILS TO
ROOF SPECIALIST’S REQUIREMENTS
OG BOX
2 NOS. Ø100mm HEAVY DUTY UPVC PIPE
EMBEDED UNDER GROUND FOR POWERGRID
INCOMING CABLES TO M&E SPEC. & APPROVAL
(LOCATION & ORIENTATION TO BE
DETERMINED ON SITE)
(LOCATION TO BE DETERMINED
ON SITE & TO RO APPROVAL)
BONDING DETAILS TO
ROOF SPECIALIST’S REQUIREMENTS
OG BOX ON CONC. PLINTH TO M&E DTLS
(LOCATION TO BE DETERMINED ON SITE &
TO POWERGRID’S APPROVAL)
LIGHTNING PROTECTION LAYOUT PLAN
OG BOX POSITION LAYOUT PLAN
FRONT ELEVATION OF OG BOX POSITION
FRONT ELEVATION OF LIGHTNING PROTECTION LAYOUT PLAN
1 2 3 4 5 6 7
A
A
Scale 1:50
Scale 1:50
Scale 1:50
1-
1-
ROOF EAVES ABOVE
1500 1500
750 3000 3000 3000 3000 3000 3000 750
1 2 3 4 5 6 7
1 2 4 5 7
1 2 3 4 5 6 7
R O A D
FRONT ELEVATION 1 (WITHOUT LEVEL DIFFERENCE)
FRONT ELEVATION WITH LEVEL DIFFERENCE
KL/STLLW/AR/STD/1006
2 NOS. Ø100mm HEAVY DUTY UPVC PIPE
EMBEDED UNDER GROUND FOR POWERGRID
INCOMING CABLES TO M&E SPEC. & APPROVAL
(LOCATION & ORIENTATION TO BE
DETERMINED ON SITE) CONC. SLAB TO ENGR’S DTLS COMPLETE WITH
20mm THK. GRANOLITHIC FINISHES TO SO’S APPROVAL
MS ANGLE ROOF FASCIA TO ENGR’S DETAIL
SUPPORT POST TO ENGR’S DETAIL
EXPANSION JOINT AT REGULAR INTERVAL
ALONG CENTRE OF GRID TO ENGR’S DETAIL
ROOF CAPPING TO MFR’S DETAIL
ROOF CAPPING TO MFR’S DETAIL
LINE OF ROAD KERB
K-
3 8
ROOF PLAN OF LINKWAY (WITHOUT LEVEL DIFFERENCE)
LAYOUT PLAN OF LINKWAY (WITHOUT LEVEL DIFFERENCE)
OG BOX
820
FFL
MS ANGLE ROOF FASCIA
TO ENGR’S DETAIL
SUPPORT POST TO ENGR’S DETAIL
FFL
MS ANGLE ROOF FASCIA
TO ENGR’S DETAIL
SUPPORT POST TO ENGR’S DETAIL
ALUM FLASHING PIECE
FFL
JL/STLLW/AR/STD/1006
SUPPORT POST TO ENGR’S DETAIL
MS ANGLE ROOF FASCIA TO
ENGR’S DETAIL
750 3000 3000 3000 3000 3000 3000 750
15001500 15001500 15001500 15001500 15001500 15001500
SUPPORT POST TO ENGR’S DETAIL
MS ANGLE ROOF FASCIA TO ENGR’S DETAIL
MIN. 10mm THK. ALUM. HONEY COMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL TO
SO’S APPROVAL
6 9 10
ROOF CAPPING TO MFR’S DETAIL
750 3000 3000 3000 3000 3000 3000 750
750 3000 3000 750
75030003000750
¨81750300030003000750
¨81
SUPPORT POST TO ENGR’S DETAIL
OG BOX
200 820
(CLEAR)
200
(CLEAR)
820
FFL
200
(CLEAR)
OG BOX
OG BOX ON CONC. PLINTH TO M&E DTLS
(LOCATION TO BE DETERMINED ON SITE &
TO POWERGRID’S APPROVAL)
OG BOX ON CONC. PLINTH TO M&E DTLS
(LOCATION TO BE DETERMINED ON SITE &
TO POWERGRID’S APPROVAL)
OG BOX ON CONC. PLINTH TO M&E DTLS
(LOCATION TO BE DETERMINED ON SITE &
TO POWERGRID’S APPROVAL)