What are stairwell fixture solutions? Stairwell fixtures are a retrofit solution that automatically adjust light output based on stairwell occupancy.
• Utilizes an integral Lutron wireless lighting control device, programmed to occupied and unoccupied light levels that are field-adjustable and specific to a project’s code requirements
• Receives signal from Radio Powr SavrTM occupancy/vacancy sensors (sold separately) via Lutron reliable Clear Connect® RF technology
• Provides the flexibility to determine occupancy/vacancy sensor quantities, mounting configuration, and placement requirements per the stairwell design
How does it work?Occupied: 50% light levelUnoccupied: 10% light level
2
3
1
Stairwell fixture
Radio Powr Savr occupancy/vacancy sensor (wall mount)
Wireless Signal ReceivedLutron ® Clear Connect ®
Wireless Signal SentLutron ® Clear Connect ®
Wireless Signal Two-wayLutron ® Clear Connect ®
Wireless Signal ReceivedLutron ® Clear Connect ®
Wireless Signal SentLutron ® Clear Connect ®
Wireless Signal Two-wayLutron ® Clear Connect ®
2
3
1
Benefits Energy savings – ability to save over 80% of lighting energy usage1
– high-end trim reduces light levels when occupied
– occupancy sensing lowers light levels when unoccupied
Simple installation – wireless communication between devices allows the occupancy/vacancy sensor(s) to be mounted in the location that provides the maximum area of coverage with no need for additional wiring
High ROI – payback as low as 3-years; utility rebates available in most locations2
Flexible – assign multiple fixtures to a single occupancy/vacancy sensor, allowing multiple fixtures to adjust to the occupied light level
Meets codes and standards (see back cover for details)
1 Rebates and savings assumes the replacement of a 2 lamp 40W T12 stairwell fixture at full output for 8760 hours with a 2 lamp 32W T8 fixture at 50% output for 2190 hours and 10% output for 6570 hours. LEDs may see greater savings due to reduced wattage.
2 Payback varies depending upon lamp wattage, usage, electricity rates, and available rebates. For more information on utility rebates, visit www.lutron.com/incentives.
3 Reduced wattage T8 lamps only available in 4 ft fixture with the lowest end dimming of 10%.
Features Stairwell fixtures
• PowPak® fixture: 2, 3, 4, or 8 ft; 1, 2, or 4 lamps; lamp options: T8, reduced wattage T83, T5HE, or T5HO• Vandal-resistant fixture: 2 or 4 ft; 2 lamps; lamp options: T8, T5HE, or T5HO• LED fixture: 2 ft; 4000 K color temperature LED module; module options: 17 W, 1500 Lumens or 30 W, 2400 Lumens• 120-277 V~ universal input voltage• Ceiling or wall surface mount• Optional emergency ballast battery backup available for Stairwell PowPak fixtures• ADA compliant
Radio Powr SavrTM occupancy/vacancy sensors• Ceiling-, wall-, hall-, and corner-mount configurations available • Customize timeout to 1, 5, 15 or 30 minutes• Exclusive Lutron XCTTM technology – enhanced passive infrared (PIR) sensing• Control up to 9 fixtures with one sensor• 10-year battery life
Stairwell PowPak® fixture
NEW Stairwell LED fixture
Stairwell vandal-resistant
fixture
Radio Powr Savr
occupancy/vacancy sensors
www.lutron.com
World Headquarters 1.610.282.3800Technical Support 1.800.523.9466 (Available 24/7)Customer Service 1.888.LUTRON1 (1.888.588.7661)
© 09/2012 Lutron Electronics Co., Inc. I P/N 367-2034 REV E
How to build a model number
Codes and standards• ASHRAE 90.1 2010 Additional Control (9.4.1.6) Lighting in stairwells shall have one or more control devices to automatically reduce lighting power in
any one controlled zone by at least 50% within 30 minutes of all occupants leaving that controlled zone.
• IgCC (International Green Construction Code) Interior Light Reduction Controls (609.3) Occupant sensor controls shall be provided to automatically reduce connected lighting power by not
less than 45% during periods when occupants are not present in all of the following locations: 1. Corridors and enclosed stairwells. 2. Storage and stack areas not open to the public. 3. Parking garages.
FXSW ____ ____ ____ ____ ____ U ____ _____ _____ WH
Size:121,2 = 1’ x 2’
13 = 1’ x 3’
142 = 1’ x 4’
18 = 1’ x 8’
Lens options:SL1 = Standard
CP = Clear Prismatic Acrylic
OA = Opal Acrylic
PO2 = PolyCarbonate
Lamp type:142 = 14 W, T5HE, 2 ft172 = 17 W, T8, 2 ft21 = 21 W, T5HE, 3 ft242 = 24 W, T5HO, 2 ft25 = 25 W, T8, 3 ft282 = 28 W, T5HE, 4 ft322 = 32 W, T8, 4 ft39 = 39 W, T5HO, 3 ft542 = 54 W, T5HO, 4 ftRW = 25, 28, 30 W T8 reduced wattage, 4 ftC11 = 17 W, 4000 K, 1500 LumensC31 = 30 W, 4000 K, 2400 Lumens
Controls:51 = 50% High, 10% Low
82 = 80% High, 20% Low
Mounting:SM = Surface-mount
M4 = 4 ft Mounting Plate
(available for 2 ft LED stairwell only)
Options:XX = None
E1 = T8 Emergency Ballast
E33,4 = T5HE Emergency Ballast
E53,4 = T5HO Emergency Ballast
Lamps:1 = 1 Lamp
22 = 2 Lamps
4 = 4 Lamps (8 ft fixture only)
L1 = LED module
Type:XX1 = Standard
VR = Vandal-resistant
Example:FXSWXX12CP114U51SMXXWHStandard, 1-lamp with clear prismatic acrylic lens, 14 W, 2 ft fixture, preset high (occupied) and low end (unoccupied) levels are 50% and 10%, no emergency ballast
For pricing and availability, please contact your local Lutron representative or [email protected].
1 Stairwell LED fixture is only available in these select options2 Stairwell vandal-resistant fixture is only available in these
select options3 Emergency ballast “option” not available
if 2’ “lamp type” is chosen 4 Emergency ballast “option” is determined by “lamp type”