Sprinkler Protection Criteria for Rack-Stored Exposed Expanded Group A Plastics
Kerry M. Bell, P.E.
Corporate Fellow
UL LLC
UL and the UL logo are trademarks of UL LLC © 2016
2
Fire Protection Research Foundation Project Team
• IKEA • Viking Sprinkler • Reliable Sprinkler • Tyco Fire and Building Products • XL Insurance • Property Insurance Research Group • Procter & Gamble• Target • Aon Insurance
• Ken Linder, Swiss Re
• Rich Pehrson, Rep. International Fire Marshals Association
• Jason Huczek, Southwest Research Institute
• John Denhardt, Strickland Fire Protection
• Steve Wolin, Code Consultants, Inc.
• Matt Klaus, NFPA Staff Liaison
Sponsors Technical Panel
Project Contractor
• UL LLC
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
3
Protection of Exposed Expanded Plastics Stored in Racks
Figure 17.1.2.1
Research Objective
To develop cost effective sprinkler system design criteria for the rack
storage of exposed expanded Group A plastic commodity with a
particular focus on ceiling only protection.
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
4
NFPA 13 Commodity Classification
Class or
Group Class or Group Material
Class IEssentially non-combustible products in corrugated cartons on combustible
pallets
Class IIClass I products in slatted wooden crates, solid wooden boxes or multiple
thickness paperboard cartons with or without pallets
Class III
Wood, paper, natural fiber cloth or Group C plastics with or without pallets.
May contain a limited amount (5% by weight or volume or less) of Group A or
Group B plastics
Class IVClass I, II or III commodities in corrugated cartons with appreciable amounts
(5-15% by weight, or 5-25% by volume) of Group A plastics
Pla
sti
cs
Cartoned Unexpanded Group A Plastic
Exposed Unexpanded Group A Plastic
Cartoned Expanded Group A Plastic
Exposed Expanded Group A Plastic
Ha
za
rd S
ev
eri
ty
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
5
Standardized Test Commodities
Class II Class III Class IV
Cartoned Unexpanded
Group A Plastic
Cartoned, Expanded
Group A PlasticExposed, Expanded
Group A Plastic
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
6
Examples of Expanded Plastics
• Cushioned furniture
• Mattresses
• Food containers
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
7
HRR Growth Curve of
Standard Test Commodities
0
500
1.000
1.500
2.000
2.500
3.000
3.500
0 20 40 60 80 100 120 140
Heat
Rele
ase R
ate
(kW
)
Time, seconds
Exposed Expanded Group A
Cartoned Expanded Group A
Cartoned Unexpanded Group A
Class II
HRR Increase = 1.3
MW/second
8
Exposed Expanded Group A Plastics –A Challenging Commodity to Protect
• Fast developing fire with high heat release rate
• Rapid fire travel (both vertical and horizontal) within the storage array
• Effectiveness of pre-wetting from sprinkler discharge is reduced due to limited commodity absorption of water
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
9
Strategy for Protecting Exposed
Expanded Group A Plastics
Stored in Racks
9
Fire Challenge Protection Strategy
Fast developing fire with high heat release rate
Large K-factor ESFR technology discharging large quantities of water. Testing was completed using nominal K=363 (25.2) pendent ESFR sprinklers in the intermediate temperature rating discharging at 4.1 bar (60 psig ) or 477 cm of water/hour (188 inches of water/hour)
Rapid fire travel (both vertical and horizontal) within the storage array
See above with vertical barriers within the storage array to limit the (1) horizontal fire travel and (2) commodity surfaces involved in the combustion process
Effectiveness of pre-wetting from sprinkler discharge is reduced due to limited commodity absorption of water
Minimum 2.4 m (8 ft.) aisle width to minimize the potential for the fire to travel to the target arrays.
Hurricane/Typhoon
Up to 20 cm of
water/hour (8 inches of
water/hour)
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED.
THIS DOCUMENT MAY NOT BE REPRODUCED OR
DISTRIBUTED WITHOUT PERMISSION OF
UNDERWRITERS LABORATORIES INC.
10
Protection of Exposed Expanded
Plastics Stored in Racks
Acceptance Criteria for Test Data to be Considered for Supporting Revisions to NFPA 13
Key Acceptance Criteria:
• Number of operated sprinklers (50% safety factor applied)• No sustained combustion at the outer edge of the ends of the main
array and outer edges of the target arrays.• 537°C (1000°F) maximum 1 minute average steel temperature
measured above the fire.
Variable Investigated, But Not Incorporated Into the Design Criteria
• Blocking of certain transverse flue spaces to simulate potential conditions that may occur in the field was evaluated, but successful test results were not achieved.
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
1111
FIRE TEST NUMBER Test 1 Test 2 Test 3 Test 5 Test 6
Test Date July 9, 2012 July 13, 2012 July 18, 2012 October 31, 2012 November 8, 2012
Test ParametersStorage Type Double Row Rack Double Row Rack Double Row Rack Double Row Rack Double Row Rack
Commodity TypeExposed Expanded
Group A PlasticExposed Expanded
Group A PlasticExposed Expanded
Group A PlasticExposed Expanded
Group A PlasticExposed Expanded
Group A Plastic
Vertical Barriers
4.9 m (16 ft.) on center –
Main Array (Non-combustible)
4.9 m (16 ft.) on center - Main Array (Non-combustible)
4.9 m (16 ft.) on center - Main Array (Non-
combustible)
7.3 m (24 ft.) on center - Main Array
(10 mm(3/8 in.) plywood)
4.9 m (16 ft.) on center - Main
Array (10 mm (3/8 in.
plywood)Number of Blocked
Traverse Flue Spaces18 12 72 98 60
Length of Main Storage Array, m( ft.)
9.7 (32) 9.7 (32) 17 (56) 17 (56) 17 (56)
Nominal Storage Height, m (ft.) 6.1 (20) 6.1 (20) 10. 7 (35) 12.2 (40) 9.1 (30)
Ceiling Height, m (ft.) 12.2 (40) 12.2 (40) 12.2 (40) 13.7 (45) 12.2 (40)Aisle Width, m (ft.) 2.4 (8) 2.4 (8) 2.4 (8) 2.4 (8) 2.4 (8)
Ignition LocationBetween 2 Sprinklers
(offset)Between 2 Sprinklers
(offset)Between 2
Sprinklers (offset)Under 1 Sprinkler
(offset)Under 1 Sprinkler
(offset)
Sprinkler Type ESFR ESFR ESFR ESFR ESFR Sprinkler Orientation Pendent Pendent Pendent Pendent Pendent
Deflector to Ceiling, cm (in.) 36 (14) 36 (14) 36 (14) 36 (14) 36 (14)Sprinkler Spacing, sprinkler by
branchline, m (ft.)3 by 3 (10 by 10) 3 by 3 (10 by 10) 3 by 3 (10 by 10) 3 by 3 (10 by 10) 3 by 3 (10 by 10)
Temperature Rating, ºC (ºF) 100 (212) 101 (214) 101 (214) 101 (214) 101 (214)Nominal Sprinkler Discharge
Coefficient K, lpm/bar 0.5
(gpm/psig 0.5)320 (22.4) 363 (25.2) 363 (25.2) 363 (25.2) 363 (25.2)
Nominal Discharge Pressure, bar (psig)
3.4 (50) 4.1 (60) 4.1 (60) 4.1 (60) 4.1 (60)
12
13
Test 6 Arrangement
Plan View Elevation View
Exposed
Expanded
Group A
Plastic
(typical)
3/8 inch
plywood
Vertical
Barriers ,
16 ft. on center
N
8 ft.
aisle
8 ft.
aisle
Ignition -
2 half
standard
igniters
Ignition Location Vertical Barrier, 4 inches
off of lab floor (typical)
Horizontal Barrier, Placed on
top of pallets to span
transverse flues
(typical – 60 positions)
40
ft.
30
ft. no
min
al
3/8 in. Plywood
Vertical Barrier
(typical)C
L
10 ft. (typ.)14 inches
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
14
Transverse Flue Space Blocking
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
15
Test 6 – Sprinkler Operations (11)
COPYRIGHT © 2016 UL LLC. ALL
RIGHTS RESERVED. THIS DOCUMENT
MAY NOT BE REPRODUCED OR
DISTRIBUTED WITHOUT PERMISSION OF
UNDERWRITERS LABORATORIES INC.
16
Test 6 – Main North Array Damage
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
17
Test 6 – Main South Array Damage
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
18
Test 6 – South Target Array Damage
View fromOutside Arrangement
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
19
Test 6 – Camera Locations
N10 ft.
(Typ.)
10 ft.
(Typ.)
Ignition location: Centered under one
sprinkler, offset in transverse flue space.
Spr 11 Spr 12 Spr 13 Spr 14 Spr 15 Spr 16 Spr 17 Spr 18 Spr 19 Spr 20
Spr 21 Spr 22 Spr 23 Spr 24 Spr 25 Spr 26 Spr 27 Spr 28 Spr 29 Spr 30
Spr 31 Spr 32 Spr 33 Spr 34 Spr 35 Spr 36 Spr 37 Spr 38 Spr 39 Spr 40
Spr 41 Spr 42 Spr 43 Spr 44 Spr 45 Spr 46 Spr 47 Spr 48 Spr 49 Spr 50
Spr 51 Spr 52 Spr 53 Spr 54 Spr 55 Spr 56 Spr 57 Spr 58 Spr 59 Spr 60
Spr 61 Spr 62 Spr 63 Spr 64 Spr 65 Spr 66 Spr 67 Spr 68 Spr 69 Spr 70
Spr 71 Spr 72 Spr 73 Spr 74 Spr 75 Spr 76 Spr 77 Spr 78 Spr 79 Spr 80
Spr 81 Spr 82 Spr 83 Spr 84 Spr 85 Spr 86 Spr 87 Spr 88 Spr 89 Spr 90
Spr 1 Spr 2 Spr 3 Spr 4 Spr 5 Spr 6 Spr 7 Spr 8 Spr 9 Spr 10
Spr 91 Spr 92 Spr 93 Spr 94 Spr 95 Spr 96 Spr 97 Spr 98 Spr 99 Spr 100
Infrared Camera View
South
Wall
View
North East Corner
Balcony Camera View
Initial
Ignition
Location
of South
Target
Array
COPYRIGHT © 2016 UL LLC. ALL RIGHTS
RESERVED. THIS DOCUMENT MAY NOT
BE REPRODUCED OR DISTRIBUTED
WITHOUT PERMISSION OF
UNDERWRITERS LABORATORIES INC.
20
Test 6 View from NE Balcony
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
21
Test 6 – View from South Target Array
COPYRIGHT © 2016 UL LLC. ALL
RIGHTS RESERVED. THIS DOCUMENT
MAY NOT BE REPRODUCED OR
DISTRIBUTED WITHOUT PERMISSION OF
UNDERWRITERS LABORATORIES INC.
22
Test 6 – View from South East Corner - Infrared
22
COPYRIGHT © 2016 UL LLC. ALL
RIGHTS RESERVED. THIS DOCUMENT
MAY NOT BE REPRODUCED OR
DISTRIBUTED WITHOUT PERMISSION OF
UNDERWRITERS LABORATORIES INC.
FIRE TEST No. Test 1 Test 2 Test 3 Test 5 Test 6 Test 7 Test 8Test Date July 9, 2012 July 13, 2012 July 18, 2012 Oct. 31, 2012 Nov. 8, 2012 June 8, 2013 June 19, 2014
Test Parameters
Storage TypeDouble
Row RackDouble
Row RackDouble
Row RackDouble
Row RackDouble
Row RackDouble
Row RackDouble
Row Rack
Commodity TypeExposed Expanded
Group A PlasticExposed Expanded
Group A PlasticExposed Expanded
Group A PlasticExposed Expanded
Group A PlasticExposed Expanded
Group A PlasticExposed Expanded
Group A PlasticExposed Expanded
Group A Plastic
Vertical Barriers
4.9 m (16 ft.) on center –
Main Array (Non-combustible)
4.9 m (16 ft.) on center - Main Array (Non-combustible)
4.9 m (16 ft.) on center - Main Array (Non-combustible)
7.3 m (24 ft.) on center - Main Array
(10 mm(3/8 in.) plywood)
4.9 m (16 ft.) on center - Main Array
(10 mm (3/8 in. plywood)
4.9 m (16 ft.) on center - Main Array
(10 mm (3/8 in. plywood)
4.9 m (16 ft.) on center - Main Array
(10 mm (3/8 in. plywood)
Number of Blocked Traverse Flue Spaces
18 12 72 98 60 None None
Length of Main Storage Array, m ( ft.)
9.7 (32) 9.7 (32) 17 (56) 17 (56) 17 (56) 12.2 (40) 17 (56)
Nominal Height, m (ft.) 6.1 (20) 6.1 (20) 10. 7 (35) 12.2 (40) 9.1 (30) 9.1 (30) 10.7 (35)
Ceiling Height, m (ft.) 12.2 (40) 12.2 (40) 12.2 (40) 13.7 (45) 12.2 (40) 12.2 (40) 12.2 (40)Aisle Width, m (ft.) 2.4 (8) 2.4 (8) 2.4 (8) 2.4 (8) 2.4 (8) 2.4 (8) 2.4 (8)
Ignition LocationBetween 2
Sprinklers (offset)Between 2 Sprinklers
(offset)Between 2 Sprinklers
(offset)Under 1 Sprinkler
(offset)Under 1 Sprinkler
(offset)Under 1 Sprinkler
(offset)
Between 2 Sprinklers (offset)
Sprinkler Type ESFR ESFR ESFR ESFR ESFR ESFR ESFRSprinkler Orientation Pendent Pendent Pendent Pendent Pendent Pendent Pendent
Deflector to Ceiling, cm (in.)
36 (14) 36 (14) 36 (14) 36 (14) 36 (14) 36 (14) 36 (14)
Sprinkler Spacing, m (ft.)3 by 3(10 by
10)3 by 3(10 by
10)3 by 3 10 by 10) 3 by 3 10 by 10)
3 by 3(10 by 10)
3 by 3(10 by 10)
3 by 3 10 by 10)
Temp Rating, ºC (ºF) 100 (212) 101 (214) 101 (214) 101 (214) 101 (214) 101 (214) 101 (214)Nominal Sprinkler
Discharge Coefficient K, lpm/bar 0.5 (gpm/psig 0.5)
320 (22.4) 363 (25.2) 363 (25.2) 363 (25.2) 363 (25.2) 363 (25.2) 363 (25.2)
Nominal Discharge Pressure, bar (psig)
3.4 (50) 4.1 (60) 4.1 (60) 4.1 (60) 4.1 (60) 4.1 (60) 4.1 (60)
Tests Used to Establish 12.2 m (40 ft.) Design Criteria
24
Test 7 – Sprinkler Operations (7)
N10 ft.
(Typ.)
10 ft.
(Typ.)
Ignition location: Centered under one
sprinkler, offset in transverse flue space.
dno dno dno dno dno dno dno dno dno dno
dno dno dno dno dno dno dno dno dno dno
dno dno dno 1:28 0:57 1:02 dno dno dno dno
dno dno dno dno 0:47 1:09 dno dno dno dno
dno dno dno dno 1:07 1:02 dno dno dno dno
dno dno dno dno dno dno dno dno dno dno
dno dno dno dno dno dno dno dno dno dno
dno dno dno dno dno dno dno dno dno dno
dno dno dno dno dno dno dno dno dno dno
dno dno dno dno dno dno dno dno dno dno
dno – did not operate
COPYRIGHT © 2016 UL LLC. ALL
RIGHTS RESERVED. THIS DOCUMENT
MAY NOT BE REPRODUCED OR
DISTRIBUTED WITHOUT PERMISSION OF
UNDERWRITERS LABORATORIES INC.
25
Test 7 – Main North Array Damage
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
26
Test 7 – View from NE Balcony
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
27
Test 8 – Main North Array Damage
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
28
Fire Travel Past Vertical Barriers –Commodity Extending Beyond Barrier
Exposed
Expanded
Group A
Plastic
(typical)
Vertical
Barrier 10 – 12.5 cm
(4 – 5 in.)
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
29
FIRE TEST NUMBER Test 1 Test 2 Test 3 Test 5 Test 6 Test 7 Test 8
Test Date July 9, 2012 July 13, 2012 July 18, 2012 October 31, 2012November 8,
2012June 8, 2013
June 19, 2014
Test Results
Length of Test, minutes 31 31 31 31 31 31 31
First Sprinkler Operation Time, min:sec
0:39 0:44 0:52 0:47 0:48 0:47 0:48
Last Sprinkler Operation Time, min:sec
8:23 3:21 1:45 1:39 4:35 1:28 2:28
Number of Operated Sprinklers
12 6 10 18 11 7 7Peak Gas Temperature at Ceiling Above Ignition, ºC
(ºF)296 (564) 292 (558) 614 (1138) 539 (1002) 116 (241) 212 (414) 469 (877)
Maximum 1 minute Average Gas Temperature at Ceiling Above Ignition,
ºC (ºF)
124 (255) 104 (220) 178 (353) 254 (489) 66 (151) 88 (191) 151 (303)
Peak Steel Temperature at Ceiling Above Ignition, ºC
(ºF)52 (126) 48 (119) 63 (145) 71 (160) 54 (129) 56 (133) 58 (136)
Maximum 1 minute Average Steel Temperature at Ceiling Above Ignition,
ºC (ºF)
51 (124) 47 (117) 61 (141) 69 (156) 53 (127) 53 (127) 57 (134)
Ignition Time of Target Array, minutes:seconds
None None None1:01
(North Target)1:27
(South Target) None None
Fire Travel to Extremities of Test Array
Yes (East and West
end of Main)
Yes (West end of Main)
No
Yes(North Target Array Burned Through to
Extremities)
Yes(South Target Array Burned Through to
Extremities)
No No
30
Testing Activity Subsequent to NFPA Second Draft TC Meeting
• During the June 2014 Second Draft meeting of the NFPA TC on
Sprinkler System Discharge Criteria, several committee members
expressed concern that there was only one design criteria for a 40 ft.
high ceiling.
• Based upon the concern expressed by members of the TC, FPRF
worked quickly to solicit sponsors and organize a Technical Panel for
follow-on research to generate data to support sprinkler system
design criteria at a lower ceiling height.
• Based upon subsequent FPRF Technical Panel discussions, it was
agreed to conduct testing to support a design criteria for a 9.1 m (30
ft.) ceiling.COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
31
Fire Protection Research Foundation Project Team 9.1 m (30 ft.) Series
Sponsors
• Viking Sprinkler
• Tyco Fire and Building Products
• Property Insurance Research Group
Project Contractor
• UL LLC
Technical Panel
• Ken Linder, Swiss Re
• Rich Pehrson, Rep. International Fire Marshals Association
• Jason Huczek, Southwest Research Institute
• John Denhardt, Strickland Fire Protection
• Matt Klaus, NFPA Staff Liaison
COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Tests for 9.1 m (30 ft.) Design Criteria (Parameters)FIRE TEST NUMBER Test 9 Test 10
Test Date Oct. 28, 2014 Oct. 30, 2014
Test Parameters
Storage Type Double Row Rack Double Row Rack
Commodity Type Exposed Expanded Group A Plastic Exposed Expanded Group A Plastic
Vertical Barriers4.9 m (16 ft.) on center - Main
Array (10 mm (3/8 in. plywood)
4.9 m (16 ft.) on center - Main Array
(10 mm (3/8 in. plywood)
Number of Blocked Traverse Flue Spaces None None
Length of Main Storage Array, m ( ft.) 9.7 (32) 9.7 (32)
Nominal Storage Height, m (ft.) 6.1 (20) 7.6(25)
Ceiling Height, m (ft.) 9.1 (30) 9.1 (30)
Aisle Width, m (ft.) 2.4 (8) 2.4 (8)
Ignition Location Under 1 Sprinkler (offset) Between 2 Sprinklers (offset)
Sprinkler Type ESFR ESFR
Sprinkler Orientation Pendent Pendent
Deflector to Ceiling, cm (in.) 36 (14) 36 (14)
Sprinkler Spacing, sprinkler by branchline, m (ft.) 3 by 3 (10 by 10) 3 by 3 (10 by 10)
Temperature Rating, ºC (ºF) 101 (214) 101 (214)Nominal Sprinkler Discharge Coefficient K,
lpm/bar 0.5 (gpm/psig 0.5)363 (25.2) 363 (25.2)
Nominal Discharge Pressure, bar (psig) 2 (30) 2 (30)
33
FIRE TEST NUMBER Test 9 Test 10Test Date October 28, 2014 October 30, 2014
Test Results
Length of Test, minutes 31 31
First Sprinkler Operation Time, min:sec
0:47 0:53
Last Sprinkler Operation Time, min:sec
1:24 1:14
Number of Operated Sprinklers
7 7
Peak Gas Temperature at Ceiling Above Ignition, ºC (ºF)
96 (204) 532 (990)
Maximum 1 minute Average Gas Temperature at Ceiling
Above Ignition, ºC (ºF)59 (138) 247 (477)
Peak Steel Temperature at Ceiling Above Ignition, ºC (ºF)
46 (114) 65 (149)
Maximum 1 minute Average Steel Temperature at Ceiling
Above Ignition, ºC (ºF)44 (112) 62 (144)
Ignition Time of Target Array, minutes:seconds None None
Fire Travel to Extremities of Test Array No No
Tests Used to Establish 9.1 m (30 ft.) Design Criteria
COPYRIGHT © 2016 UL LLC. ALL
RIGHTS RESERVED. THIS DOCUMENT
MAY NOT BE REPRODUCED OR
DISTRIBUTED WITHOUT PERMISSION OF
UNDERWRITERS LABORATORIES INC.
34
Tests Used to Establish Design Criteria (12.2 and 9.1 m High Ceilings)
ResultsFIRE TEST NUMBER Test 2 Test 7 Test 8 Test 9 Test 10Test Date July 13, 2012 June 8, 2013 June 19, 2014 October 28, 2014 October 30, 2014
Test ResultsLength of Test, minutes 31 31 31 31 31
First Sprinkler Operation Time, min:sec
0:44 0:47 0:48 0:47 0:53
Last Sprinkler Operation Time, min:sec
3:21 1:28 2:28 1:24 1:14
Number of Operated Sprinklers
6 7 7 7 7
Peak Gas Temperature at Ceiling Above Ignition, °F
292 (558) 212 (414) 469 (877) 96 (204) 532 (990)
Maximum 1 minute Average Gas Temperature at Ceiling
Above Ignition, °F104 (220) 88 (191) 151 (303) 59 (138) 247 (477)
Peak Steel Temperature at Ceiling Above Ignition, °F
48 (119) 56 (133) 58 (136) 46 (114) 65 (149)
Maximum 1 minute Average Steel Temperature at Ceiling
Above Ignition, °F47 (117) 53 (127) 57 (134) 44 (112) 62 (144)
Ignition Time of Target Array, minutes:seconds
None None None None None
Fire Travel to Extremities of Test Array
Yes (West end of Main)
No No No No
35
NFPA 13-2016 Edition Including TIAKey Criteria in Chapter 17
(Rack Stored Exposed, Expanded Plastics)
Criteria 12.2 m (40 ft.) Ceiling 9.1 m (30 Ft.) Ceiling
Maximum storage height 10.7 m (35 ft.) 7.6 m (25 ft.)
Minimum design pressure 4.1 bar (60 psi) 2.0 bar (30 psi)
Minimum aisle width 2.4 m (8 ft.)
Sprinkler K=363 (25.2) Pendent ESFR -Intermediate Temperature Rated
Design area 12 most demanding sprinklers
Minimum water duration 60 minutes
Minimum hose allowance 945 Lpm (250 gpm)
Max vertical barrier distance 5 m (16.5 ft.)
Vertical barrier material 10 mm (3/8 in) plywood, 0.8 mm (22 gauge) steel or
equivalent
Max area between vertical barriers and aisles
11.5 m2 (124 ft2)
Vertical barrier size Extend across longitudinal flue to the top of the storage
Commodity extension into aisle 101 mm (4 in.) allowed beyond barrier into aisle
36
Protection of Exposed ExpandedPlastics Stored in Racks