Page 1: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

1

Sprinkler Protection Criteria for Rack-Stored Exposed Expanded Group A Plastics

Kerry M. Bell, P.E.

Corporate Fellow

UL LLC

UL and the UL logo are trademarks of UL LLC © 2016

Page 2: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

2

Fire Protection Research Foundation Project Team

• IKEA • Viking Sprinkler • Reliable Sprinkler • Tyco Fire and Building Products • XL Insurance • Property Insurance Research Group • Procter & Gamble• Target • Aon Insurance

• Ken Linder, Swiss Re

• Rich Pehrson, Rep. International Fire Marshals Association

• Jason Huczek, Southwest Research Institute

• John Denhardt, Strickland Fire Protection

• Steve Wolin, Code Consultants, Inc.

• Matt Klaus, NFPA Staff Liaison

Sponsors Technical Panel

Project Contractor

• UL LLC

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 3: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

3

Protection of Exposed Expanded Plastics Stored in Racks

Figure 17.1.2.1

Research Objective

To develop cost effective sprinkler system design criteria for the rack

storage of exposed expanded Group A plastic commodity with a

particular focus on ceiling only protection.

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 4: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

4

NFPA 13 Commodity Classification

Class or

Group Class or Group Material

Class IEssentially non-combustible products in corrugated cartons on combustible

pallets

Class IIClass I products in slatted wooden crates, solid wooden boxes or multiple

thickness paperboard cartons with or without pallets

Class III

Wood, paper, natural fiber cloth or Group C plastics with or without pallets.

May contain a limited amount (5% by weight or volume or less) of Group A or

Group B plastics

Class IVClass I, II or III commodities in corrugated cartons with appreciable amounts

(5-15% by weight, or 5-25% by volume) of Group A plastics

Pla

sti

cs

Cartoned Unexpanded Group A Plastic

Exposed Unexpanded Group A Plastic

Cartoned Expanded Group A Plastic

Exposed Expanded Group A Plastic

Ha

za

rd S

ev

eri

ty

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 5: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

5

Standardized Test Commodities

Class II Class III Class IV

Cartoned Unexpanded

Group A Plastic

Cartoned, Expanded

Group A PlasticExposed, Expanded

Group A Plastic

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 6: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

6

Examples of Expanded Plastics

• Cushioned furniture

• Mattresses

• Food containers

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 7: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

7

HRR Growth Curve of

Standard Test Commodities

0

500

1.000

1.500

2.000

2.500

3.000

3.500

0 20 40 60 80 100 120 140

Heat

Rele

ase R

ate

(kW

)

Time, seconds

Exposed Expanded Group A

Cartoned Expanded Group A

Cartoned Unexpanded Group A

Class II

HRR Increase = 1.3

MW/second

Page 8: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

8

Exposed Expanded Group A Plastics –A Challenging Commodity to Protect

• Fast developing fire with high heat release rate

• Rapid fire travel (both vertical and horizontal) within the storage array

• Effectiveness of pre-wetting from sprinkler discharge is reduced due to limited commodity absorption of water

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 9: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

9

Strategy for Protecting Exposed

Expanded Group A Plastics

Stored in Racks

9

Fire Challenge Protection Strategy

Fast developing fire with high heat release rate

Large K-factor ESFR technology discharging large quantities of water. Testing was completed using nominal K=363 (25.2) pendent ESFR sprinklers in the intermediate temperature rating discharging at 4.1 bar (60 psig ) or 477 cm of water/hour (188 inches of water/hour)

Rapid fire travel (both vertical and horizontal) within the storage array

See above with vertical barriers within the storage array to limit the (1) horizontal fire travel and (2) commodity surfaces involved in the combustion process

Effectiveness of pre-wetting from sprinkler discharge is reduced due to limited commodity absorption of water

Minimum 2.4 m (8 ft.) aisle width to minimize the potential for the fire to travel to the target arrays.

Hurricane/Typhoon

Up to 20 cm of

water/hour (8 inches of

water/hour)

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED.

THIS DOCUMENT MAY NOT BE REPRODUCED OR

DISTRIBUTED WITHOUT PERMISSION OF

UNDERWRITERS LABORATORIES INC.

Page 10: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

10

Protection of Exposed Expanded

Plastics Stored in Racks

Acceptance Criteria for Test Data to be Considered for Supporting Revisions to NFPA 13

Key Acceptance Criteria:

• Number of operated sprinklers (50% safety factor applied)• No sustained combustion at the outer edge of the ends of the main

array and outer edges of the target arrays.• 537°C (1000°F) maximum 1 minute average steel temperature

measured above the fire.

Variable Investigated, But Not Incorporated Into the Design Criteria

• Blocking of certain transverse flue spaces to simulate potential conditions that may occur in the field was evaluated, but successful test results were not achieved.

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 11: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

1111

FIRE TEST NUMBER Test 1 Test 2 Test 3 Test 5 Test 6

Test Date July 9, 2012 July 13, 2012 July 18, 2012 October 31, 2012 November 8, 2012

Test ParametersStorage Type Double Row Rack Double Row Rack Double Row Rack Double Row Rack Double Row Rack

Commodity TypeExposed Expanded

Group A PlasticExposed Expanded

Group A PlasticExposed Expanded

Group A PlasticExposed Expanded

Group A PlasticExposed Expanded

Group A Plastic

Vertical Barriers

4.9 m (16 ft.) on center –

Main Array (Non-combustible)

4.9 m (16 ft.) on center - Main Array (Non-combustible)

4.9 m (16 ft.) on center - Main Array (Non-

combustible)

7.3 m (24 ft.) on center - Main Array

(10 mm(3/8 in.) plywood)

4.9 m (16 ft.) on center - Main

Array (10 mm (3/8 in.

plywood)Number of Blocked

Traverse Flue Spaces18 12 72 98 60

Length of Main Storage Array, m( ft.)

9.7 (32) 9.7 (32) 17 (56) 17 (56) 17 (56)

Nominal Storage Height, m (ft.) 6.1 (20) 6.1 (20) 10. 7 (35) 12.2 (40) 9.1 (30)

Ceiling Height, m (ft.) 12.2 (40) 12.2 (40) 12.2 (40) 13.7 (45) 12.2 (40)Aisle Width, m (ft.) 2.4 (8) 2.4 (8) 2.4 (8) 2.4 (8) 2.4 (8)

Ignition LocationBetween 2 Sprinklers

(offset)Between 2 Sprinklers

(offset)Between 2

Sprinklers (offset)Under 1 Sprinkler

(offset)Under 1 Sprinkler

(offset)

Sprinkler Type ESFR ESFR ESFR ESFR ESFR Sprinkler Orientation Pendent Pendent Pendent Pendent Pendent

Deflector to Ceiling, cm (in.) 36 (14) 36 (14) 36 (14) 36 (14) 36 (14)Sprinkler Spacing, sprinkler by

branchline, m (ft.)3 by 3 (10 by 10) 3 by 3 (10 by 10) 3 by 3 (10 by 10) 3 by 3 (10 by 10) 3 by 3 (10 by 10)

Temperature Rating, ºC (ºF) 100 (212) 101 (214) 101 (214) 101 (214) 101 (214)Nominal Sprinkler Discharge

Coefficient K, lpm/bar 0.5

(gpm/psig 0.5)320 (22.4) 363 (25.2) 363 (25.2) 363 (25.2) 363 (25.2)

Nominal Discharge Pressure, bar (psig)

3.4 (50) 4.1 (60) 4.1 (60) 4.1 (60) 4.1 (60)

Page 12: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

12

Page 13: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

13

Test 6 Arrangement

Plan View Elevation View

Exposed

Expanded

Group A

Plastic

(typical)

3/8 inch

plywood

Vertical

Barriers ,

16 ft. on center

N

8 ft.

aisle

8 ft.

aisle

Ignition -

2 half

standard

igniters

Ignition Location Vertical Barrier, 4 inches

off of lab floor (typical)

Horizontal Barrier, Placed on

top of pallets to span

transverse flues

(typical – 60 positions)

40

ft.

30

ft. no

min

al

3/8 in. Plywood

Vertical Barrier

(typical)C

L

10 ft. (typ.)14 inches

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 14: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

14

Transverse Flue Space Blocking

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 15: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

15

Test 6 – Sprinkler Operations (11)

COPYRIGHT © 2016 UL LLC. ALL

RIGHTS RESERVED. THIS DOCUMENT

MAY NOT BE REPRODUCED OR

DISTRIBUTED WITHOUT PERMISSION OF

UNDERWRITERS LABORATORIES INC.

Page 16: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

16

Test 6 – Main North Array Damage

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 17: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

17

Test 6 – Main South Array Damage

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 18: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

18

Test 6 – South Target Array Damage

View fromOutside Arrangement

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 19: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

19

Test 6 – Camera Locations

N10 ft.

(Typ.)

10 ft.

(Typ.)

Ignition location: Centered under one

sprinkler, offset in transverse flue space.

Spr 11 Spr 12 Spr 13 Spr 14 Spr 15 Spr 16 Spr 17 Spr 18 Spr 19 Spr 20

Spr 21 Spr 22 Spr 23 Spr 24 Spr 25 Spr 26 Spr 27 Spr 28 Spr 29 Spr 30

Spr 31 Spr 32 Spr 33 Spr 34 Spr 35 Spr 36 Spr 37 Spr 38 Spr 39 Spr 40

Spr 41 Spr 42 Spr 43 Spr 44 Spr 45 Spr 46 Spr 47 Spr 48 Spr 49 Spr 50

Spr 51 Spr 52 Spr 53 Spr 54 Spr 55 Spr 56 Spr 57 Spr 58 Spr 59 Spr 60

Spr 61 Spr 62 Spr 63 Spr 64 Spr 65 Spr 66 Spr 67 Spr 68 Spr 69 Spr 70

Spr 71 Spr 72 Spr 73 Spr 74 Spr 75 Spr 76 Spr 77 Spr 78 Spr 79 Spr 80

Spr 81 Spr 82 Spr 83 Spr 84 Spr 85 Spr 86 Spr 87 Spr 88 Spr 89 Spr 90

Spr 1 Spr 2 Spr 3 Spr 4 Spr 5 Spr 6 Spr 7 Spr 8 Spr 9 Spr 10

Spr 91 Spr 92 Spr 93 Spr 94 Spr 95 Spr 96 Spr 97 Spr 98 Spr 99 Spr 100

Infrared Camera View

South

Wall

View

North East Corner

Balcony Camera View

Initial

Ignition

Location

of South

Target

Array

COPYRIGHT © 2016 UL LLC. ALL RIGHTS

RESERVED. THIS DOCUMENT MAY NOT

BE REPRODUCED OR DISTRIBUTED

WITHOUT PERMISSION OF

UNDERWRITERS LABORATORIES INC.

Page 20: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

20

Test 6 View from NE Balcony

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 21: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

21

Test 6 – View from South Target Array

COPYRIGHT © 2016 UL LLC. ALL

RIGHTS RESERVED. THIS DOCUMENT

MAY NOT BE REPRODUCED OR

DISTRIBUTED WITHOUT PERMISSION OF

UNDERWRITERS LABORATORIES INC.

Page 22: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

22

Test 6 – View from South East Corner - Infrared

22

COPYRIGHT © 2016 UL LLC. ALL

RIGHTS RESERVED. THIS DOCUMENT

MAY NOT BE REPRODUCED OR

DISTRIBUTED WITHOUT PERMISSION OF

UNDERWRITERS LABORATORIES INC.

Page 23: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

FIRE TEST No. Test 1 Test 2 Test 3 Test 5 Test 6 Test 7 Test 8Test Date July 9, 2012 July 13, 2012 July 18, 2012 Oct. 31, 2012 Nov. 8, 2012 June 8, 2013 June 19, 2014

Test Parameters

Storage TypeDouble

Row RackDouble

Row RackDouble

Row RackDouble

Row RackDouble

Row RackDouble

Row RackDouble

Row Rack

Commodity TypeExposed Expanded

Group A PlasticExposed Expanded

Group A PlasticExposed Expanded

Group A PlasticExposed Expanded

Group A PlasticExposed Expanded

Group A PlasticExposed Expanded

Group A PlasticExposed Expanded

Group A Plastic

Vertical Barriers

4.9 m (16 ft.) on center –

Main Array (Non-combustible)

4.9 m (16 ft.) on center - Main Array (Non-combustible)

4.9 m (16 ft.) on center - Main Array (Non-combustible)

7.3 m (24 ft.) on center - Main Array

(10 mm(3/8 in.) plywood)

4.9 m (16 ft.) on center - Main Array

(10 mm (3/8 in. plywood)

4.9 m (16 ft.) on center - Main Array

(10 mm (3/8 in. plywood)

4.9 m (16 ft.) on center - Main Array

(10 mm (3/8 in. plywood)

Number of Blocked Traverse Flue Spaces

18 12 72 98 60 None None

Length of Main Storage Array, m ( ft.)

9.7 (32) 9.7 (32) 17 (56) 17 (56) 17 (56) 12.2 (40) 17 (56)

Nominal Height, m (ft.) 6.1 (20) 6.1 (20) 10. 7 (35) 12.2 (40) 9.1 (30) 9.1 (30) 10.7 (35)

Ceiling Height, m (ft.) 12.2 (40) 12.2 (40) 12.2 (40) 13.7 (45) 12.2 (40) 12.2 (40) 12.2 (40)Aisle Width, m (ft.) 2.4 (8) 2.4 (8) 2.4 (8) 2.4 (8) 2.4 (8) 2.4 (8) 2.4 (8)

Ignition LocationBetween 2

Sprinklers (offset)Between 2 Sprinklers

(offset)Between 2 Sprinklers

(offset)Under 1 Sprinkler

(offset)Under 1 Sprinkler

(offset)Under 1 Sprinkler

(offset)

Between 2 Sprinklers (offset)

Sprinkler Type ESFR ESFR ESFR ESFR ESFR ESFR ESFRSprinkler Orientation Pendent Pendent Pendent Pendent Pendent Pendent Pendent

Deflector to Ceiling, cm (in.)

36 (14) 36 (14) 36 (14) 36 (14) 36 (14) 36 (14) 36 (14)

Sprinkler Spacing, m (ft.)3 by 3(10 by

10)3 by 3(10 by

10)3 by 3 10 by 10) 3 by 3 10 by 10)

3 by 3(10 by 10)

3 by 3(10 by 10)

3 by 3 10 by 10)

Temp Rating, ºC (ºF) 100 (212) 101 (214) 101 (214) 101 (214) 101 (214) 101 (214) 101 (214)Nominal Sprinkler

Discharge Coefficient K, lpm/bar 0.5 (gpm/psig 0.5)

320 (22.4) 363 (25.2) 363 (25.2) 363 (25.2) 363 (25.2) 363 (25.2) 363 (25.2)

Nominal Discharge Pressure, bar (psig)

3.4 (50) 4.1 (60) 4.1 (60) 4.1 (60) 4.1 (60) 4.1 (60) 4.1 (60)

Tests Used to Establish 12.2 m (40 ft.) Design Criteria

Page 24: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

24

Test 7 – Sprinkler Operations (7)

N10 ft.

(Typ.)

10 ft.

(Typ.)

Ignition location: Centered under one

sprinkler, offset in transverse flue space.

dno dno dno dno dno dno dno dno dno dno

dno dno dno dno dno dno dno dno dno dno

dno dno dno 1:28 0:57 1:02 dno dno dno dno

dno dno dno dno 0:47 1:09 dno dno dno dno

dno dno dno dno 1:07 1:02 dno dno dno dno

dno dno dno dno dno dno dno dno dno dno

dno dno dno dno dno dno dno dno dno dno

dno dno dno dno dno dno dno dno dno dno

dno dno dno dno dno dno dno dno dno dno

dno dno dno dno dno dno dno dno dno dno

dno – did not operate

COPYRIGHT © 2016 UL LLC. ALL

RIGHTS RESERVED. THIS DOCUMENT

MAY NOT BE REPRODUCED OR

DISTRIBUTED WITHOUT PERMISSION OF

UNDERWRITERS LABORATORIES INC.

Page 25: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

25

Test 7 – Main North Array Damage

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 26: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

26

Test 7 – View from NE Balcony

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 27: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

27

Test 8 – Main North Array Damage

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 28: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

28

Fire Travel Past Vertical Barriers –Commodity Extending Beyond Barrier

Exposed

Expanded

Group A

Plastic

(typical)

Vertical

Barrier 10 – 12.5 cm

(4 – 5 in.)

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 29: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

29

FIRE TEST NUMBER Test 1 Test 2 Test 3 Test 5 Test 6 Test 7 Test 8

Test Date July 9, 2012 July 13, 2012 July 18, 2012 October 31, 2012November 8,

2012June 8, 2013

June 19, 2014

Test Results

Length of Test, minutes 31 31 31 31 31 31 31

First Sprinkler Operation Time, min:sec

0:39 0:44 0:52 0:47 0:48 0:47 0:48

Last Sprinkler Operation Time, min:sec

8:23 3:21 1:45 1:39 4:35 1:28 2:28

Number of Operated Sprinklers

12 6 10 18 11 7 7Peak Gas Temperature at Ceiling Above Ignition, ºC

(ºF)296 (564) 292 (558) 614 (1138) 539 (1002) 116 (241) 212 (414) 469 (877)

Maximum 1 minute Average Gas Temperature at Ceiling Above Ignition,

ºC (ºF)

124 (255) 104 (220) 178 (353) 254 (489) 66 (151) 88 (191) 151 (303)

Peak Steel Temperature at Ceiling Above Ignition, ºC

(ºF)52 (126) 48 (119) 63 (145) 71 (160) 54 (129) 56 (133) 58 (136)

Maximum 1 minute Average Steel Temperature at Ceiling Above Ignition,

ºC (ºF)

51 (124) 47 (117) 61 (141) 69 (156) 53 (127) 53 (127) 57 (134)

Ignition Time of Target Array, minutes:seconds

None None None1:01

(North Target)1:27

(South Target) None None

Fire Travel to Extremities of Test Array

Yes (East and West

end of Main)

Yes (West end of Main)

No

Yes(North Target Array Burned Through to

Extremities)

Yes(South Target Array Burned Through to

Extremities)

No No

Page 30: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

30

Testing Activity Subsequent to NFPA Second Draft TC Meeting

• During the June 2014 Second Draft meeting of the NFPA TC on

Sprinkler System Discharge Criteria, several committee members

expressed concern that there was only one design criteria for a 40 ft.

high ceiling.

• Based upon the concern expressed by members of the TC, FPRF

worked quickly to solicit sponsors and organize a Technical Panel for

follow-on research to generate data to support sprinkler system

design criteria at a lower ceiling height.

• Based upon subsequent FPRF Technical Panel discussions, it was

agreed to conduct testing to support a design criteria for a 9.1 m (30

ft.) ceiling.COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 31: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

31

Fire Protection Research Foundation Project Team 9.1 m (30 ft.) Series

Sponsors

• Viking Sprinkler

• Tyco Fire and Building Products

• Property Insurance Research Group

Project Contractor

• UL LLC

Technical Panel

• Ken Linder, Swiss Re

• Rich Pehrson, Rep. International Fire Marshals Association

• Jason Huczek, Southwest Research Institute

• John Denhardt, Strickland Fire Protection

• Matt Klaus, NFPA Staff Liaison

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.

Page 32: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

Tests for 9.1 m (30 ft.) Design Criteria (Parameters)FIRE TEST NUMBER Test 9 Test 10

Test Date Oct. 28, 2014 Oct. 30, 2014

Test Parameters

Storage Type Double Row Rack Double Row Rack

Commodity Type Exposed Expanded Group A Plastic Exposed Expanded Group A Plastic

Vertical Barriers4.9 m (16 ft.) on center - Main

Array (10 mm (3/8 in. plywood)

4.9 m (16 ft.) on center - Main Array

(10 mm (3/8 in. plywood)

Number of Blocked Traverse Flue Spaces None None

Length of Main Storage Array, m ( ft.) 9.7 (32) 9.7 (32)

Nominal Storage Height, m (ft.) 6.1 (20) 7.6(25)

Ceiling Height, m (ft.) 9.1 (30) 9.1 (30)

Aisle Width, m (ft.) 2.4 (8) 2.4 (8)

Ignition Location Under 1 Sprinkler (offset) Between 2 Sprinklers (offset)

Sprinkler Type ESFR ESFR

Sprinkler Orientation Pendent Pendent

Deflector to Ceiling, cm (in.) 36 (14) 36 (14)

Sprinkler Spacing, sprinkler by branchline, m (ft.) 3 by 3 (10 by 10) 3 by 3 (10 by 10)

Temperature Rating, ºC (ºF) 101 (214) 101 (214)Nominal Sprinkler Discharge Coefficient K,

lpm/bar 0.5 (gpm/psig 0.5)363 (25.2) 363 (25.2)

Nominal Discharge Pressure, bar (psig) 2 (30) 2 (30)

Page 33: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

33

FIRE TEST NUMBER Test 9 Test 10Test Date October 28, 2014 October 30, 2014

Test Results

Length of Test, minutes 31 31

First Sprinkler Operation Time, min:sec

0:47 0:53

Last Sprinkler Operation Time, min:sec

1:24 1:14

Number of Operated Sprinklers

7 7

Peak Gas Temperature at Ceiling Above Ignition, ºC (ºF)

96 (204) 532 (990)

Maximum 1 minute Average Gas Temperature at Ceiling

Above Ignition, ºC (ºF)59 (138) 247 (477)

Peak Steel Temperature at Ceiling Above Ignition, ºC (ºF)

46 (114) 65 (149)

Maximum 1 minute Average Steel Temperature at Ceiling

Above Ignition, ºC (ºF)44 (112) 62 (144)

Ignition Time of Target Array, minutes:seconds None None

Fire Travel to Extremities of Test Array No No

Tests Used to Establish 9.1 m (30 ft.) Design Criteria

COPYRIGHT © 2016 UL LLC. ALL

RIGHTS RESERVED. THIS DOCUMENT

MAY NOT BE REPRODUCED OR

DISTRIBUTED WITHOUT PERMISSION OF

UNDERWRITERS LABORATORIES INC.

Page 34: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

34

Tests Used to Establish Design Criteria (12.2 and 9.1 m High Ceilings)

ResultsFIRE TEST NUMBER Test 2 Test 7 Test 8 Test 9 Test 10Test Date July 13, 2012 June 8, 2013 June 19, 2014 October 28, 2014 October 30, 2014

Test ResultsLength of Test, minutes 31 31 31 31 31

First Sprinkler Operation Time, min:sec

0:44 0:47 0:48 0:47 0:53

Last Sprinkler Operation Time, min:sec

3:21 1:28 2:28 1:24 1:14

Number of Operated Sprinklers

6 7 7 7 7

Peak Gas Temperature at Ceiling Above Ignition, °F

292 (558) 212 (414) 469 (877) 96 (204) 532 (990)

Maximum 1 minute Average Gas Temperature at Ceiling

Above Ignition, °F104 (220) 88 (191) 151 (303) 59 (138) 247 (477)

Peak Steel Temperature at Ceiling Above Ignition, °F

48 (119) 56 (133) 58 (136) 46 (114) 65 (149)

Maximum 1 minute Average Steel Temperature at Ceiling

Above Ignition, °F47 (117) 53 (127) 57 (134) 44 (112) 62 (144)

Ignition Time of Target Array, minutes:seconds

None None None None None

Fire Travel to Extremities of Test Array

Yes (West end of Main)

No No No No

Page 35: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

35

NFPA 13-2016 Edition Including TIAKey Criteria in Chapter 17

(Rack Stored Exposed, Expanded Plastics)

Criteria 12.2 m (40 ft.) Ceiling 9.1 m (30 Ft.) Ceiling

Maximum storage height 10.7 m (35 ft.) 7.6 m (25 ft.)

Minimum design pressure 4.1 bar (60 psi) 2.0 bar (30 psi)

Minimum aisle width 2.4 m (8 ft.)

Sprinkler K=363 (25.2) Pendent ESFR -Intermediate Temperature Rated

Design area 12 most demanding sprinklers

Minimum water duration 60 minutes

Minimum hose allowance 945 Lpm (250 gpm)

Max vertical barrier distance 5 m (16.5 ft.)

Vertical barrier material 10 mm (3/8 in) plywood, 0.8 mm (22 gauge) steel or

equivalent

Max area between vertical barriers and aisles

11.5 m2 (124 ft2)

Vertical barrier size Extend across longitudinal flue to the top of the storage

Commodity extension into aisle 101 mm (4 in.) allowed beyond barrier into aisle

Page 36: Sprinkler Protection Criteria for Rack- Stored Exposed Expanded … · 2017-03-22 · To develop cost effective sprinkler system design criteria for the rack storage of exposed expanded

36

Protection of Exposed ExpandedPlastics Stored in Racks

FPRF Reports can be found at:

www.nfpa.org/foundation

• Reports and Proceedings

• Suppression

• Applications

• Protection of Exposed

Expanded Group A Plastics

with ESFR Sprinklers and

Vertical Barriers

COPYRIGHT © 2016 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.