sprinkler pressure/flux densityconforms with gost r 51043-2002, automatic water and foam fire...

26
General Description Pressure/Flux Density data provided in this document are determined by calculating the average rate of water collection in spray tests using the fol- lowing parameters: • Test array 1,5m x 1,5m area • Collection pans 0,5m 2 area Sprinkler deflectors located 2,5m distance from tops of pans Sprinkler deflectors located 17,8cm distance below ceiling Discharge pressures 0,1MPa to 1,1MPa The Pressure/Flux Density test method conforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical requirements. Test methods. NOTICE The effects of various deflector to ceiling distances, flowing pressures other than those shown, obstruc- tion to water distribution, ventilation, and sample to sample variation are not included. The method chosen to portray the sprinkler distribution is based on giving the sprinkler designer the quickest reference as to the overall spray pattern in a laboratory environ- ment and may not reflect actual condi- tions experienced in the field. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. SPRINKLER PRESSURE/FLUX DENSITY Page 1 of 26 FEBRUARY 2020 TFP711 IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Worldwide Contacts www.tyco-fire.com

Upload: others

Post on 12-Oct-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

General DescriptionPressure/Flux Density data provided in this document are determined by calculating the average rate of water collection in spray tests using the fol-lowing parameters:

• Test array 1,5m x 1,5m area

• Collection pans 0,5m2 area

• Sprinkler deflectors located 2,5m distance from tops of pans

• Sprinkler deflectors located 17,8cm distance below ceiling

• Discharge pressures 0,1MPa to 1,1MPa

The Pressure/Flux Density test method conforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical requirements. Test methods.

NOTICEThe effects of various deflector to ceiling distances, flowing pressures other than those shown, obstruc-tion to water distribution, ventilation, and sample to sample variation are not included. The method chosen to portray the sprinkler distribution is based on giving the sprinkler designer the quickest reference as to the overall spray pattern in a laboratory environ-ment and may not reflect actual condi-tions experienced in the field.

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

SPRINKLER PRESSURE/FLUX DENSITY

Page 1 of 26 FEBRUARY 2020 TFP711

IMPORTANTRefer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information.

Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.

Worldwide Contacts www.tyco-fire.com

Page 2: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

Table of Contents

SIN Model K-factor Type Data Sheet Page

TY1121 TY-FRL 2.8k (K40) Std. Coverage Upright TFP130 4

TY1131 TY-FRB 2.8k (K40) Std. Coverage Upright TFP171 4TY1151 TY-B 2.8k (K40) Std. Coverage Upright TFP151 4TY1221 TY-FRL 2.8k (K40) Std. Coverage Pendent TFP130 5TY1231 TY-FRB 2.8k (K40) Std. Coverage Pendent TFP171 5TY1251 TY-B 2.8k (K40) Std. Coverage Pendent TFP151 5TY2108 TY-B K58 Upright (LPCB, VdS Coverage) TFP670 6TY2109 TY-FRB K58 Upright (LPCB, VdS Coverage) TFP670 6TY2131 TY-FRB 4.2k (K60) Std. Coverage Upright TFP171 7TY2149 TY-B (4mm) K57 Std. Coverage Upright TFP672 6TY2208 TY-B K58 Pendent (LPCB, VdS Coverage) TFP670 7TY2209 TY-FRB K58 Pendent (LPCB, VdS Coverage) TFP670 7TY2231 TY-FRB 4.2k (K60) Std. Coverage Pendent TFP171 8TY2234 LFII 4.9k (K70) Residential Pendent TFP400 8TY2249 TY-B (4mm) K57 Std. Coverage Pendent TFP672 9TY3111 TY-L 5.6k (K80) Std. Coverage Upright TFP110 9TY3121 TY-FRL 5.6k (K80) Std. Coverage Upright TFP130 10TY313 TY-FRB 5.6k (K80) Std. Coverage Upright TFP172 10TY3131 TY-FRB 5.6k (K80) Std. Coverage Upright TFP171 11TY3141 TY-B (4mm) K80 Std. Coverage Upright TFP672 11TY315 TY-B 5.6k (K80) Std. Coverage Upright TFP152 10TY3151 TY-B 5.6k (K80) Std. Coverage Upright TFP151 11TY3211 TY-L 5.6k (K80) Std. Coverage Pendent TFP110 11TY3221 TY-FRL 5.6k (K80) Std. Coverage Pendent TFP130 12TY3230 DS-1 5.6k (K80) Std. Coverage Dry SS Pendent TFP560 12TY3231 TY-FRB 5.6k (K80) Std. Coverage Pendent TFP171 13TY323 TY-FRB 5.6k (K80) Std. Coverage Pendent TFP172 13

TY3235 DS-1 5.6k (K80) Std. Coverage Dry Pendent TFP510 12TY3241 TY-B (4mm) K80 Std. Coverage Pendent TFP672 13TY3250 DS-1 5.6k (K80) Std. Coverage Dry SS Pendent TFP560 12TY3251 TY-B 5.6k (K80) Std. Coverage Pendent TFP151 13TY325 TY-B 5.6k (K80) Std. Coverage Pendent TFP152 13

TY3255 DS-1 5.6k (K80) Std. Coverage Dry Pendent TFP500 12TY3531 RFII 5.6k (K80) Std. Cov. QR Concealed Pendent TFP181 14TY3532 RFII 5.6k (K80) Ext. Cov. Concealed Pendent TFP260 14TY3551 RFII 5.6k (K80) Std. Cov. SR Concealed Pendent TFP181 14TY363 TY-FRB 5.6k (K80) Conventional “Old Style” TFP667 14TY3631 TY-FRB 5.6k (K80) Conventional “Old Style” TFP666 15TY3641 TY-B (4mm) K80 Conventional “Old Style” TFP663 15

TFP711Page 2 of 26

Page 3: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

Table of Contents

SIN Model K-factor Type Data Sheet Page

TY365 TY-B 5.6k (K80) Conventional “Old Style” TFP662 14TY3651 TY-B 5.6k (K80) Conventional “Old Style” TFP661 15TY3935 DS-1 5.6k (K80) Std. Coverage Dry Pendent TFP510 12TY4111 TY-L 8.0k (K115) Std. Coverage Upright TFP110 15TY4121 TY-FRL 8.0k (K115) Std. Coverage Upright TFP130 16TY4131 TY-FRB 8.0k (K115) Std. Coverage Upright TFP171 16TY4141 TY-FRB (4mm) K115 Std. Coverage Upright TFP672 16TY4151 TY-B 8.0k (K115) Std. Coverage Upright TFP151 16TY4211 TY-L 8.0k (K115) Std. Coverage Pendent TFP110 17TY4221 TY-FRL 8.0k (K115) Std. Coverage Pendent TFP130 17TY4231 TY-FRB 8.0k (K115) Std. Coverage Pendent TFP171 18TY4241 TY-B (4mm) K115 Std. Coverage Pendent TFP672 18TY4251 TY-B 8.0k (K115) Std. Coverage Pendent TFP151 18TY4631 TY-FRB 8.0k (K115) Conventional “Old Style” TFP666 18TY4641 TY-B (4mm) K115 Conventional “Old Style” TFP663 18TY4651 TY-B 8.0k (K115) Conventional “Old Style” TFP661 18TY5111 ELO-231 11.2k (K160) Std. Coverage Upright TFP340 19TY5131 ELO-231FRB 11.2k (K160) Std. Coverage Upright TFP344 19TY5137 EC-11 11.2k (K160) Ext. Coverage Upright TFP220 19TY5151 ELO-231B 11.2k (K160) Std. Coverage Upright TFP342 19TY5211 ELO-231 11.2k (K160) Std. Coverage Pendent TFP340 20TY5231 ELO-231FRB 11.2k (K160) Std. Coverage Pendent TFP344 20TY5237 EC-11 11.2k (K160) Ext. Coverage Pendent TFP220 20TY5251 ELO-231B 11.2k (K160) Std. Coverage Pendent TFP342 20TY6137 EC-14 14.0k (K200) Ext. Coverage Upright TFP220 21TY6226 ESFR-1 14.0k (K200) ESFR Pendent TFP318 21TY6236 ESFR-14 14.0k (K200) ESFR Pendent TFP319 22TY6237 EC-14 14.0k (K200) Ext. Coverage Pendent TFP220 22TY7103 Ultra K17 16.8k (K240) Storage CMSA Upright (QUELL Only) TFP331 23TY7126 ESFR-17 16.8k (K240) ESFR Upright TFP316 23TY7151 K17-231 16.8k (K240) Std. Coverage Upright TFP332 23TY7153 Ultra K17 16.8k (K240) Storage CMSA Upright TFP330 23TY7223 ESFR-17 16.8k (K240) ESFR Pendent TFP317 24TY7226 ESFR-17 16.8k (K240) ESFR Pendent TFP315 24TY7229 ESFR-17 16.8k (K240) ESFR Dry Pendent TFP320 25TY7251 K17-231 16.8k (K240) Std. Coverage Pendent TFP332 25TY9128 EC-25 25.2k (K360) Ext. Coverage Upright TFP213 26TY9226 ESFR-25 25.2k (K360) ESFR Pendent TFP312 26

TFP711Page 3 of 26

Page 4: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

Den

sitie

s (l/

m2∙

s)TY1121 - K40

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

Den

sitie

s (l/

m2∙

s)

TY1131, TY1151 - K40

TFP711Page 4 of 26

Page 5: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.02

0.04

0.06

0.08

0.10

0.12

0.14

0.16

Den

sitie

s (l/

m2∙

s)TY1221 - K40

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

Den

sitie

s (l/

m2∙

s)

TY1231, TY1251 - K40

TFP711Page 5 of 26

Page 6: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

Den

sitie

s (l/

m2∙

s)TY2108, TY2109 - K58

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

Den

sitie

s (l/

m2∙

s)

TY2149 - K57

TFP711Page 6 of 26

Page 7: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

Den

sitie

s (l/

m2∙

s)TY2131 - K60

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

Den

sitie

s (l/

m2∙

s)

TY2208, TY2209 - K58

TFP711Page 7 of 26

Page 8: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

Den

sitie

s (l/

m2∙

s)

TY2234 - K70

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

Den

sitie

s (l/

m2∙

s)TY2231 - K60

TFP711Page 8 of 26

Page 9: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.1

0.2

0.3

0.4

0.5

0.6

Den

sitie

s (l/

m2∙

s)

TY3111 - K80

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

Den

sitie

s (l/

m2∙

s)TY2249 - K57

TFP711Page 9 of 26

Page 10: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.1

0.2

0.3

0.4

0.5

0.6

Den

sitie

s (l/

m2∙

s)TY3121 - K80

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0

Den

sitie

s (l/

m2∙

s)

TY313, TY315 - K80

TFP711Page 10 of 26

Page 11: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.1

0.2

0.3

0.4

0.5

0.6

Den

sitie

s (l/

m2∙

s)TY3131, TY3141, TY3151 - K80

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

Den

sitie

s (l/

m2∙

s)

TY3211 - K80

TFP711Page 11 of 26

Page 12: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

Den

sitie

s (l/

m2∙

s)TY3221 - K80

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

Den

sitie

s (l/

m2∙

s)

TY3230, TY3235, TY3250, TY3255, TY3935 - K80

TFP711Page 12 of 26

Page 13: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

Den

sitie

s (l/

m2∙

s)TY3231, TY3241, TY3251 - K80

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0

Den

sitie

s (l/

m2∙

s)

TY323, TY325 - K80

TFP711Page 13 of 26

Page 14: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

Den

sitie

s (l/

m2∙

s)

TY363, TY365 - K80

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

Den

sitie

s (l/

m2∙

s)TY3531, TY3532, TY3551 - K80

TFP711Page 14 of 26

Page 15: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0

Den

sitie

s (l/

m2∙

s)

TY4111 - K115

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

Den

sitie

s (l/

m2∙

s)TY3631, TY3641, TY3651 - K80

TFP711Page 15 of 26

Page 16: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

Den

sitie

s (l/

m2∙

s)

TY4131, TY4141, TY4151 - K115

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

Den

sitie

s (l/

m2∙

s)TY4121 - K115

TFP711Page 16 of 26

Page 17: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0

Den

sitie

s (l/

m2∙

s)TY4211 - K115

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

Den

sitie

s (l/

m2∙

s)

TY4221 - K115

TFP711Page 17 of 26

Page 18: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

Den

sitie

s (l/

m2∙

s)

TY4631, TY4641, TY4651 - K115

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0

Den

sitie

s (l/

m2∙

s)TY4231, TY4241, TY4251 - K115

TFP711Page 18 of 26

Page 19: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.2

0.4

0.6

0.8

1.0

1.2

Den

sitie

s (l/

m2∙

s)TY5111, TY5131, TY5151 - K160

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

Den

sitie

s (l/

m2∙

s)

TY5137 - K80

TFP711Page 19 of 26

Page 20: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

Den

sitie

s (l/

m2∙

s)

TY5237 - K160

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.2

0.4

0.6

0.8

1.0

1.2

Den

sitie

s (l/

m2∙

s)TY5211, TY5231, TY5251 - K160

TFP711Page 20 of 26

Page 21: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

Den

sitie

s (l/

m2∙

s)TY6137 - K200

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0

Den

sitie

s (l/

m2∙

s)

TY6226 - K200

TFP711Page 21 of 26

Page 22: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.05

0.10

0.15

0.20

0.25

0.30

Den

sitie

s (l/

m2∙

s)

TY6237 - K200

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

Den

sitie

s (l/

m2∙

s)TY6236 - K200

TFP711Page 22 of 26

Page 23: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

0

Den

sitie

s (l/

m2∙

s)TY7103, TY7151, TY7153 - K240

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

0

Den

sitie

s (l/

m2∙

s)

TY7126 - K240

TFP711Page 23 of 26

Page 24: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

0

Den

sitie

s (l/

m2∙

s)

TY7226 - K240

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

0

Den

sitie

s (l/

m2∙

s)TY7223 - K240

TFP711Page 24 of 26

Page 25: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.5

1.0

1.5

2.0

2.5

Den

sitie

s (l/

m2∙

s)TY7229 - K240

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.5

1.0

1.5

2.0

2.5

Den

sitie

s (l/

m2∙

s)

TY7251 - K240

TFP711Page 25 of 26

Page 26: Sprinkler Pressure/Flux Densityconforms with GOST R 51043-2002, Automatic water and foam fire fighting systems. Sprinklers, spray nozzles and water mist nozzles. General technical

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.5

1.0

1.5

2.0

2.5

Den

sitie

s (l/

m2∙

s)

TY9226 - K360

0 0.2 0.4 0.6 0.8 1.0 1.2

Pressure (MPa)

0

0.5

1.0

1.5

2.0

2.5

Den

sitie

s (l/

m2∙

s)TY9128 - K360

EDIT DATA SHEET NUMBERPage 26 of EDIT PAGE COUNT