specification for alternating current switches for voltages above 1 000 v

13
Gr 3 IS 9920 ( Pad III ) : 1982 Indian Standard SPECIFICATION FOR ALTERNATING CURRENT SWITCHES FOR VOL TAGES AB OVE 1 000 V PART Ill DESIGN AND CONSTRUCTION First Reprint AUGUST 1996 ) UDC 621.316.542.025 0 Copyright 1982 BUREAU OF INDIAN STANDARDS MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG NEW DELHI I 10002 November 1982 ( Reaffirmed 1997 )

Upload: vikas-razdan

Post on 03-Jun-2018

226 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SPECIFICATION FOR  ALTERNATING CURRENT SWITCHES  FOR VOLTAGES ABOVE 1 000 V

8/12/2019 SPECIFICATION FOR ALTERNATING CURRENT SWITCHES FOR VOLTAGES ABOVE 1 000 V

http://slidepdf.com/reader/full/specification-for-alternating-current-switches-for-voltages-above-1-000-v 1/12

Page 2: SPECIFICATION FOR  ALTERNATING CURRENT SWITCHES  FOR VOLTAGES ABOVE 1 000 V

8/12/2019 SPECIFICATION FOR ALTERNATING CURRENT SWITCHES FOR VOLTAGES ABOVE 1 000 V

http://slidepdf.com/reader/full/specification-for-alternating-current-switches-for-voltages-above-1-000-v 2/12

IS : 9920 Part III ) - 1982

Indian Standard

SPEClFICATION FORALTERN~ATING CURRENT SWITCHES

FOR VOLTAGES ABOVE 1000 VP RT III DESIGN ND CONSTRUCTION

High Voltage Switchgear and Controlgear

Sectional Committee, ETDC 58

Chairtnon Represetzting

SHRI H. M. PAI The Ahmedabad Electricity Co Ltd, Ahmadabad

MembersSHRI M. B. BAHUL KAR Alternate to

Shri H. M. Pai )SHRI K. K. BOSE Calcutta Electric Supply Corporation L td, Calcutta

SHRI T. K . GHOSE Alternate )SHR~ R. CHANDRAM OUL ISMT C. BALIGA ( Alternate )

Tata Hydro-Electric Power Supply Co Ltd, Bombay

DIRECTOR, SUB-STATION Central Electricity Authority, New DelhiDIRECTORATE

DEPUTY DIRE CTOR, SUB-STATION ( Alternate )

DIRECTORSHRI S. ANANT HA KRISHNAN

Central Power Research Institute, Bangalore

( Alternate )SHRI V. J AYACHANDRAN Alternate )

SHRI M. L. DONGRE Bombay Electric Supply and Transport Undertaking,Born bay

SHRI Y. K . PALVANK AR Alternate )SHRI B. V. ESWAR ASEA, Nasik

SHRI S. SLIBK AMANI AN Alternate 1SHRI K . L . GARG Directorate General of Supplies and Disposals,

New DelhiSHRI R. V. NARAY ANAN ( Alternate )

SHRI B. N. GHOSHSHRI D. K . SINGLE Akernate )

Bharat Heavy Electricals Ltd, R D Unit, Bhopal

SHR~ A. RAJ A RAO ( Alternute )

Continued on page 2

@ Copyright 1982BUREAU OF I NDIAN STANDARDS

This publication is protected under the Indian Copyright Act XI V of 1957 ) andreproduction in whole or in part by any means except wi th written permission ofthe publisher shall be deemed to be an infringement of copyright under the said Act.

Page 3: SPECIFICATION FOR  ALTERNATING CURRENT SWITCHES  FOR VOLTAGES ABOVE 1 000 V

8/12/2019 SPECIFICATION FOR ALTERNATING CURRENT SWITCHES FOR VOLTAGES ABOVE 1 000 V

http://slidepdf.com/reader/full/specification-for-alternating-current-switches-for-voltages-above-1-000-v 3/12

IS : 9920 Part HI ) - 1982

( Contimed from page 1 )

M ember s

SHRI D. P. GUPTA

Representing

Directorate General of Technical Development,New Delhi

SHRI L. GOPALAKRISHNAN AI tern ate )SHRI J AYANT N. GURJ ARSHRI P. D. J AHAGI RDAR

Kirloskar-Asea Limited, Bangalore

SHRI J AVEED AHMEDMaharashtra State Electricity Board, BombayNGEF Limited, Bangalore

SHR~ K . P. SARATH Y ( Alternate )SHRI P. M. J OSEPH Aluminium Industries L imited, K undara

SHRI C. M. A. NAY AR ( Alternate )SHRI S. C. K HU RANA Rural Electri fication Corporation Ltd, New Delhi

SHRI G. L . DUA ( Alternate )SHRI B. N. KISHORE Crompton Greaves L td, Bombay

SHRI A. N . VENUGOPAL Alternate )SHRI P. C. MAL K ANI Central Public Works Department, New Delhi

SURVEYOR OF WORKS II I ( Alternate )SHRI V. S. MANI Hindustan Brown Boveri L td, Bombay

SHRI S. R. POTNI S ( Alternate )SHRI S. G. ME NON Tata Consulting Engineer, Bombay

SHRI C. S. KUM AR ( Alternate )SHRI S. K. MUK HERJ EE National Test ‘House, Calcutta

SHRI P. C. PRADHAN ( Alternate )SHRI B. S. NARASIMHAN Mysore Electrical Industries, Bangalore

SHRI R. SATYANARAYANA Alternate )SHRI J . S. NEGI J yoti Limited, Vadodara

SHRI R. M. NANAVAT I ( Alternate )SHRI S. G. NE NE Siemens India L td, Bombay

SHRI T. C. NE EL AKANT AN Alternate )SHRI A. S. PINTO

SHRI S. K. BASU ( Alternate )Delhi E lectric Supply Undertaking, New Delhi

THI RU T. E. B. SAMUEL Tamil Nadu Electricity Board, MadrasTHIRU T. SHEMBAHARAJ AN Alternate )

SHRI S. P. SACHDEV,Director ( Elec tech )

Director General , I S1 ( Ex-officio Member)

Secretary

SHRI K . GANESHAssistant Director (.Elec tech ), ISI

Page 4: SPECIFICATION FOR  ALTERNATING CURRENT SWITCHES  FOR VOLTAGES ABOVE 1 000 V

8/12/2019 SPECIFICATION FOR ALTERNATING CURRENT SWITCHES FOR VOLTAGES ABOVE 1 000 V

http://slidepdf.com/reader/full/specification-for-alternating-current-switches-for-voltages-above-1-000-v 4/12

IS : 9920 Part III ) - 1982

Indian Standard

SPECIFICATION FORALTERNATING CURRENT SWITCHES

FOR VOLTAGES ABOVE 1000 V

PART III DESIGN AND CONSTRUCTION

a. FOREWORD

0.1 This Indian Standard ( Part III ) was adopted by the Indian StandardsInstitution on 26 May 1982, after the draft finalized by the High Voltage

Switchgear and Controlgear Sectional Committee had been approved bythe Electrotechnical Division Council.

0.2 High voltage switches are manufactured in large quantities in India,for applications in systems where the voltage exceeds 1000 V. Thisstandard was originally brought out in 1968 as IS-:4710 to cover theessential requirements and methods of tests of switches and switch isolatorsfor voltages above 1000 V, but not exceeding 11000 V.

0.3 In the last few years in the development of high voltage switchgearthere has been considerable advancement in know-how on the performance

of the equipment and the associated stipulations that are to be preciselymade in the national standards. Considerable modifications, therefore,became necessary in the specification on circuit breakers, isolators, fuses,etc in order to keep pace with the international thinking on the subject.

0.4 This standard is therefore being brought out to incorporate the latestin technology as is also recognized in the international field. For thepurposes of clarity, this standard is being brought out in four parts asfollows:

Part I General and definitions

Part II RatingPart III Design and constructionPart IV Type tests and routine tests ( under consi derat i on

All parts shall be read in conjunction with one another. This standard( Part Ill ) which deals with the design and constructional aspects of theequipment partly replaces IS:4710-1968”. All the parts of this standardwhen published shall replace IS:4710 completely.

*Specification for switches and switch-isolators above 1 000 V but not exceeding11000 v.

3

Page 5: SPECIFICATION FOR  ALTERNATING CURRENT SWITCHES  FOR VOLTAGES ABOVE 1 000 V

8/12/2019 SPECIFICATION FOR ALTERNATING CURRENT SWITCHES FOR VOLTAGES ABOVE 1 000 V

http://slidepdf.com/reader/full/specification-for-alternating-current-switches-for-voltages-above-1-000-v 5/12

IS : 9920 Part III ) - 1982

0.5 While preparing this standard, considerable assistance has been derivedfrom the following publications issued by the International ElectrotechnicalCommission:

IEC Pub 265 ( 1968 ) High voltage switches.

IEC Pub 265A ( 1969 ) High voltage switches. Tests for singlecapacitor bank switching.

IEC Pub 265B (1969) Second supplement to Publication 265 ( 1968).

IEC Pub 265C ( 1970 ) Third supplement to Publication 265 ( 1968 ).Tests for line and cable switching.

0.6 In order to facilitate comparison with the international standards andfor ease of reference, the Committee has decided to add in the form of anAppendix, the major differences between the various parts of this Indian

Standard and the corresponding IEC Publications. However, this standard(Part III) corresponds appreciably with the IEC Publications given in -0.5.

0.7 For the purpose of deciding whether a particular requirement of thestandard is complied with, the final values, observed or calculated, express-ing the result of a test, shall be rounded off in accordance with IS : 2-1960*.The number of significant places retained in the rounded off value shouldbe the same as that of the specified value in this standard.

1. SCOPE

1.1 This standard ( Part III ) covers the design and constructionalrequirements of switches and switch disconnectors for use on systemvoltages above 1000 V ac.

NOTE - For detailed scope of this series of standards on high voltage switches andswitch isolators, see 1 of Part I of this standard.

2. TERMINO-LOGY

2.1 For the purposes of this standard, the definitions given in 3 of Part Iof this standard shall apply.

3. CLOSING MECHANISM FOR DEPENDENT MANUALOPERATION

3.1 In order that a switch shall be safely closed on short-circuit, it isnecessary for it to be operated with the same speed and force as duringtype tests for proving the short-circuit making capacity. The closing inservice of a switch fitted with a closing mechanism for dependent manual

*Rules for rounding off numerical values ( revised ).

4

Page 6: SPECIFICATION FOR  ALTERNATING CURRENT SWITCHES  FOR VOLTAGES ABOVE 1 000 V

8/12/2019 SPECIFICATION FOR ALTERNATING CURRENT SWITCHES FOR VOLTAGES ABOVE 1 000 V

http://slidepdf.com/reader/full/specification-for-alternating-current-switches-for-voltages-above-1-000-v 6/12

IS : 9920 Part III ) - 1982

operation being a function of the skill and physical strength of theoperator, it is impossible to give for these switches a guarantee of ratedshort-circuit making capacity unless the peak short-circuit making currentis timited to 7.5 kA peak, for example, by means of a suitable current-limiting fuse.

4. REQUIREMENTS FOR LIQUlD IN LIQUID-FILLED SWITCHES

4.1 Liquid-Level - It shall be possible to fill and drain liquid-filled,switcheseasily. The liquid-level shall be clearly marked.

4.2 Liquid Quality - Liquid for use in liquid-filled switches shall complywith the instructions of the manufacturer.

5. REQUIREMENTS FOR GAS IN GAS-INTERRUPTER SWITCHES

5.1 The manufacturer shall specify the type and the required quantity andqpality of the gas to be used in a gas-interrupter switch and provide theuser with necessary instructions for renewing the gas and maintaining itsrequired quality.

6. REQUIREMENTS IN RESPECT OF THE ISOLATlNGDISTANCE OF SWITCH-DISCONNECTORS

6.1 For reasons of safety, switch-disconnectors should be so designed thatno dangerous leakage currents can pass from the terminals of one~side toany of the terminals of the other side of the switch-disconnector.

6.2 This safety requirement is met when the insulation involved iseffectively protected against pollution in service* or when any leakagecurrent would be led away to earth by a reliable earth connection.

NOTE - For switch-disconnectors which contain a dielectric other than air atatmospheric pressure, the dielectric conditions to be specified for the isolatingdistance may form the subject of agreement between manufacturer and the user.

7. EARTHING OF SWITCHES

7.1 The frame of each switch shall be provided with a reliable earthingterminal having a clapping screw of at least 12 mm diameter. It shall bemarked with the earth symbol.

*Tests to prove the effectiveness of the protection against pollution and the perform-ance of insulation material in respect of leakage currents is a subject under

consideration.

5

Page 7: SPECIFICATION FOR  ALTERNATING CURRENT SWITCHES  FOR VOLTAGES ABOVE 1 000 V

8/12/2019 SPECIFICATION FOR ALTERNATING CURRENT SWITCHES FOR VOLTAGES ABOVE 1 000 V

http://slidepdf.com/reader/full/specification-for-alternating-current-switches-for-voltages-above-1-000-v 7/12

IS : 9920 Part III ) - 1982

8. MECHANICAL STRENGTH

s.1 Switches shall be able to bear the mechanical force on the terminalswhen installed according to the manufacturer’s instructions as well as theelectto-dynamic forces without reduction of their reliability or current-carrying capacity.

9. POSITION OF THE MOVABLE CONTACT SYSTEM ANDITS INDICATING OR SIGNALLING DEVICES

9.1 Securing of Position

9.1.1 Switches, including their operating mechanisms, shall be soconstructed that they cannot come out of their open or closed positions bygravity, wind pressure, vibrations, reasonable shocks-or accidental touchingof the connecting rods of their operating mechanism.

9.1.2 Switches or their operating devices shall be constructed to permitlocking in both the open and closed positions, so as to preventunauthorized operation.

9.2 Indication of Position

9.2.1 It shall be possible to know the operating position of the switch orswitch-disconnector,

This requirement is met if one of the follotiing conditions is fulfilled:

a) the gap or isolating distance is visible;

b) the position of each movable contact is indicated by a reliableindicating device.

NOTE 1 - A visible moving contact may serve as the indicating device,

NOTE 2 - In case all poles of a switch are so coupled as to be operable Asia singleunit, it is permissible to use a common indicating device.

9.3 Auxiliary Contacts for Signalling

9.3.1 Signalling of the closed position shall not take place unless it iscertain that the movable contacts will reach a position in which the ratednormal, peak withstand and short-time currents can be carried safely.

9.3.2 Signalling of the open position shall not take place unless themovable contacts have reached a position such that the corresponding gapor isolating distance is at least 80 percent of the gap or the isolatingdistance, or unless it is certain that the ‘movable contacts will reach theirfully open position.

6

Page 8: SPECIFICATION FOR  ALTERNATING CURRENT SWITCHES  FOR VOLTAGES ABOVE 1 000 V

8/12/2019 SPECIFICATION FOR ALTERNATING CURRENT SWITCHES FOR VOLTAGES ABOVE 1 000 V

http://slidepdf.com/reader/full/specification-for-alternating-current-switches-for-voltages-above-1-000-v 8/12

IS : 9920 ( Part I I I ) - 1982

10. AUXILIARY EQUI PMENT

10.1 Auxiliary switches and auxiliary circuits shall have a cor~tirruous

current-carrying capacity of at least 10 A. Permissible temperature risesshall be in accordance with Table 4 of Part II of this standard.

10.2 The breaking capacity of auxiliary switches shall be adequate for thecircuits to be controlled, particulars of which should be specified to themanufacturer.

In the absence of such a specification, the breaking capacity shall beat least 2 A at 220 V dc with a circuit time-constant not less than20 minutes.

10.3 The auxiliary switches shall be positively driven in both directions.

Auxiliary switches which are installed on the frame of switches shallbe suitably protected against accidental arcing from the main circuit.

The insulating materials of auxiliary switches and terminals ofauxiliary circuits which are to be used under outdoor conditions, shall beceramics or other non-tracking materials.

11. INFORMATI ON TO BE SUPPLIED BY THE MANUFACTURER

11.1 Where applicable, information on the following matters should begiven by the manufacturer:

a) Transport, erection and dismantling.

b) Installation and maintenance.

1) The information should include indications for permissiblemounting positions.

The instruction should also comprise the maintenancemeasures to be observed under normal service conditions. Itis desirable that the manufacturer should specify the numberof operations ( or the time ) after which different parts of theswitch should be subject to maintynance.

The manufacturer should further give information regardingthe complete overhaul of switches, made necessary ‘by normalservice and the making and carrying of short-circuit current.

2) The replacement of parts which are subject to deterioration,for instance contacts.

3) List of spare parts.

4) List of special tools

5) Lubrication data.

Page 9: SPECIFICATION FOR  ALTERNATING CURRENT SWITCHES  FOR VOLTAGES ABOVE 1 000 V

8/12/2019 SPECIFICATION FOR ALTERNATING CURRENT SWITCHES FOR VOLTAGES ABOVE 1 000 V

http://slidepdf.com/reader/full/specification-for-alternating-current-switches-for-voltages-above-1-000-v 9/12

IS : 9920 ( Part III ) - 1982

6) For switches consisting of several independent poles, minimumdistances from pole to pole with regard to insulation andforces caused by short-circuit currents.

7) For liquid-filled switches, >quantity and type or quality ofliquid.

8) For gas-interrupter switches, quantity, type and quality of gasused in the interrupter and its permissible range of pressure.

12. NAMEPLATES

12.1 Switches and their operating devices shall be provided with a name-plate which contains the information in accordance with Table 1. Foroutdoor switches this nameplate shall be weather-proof and corrosion-proof.

12.2 If a switch consists of several independent poles, each pole shall beprovided with a nameplate.

12.3 For an inseparably combined operating device and switch, it may besufficient to use only one combined namepiate for both parts.

12.4 The nameplate shall be visible in the position of normal installation.

Page 10: SPECIFICATION FOR  ALTERNATING CURRENT SWITCHES  FOR VOLTAGES ABOVE 1 000 V

8/12/2019 SPECIFICATION FOR ALTERNATING CURRENT SWITCHES FOR VOLTAGES ABOVE 1 000 V

http://slidepdf.com/reader/full/specification-for-alternating-current-switches-for-voltages-above-1-000-v 10/12

IS : 9920 Part III 10 1982

TABLE 1 INFORMATION TO BE PROVIDEDON THE NAMEPLATE

DESCRIPTION ABBREVI-ATION

0).

Manufacturer

Designation of type

Serial number

General purpose switch,transformer off-loadswitch, or single capa-citor bank switch

Switch or switch - dis-connector

Class

Category

Rated voltage

Rated lightning impulsewithstand voltage

Rated switching impulsewithstand voltage andthe class (A or B) for420 kV

Rated normal current

Rated short-time current

Short-time

Rated mainly activeload breaking capacity

(2)

-

-

T”*c:---un

u,

I,

Ith

t

I,

( Clause 12.1 )

UNIT

(3)

-

-

-

-

-

-

kV

kV

kV

A

kA

S

A

SWITCH

(4)

X

X

Xl

X

X

X

V

X

Y

X

X

X

Y

x)

OPERATING CONDITION:DEVICE MARKING REQ-

IllRED ONLY IF

5) 6)

X -

X

X, -

-

- Category B (see 4.1.1of Part II of thisstandard)

- -

- U,, ,729 kV

-

-

-

- yferent from 1

-

Continu ed )

9

Page 11: SPECIFICATION FOR  ALTERNATING CURRENT SWITCHES  FOR VOLTAGES ABOVE 1 000 V

8/12/2019 SPECIFICATION FOR ALTERNATING CURRENT SWITCHES FOR VOLTAGES ABOVE 1 000 V

http://slidepdf.com/reader/full/specification-for-alternating-current-switches-for-voltages-above-1-000-v 11/12

IS : 9920 Part III ) - 1982

TABLE 1 INFORMATION TO BE PROVIDEDON THE NAMEPLATE - Conrd

DESCRIPTION -ABBREVI-ATION

(1)Rated closed loop brea-

king capacity

Rated transformer off-load breaking capacity

Rated single capacitorbank b r e a k i n gcapacity

R a ted line - chargingbreaking capacity

Rated cable - chargingbreaking capacity

Rated short -circuitmaking capacity

Rated pressure of-eom-pressed gas foroperation

Rated pressure of com-pressed gas supply forinterruption

Rated auxiliary voltage

Mass (including liquid)

P OP

Pint

-ua

111

( CIause 12.1 )

UNIT SWITCH OPERATINQ CONDITION:DEVICF MARKING REQ-

(3)

A

A

A

A

A

kA

kp/cml

kp/cm

V

kg

(3

@I

Y

(x)

(X)

(9

X

X

X

Y

IJ IRED ONLY Ii

5) 6)

- -

- Transformer off-loadswitch

- -

-

-

X

-

- -

More than 300 kg

x The marking of these values is mandatory; blanks for these values on thenameplate indicate the value zero.

(x) The marking of these values is optional.y The marking of these values is subject to the condition in column (6).

NATE 1 -Abbreviations in column (2) may be used instead of terms in~column (1)When terms in column (1) are used, the word ‘rated’ need not appear.

NOTE 2 - It is permissible to combine abbreviations where values are identical,for example: In Z, Z, 400 A.

10

Page 12: SPECIFICATION FOR  ALTERNATING CURRENT SWITCHES  FOR VOLTAGES ABOVE 1 000 V

8/12/2019 SPECIFICATION FOR ALTERNATING CURRENT SWITCHES FOR VOLTAGES ABOVE 1 000 V

http://slidepdf.com/reader/full/specification-for-alternating-current-switches-for-voltages-above-1-000-v 12/12