Made in Everson, WA USA Simple cloth panel systems for lowest cost Modular hard panel systems for fast,  professional testing Retrotec’s exclusive Flex Duct system for false ceiling & sub foor systems. NFPA 2001-ANNEX C, ISO14520-ANNEX E, EN15004 Choose the perfect system from our wide range Enclosure Integrity Systems Selector SP510 rev-2012-10-08

Upload: sachin-darne

Post on 14-Apr-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Spec-Selector Fire-SP510.pdf

7/27/2019 Spec-Selector Fire-SP510.pdf

http://slidepdf.com/reader/full/spec-selector-fire-sp510pdf 1/8

Made in Everson, WA USA

Simple cloth panelsystems for lowest cost 

Modular hard panelsystems for fast,

 professional testing

Retrotec’s exclusive Flex Duct system for false ceiling &sub foor systems.

NFPA 2001-ANNEX C, ISO14520-ANNEX E, EN15004Choose the perfect system from our wide range

Enclosure IntegritySystems Selector

SP510 rev-2012-10-08

Page 2: Spec-Selector Fire-SP510.pdf

7/27/2019 Spec-Selector Fire-SP510.pdf

http://slidepdf.com/reader/full/spec-selector-fire-sp510pdf 2/8

Automatic speed controlSet to any percent speed and Jog upor down in 1% or 5% increments.

Cruise Control

Set any pressure, and then Jog up ordown in 5 Pa increments for fastmultipoint tests.

... or super fast!

...now use the @ key to immediatelyextrapolate to the exactpressure selected by the“Jog” key, in order toacquire a set of test

points as fast as they canbe written down.Laptop controlAdvanced USB

connection to anylaptop allows for theuse of a wide variety

of software.

Control from a distanceThe standard gauge-to-fan cable is20’, but 70’ and 250’ extensions allowcontrol from any distance.

Manual controlPlug this manual control unit into anyRetrotec fan to adjust the speed withthe simple turn of the dial.An on/off switch allowsspeed to be restored tothe previous setting.

DM-2 mkII Digital GaugeThe DM-2 mkII is more than just adigital gauge. It is the advancedcontrol center at the heart of everyRetrotec system. It has everyimaginable feature neededto make testing faster,easier, and moreaccurate, withoutthe need for acomputer, yet isstill simple to use

1000 standard power fanThis 24 inch (60 cm) fan is ideallysuited for testing most houses andsome small commercial andindustrial buildings.

3300SR large building fanThis Retrotec exclusive fan is superpowerful and super stable. Its customindustrial strength motor is designedfor continuous operation and willnever over-heat.

The 3300 SR fans are "Self Referenced", making them the ideal

building science tool since theycannot be hooked up incorrectly andalways reference the ow properlyeven when attaching a Flex Duct tocreate the world’s largest duct tester,or when performing oor-at-a-timehigh rise building tests.

Digital Gauge Fan Performance

Fan Control

Door Panels

Cloth Panel for economyOur Standard Aluminum Frame withCloth Panel will t any residentialdoorway. Ergonomic knobs, sturdycam levers, and numbered framepieces make this frame easy to use.

Modular Panel for exibilityRetrotec’s unique hard panels t thewidest variety of doorways. They

are lightweight, quick and easy toset up, and provide an impressiveprofessional appearance.

Page 2 of 8

Page 3: Spec-Selector Fire-SP510.pdf

7/27/2019 Spec-Selector Fire-SP510.pdf

http://slidepdf.com/reader/full/spec-selector-fire-sp510pdf 3/8

Page 3 of 8

DM-2 Digital Gauge Dimensions 

Weight 14oz/397g 

Size 8.75 x 4.25 x 3 in22.2 x 10.8 x 7.6 cm

Power AC adapter4 NiMH AA rechargeable batteries

Accuracy + 1 %− 

[Mode] Units Available

Pressure: Pascals, inches, water column, psf  PrB 53.5 Pa

Flow: cfm, L/s, m³/s, m³/h Flow 253.5 cfm

Flow per area: CFM/ft², L/s/m², CFM/100ft², m³/h/m², cfm/1000ft² 0.25Leakage Area: EqLA (Canadian) and/or EfLA (US): cm², in², ft² EqLA 12.8

EqLA and EfLA per area: in²/100ft², cm²/m², in²/in² 1.15

Air changes per hour according to volume entered: /h 2.7

Hole Flow: CFM, L/s, m³/s, m³/h 103.7 cfm

Flow/ Area

 /hAirChg

in²/100ft²@10.0Pa

HoleFlow

ft²@10.0Pa

EqLA/ Area

cfm/ft²@75.0Pa

The Retrotec DM-2 displays every possible result with manual and fully automatic (or computerized) fan speed control.

Connect to FanTestic PC software viaUSB for data acquisition, automaticcontrol, or data monitoring.

Match tube to same color port.

Use an unlimitedlength of ethernetstyle Speed ControlCable to control fan.

Rechargebatteries.

[Set Pressure]Control to any pressure.

[Volume Area]For Air Changes and ELA per area.

[Set Speed]Set to any % speed.

[@ Pressure]Immediate results estimatedat any test pressure.

[Jog/ Hold]Adjust up/down in 5 Pa incrementsfor multi-point tests.

[Setup]Add/remove modes and devices.

Digital Gauge

Page 4: Spec-Selector Fire-SP510.pdf

7/27/2019 Spec-Selector Fire-SP510.pdf

http://slidepdf.com/reader/full/spec-selector-fire-sp510pdf 4/8

Fan Control

Model 1000 fanStandard 

Dimensions: 26” x 25.5” x 9.5” (66 x 65 x 24 cm)

Weight: 34 lb (15.4 kg)

Power in: Available in 115V or 230V, 50 or 60 Hz, 1000 Watts

Motor & fan blade: 3/4 hp, PSC motor w/ 8 blade fan

Model 3300SR fanHigh Output 

Dimensions: 26” x 25.5” x 9.5” (66 x 65 x 24 cm)

Weight: 37 lb (16.8 kg)

Single Phase power in: Available in 120V, 15A or 240V 8A, 1ph

Motor & fan blade: 2.0 hp, 3 phase w/ 8 blade fan

Model 3300SR Model 1000

 Advanced controlRetrotec ups the ante withits regulated speed control

to eliminate the speeductuations experienced

with typical manual controls.

Super advanced controlThe unique variable speeddrive provides advancedspeed control withRetrotec’s 2 hp HighOutput speed fan. It

generates faster speedcontrol with less than 0.1%speed variation. Use a 100to 280V, 50 to 60 Hz, walloutlet (non GFCI).

 2 sizes of motor 

Choose a 0.75 hp or 2 hp motor in a25 inch (75 cm) fan shell housing.

Standard fan

High Output fan and Drive

8-point mount Super stable mounting maintains fan alignment under themost stressful conditions. Attachment points are moldedin permanently, so there is nothing that can come loose.

Tough constructionSpace age constructionuses a hollow fan shelllled with structural

foam for superiorstrength and durability

Page 4 of 8

Page 5: Spec-Selector Fire-SP510.pdf

7/27/2019 Spec-Selector Fire-SP510.pdf

http://slidepdf.com/reader/full/spec-selector-fire-sp510pdf 5/8

The wide span between the minimum/maximum ow on each Range Conguration, coupled with a huge number of ranges, enables faster tests over the widest range of buildings or enclosures.

1 CFM 1 m3 /hr 1 L/s

1017 5

5 7 100170 47 

1,0001,700 472

10,00017,000 4,719

Retrotec Fan Flow for each Range(Flow at 50 Pascals)

Open

 A

B

C8 

C6

C4

C2

C1

L4

L2

L1

1000 series fan (110v/50Hz)1000 series fan (120v/60Hz)

3000 fans (all voltages)

Fan Performance

Standard Range Plates

Model 1000(reduce by 15% for 50Hz)

Free Air 6,300 2,973 10,704

50 Pa 5 to 5,600 2 to 2,643 8 to 9,514

Model Q4E & Q5E(reduce by 15% for 50Hz)

Free Air 8,500 4,012 14,440

50 Pa 5 to 8,300 2 to 3,917 8 to 14,100

300 Pa 2,300 1,085 3,907

Model Q4E-2X & Q5E-2X Free Air 17,000 8,024 28,880

50 Pa 5 to 16,600 2 to 7,834 8 to 28,200

300 Pa 7,500 5,664 20,988

Maximum Fan Flow Rates Flow into: CFM L/s m3 /h

Flow-restrictor plates allow one fan to test a wide range of enclosures, fromsuper-leaky to super-tight. Model 1000 and 3300SR fans include 11 owranges (right) to provide accurate results over the widest range of enclosures.

Select the Range Conguration on Retrotec’s DM-2 digital gauge for instant

accurate results in any desired units.

Page 5 of 8

Page 6: Spec-Selector Fire-SP510.pdf

7/27/2019 Spec-Selector Fire-SP510.pdf

http://slidepdf.com/reader/full/spec-selector-fire-sp510pdf 6/8

Door Panels

Door widths (min/max) 29.5 to 41.5 in (75 to 105.4 cm)

Door heights (max) 51.5 to 95 in (131 to 241 cm)

Frame thickness 1.75 in (5.3 cm)

Frame case (included) 53 x 10 x 4 in (134 x 25 x 10 cm)

Panel set in case 14.2 lb (6.4 kg)

Shipping weight 20 lb (9 kg)

30 to 48 in (76 to 122 cm)

60 to 105 in (152 to 267 cm)

Cloth Door PanelRetrotec’s least expensive choice for residential testing.

Options:

● Extension Kit enlarges the frame horizontally and/or vertically.● High pressure cloth for 300 Pa rain penetration testing.● Double hole fan cloth.● Small hole fan cloth to mount 200 series fan for tight houses.

Modular Door PanelFor rapid set up and a professional appearance, choose themodular door panels. Three light-weight panels expand tot the widest doorways.

Options:● Small X Panel increases height to 97.5 inches (248 cm).

Door widths (min/max) 32 to 48.75 in (81 to 124 cm)

Door height (max) 76.5 to 87 in (194 to 221 cm)

Panel case (included) 31 x 30 x 7 in (79 x 76 x 18 cm)

Panel set in case 24 lb (11 kg)

Shipping weight 31 lb (14 kg)

Dimensions

Dimensions

with extension kit 

Page 6 of 8

Page 7: Spec-Selector Fire-SP510.pdf

7/27/2019 Spec-Selector Fire-SP510.pdf

http://slidepdf.com/reader/full/spec-selector-fire-sp510pdf 7/8

Enclosure Integrity Systems

1000 Q5E

Q4E Q5E-2X or Q4E-2X (not shown)

For testing to NFPA2001 and ISO14520

Best ValueThe Model 1000 system has

automatic pressure control andan advanced regulated controlcircuit to prevent fan speedfrom wavering. Simply key inthe test pressure required andthe 1000 will take it there anddisplay the leakage area on theDM-2 screen.

Measure Upper and Lower Leaks Separately The Model Q5E-2X system is actuallythree systems in one. The two Model3300SR fans can be used as twoseparate Q5E systems, orcombined into one system fortesting large buildings.When used with the includedFlex Duct, it is the onlysystem that will performthe Below CeilingLeakage Area test, to

test enclosures withleaks above asuspended ceiling.

Both fans can beused together totest enclosuresup to 21,600 ft2

(2,000 m2) of oor area.

Test larger enclosuresThe Model Q4E systemfeatures the powerful 3300SRfan (0.75 Vs 2 hp). Test largeenclosures with only ONE fan!The Cloth Door Panel keepsthe cost down, giving youthe best performance at thelowest price. Ideal for testinglarge & small enclosures of alltypes and for Pressure Relief Vent testing.

The Perfect EnclosureTesting System

The Model Q5E Inltrometersystem combines the best of everything; gauge, controller,fan and a modular door panel,to create our most exiblesystem for whole roomtesting. Fits almost anydoorway in virtually any sizeof enclosure. Tests installedrelief vent damperswhere the addedpressure andow capability

is needed.

Page 7 of 8

Page 8: Spec-Selector Fire-SP510.pdf

7/27/2019 Spec-Selector Fire-SP510.pdf

http://slidepdf.com/reader/full/spec-selector-fire-sp510pdf 8/8

Gauge DM-2 Digital 2 DM-2 Digital

Gauge accuracy ± 1% or 1 Pa

Door Panel Cloth Panel and Aluminium Frame Modular Hard

Panel

Cloth Panel and

Aluminium Frame

Modular Hard

Panel

Door Panel width 29.5 to 41.5 in(75 to 105 cm)

32 to 48.5 in(81 to 123 cm)

29.5 to 41.5 in(75 to 105 cm)

32 to 48.5 in(81 to 123 cm)

Door Panel height 51.5 to 95 in

(131 to 241 cm)

30 in to no limit

(76 to 220 cm)

51.5 to 95 in

(131 to 241 cm)

30 in to no limit

(76 to 220 cm)

Fan motor 0.75 hp 2 hp 2 hp 2 x 2 hp

Voltage 110 or 240 100 to 280

(auto-switching)

100 to 280

(auto-switching)

Frequency 50 or 60 Hz

Typical maxiumum volume for All inerts (ISO)* 55,000 ft3

1,550 m3

80,000 ft3

2,250 m3

80,000 ft3

2,250 m3

160,000 ft3

4,500 m3

160,000 ft3

4,500 m3

for Halocarbons 110,000 ft3

3,100 m3

162,000 ft3

4,600 m3

162,000 ft3

4,600 m3

324,000 ft3

9,200 m3

324,000 ft3

9,200 m3

Typcal maximum volume for All inerts (NFPA)* 35,000 ft3

1,000 m3

51,000 ft3

1,450 m3

51,000 ft3

1,450 m3

102,000 ft3

2,900 m3

102,000 ft3

2,900 m3

for Halocarbons (NFPA)* 70,000 ft3

2,000 m3

106,000 ft3

3,000 m3

106,000 ft3

3,000 m3

212,000 ft3

6,000 m3

212,000 ft3

6,000 m3

1000 Q4E Q5E Q4E-2X Q5E-2X

Test System Specications

Recommended Options

Page 8 of 8

Grill Mask is essentialfor covering leaks tosequentially determinewhich leaks are causingthe enclosure to fail.

Level 1, 2 and 3 trainingare required for singlefan testing and level 3 forthe Q5E2X and the BelowCeiling Leakage Area test.

 Air Current Testers areessential for nding leaksand indicating airowdirection.

The pie graph shows what percentage of Retrotec customers buy a particular model.Most people choose the Q4E or Q5E,because it will test almost any room, with asmall, quick to set up package. Enclosurescommonly fail due to excessive above-ceiling leaks, but a Q4E-2X or Q5E-2X willoften show these rooms can pass whenthe 2 fans are used along with the includedleakage split kit and will often eliminate theneed for a PRV.

Pressure Relief VentsGravity actuated PRV’s are fully closed at80 Pa and fully open at 95 Pa, ensuringsafe dissipation of the peak pressurescreated by clean agent discharge.

Models Sold (for this application)

Dual Flow Pressure Relief VentsThe RSH dual ow PRV’s have beencarefully engineered to relieve boththe positive and negative pressurescaused by halocarbon discharge.

* Flooded volume is based on a 4m (13.1 ft) high room with a minimum protected height of 3.6m (11.8 ft) and a retention time of 10 minutes.Numbers are approximate.

Q4E-2X 45%

Q5E-2X 20%

Q4E 15%

1000

10%

Q5E 10%

www.retrotec.com Sales & Support: (855)738-7683 Internaonal: 1(604)732-0142 Made in Everson, WA USA