south jordan, utah 84095 11.20.2018 permit set … · salt lake county equestrian center...
TRANSCRIPT
Nexus Project #: Owner Project #:
SALT LAKE COUNTY
EQUESTRIAN CENTERRESTROOM/SHOWERBUILDING2100 WEST 11400 SOUTH,SOUTH JORDAN, UTAH 84095
PERMIT SET
11.20.2018
18142
[STAMP]
CONTACT: E-MAIL:
PHONE: INTERNET:
[LOGO]
OW NER
SALT LAKE COUNTY
385.468.1820
Andrea Sorensen [email protected]
https://slco.org/
CONTACT: E-MAIL:
PHONE: INTERNET:
ARCHITECT
Architectural NEXUS, Inc.2505 East Parleys Way
Salt Lake City, UT 84109
801.924.5000
Holli Adams [email protected]
http://www.archnexus.com
CONTACT: E-MAIL:
PHONE: INTERNET:
LANDSCAPE ARCHITECT
Architectural NEXUS, Inc.2505 East Parleys Way
Salt Lake City, UT 84109
801.924.5000
xxxxx [email protected]
http://www.archnexus.com[STAMP]
CONTACT: E-MAIL:
PHONE: INTERNET:
[LOGO]
STRUCTURAL
Dunn Associates, Inc380 W 800 S
Salt Lake City, UT 84101
801.575.8877
Tait Ketchum [email protected]
http://www.dunn-se.com
[STAMP]
CONTACT: E-MAIL:
PHONE: INTERNET:
[LOGO]
MECHANICAL
VBFA330 South 300 East
Salt Lake City, UT 84111
801.530.3148
Jacob Beck [email protected]
http://www.vbfa.com
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/27/2
01
8 9
:30
:28
AM
COVERSHEET
LAH
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PERMIT SET
G001
HKA
[STAMP]
CONTACT: E-MAIL:
PHONE: INTERNET:
[LOGO]
ELECTRICAL
EELD1220 S 300 W
Salt Lake City, UT 84101
801.486.2222
Mansour Aghdasi [email protected]
http://www.ee-ld.com
VICINITY MAP
# Date Revision
MATCH LINE
SEE A2222MATCH LINE TAG
EXISTING WALL TO REMAIN
WALL TO BE DEMOLISHED
NEW WALL
BREAK LINE
CENTER LINE SYMBOL
0' 4' 8' 16'
REVISION DESIGNATION
ELEVATION SYMBOL
1
T.O. WALL
100'-0"
REVISION NUMBER
ELEVATION ABOVE DATUM
ELEVATION DESCRIPTION
DRAWING SYMBOL LEGEND
000M
CASEWORK TYPE DESIGNATION
CDS NUMBER (M DENOTES MODIFICATION - SEE SHEET A551 FOR MODIFIED MILLWORK ELEVATIONS AND DETAILS)
00"
00"
00"
MODIFICATION DESCRIPTION
AWS STANDARD CDS NUMBERING SYSTEM
WIDTH
HEIGHTDEPTH
NORTH ARROW
PLAN NORTH
GRAPHIC SCALES
ROUND BREAK LINE
REVISION CLOUD
SLOPE INDICATION
1/2" / 12"
DETAIL REFERENCE
A2 A401
A1
A3INTERIOR ELEVATIONS
DETAIL NUMBER
SHEET NUMBER
A1
A501
DETAIL REFERENCE
DETAIL NUMBER
SHEET NUMBER
A1
A201
EXTERIOR ELEVATION REFERENCE
SHEET NUMBER
DETAIL NUMBER
A1
A302
WALL SECTION REFERENCE
SHEET NUMBER
DETAIL NUMBER
A1
A301
BUILDING SECTION REFERENCE
DETAIL NUMBER
SHEET NUMBER
XX000X00'-00"
ROOM DESIGNATION (FLOOR PLAN)
ROOM NUMBER
ROOM NAME
A1
A301DETAIL NUMBER
SHEET NUMBER
ROOM DESIGNATION (REFLECTED CEILING PLAN)
CEILING HEIGHT ABOVE FINISH FLOORROOM NUMBER
00001
A
1
1
GLASS TYPE DESIGNATION
KEYED NOTE DESIGNATION
WALL TYPE DESIGNATION
EQUIPMENT DESIGNATION
WINDOW DESIGNATION
DOOR DESIGNATION
GLASS TYPE
EQUIPMENT NUMBER
KEY NOTE NUMBER
WINDOW TYPE
DOOR NUMBER
WALL TYPE
101
XXX
N
MATERIAL TYPE DESIGNATION
FINISH NUMBER
SEE AI601 FINISH LEGEND00001
12"1/2"
RISE
RUN
TRUE NORTH
CL
LIST OF ABBREVIATIONS
THE PRECEDING LIST OF ABBREVIATIONS IS PRESENTED AS A GENERAL GUIDE AND DOES NOT NECESSARILY SHOW ALL ABBREVIATIONS USED. OTHER GENERALLY ACCEPTED ABBREVIATIONS MAY BE FOUND AMONG THE DRAWINGS -SOME ABBREVIATIONS SHOWN ABOVE MAY NOT BE USED WITHIN THIS DRAWING SET.
AA/C AIR CONDITIONINGAD AREA DRAINAFF ABOVE FINISHED FLOORAHU AIR HANDLING UNITALUM ALUMINUMANOD ANODIZEDARCH ARCHITECT@ AT
BBD BOARDBLDG BUILDINGBO BOTTOM OF
CC CELSIUSCH COAT HOOKCFCI CONTRACTOR FURNISHED,
CONTRACTOR INSTALLEDCG CORNER GUARDCI CONTINUOUS INSULATIONCJ CONTROL JOINTCL CENTERLINECLG CEILINGCLO CLOSETCLR CLEARCMU CONCRETE MASONRY UNITCOL COLUMNCONC CONCRETECONT CONTINUOUSCORR CORRIDORCT CERAMIC TILECTJ CONSTRUCTION JOINTCUH CABINET UNIT HEATER
DD DEEPDEG DEGREEDEMO DEMOLITIONDF DRINKING FOUNTAINDIA DIAMETERDIM DIMENSIONDN DOWNDS DOWNSPOUTDWGS DRAWINGS
EEA EACHEJ EXPANSION JOINTEIFS EXTERIOR INSULATION AND FINISH
SYSTEMEL ELEVATIONELEC ELECTRICALELEV ELEVATOREOS EDGE OF SLABERD EXISTING ROOF DRAINEQ EQUALEQUIP EQUIPMENTEWC ELECTRIC WATER COOLEREXIST EXISTINGEXP EXPOSEDEXT EXTERIOR
FF FAHRENHEITFA FIRE ALARMFACP FIRE ALARM CONTROL PANELFDC FIRE DEPARTMENT CONNECTIONFD FLOOR DRAINFEC FIRE EXTINGUISHER CABINETFE FIRE EXTINGUISHERFG FINISH GRADEFHC FIRE HOSE CABINETFIN FINISHFLR FLOORFND FOUNDATIONFO FINISHED OPENINGFOC FACE OF CONCRETEFOM FACE OF MASONRYFOS FACE OF STUDFOW FACE OF WALLFRG FIBER REINFORCED GYPSUMFSP FIRE STANDPIPEFT FEETFV FIELD VERIFY
GGA GAUGEGALV GALVANIZEDGFRC GLASS-FIBER-REINFORCED
CONCRETEGFRG GLASS-FIBER-REINFORCED GYPSUMGL GLASSGWB GYPSUM WALL BOARDGYP GYPSUM
HH HIGHHB HOSE BIBBHDR HEADERHM HOLLOW METALHPT HIGH POINTHR HOURHT HEIGHT
IID INSIDE DIAMETER; INSIDE DIMENSIONIN INCHINFO INFORMATIONINT INTERIOR
JJAN JANITOR
K (NOT USED)
LLAB LABORATORYLAV LAVATORYLBS POUNDSLLH LONG LEG HORIZONTALLLV LONG LEG VERTICALLPT LOW POINT
MMACH RM MACHINE ROOMMAX MAXIMUMMFR MANUFACTURERMECH MECHANICALMEZZ MEZZANINEMIN MINIMUMMO MASONRY OPENING
NNA NOT APPLICABLENIC NOT IN CONTRACTNOM NOMINALNTS NOT TO SCALE
OOC ON CENTEROD OUTSIDE DIAMETER;
OUTSIDE DIMENSIONOFD OVERFLOW DRAINOH DR OVERHEAD DOOROPH OPPOSITE HANDOPP OPPOSITEORIG ORIGINAL
PP LAM PLASTIC LAMINATEPLAS PLASTERPLUMB PLUMBINGPR PAIRPSI POUNDS PER SQUARE INCHPSF POUNDS PER SQUARE FOOTPVC POLYVINYL CHLORIDE
QQT QUARRY TILE
RR RISER OR RADIUSRAD RADIUSRCP REFLECTED CEILING PLANRD ROOF DRAINREF REFRIDGERATORREQD REQUIREDREV REVISIONRH RELATIVE HUMIDITYRM ROOMRO ROUGH OPENINGRTU ROOF TOP UNITRWL RAIN WATER LEADER
SS SMOKE DETECTORSAM SELF ADHESIVE MEMBRANESCHED SCHEDULESECT SECTIONSIM SIMILARSPEC SPECIFICATIONSS STAINLESS STEELSTD STANDARDSTRUCT STRUCTURAL
TT TREADTEL TELEPHONETEMP TEMPORARYTHK THICKTOC TOP OF CONCRETETOM TOP OF MASONRYTOP TOP OF PARAPETTOS TOP OF SLAB; TOP OF STEELTOW TOP OF WALLTYP TYPICALTO TOP OF
UUL UNDERWRITER'S LABORATORIESUNO UNLESS NOTED OTHERWISE
VVCT VINYL COMPOSITE TILEVERT VERTICALVEST VESTIBULEVIF VERIFY IN FIELD
WW/ WITHW/O WITHOUTWD WOODWH WALL HYDRANTWP WORKING POINTWRB WEATHER RESISTIVE BARRIER
X,Y,Z (NOT USED)
CAST-IN-PLACE CONCRETE
CONCRETE MASONRY UNIT
PRECAST CONCRETE / GLASS FIBER REINFORCED CONCRETE (GFRC)
STEEL STUDS
WOOD STUDS
BRICK VENEER
RIGID INSULATION
BATT INSULATION
CONTINUOUS MATERIAL
NON CONTINUOUS MATERIAL (BLOCKING)
GYPSUM BOARD
PLYWOOD
GRAVEL
UNDISTURBED EARTH
HATCH LEGEND
NOTE: HATCHING ANGLES MAY VARY DUE TO ANGLE OF WALL DRAWN, WHILE HATCHING PATTERN REMAINS SIMILAR.
BACKFILL OR FILL
EXTERIOR SHEATHING
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/27/2
01
8 9
:30
:32
AM
GENERALINFORMATION
LAH
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PERMIT SET
G002
HKA
SHEET INDEX
GENERAL:
G001 COVER SHEET
G002 GENERAL INFORMATION
G501 ASSEMBLY TYPES
G701 ACCESSIBILITY COMPLIANCE
ARCHITECTURAL:
A101 FLOOR PLAN
A121 ROOF PLAN & REFLECTED CEILING PLAN
A201 BUILDING ELEVATIONS
A251 INTERIOR ELEVATIONS
A301 BUILDING SECTIONS
A351 WALL SECTIONS
A501 ARCHITECTURAL DETAILS
A601 DOOR SCHEDULES & TYPICAL DETAILS
STRUCTURAL
S001 GENERAL STRUCTURAL NOTES
S002 GENERAL STRUCTURAL NOTES
S003 GENERAL STRUCTURAL NOTES
S201 FOOTING AND FOUNDATION PLAN
S301 SCHEDULES
S501 FOOTING AND FOUNDATION DETAILS
S502 FOOTING AND FOUNDATION DETAILS
S701 ROOF FRAMING DETAILS
MECHANICAL
M000 MECHANICAL SYMBOLS AND LEGEND
M001 MECHANICAL GENERAL NOTES
M101 MECHANICAL PLAN
M501 MECHANICAL DETAILS
M502 MECHANICAL DETAILS
M503 MECHANICAL DETAILS
M504 MECHANICAL DETAILS
M505 MECHANICAL DETAILS
M506 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
P101 PLUMBING SUPPLY PLAN
P102 PLUMBING DRAIN & VENT PLAN
P601 PLUMBING SCHEDULES
ELECTRICAL
EE-001 GENERAL NOTES & DETAILS
EE-002 LIGHT FIXTURE/ MECHANICAL/ PANELSCHEDULES
ELP-101 MAIN FLOOR PLAN - LIGHTING & POWERINTERNATIONAL PLUMBING CODE
NATIONAL ELECTRICAL CODE
ZONING ORDINANCE:
INTERNATIONAL MECHANICAL CODE
INTERNATIONAL FIRE CODE
INTERNATIONAL ENERGY CONSERVATION CODE
INTERNATIONAL BUILDING CODE
ACCESSIBILITY CODE
DESIGN CRITERIAAPPLICABLE CODES OTHER CRITERIA
DEFERRED SUBMITTALS
ICC/ANSI A117.1-2009
2015 EDITION
2015 EDITION
2015 EDITION
2015 EDITION
2015 EDITION
2014 EDITION
Zoning OrdinanceSouth Jordan
# Date Revision
FIRE RATING:
FIRE TEST:
SOUND RATING:
SOUND TEST:
HEAD DETAIL:
SILL DETAIL:
WALL TYPE:
HEIGHT:
XM08 NONE
NONE
SEE A210 SERIES
EXTERIOR INTERIOR
FIRE RATING:
FIRE TEST:
SOUND RATING:
SOUND TEST:
HEAD DETAIL:
SILL DETAIL:
WALL TYPE:
HEIGHT:
M06 NONE
NONE
TO DECK ABOVE
PLAIN FACED CMU
HONED CMU
PLAIN FACED CMU
FIRE RATING:
FIRE TEST:
SOUND RATING:
SOUND TEST:
HEAD DETAIL:
SILL DETAIL:
WALL TYPE:
HEIGHT:
M08 NONE
NONE
SEE A210 SERIES
EXTERIOR INTERIOR
HONED CMU
+/- 1' - 2 1/4"7 5/8"5 5/8"
REFER TO FINISH SCHEDULE FOR FINISH
REFER TO FINISH SCHEDULE FOR FINISH
REFER TO FINISH SCHEDULE FOR FINISH
2" 20 PSI POLYISOCYANURATE BOARDINSULATION
FIRE RATING:
FIRE TEST:
SOUND RATING:
SOUND TEST:
HEAD DETAIL:
SILL DETAIL:
WALL TYPE:
HEIGHT:
M06.I NONE
NONE
TO DECK ABOVE
PLAIN FACED CMU
7 5/8"
REFER TO FINISH SCHEDULE FOR FINISH
2" 20 PSI POLYISOCYANURATE BOARDINSULATION
1" AIR GAP
FIRE RATING:
FIRE TEST:
SOUND RATING:
SOUND TEST:
HEAD DETAIL:
SILL DETAIL:
WALL TYPE:
HEIGHT:
XM08.B NONE
NONE
SEE A210 SERIES
EXTERIOR INTERIOR
HONED CMU
PLAIN FACED CMU
+/- 1' - 2"
REFER TO FINISH SCHEDULE FOR FINISH
2" 20 PSI POLYISOCYANURATE BOARDINSULATION
FIRE RATING:
FIRE TEST:
SOUND RATING:
SOUND TEST:
HEAD DETAIL:
SILL DETAIL:
WALL TYPE:
HEIGHT:
XM08.A NONE
NONE
SEE A210 SERIES
EXTERIOR INTERIOR
HONED CMU
+/- 1' - 3 1/4"
REFER TO FINISH SCHEDULE FOR FINISH
2" 20 PSI POLYISOCYANURATE BOARDINSULATION
2" AIR GAP3/4" AIR GAP
PLAIN FACED CMU
CEILING TYPE: FIRE RATING:
FIRE TEST:
SOUND RATING:
SOUND TEST:
CL-01CEILING TYPE: FIRE RATING:
FIRE TEST:
SOUND RATING:
SOUND TEST:
CL-02
WALL. SEE ASSEMBLY TYPES.
2X FURRING FORCEILING, AS NEEDED
NON-SAG CEMENT BOARD, FINISHED & PAINTED
2X FURRING FORCEILING, AS NEEDED
EXTERIOR GYPSUM SOFFIT BOARD, FINISHED & COATED
J BEAD TRIM, COATED
ROOF TYPE: FIRE RATING:
FIRE TEST:
SOUND RATING:
SOUND TEST:
R-01
ROOF STRUCTURE; COORDINATE WITH STRUCTURAL DRAWINGS
1" 20 PSI FACED POLYISOCYANURATEBOARD INSULATION
STANDING SEAM METAL ROOF
HIGH TEMP. ICE & WATER SHIELD,CONTINUOUS
FOIL-FACED, TAPED R30 BATTINSULATION
5/8" PARTICLE BOARDSHEATHING
A. WALL TYPES DESCRIBED ON THIS SHEET DO NOT ACCOUNT FOR REQUIRED BACKING AND/OR SUPPORT FOR WALL MOUNTED FIXTURES, EQUIPMENT, CASEWORK, AND/OR SYSTEMS FURNITURE, COORDINATE WITH ENLARGED FLOOR PLANS, INTERIOR ELEVATIONS, AND EQUIPMENT PLANS PRIOR TO THE COVERING OF STUD FRAMING. REFER TO MANUFACTURER'S RECOMMENDATIONS AND USE DETAIL XX/XXXX WHERE APPLICABLE
B. PROVIDE SEIMIC BRACING PER DETAIL XX/XXXX AT ALL WALL TYPES THAT DO NOT EXTEND TO DECK
C. PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE PROVIDED PER SHEET G101
D. WALL THICKNESS DESCRIBED ON THIS SHEET ARE SHOWN AT ACTUAL SIZE IN PLAN REPRESENTATIONS. DIMENSIONS ARE TO FACE OF STUD/STRUCTURE OR GRID. "CLEAR" DIMENSIONS ARE TO FACE OF FINISH.
GENERAL NOTE - WALL TYPE
FLOOR TYPE: FIRE RATING:
FIRE TEST:
SOUND RATING:
SOUND TEST:
F-01
4"
COMPACTED GRAVEL SUB-BASE
CAST-IN-PLACE CONCRETE FLOOR;COORDINATE WITH STRUCTURAL
SCHEDULED FINISH
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/27/2
01
8 9
:30
:38
AM
ASSEMBLYTYPES
LAH
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PERMIT SET
G501
HKA
# Date Revision
17"
- 19
"
18"
33"
- 36
"
BACK
17"
- 19
"
1/2" MAX THRESHOLD(BEVELED ROUNDED
OR VERTICAL)
SEAT WALL
36" x 36" STALL
CENTERLINE OF CONTROL WALL
33"
- 36
"
38"
MIN
.
48"
MA
X
60" LONG HOSE, MIN. W/ VERTICAL BAR FOR ADJUSTABLE HEIGHT OF HAND SHOWER. MOUNT SO AS TO NOT OBSTRUCT THE USE OF GRAB BARS.
CONTROL AREA
CONTROL WALL
SEAT SEAT
18"
3" -
6"
4"
MAX
15"
NOTE: DIMENSIONS ARE TO TOP/BOTTOM OF GRAB BARS.
17" MIN.
34"
MA
X
34"
MA
X.
27"
MIN
.
9" M
IN. T
OE
CLE
AR
AN
CE
11" MIN.
8" MIN.
LEG CLEARANCE
44"
MA
X.
27"
MIN
.
34"
MA
X
40"
MA
X
ADA STYLE LEVER FAUCETSSOAP DISPENSER
MIRROR W/ SHELF
INSULATED PIPES
25" M
AX
-17
" MIN
.
48"
MIN
.
30" MIN.
TO R
EFL
EC
TIV
ES
UR
FAC
E
33"
- 36
"
39"
- 41
"18
" M
IN.
39" - 41"
12" MAX 42" MIN.
54" MIN.
17"
- 19
"
24" MIN. 12" MIN.
16" - 18"
33"
- 36
"
16" - 18"
56" M
IN W
ALL
HU
NG
TO
ILE
T
60" MIN.
NOTE: DIMENSIONS ARE TO TOP/BOTTOM OF GRAB BARS UNLESS NOTED OTHERWISE.
7" - 9"
18"
MIN
.
1 1/
2" M
IN. C
LEA
R
12"
MIN
. CLE
AR
48"
MA
X
RECESSED DISPENSERS
ARE ALLOWED WITHIN SHADED
AREA
TOILET PAPER DISPENSER LOCATION
VERTICAL CHANGES IN LEVELS
1/4" MAX
BEVELED CHANGES IN LEVELS
21
GREATER THAN 1/4" BUT NOT MORE THAN 1/2". IF GREATER THAN 1/2", MUST MEET RAMP REQUIREMENTS.
5" MAX.
15" MIN.
8" MIN.
9" M
IN.
27"
MIN
.
WH
EE
L C
HA
IR
34"
MA
X.
11" MIN.
30"
MIN
.
48" MIN.
CLEAR FLOOR SPACE
CONTROLS AT OR NEAR FRONT EDGE
CANTILEVERED DRINKING FOUNTAIN & WATER COOLERS
WH
EE
L C
HA
IR
36"
MA
X.
ST
AN
DIN
G P
ER
SO
N
38"
- 43
"RECEPTACLE OUTLET
UNOBSTRUCTED THERMOSTAT
UNOBSTRUCTED SWITCH
RECEPTACLES AND SWITCH MOUNTING HEIGHTS
UNOBSTRUCTED FIRE ALARM PULL
BOX
15"
MIN
.
36"
MIN
.
48"
MA
X.
48"
MA
X.
48"
MA
X
48"
MA
X
TO C
ON
TRO
LS
TO C
ON
TRO
LS
PAPER TOWEL DISPENSER AND TRASH (UNOBSTRUCTED)
PAPER TOWEL DISPENSER (UNOBSTRUCTED)
SANITARY NAPKIN VENDOR (UNOBSTRUCTED)
48"
MA
X
TOILET SEATCOVERS(UNOBSTRUCTED)
BABY CHANGING STATION (UNOBSTRUCTED)
27"
HAND DRYER (UNOBSTRUCTED)
48"
MA
X
TO C
ON
TRO
LS
18" MIN
TO
RE
FLE
CT
IVE
SU
RF
AC
E
74"
MIN
.
18"
MA
X
FULL LENGTH MIRROR (UNOBSTRUCTED)
TO R
EFL
EC
TIV
E
SU
RFA
CE
WALL MOUNTED SIGNAGE TO BE LOCATED ON LATCH SIDE OF DOOR & CLEAR OF DOOR
SWING, MOUNT AT 48" MIN TO BASELINE OF LOWEST TACTILE CHARACTER AND 60" MAX
TO BASELINE OF HIGHEST TACTILE CHARACTER FROM FINISH FLOOR
WOMEN
MEN
HEIGHT OF LETTERING, 5/8" TO 2" MAX, WITH
UPPER CASE CHARACTERS
CORRESPONDING GRADE 2 BRAILLE
INSTALL ON THE RIGHT SIDE OF DOUBLE DOORS
MEN WOMEN UNISEX
48"
MIN
- 6
0" M
AX
* USE 1/8" ALUMINUM PLATE
SOLID HEAD EXPANSION ANCHORS, TYP. EACH CORNER
2 1/2" MAX.
1 1/
2" M
AX
.
3" M
AX
.
15"-16" MAX.
CLEAR FLOOR SPACE
SE
AT
WA
LL
CO
NTR
OL
WA
LL
BACK
18"CLEAR INSIDE
36"
36"
CLE
AR
INS
IDE
36"
48"
4"
18" VERTICAL GRAB BAR1'
- 5
" M
AX
A. THESE DETAILS ARE SHOWN FOR MINIMUM ACCESSIBILITY REQUIREMENTS. SEE PROJECT SPECIFIC DETAILS FOR ADDITIONAL INFORMATION. VERIFY WITH ARCHITECT ANY DIFFERENCES BEFORE PROCEEDING WITH CONSTRUCTION.
GENERAL NOTE - ACCESSIBILITY
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/27/2
01
8 9
:30
:41
AM
ACCESSIBILITYCOMPLIANCE
LAH
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PERMIT SET
G701
HKA
3/8" = 1'-0"G701
B4 ACCESSIBLE 36"x36" SHOWER STALL
3/8" = 1'-0"G701
A1 ACCESSIBLE SINK DETAIL3/8" = 1'-0"G701
A3 ACCESSIBLE WALL / FLOOR MOUNTED TOILET DETAIL
6" = 1'-0"G701
D3 CHANGE IN LEVELS
3/8" = 1'-0"G701
C2 DRINKING FOUNTAIN DETAIL3/8" = 1'-0"G701
C1 MISC. MOUNTING HEIGHTS3/8" = 1'-0"G701
C3 RESTROOM MOUNTING HEIGHTS
3/8" = 1'-0"G701
D1 RESTROOM SIGNAGE
3/8" = 1'-0"G701
B2 SHOWER SEAT DESIGN3/8" = 1'-0"G701
B3 TRANSFER SHOWER STALL3/8" = 1'-0"G701
B1 URINAL MOUNTING HEIGHT
# Date Revision
WH
M
J
T
A. PLAN WALL DIMENSIONS ARE TO GRID LINE, EXISTING STEM WALL, OR FACE OF WALL STRUCTURE. "CLEAR" DIMENSIONS ARE TO FACE OF WALL FINISH.
B. FIELD VERIFY ALL EXISTING CONDITIONS AND THEIR COMPATIBILITY WITH NEW CONSTRUCTION PRIOR TO THE COMMENCEMENT OF WORK. COORDINATE DISCREPANCIES WITH ARCHITECT.
C. DO NOT SCALE DRAWINGS.D. SEE STRUCTURAL, MECHANICAL AND
ELECTRICAL DRAWINGS FOR MORE INFORMATION.
E. SEE G SERIES SHEETS FOR WALL TYPES AND TYPICAL ACCESSIBILITY CLEARANCE AND COMPLIANCE REQUIREMENTS.
F. ADJUST MASONRY COURSING WHERE APPLICABLE SO THAT NO BLOCKS ARE CUT TO BE LESS THAN HALF A BLOCK IN WIDTH.
G. ADJUST EXISTING GRADES TO REQUIRED ELEVATIONS - 95% COMPACTION MINIMUM.
H. PROVIDE MINIMUM 2% SLOPE TO FLOOR DRAINS, TYPICAL.
GENERAL NOTE - FLOOR PLAN
8
9
10
K L
MEN'S TOILETSS101
WOMEN'S TOILETSS102
SHOWER ROOMS106
SHOWER ROOMS105
SHOWER ROOMS104 SHOWER ROOM (ADA)
S103
MECH ROOM / CHASES107
10' - 0" 11' - 4" 10' - 0"
29' - 0"
6' -
2"
6' - 1" 6' - 4" 10' - 0"
2' - 0"
F.V.
11"
S101 S102
S105S106
S107
XM08
XM08
XM
08
M06
M08
M04 M04
M08
M06
M06
M08
M06
.I
M06
XM
08XM08 XM08
XM
08
M08
A201
A1
XM08.A
XM
08.B
3' - 4" 3' - 0 7/8"
17' -
6"
20' -
0"
5' -
1"
A251
B4
B1
5' -
4"
4' -
0"
6' -
8"
A201
C3A201
A3
A201
C1
5' - 0"
3
4 4
2
1717
34 13
1717
1717
6' - 8"
3 3' - 0" 3' - 4"
11' -
4"
3' -
4"
8' -
8"
2424
5' - 4 3/8" 7' - 8 3/8" 8' - 1"
1' - 4"F.V.
1' - 0"
4' -
0"
6' -
0"
2' -
0"
3' -
10"
2' -
8"
27
C2
A301
13
A4
A351
3' -
5"
1' -
4"
A4
A351
A2
A301
1919
3
3 3
3
4
29 A3A351
SIM.
1
1
C2A5
9' -
4"
10' -
0"
A251
A3
A1
A2A4
2' -
8"
3' -
4"
1' -
4"
2' - 7 3/8" 3' - 5 5/8" 3' - 3 5/8" 2' - 4 3/4"
10' - 2" 9' - 10" 5' - 9"
43' - 6"
31' -
4"
5' -
0"
13
XM
08
XM08
2' -
8"
3' -
4"
2% MAX.2% MAX.
2% MAX.
2% MAX.
TYP.
35
TYP.
35
2% MAX. 2% MAX.
2' - 0"
4' -
0"
S104 S103
M06
6' -
4 3
/8"
XM08
M08
XM
08
XM08
M08
M08
M06M06
XM
08
A601A4
TYP.
5' -
0"
A1A351
C5
A501
30
3030
3030
30
3030
3030
4318
XM08
30
1' - 6" 3' - 3"3' - 0 1/2"
1' - 6"1' - 6"
4' - 11"
6' - 6"
36 3636
36
36
36
36
5' -
0"
5' - 0"
33 33
A501A126
26
71
A. INSTALL 4" OF FIBER REINFORCED OR REBAR REINFORCED, PORTLAND CEMENT CONCRETE OVER 4" OF COMPACTED AGGREGATE BASE, UNLESS OTHERWISE SPECIFIED OR REQUIRED.
B. WHERE NEW SIDEWALK IS FLUSH AGAINST EXISTING BUILDING, INSTALL EXPANSION JOINTS BETWEEN BUILDING FOUNDATION WALL AND NEW CONCRETE SIDEWALK.
C. PROVIDE SAW CUT OR TOOLED CONTROL JOINTS AT INTERVALS EQUAL TO THE WIDTH OF NEW SIDEWALK, PERPENDICULAR TO THE DIRECTION OF PEDESTRIAN TRAVEL.
D. PROVIDE AN EXPANSION JOINT AT ALL CHANGES OF DIRECTION IN NEW SIDEWALK.
E. SLOPE NEW CONCRETE SIDEWALK AWAY FROM EXISTING BUILDING AT A MAXIMUM SLOPE OF 2%. ALL FINISH ELEVATIONS, DOOR THRESHOLDS, AND SLOPES SHALL COMPLY WITH ADA ACCESSIBILITY GUIDELINES.
F. FINISH NEW CONCRETE SIDEWALK WITH A MEDIUM BROOM, PERPENDICULAR TO THE DIRECTION OF PEDESTRIAN TRAVEL.
NEW CONCRETE
SIDEWALK NOTES
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/27/2
01
8 9
:29
:32
AM
FLOORPLAN
LAH
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PERMIT SET
A101
HKA
3/8" = 1'-0"A101C2 LEVEL 01
KEYNOTE LEGEND1 STAINLESS STEEL BABY CHANGING
FOLD-DOWN STATION
2 STAINLESS STEEL ACCESSIBLE DRINKINGFOUNTAIN, CONT. SEALANT
3 STAINLESS STEEL WALL-MOUNTEDLAVATORY, RE: PLUMBING
4 WALL-MOUNTED STAINLESS STEEL TOILET,RE: PLUMBING
13 EXISTING CONCRETE STEM WALL, FIELDVERIFY LOCATION AND EXTENTS OFEXISTING OPENINGS
17 NEW CONCRETE SIDEWALK
18 MOP SINK
19 CUSTOM DIAMOND PLATE METAL TOILETPARTITIONS; WELDED TO STEEL COLUMNS
24 EXISTING PREFAB METAL BLDG COLUMN(FIELD VERIFY SIZE AND LOCATION)
26 PRECAST SHOWER SEAT
27 EXISTING PREFAB METAL BLDG CROSSBRACING
29 STAINLESS STEEL WALL-MOUNT URINAL
30 FLOOR DRAIN, SLOPE FLOOR TO DRAIN. RE:PLUMBING
33 HOSE BIB, RE: PLUMBING
34 SHIFT OPENING (SAWCUT AND FILL ASREQUIRED) IN CONCRETE WALL TOACCOMMODATE NEW DOOR LOCATION
35 SIDEWALK EXPANSION JOINT
36 ADA WALL MOUNTED SIGNAGE, REFER TODETAIL D1/G701
43 WATER HEATER; SEE PLUMBING
71 MOP RACK
N
# Date Revision
M M
M
MM M
J
J
T
J
T
A. COORDINATE ALL PENETRATIONS OF ROOF SYSTEM WITH MECHANICAL AND ELECTRICAL DRAWINGS.
GENERAL NOTE - ROOF PLAN
8
9
10
K L
2 1/2" / 1'-0"
9' - 5 13/16"
9' - 5 13/16"
33' -
3 5
/8"
33' - 11 5/8"
2 1/2" / 1'-0"
13' - 0 5/16"
3' - 0"
2' -
0"
2' - 11 5/8"
5' -
0"
3' - 11"
6' -
4"
2323
D2
A121
D1
A121
D2
A121
D1
A121
D4
A121
EQ EQ
32
A5
A501
A5
A501
SIM.
8
9
10
K L
CL-028' - 6 1/4"
CL-028' - 6 1/4"
CL-028' - 6 1/4"
CL-028' - 6 1/4"
S101S102
S103S104S105
S106
S107
O.T.S.
24
CL-028' - 6 1/4"
CL-028' - 6 1/4"
1' -
0"
1' - 0" 1' - 0"
1' - 0"
1' -
0"
24
C1A501
CL-018' - 6 1/4"
37
37
37
37
38
39
39
38
38
38
38
39
38 39
3938
3838
38 39
39
3838
3838
39
39
3838
24
24
39
C5
A501
32 32
32
3232
3232
32
32
32
32
32
32
CL-01
CL-01
CL-01
CL-01
CL-01
38
A5
A501
A. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL LIGHTING AND DIFFUSER INFORMATION.
B. THE CEILING HEIGHT SHOWN IN THE ROOM TAG INDICATES THE HEIGHT OF THE DOMINANT CEILING FINISH. SEE ADDITIONAL CEILING FINISH CALLOUTS FOR OTHER CEILING HEIGHT OR FEATURES.
C. THE CONTRACTOR SHALL COORDINATE ALL TRADES TO ENSURE THAT DESIGNATED CEILING HEIGHTS CAN BE ACHEIVED. NOTIFY ARCHITECT OF ANY CONFLICTS OR CONDITIONS THAT PREVENT THIS FROM OCCURRING BEFORE PROCEEDING WITH THE WORK.
GENERAL NOTE - RCPPRE-FINSIHED ARCHITECTURAL METAL ROOFING PANEL
PRE-FINISHED CONTINUOUS METAL CLEAT
SLIP SHEET (AS REQUIRED BY METAL PANEL MANUFACTURER)
FULLY ADHERED WATERPROOF MEMBRANE UNDERLAYMENT, LAP END MIN. 2"
EXTENDED RAKE EDGE METAL FLASHING (STAGGER FASTENERS)
WOOD NAILER, WHERE APPLICABLE
RE: ASSEMBLY TYPES
ROOF DECK(RE: STRUCTURAL/ ASSEMBLY TYPES)
PRE-FINSIHED ARCHITECTURAL METAL ROOFING PANEL
PANEL CLIP
DOWNSIDE PERIMETER METAL FLASHING (STAGGER FASTENERS)
PRE-FINISHED CONTINUOUS METAL CLEAT
SLIP SHEET (AS REQUIRED BY METAL PANEL MANUFACTURER)
FULLY ADHERED WATERPROOF MEMBRANE, LAP END MIN. 2"
ROOF DECKRE: STRUCTURAL
WOOD NAILER, WHERE APPLICABLE
4" MIN. OVERLAP (LAPJOINTS AWAY FROMPREVAILING WIND)
4" MIN.PRE-FINSIHED ARCHITECTURAL METAL ROOFING PANEL
SLIP SHEET (AS REQUIRED BY METAL PANEL MANUFACTURER)FULLY ADHERED WATERPROOF MEMBRANE
TURN PANEL PANS UP ATRIDGE TO PROVIDE SECONDARY CLOSURE
"Z" CLOSURE (FASTENED AND SET IN SEALANT OR SOLDERED AS MATERIAL PERMITS
SEALANT, MIN. 2 BEADS
PRE-FINSIHED ARCHITECTURAL METAL ROOFING RIDGE CAP
RE: ASSEMBLY TYPES
ROOF DECK(RE: STRUCTURAL/ ASSEMBLY TYPES)
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/27/2
01
8 9
:29
:39
AM
ROOF PLAN&REFLECTEDCEILINGPLAN
LAH
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PERMIT SET
A121
HKA
1/4" = 1'-0"A121
A1 ROOF PLAN1/4" = 1'-0"A121
A3 LEVEL 01
KEYNOTE LEGEND23 STANDING SEAM METAL ROOF
24 EXISTING PREFAB METAL BLDG COLUMN(FIELD VERIFY SIZE AND LOCATION)
32 MECHANICAL EQUIPMENT, RE: MECHANICAL
37 EXTERIOR WALL-MOUNTED LIGHT FIXTURE,SEE ELECTRICAL
38 LIGHT FIXTURE. RE: ELECTRICAL
39 ELECTRICAL FIXTURE. RE: ELECTRICAL
N N
1 1/2" = 1'-0"A121D2 ROOFING (METAL) - EDGE w/ RAKE
1 1/2" = 1'-0"A121D1 ROOFING (METAL) - EAVE
1 1/2" = 1'-0"A121D4 ROOFING (METAL) - RIDGE
# Date Revision
A. COORDINATE GRADING SHOWN ON ELEVATIONS w/ CIVIL
B. PROVIDE GUTTERS AND DOWN SPOUTS w/ HEAT CABLE, SNOW FENCES, AND SNOW CLIPS - SEE ROOF PLAN
C. FOR TYPICAL WALL ASSEMBLY INCLUDING MATERIAL DESIGNATIONS AND DETAILING APPROACH, SEE A350 SERIES
GENERAL NOTE -
BUILDING ELEVATION
K L
EXIST. OPENING
3' - 4" 11' - 4"
EXIST. OPENING
3' - 4 1/2" 2' - 3 1/8" 3' - 4" 4' - 4 3/8"
EXIST. OPENING
3' - 4 1/2" 4' - 8 1/2" 3' - 4" 3' - 4"
2424
13
27
70
1616
47
36 3636 36
67
32
72
32
72
LEVEL 01100' - 0"
8910
24
13
T.O. EXIST. STEM WALL102' - 0"
24
24
70
47
23
32
72
LEVEL 01100' - 0"
8 9 10
24
T.O. EXIST. STEM WALL102' - 0"
27
13
5' - 4 3/8"
70
23
47
32
32
72
KL
2424
132
27
708' -
0"
10' - 8 3/8"
47
32
7232
72
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/27/2
01
8 9
:29
:53
AM
BUILDINGELEVATIONS
LAH
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PERMIT SET
A201
HKA
1/4" = 1'-0"A201
A1 BUILDING ELEVATION - SOUTH
1/4" = 1'-0"A201
C3 BUILDING ELEVATION - EAST
1/4" = 1'-0"A201
A3 BUILDING ELEVATION - WEST
1/4" = 1'-0"A201
C1 BUILDING ELEVATION - NORTH
KEYNOTE LEGEND2 STAINLESS STEEL ACCESSIBLE DRINKING
FOUNTAIN, CONT. SEALANT
13 EXISTING CONCRETE STEM WALL, FIELDVERIFY LOCATION AND EXTENTS OFEXISTING OPENINGS
16 SAW CUT NEW OPENING IN CONCRETE STEMWALL FOR DOOR
23 STANDING SEAM METAL ROOF
24 EXISTING PREFAB METAL BLDG COLUMN(FIELD VERIFY SIZE AND LOCATION)
27 EXISTING PREFAB METAL BLDG CROSSBRACING
32 MECHANICAL EQUIPMENT, RE: MECHANICAL
36 ADA WALL MOUNTED SIGNAGE, REFER TODETAIL D1/G701
47 PREFINISHED METAL FASCIA, TO MATCHROOF
67 ADA WALL MOUNTED CONDUCT SIGNAGE,REFER TO DETAIL D1/G701
70 HONED CMU
72 SHEET METAL FLASHED CURB W/CONTINUOUS ICE & WATER SHIELD
# Date Revision
A. ENSURE THAT ALL REQUIRED FIXTURE AND CABINET CLEARANCES AND OTHER REQUIREMENTS ARE MAINTAINED PURSUANT TO ADAAG AND ANSI A117.1. SEE SHEET G701 FOR GENERAL GUIDANCE ON COMMON MOUNTING HEIGHTS.
B. PROVIDE BLOCKING/BACKING AS NECESSARY FOR MOUNTING OF WALL-MOUNTED CABINETS, FIXTURES AND EQUIPMENT PER MANUFACTURERS RECOMMENDATIONS. COORDINATE THIS REQUIREMENT THROUGH ALL FLOOR PLANS, EQUIPMENT PLANS, AND INTERIOR ELEVATIONS.
C. ON ALL EXPOSED CABINET SIDES, INCLUDING KNEE OPENINGS, PROVIDE FINISHED FACE TO MATCH CABINET FRONTS . PROVIDE SIDESPLASHES WHENEVER COUNTERTOPS ARE ADJACENT TO WALLS.
GENERAL NOTE -
INTERIOR ELEVATIONA. SEE REFLECTED CEILING PLANS FOR CEILING
FEATURES AND FINISH ELEVATIONS.
GENERAL NOTE - FINISH SCHEDULE
8 8 8 8
3
TYP.
37
TYP.
7
11
W1
12 12
A251C5
28
22
TYP.
19
15
TYP.
21
1' -
0"
5' -
0"
4" 2' - 8" 3' - 9" 2' - 2" 11" 2' - 2" 4" 4" 2' - 8" 3' - 2" 2' - 2" 4"
A251C3
W1
CONTINUOUS HINGE
CUSTOM DIAMOND PLATE METALTOILET PARTITIONS; WELDED TO STEELCOLUMNS
(TYP)
3" RAD.
3 1/
2"
C4
A251
HSS COLUMN RE: STRUCTURAL FORSIZE
HSS COLUMN RE: STRUCTURAL FORSIZE
CONTINUOUSLY WELD DIAMOND PLATEPARTITIONS TO HSS COLUMN, TYP.
HSS COLUMN RE: STRUCTURAL FORSIZE
SCHEDULED WALL; SEE FLOOR PLAN
12"
42"
24"
3" RADIUS, TYP.
24"
PLAN VIEW SECTION
CUSTOM DIAMOND PLATE URINAL PARTITION
29
1
A251C3
W1
6
4
28
2222
9
8' -
0"
S103
W18
7
3
39
6
W1
12
1' - 3"
A501A1
4
6
10
6
1' - 6"
1' - 6"W1
6
9
W1
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/27/2
01
8 9
:30
:07
AM
INTERIORELEVATIONS
LAH
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PERMIT SET
A251
HKA
FINISH LEGEND
HIDE THESE COLUMNS
CODE DESCRIPTION REMARKSFinish
Category Finish Type
CEILING FINISHES
CEILINGFINISHES
CEILING CL1 TYPE X GYPSUM BOARD PANELS,PAINTED. COLOR, P2
FLOOR FINISHES
FLOORFINISHES
CONCRETE F1 EXPOSED CONCRETE
FLOORFINISHES
EPOXY F2 RESINOUS FLOORING
PAINT
PAINT PAINT P1 WALL COLOR, HOLLOW METALDOOR FRAMES & DOORS, SW 7015,REPOSE GRAY
PAINT PAINT P2 CEILING COLOR,
WALL FINISHES
WALLFINISHES
WALL W1 BLOCK FILLER ON HONED CMUWITH HIGH PERFORMANCECOATING, COLOR, P1
ROOM FINISH SCHEDULE
Room Name Floor Base
Walls
Ceiling Notes RoomN E S W
S101 MEN'S TOILETS F2 - W1 W1 W1 W1 CL1 S101
S102 WOMEN'S TOILETS F2 - W1 W1 W1 W1 CL1 S102
S103 SHOWER ROOM (ADA) F2 - W1 W1 W1 W1 CL1 S103
S104 SHOWER ROOM F2 - W1 W1 W1 W1 CL1 S104
S105 SHOWER ROOM F2 - W1 W1 W1 W1 CL1 S105
S106 SHOWER ROOM F2 - W1 W1 W1 W1 CL1 S106
S107 MECH ROOM / CHASE F1 - - - - - OTS S107
KEYNOTE LEGEND1 STAINLESS STEEL BABY CHANGING
FOLD-DOWN STATION
3 STAINLESS STEEL WALL-MOUNTEDLAVATORY, RE: PLUMBING
4 WALL-MOUNTED STAINLESS STEEL TOILET,RE: PLUMBING
6 ADA GRAB BARS
7 SOAP DISPENSER
8 24"X36" GLASS MIRROR WITH SHELF
9 TOILET TISSUE DISPENSER
10 SHOWER CONTROLS
12 ELECTRIC HAND DRYER
15 CONTINUOUS HINGE, INTERIOR SURFACEMOUNTED
19 CUSTOM DIAMOND PLATE METAL TOILETPARTITIONS; WELDED TO STEEL COLUMNS
20 CONTINUOUSLY WELD DIAMOND PLATEPARTITIONS TO HSS COLUMN, TYP.
21 PARTITION SLIDING LATCH WITH SWINGBUMPER, INTERIOR SURFACE MOUNTED
22 HSS COLUMN RE: STRUCTURAL FOR SIZE
28 HSS BEAM, RE: STRUCTURAL FOR SIZE
29 STAINLESS STEEL WALL-MOUNT URINAL
39 ELECTRICAL FIXTURE. RE: ELECTRICAL
3/8" = 1'-0"A251B1 INTERIOR ELEVATION - RESTROOMS S101/S102 NORTH
3/8" = 1'-0"A251B4 INTERIOR ELEVATION - RESTROOMS S102/S101 SOUTH
1 1/2" = 1'-0"A251C5 ENLARGED CUSTOM PARTITION DETAIL
1 1/2" = 1'-0"A251C4 TYP. STALL COLUMN
3/8" = 1'-0"A251C3 URINAL SCREEN
3/8" = 1'-0"A251
A5 S101 MENS RR - WEST
3/8" = 1'-0"A251C2 TYPICAL ADA TOILET STALL
3/8" = 1'-0"A251
A3 S103 ADA RR - SOUTH3/8" = 1'-0"A251
A4 S103 ADA RR - WEST3/8" = 1'-0"A251
A1 S103 ADA RR - NORTH3/8" = 1'-0"A251
A2 S103 ADA RR - EAST
# Date Revision
A. WALL DIMENSIONS ARE TO GRID LINE, EXISTING STEM WALL, OR FACE OF WALL STRUCTURE. "CLEAR" DIMENSIONS ARE TO FACE OF WALL FINISH.
B. SEE CIVIL, STRUCTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR MORE INFORMATION.
C. SEE G SERIES SHEETS FOR WALL TYPES AND TYPICAL ACCESSIBILITY CLEARANCE AND COMPLIANCE REQUIREMENTS.
D. DO NOT SCALE DRAWINGS.
GENERAL NOTE - SECTION
LEVEL 01100' - 0"
ROOF PLAN108' - 8"
8 9 10
T.O. EXIST. STEM WALL102' - 0"
22
32
CL-
01
CL-
02
CL-
02
XM08
R-0
1
A2
A301
10
24
24 24
A501C1
A351C423
SHOWER ROOMS105
F-01
C5
A50132
19
F-01F-01 M08
M08
M06
M06.I
72
LEVEL 01100' - 0"
ROOF PLAN108' - 8"
K L
T.O. EXIST. STEM WALL102' - 0"
C2A301
1010
33
336
XM08XM08.A
M06 M06M06 M04M04CL-
02
CL-
02
CL-
02
CL-
02
R-0
1
A351A3
A351A3
SIM, OPP
SHOWER ROOMS105
SHOWER ROOMS104
SHOWER ROOM (ADA)S103
F-01
2424
13' - 0 5/16"
32
8 8
77
3737
2 1/2" / 1'-0"2 1/2" / 1'-0"
32
72
72
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/27/2
01
8 9
:30
:14
AM
BUILDINGSECTIONS
LAH
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PERMIT SET
A301
HKA
3/8" = 1'-0"A301C2 BUILDING SECTION (N/S)
3/8" = 1'-0"A301
A2 BUILDING SECTION (E/W)
KEYNOTE LEGEND2 STAINLESS STEEL ACCESSIBLE DRINKING
FOUNTAIN, CONT. SEALANT
3 STAINLESS STEEL WALL-MOUNTEDLAVATORY, RE: PLUMBING
6 ADA GRAB BARS
7 SOAP DISPENSER
8 24"X36" GLASS MIRROR WITH SHELF
10 SHOWER CONTROLS
19 CUSTOM DIAMOND PLATE METAL TOILETPARTITIONS; WELDED TO STEEL COLUMNS
22 HSS COLUMN RE: STRUCTURAL FOR SIZE
23 STANDING SEAM METAL ROOF
24 EXISTING PREFAB METAL BLDG COLUMN(FIELD VERIFY SIZE AND LOCATION)
32 MECHANICAL EQUIPMENT, RE: MECHANICAL
37 EXTERIOR WALL-MOUNTED LIGHT FIXTURE,SEE ELECTRICAL
72 SHEET METAL FLASHED CURB W/CONTINUOUS ICE & WATER SHIELD
# Date Revision
XM08
CL-02
CONCRETE FOUNDATIONWALL; RE: STRUCTURAL
EXISTING PREFAB METALBLDG COLUMN (FIELDVERIFY SIZE ANDLOCATION)
F-01
EXISTING CONCRETE STEMWALL/PIER, FIELD VERIFY
EXPANSION JOINT
EXISTING PREFAB METALBLDG COLUMN (FIELDVERIFY SIZE ANDLOCATION)
PREFINISHED METALFASCIA, TO MATCH ROOF
R-01
2X PRESSURE TREATEDFRAMING FOR SOFFIT ANDFASCIA
5/8" PLYWOOD SHEATHING
XM08 5/8" ANCHOR BOLTS @ 32"O.C., RE: STRUCTURAL
FOIL-FACED, TAPED R30BATT INSULATION
3X8 PRESSURE TREATEDSILL PLATE
2X4 FRAMING @ 16" O.C.MAX. FOR CEILING, SHIMAS NECESSARY
HIGH TEMP. ICE & WATERSHIELD, CONTINUOUS
OV
ER
LAP
1" M
IN.
XM08
EXISTING CONCRETE STEMWALL/PIER, FIELD VERIFY
F-01
EXPANSION JOINT
CONCRETE FOUNDATIONWALL; RE: STRUCTURAL
EXTERIOR WALL-MOUNTED LIGHTFIXTURE, SEE ELECTRICAL
5/8" ANCHOR BOLTS @ 32" O.C., RE:STRUCTURAL
3X8 PRESSURE TREATED SILL PLATE
2X BLOCKING BETWEEN TRUSSES, RE:STRUCTURAL
PREFINISHED METAL FASCIA, TOMATCH ROOF
2X10 PRESSURE TREATED RIM JOIST
EXTERIOR GYPSUM SOFFIT BOARD
1" X 3" WOOD FURRING STRIPS, 16" O.C.MAX.
J BEAD TRIM, COATED
R-01
CL-02
PREFINISHED CUSTOM METALFLASHING, TO MATCH ROOF
XM08
FOIL-FACED, TAPED R30BATT INSULATION
HIGH TEMP. ICE & WATERSHIELD, CONTINUOUS
R-01
PREFINISHED METALFASCIA, TO MATCH ROOF
PREFINISHED CUSTOM METALFLASHING, TO MATCH ROOF
J BEAD TRIM, COATED
EXTERIOR GYPSUM SOFFIT BOARD
XM08
CL-02PREFINISHED CUSTOM METALFLASHING, TO MATCH ROOF
5/8" ANCHOR BOLTS @ 32" O.C., RE:STRUCTURAL
8"
1"
1"1"
TYPICAL CHAMFER @ CONCRETE
FOUNDATION WALL
EXPANSION JOINTEXPANSION JOINT
CONCRETE FOUNDATION WALL; RE:STRUCTURAL
FOIL-FACED, TAPED R30BATT INSULATION
2X10 PRESSURE TREATEDRIM JOIST
2X4 FRAMING @ 16" O.C.MAX. FOR CEILING, SHIMAS NECESSARY
8' - 8"
HIGH TEMP. ICE & WATERSHIELD, CONTINUOUS
3X8 PRESSURE TREATEDSILL PLATE
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/27/2
01
8 9
:30
:19
AM
WALLSECTIONS
Author
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PERMIT SET
A351
Checker
1 1/2" = 1'-0"A351
A3 WALL SECTION @ EXISTING STEEL COLUMN PIER1 1/2" = 1'-0"A351
A4 SECTION DETAIL, EXISTING STEM WALL
1 1/2" = 1'-0"A351
C4 SECTION DETAIL - RAKE WALL @ ROOF
1 1/2" = 1'-0"A351
A1 WALL SECTION @ LOW ROOF/EXT. SIDEWALK
# Date Revision
CL-01
XM08
R-01
M06.I
M06
TYP.1/4" MIN.
2X10 PRESSURETREATED RIM JOIST
PREFINISHED METALFASCIA, TO MATCH
ROOF
EXTERIOR GYPSUMSOFFIT BOARD
J BEAD TRIM, COATED
5/8" ANCHOR BOLTS @ 32"O.C., RE: STRUCTURAL
8' - 0"A601
A2
TYP.
3X8 PRESSURETREATED SILL PLATE
1" X 3" WOOD FURRINGSTRIPS, 16" O.C. MAX.
C5
A501
HIGH TEMP. ICE & WATERSHIELD, CONTINUOUS
PREFINISHED CUSTOMMETAL FLASHING, TO
MATCH ROOF
FOIL-FACED, TAPED R30BATT INSULATION
FOIL-FACED, TAPED R30BATT INSULATION CL-01 CL-02
XM08
R-01
2X PRESSURE TREATEDFRAMING FOR SOFFIT ANDFASCIA
2X PRESSURE TREATEDFRAMING FOR SOFFIT ANDFASCIA
ROOF STRUCTURE, RE:STRUCTURAL
TRUSS BLOCKING; RE:STRUCTURAL
5/8" ANCHOR BOLTS @ 32"O.C., RE: STRUCTURAL
3X8 PRESSURE TREATEDSILL PLATE
HIGH TEMP. ICE & WATERSHIELD, CONTINUOUS
FOIL-FACED, TAPED R30BATT INSULATION
ADDITIONAL VERT MEMBER AS REQ. RE: STRUCTURAL
CL-02
FOIL-FACED, TAPED R30BATT INSULATION
MECHANICAL EQUIPMENT,RE: MECHANICAL
5/8" PARTICLE BOARDSHEATHING
2X6 BEARING WALL2X6 BEARING WALL
ROOF STRUCTURE, RE:STRUCTURAL
TRUSS BLOCKING; RE:STRUCTURAL
2X BLOCKING BETWEENTRUSSES, RE:STRUCTURAL
2X10 JOIST, RE: STRUCTURAL
R-01
A501A3
HIGH TEMP. ICE & WATERSHIELD, CONTINUOUS
2" RIGID INSULATIONCONTINUOUS BEAD OF BUTYL TAPE FLASHING
AROUND ENTIRE PERIMETER OF ROOF CURB, FASTENED
AS SPEC'D
MFR SUGGESTED FASTENER WITH NEOPRENE GASKET
ROOF CRICKET BUILT INTO ROOF CURB
PLAN VIEW
3"3"
1' - 4"1-1/2" DIA. RADIUS
MASONRY WALL BELOWFACE OF SHOWER WALL
SEALED PRE-CAST CONC. BENCH SEAT
3"
3" T
YP
.
3" TYP.3/4" RADIUS
1' -
6"
6" CMU, GROUT SOLID. SAWCUT TOP BLOCK AS NEEDED FOR HEIGHT.
#4 BAR, 6" FROM EA. END & (1) AT RETURN WALL
SECTION VIEW
EMBED @ 2'-0" O.C.
SEALED PRECAST CONC. BENCH TOP
CONT. SEALANT AT WALL
1-1/2" X 1-1/2" CONT. ANGLE ANCHORED AT 16"
O.C. WITH 1/2" X 3" EXPANSION BOLTS
PROVIDE STRUCTURAL SUPPORT AT EACH END OF ROOF PANEL AND CURB
CRICKET (FLANGES OVERLAPPED AND SOLDERED)
END CLOSURE
EQUIPMENT CURB WRAP WITH PRE-FINISHED METAL OR PAINT TO MATCH ROOF PANELS
METAL ROOF PANELS (RE: SPECS)
END CLOSURE
8" MIN.
1"
MIN
.
1/2" MIN.
8" MIN.
HIGH-DOMED , CAPPED, GASKETED STAINLESS STEEL FASTENERS 18" O.C. (MIN. 2 FASTENERS PER SIDE)
REMOVABLE PRE-FINISHED SHEET METAL COUNTER FLASHING
STAINLESS STEEL FASTENERS APPROX. 8" O.C.
BUILT UP BUILT UP CURB ASSEMBLY (RE: STRUCT.)
ROOFING SYSTEM (RE: SPECS)
SEE SECTION DETAIL BELOW FOR CLARITY
CONTINUOUS SEALING MATERIAL AT TOP OF CURB (RE: SPECS)
STAINLESS STEEL FASTENERS 8" O.C.
MECHANICAL UNIT, HOOD, ETC. BASE EXTENDS 1/2" MIN.
BEYOND EDGE OF CURB
HIGH TEMP. ICE & WATER SHIELD, CONTINUOUS
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/27/2
01
8 9
:30
:24
AM
ARCHITECTURALDETAILS
LAH
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PERMIT SET
A501
HKA
1 1/2" = 1'-0"A501
C1 ROOF DETAIL, SOFFIT @ RESTROOM ENTRANCE1 1/2" = 1'-0"A501
C5 SECTION DETAIL, ROOF @ RESTROOM ENTRANCE
1" = 1'-0"A501A5 SECTION DETAIL - EQUIPMENT CURB
3/4" = 1'-0"A501A1 SHOWER BENCH DETAIL
1 1/2" = 1'-0"A501
B3 ROOFING (METAL) - EQUIPMENT CURB
1 1/2" = 1'-0"A501A3 ROOFING (METAL) - EQUIPMENT CURB DETAIL
# Date Revision
A. FIELD VERIFY ALL DIMENSIONS PRIOR TO SHOP DRAWING SUBMITTAL & SUBSEQUENT FABRICATION OF ALL DOOR FRAMES.
B. PROVIDE CLEARANCE REQUIRED BY ACCESSIBILITY CODES ANSI A117.1 AND ADAAG AT ALL DOORS, AS DEPICTED IN DETAILS ON SHEET G003b.
GENERAL NOTE -
DOOR TYPES
FRAME TYPE: SH HOLLOW METAL
SINGLE
2" 2"
SCHED
SEE
SE
E S
CH
ED
ULE
4"
DOOR TYPE: HS01CONST: HM
GRADE II 18GA PRIMED
SCHED
SEE
SEE
SCH
EDU
LE
1 1/2"
SCHEDULED WALL
GROUT FULL
1 1/
2"
FR
AM
E
7 5/
8" T
YP
.
SCHEDULED WALL
DOOR - SEE SCHEDULE
HOLLOW METAL FRAMEPAINTED, BEYOND
SCHEDULED FLOOR
ALUMINUM SADDLE THRESHOLD, SET IN BED OF MASTIC.
5"
1/4"
2" 2"
GYPSUM J-CHANNEL
2X4 FRAMING, SECURED TO UNDERSIDE OF ROOF STRUCTURE
EDGE ANGLE TRIM
SCHEDULED WALL
SEE CEILING ASSEMBLY TYPES
NOTE: PROVIDE 2" PERIMETER SUPPORTING CLOSURE ANGLE. .
1/4" MIN.1/4" MIN.
SINGLE BULLNOSE BLOCK
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/27/2
01
8 9
:30
:27
AM
DOORSCHEDULES& TYPICALDETAILS
LAH
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PERMIT SET
A601
HKA
1/4" = 1'-0"A601
C3 FRAME TYPES - HOLLOW METAL1/4" = 1'-0"A601
C4 DOOR TYPES - HOLLOW METAL
DOOR SCHEDULE
NUMBER
DOOR FRAME
FIRERATING
HARDWAREGROUP NOTES NUMBER
SIZE
TYPE FINISH
DETAIL
TYPE FINISHWIDTH HEIGHT HEAD JAMB THRES
S101 3' - 0" 7' - 0" HS01 B3/A601 B4/A601 B2/A601 SH 01 S101
S102 3' - 0" 7' - 0" HS01 B3/A601 B4/A601 B2/A601 SH 01 S102
S103 3' - 0" 7' - 0" HS01 B3/A601 B4/A601 B2/A601 SH 03 S103
S104 3' - 0" 7' - 0" HS01 B3/A601 B4/A601 B2/A601 SH 03 S104
S105 3' - 0" 7' - 0" HS01 B3/A601 B4/A601 B2/A601 SH 04 S105
S106 3' - 0" 7' - 0" HS01 B3/A601 B4/A601 B2/A601 SH 04 S106
S107 3' - 0" 7' - 0" HS01 B3/A601 B4/A601 B2/A601 SH 02 S107
1 1/2" = 1'-0"A601B3 HEADER DETAIL - HM DOOR - INSULATED
1 1/2" = 1'-0"A601B4 JAMB DETAIL - HM DOOR - INSULATED
3" = 1'-0"A601B2 THRESHOLD DETAIL - SADDLE
3" = 1'-0"A601
A2 GYPSUM CEILING EDGE AT MASONRY1 1/2" = 1'-0"A601
A4 TYP. INTERIOR CMU WALL CORNER
# Date Revision
GENERAL
1. The structural notes are intended to complement the project specifications. Specific notes and details in the drawings shall govern over the structural notes and typical details.
2. Typical details and sections shall apply where specific details are not shown.3. The contractor shall verify all site conditions and dimensions. If actual conditions differ from those shown in the
contract drawings, the contractor shall immediately notify the architect/engineer before proceeding with the fabrication or construction of any affected elements.
4. Drawings shall not be scaled for the purpose of preparing shop drawings or for construction. Where dimensions on the design drawings are not provided or inferred, the contractor may scale drawings only to estimate member lengths for the purpose of bidding.
5. Changes to these contract drawings may be made only by an authorized representative of Dunn Associates, Inc. Dunn Associates, Inc. shall not be held responsible or liable for any claims arising directly or indirectly from changes made without written authorization by an authorized representative of Dunn Associates, Inc.
6. Omissions or conflicts between the contract drawings and/or specifications shall be brought to the attention of the architect/engineer before proceeding with any work involved. In case of conflict, follow the most stringent requirement as directed by the architect/engineer at no additional cost to the owner.
7. The contractor shall submit a written request to the architect/engineer before proceeding with any changes, substitutions, or modifications. Any work done by the contractor before receiving written approval will be at the contractor's risk.
8. The contractor shall coordinate with all trades any items that are to be integrated into the structural system such as openings, penetrations, mechanical and electrical equipment, etc. Sizes and locations of mechanical and other equipment that differs from those shown on the contract drawings shall be reported to the architect/engineer. Contractor shall take measures as required to insure that construction loads shall not exceed design loads for the structure.
9. Any structural items shown on other discipline's drawings that are not shown on the structural drawings, but that are noted as "refer to structural drawings" for additional information, shall be brought to the attention of the structural engineer by the contractor.
10. Items such as fireproofing, waterproofing, insulation, vapor barrier, etc, may be shown or noted on structural drawings for reference only. Refer to the architectural drawings or specifications for more information.
11. The contractor shall be responsible for means, methods, techniques, sequences, and procedures in order to comply with the contract drawings and specifications. The contractor shall provide adequate shoring and bracing as required for the chosen method of erection. Shoring and bracing shall remain in place until final connections for the permanent members are completed. The building shall not be considered stable until all connections are completed. Walls shall not be considered self-supporting and shall be braced until the floor/roof system is completed.
12. Site observations by a field representative of Dunn Associates, Inc. shall not be construed as approval of construction, the procedures, nor special inspection.
13. All work shall be done in accordance with OSHA requirements. Potential conflicts between these documents and OSHA requirements shall be brought to the attention of the structural engineer before proceeding with the work.
14. Shop Drawings and submittals:A. Review of shop drawings and submittals by Dunn Associates, Inc. is for general compliance only and is not
intended for approval. The shop drawing review shall not relieve the contractor from the responsibility of completing the project according to the contract documents.
B. Submittals for the following items shall be submitted to the Project Architect/Engineer for review prior to fabrication and/or installation:1. Concrete Mix Design2. Concrete Reinforcing3. Masonry Block and Grout4. Masonry Reinforcing5. Anchorage and Embeds6. Pre-Fabricated Wood Trusses7. Deferred Design Items
C. Quality control submittals shall be submitted to special inspector for review prior to fabrication/installation. Courtesy copies shall be provided to the project architect and engineer for their records.
D. Detailing and shop drawing production for structural elements will require information (including dimensions) contained in the architectural, structural and/or other consultants' drawings. The structural drawings shall be used in conjunction with the architectural and other consultant's drawings. See the Architectural Drawings for dimensions, doors, windows, non-bearing interior and exterior walls, elevations, slopes, stairs, curbs, drains, recesses, depressions, railings, waterproofing, finishes, chamfers, kerfs, etc.
E. Shop drawings made from reproductions of the structural drawings will be rejected unless the contractor signs a release agreement prior to the shop drawings being reviewed. The contractor may also obtain electronic files of the plan sheets after signing a release agreement. Electronic files of the detail sheets and schedule sheets will not be made available.
F. The Contractor may choose to submit shop drawings and submittals for review electronically. The Contractor may do this provided a minimum of one hard copy set is submitted for review. The submittal will be stamped as received by Dunn Associates, Inc. when the hard copy is received by our office. Hard copies of small submittals need not be submitted if the Contractor receives the approval for this exception by the Engineer of Record.
BASIS OF DESIGN
1. Governing Building Code---------------------------------------------- International Building Code 20152. Risk Category------------------------------------------------------------- II3. Roof
a: Live Load (Not concurrent with Roof Snow Load)------- 20 psfb: Snow Loads.................................................................30 psf
4. Seismic Design CriteriaA. Mapped Spectral Response Accelerations
1. Short Period Acceleration------------------------------------ SS = 1.2692. 1-Second Acceleration---------------------------------------- S1 = 0.422
B. Spectral Response Coefficients1. Short Period Acceleration------------------------------------ SDS = 0.8462. 1-Second Acceleration---------------------------------------- SD1 = 0.444
C. Site Class (Soil Profile)------------------------------------------- DD. Seismic Importance Factor-------------------------------------- 1.0E. Seismic Design Category---------------------------------------- DF. Effective Structural Seismic Weight--------------------------- WG. Lateral Force Resisting System-------------------------------- Special Reinforced Masonry Shear Walls
1. Response Modification Coefficient------------------------ R = 52. System Overstrength Factor-------------------------------- Ωo = 2.53. Deflection Amplification Factor----------------------------- CD = 3.5 4. Design Base Shear-------------------------------------------- V = Cs*W = 0.169W
H. Analysis Procedure------------------------------------------------- Equivalent Lateral Force 5. Serviceability Criteria
A. Deflection Limits----------------------------------------------------- Total----------------- Live/Snow/WindWall------------------------------------------------------------------------------------- L/240
FOUNDATION
1. Soils Report by:---------------------------------------------------------- Not Available2. Soil Bearing Pressure:-------------------------------------------------- 1500 psf on Native Soil (Assumed)3. Frost Protection:---------------------------------------------------------- 30 inches minimum
EARTHWORK
1. Consult the project specifications and soils report for further earthwork requirements. In absence of information, refer to the following notes.
2. Clearing: The entire building area shall be scraped to remove the top 4" of soil including all vegetation and debris.
3. Contractor shall provide temporary shoring for excavations as required.4. Contractor shall provide measures necessary to prevent damage to or settlement of new or existing
construction and utilities on or adjacent to project site.5. Contractor shall provide dewatering as required to protect the site from flooding.6. Proof rolling: The natural undisturbed soil below all footings shall be proof rolled prior to placing concrete.
Remove all soft spots and replace with compacted structural fill.7. Compacted structural fill: All fill material shall be a well-graded granular material with a maximum size less than
4" and with not more than 10% passing a #200 sieve. Fill beneath footings shall be compacted to 95% of the maximum laboratory density as determined by ASTM D 1557. All fill shall be tested. Compacted structural fill shall be placed in lifts not exceeding 8" in uncompacted thickness.
8. Floor slabs shall be underlain by a granular layer at least 4" thick. The granular layer shall have a maximum size less than 1" with not more than 5% passing a #200 sieve and shall be compacted to at least 90% of the maximum laboratory density as determined by ASTM D 1557.
9. The special inspector shall review all excavations and fill placement prior to placing concrete.
Table Footnotes:a. Cement to comply with ASTM C150. Use Type V cement where required by soils report.b. Air content ± 1.5%, measured at point of final placement. Air-entraining admixtures shall comply with ASTM
C260 (when used). Calcium chloride shall not be added to the concrete mix. Unreinforced concrete slabs on grade may have calcium chloride not exceeding one percent.
c. Air entrainment shall be adjusted for the use of admixtures and fly ash.d. Slump limit ± 1" applies to non-plasticized concrete. Test shall be conducted prior to adding plasticizer if
used.e. These values shall be used for parking slabs on grade or other slabs within the building footprint with
exterior exposure. See civil drawings for site concrete requirements.1. Materials unless noted otherwise:
A. Normal Weight aggregates----------------------------------------------------------- ASTM C33B. Fly Ash, Class F Pozzolan----------------------------------------------------------- ASTM C618C. Reinforcing Steel
1. General------------------------------------------------------------------- ASTM A615 Grade 60D. Deformed Bar Anchors (DBA) ------------------------------------------------------ ASTM A496E. Anchor Bolts: See steel and/or wood section(s) of general notes.F. No aluminum conduit or product containing aluminum or any other material injurious to concrete shall be
embedded in concrete.2. The contractor shall be responsible for the design, detailing, care, placement and removal of all formwork and
shores.A. Supporting forms and shoring shall not be removed until structural members have acquired sufficient
strength to safely support their own weight and any construction load to which they may be subjected. In no case, however, shall forms and shoring be removed in less than 24 hours after concrete placement.
3. Reinforcement shall have the following concrete clear cover:A. Cast-in-place Concrete
1. Cast against and permanently exposed to earth------------------- 3"2. Formed concrete exposed to earth or weather:
#6 thru #18 bars-------------------------------------------------------- 2"#5 and smaller bars--------------------------------------------------- 1 1/2"
3. Concrete not exposed to weather or in contact with ground:Slabs, Walls, Joists; #11 bars and smaller --------------------- 3/4"Beams, Columns: Primary Reinforcement, Ties,-------------- 1 1/2"Stirrups, Spirals
4. Construction Joints and Control Joints:A. Provide a beveled 2" x 4" x continuous or intermittent keyway in all horizontal and vertical construction joints
including between top of footing and foundation walls. In addition, all joints shall be intentionally roughened to a full amplitude of approximately 1/4".
B. Control joints shall be installed in slabs on grade so the length to width ratio of the slab is no more than 1.25:1. Control joints shall be completed within 12 hours of concrete placement. Control joints may be installed by either:1. Saw cut with depth of 1/4 the thickness of the slab2. Tooled joints with depth of 1/4 the thickness of the slab
C. Install construction or control joints in slabs on grade at a spacing not to exceed 30 times the slab thickness in any direction, unless noted otherwise. Construction joints shall not exceed a distance of 125'-0" on center in any direction.
D. Install construction joints in walls at a spacing not to exceed 30 times the wall thickness, except in concrete shear walls. For masonry walls above, align joints in concrete walls with masonry control joints.
Concrete Use Comp. Strength f 'c (psi)
Exposure Classes Air Content (b,c)
Cement Type (a)
Aggregate Size, Max.
Max. W/CM Ratio
Max. Flyash
Slump Limit (d)
F0, S0, W0, C0 I, II3000 0.50 25% 1.5% 1 1/2" 5"Footings
F1, S0, W0, C1 I, II3500 0.50 25% 5% 3/4" 4"Foundation Walls
F0, S0, W0, C0 I, II3500 0.45 25% 1.5% 3/4" 5"Interior Slabs on Grade
F3, S0, W0, C2 I, II5000 0.40 25% 6% 3/4" 4"Exterior Concrete (e)
(reinforced)
F3, S0, W0, C0 I, II4500 0.45 25% 6% 3/4" 4"Exterior Concrete (e)
(unreinforced)
CONCRETE
Concrete shall be supplied in accordance with ACI 318 and the following requirements:
6. ConstructionA. Use chairs or other support devices recommended by the CRSI to support bar and tie reinforcement bars
and WWR prior to placing concrete. WWR shall be continuously supported at 36" on center maximum. Reinforcing steel for slabs on grade shall be adequately supported on precast concrete units. Lifting the reinforcing off the grade during placement of concrete is not permitted.
B. Contractor shall coordinate placement of all openings, curbs, dowels, sleeves, conduits, bolts, inserts and other embedded items prior to concrete placement.
C. All embeds and dowels shall be securely tied to formwork or to adjacent rebar prior to concrete placement.D. No pipes, ducts, sleeves, etc. shall be placed in structural concrete unless specifically detailed or approved
by the structural engineer. Penetrations through walls when approved shall be built into the wall prior to concrete placement. Penetrations will not be allowed in footings or grade beams unless detailed. Piping shall be routed around these elements and footings stepped to avoid piping.
E. Reinforcing bars shall not be welded unless specifically shown on drawings. In such cases, use only AWS standards. Do not substitute reinforcing bars for DBAs or HSAs.
F. Reinforcing bars shall not be field bent, except as shown in the contract drawings or permitted by the EOR.7. Detailing:
A. Lap splice lengths shall be detailed to comply with the "Reinforcing Bar Lap Splice Schedule" contained within the contract drawings. 1. Do not splice stirrups and ties. Do not splice vertical bars in retaining walls unless specifically shown.2. At shear wall boundary elements lap lengths shall be increased by 25%. 3. Splices may be made with mechanical splices capable of 125% of yield strength of the bar being spliced
(Type 1). Splices located within lateral resisting elements shall also develop the tensile strength of the bar (Type 2). Mechanical splices shall be the positive connecting type coupler and shall meet all ACI requirements. Use "Cadweld", "Lenton" Standard Couplers, "Bar-Lock" or equal with internal protector. If mechanical splices are used, splices or couplers on adjacent bars shall be staggered a minimum of 24" apart along the longitudinal axis of the reinforcing bars.
B. All 90, 135 and 180° hooks shown graphically in the drawings shall be detailed as ACI standard hooks, unless noted otherwise.
C. At joints provide reinforcing dowels to match the member reinforcing, unless noted otherwise.D. At all discontinuous control or construction slab on grade joints, provide (2) #4 x 48".E. Provide corner bars at intersecting wall corners using the same bar size and spacing as the horizontal wall
reinforcing.F. All vertical reinforcing shall be doweled to footings, or to the structure below with the same size and spacing
as the vertical reinforcing for the element above. Dowels extending into footings shall terminate with a 90° standard hook and shall extend to within 4" of the bottom of the footing. Footing dowels (#8 bars and smaller) with hooks need not extend more than 20" into footings.
G. See details for reinforcing around miscellaneous openings. All recesses that interrupt reinforcing shall be reinforced the same as an opening.
H. Reference ACI 315 for additional detailing requirements.8. Contractor required to submit concrete mix design for review by the engineer prior to any placement of
concrete.9. All concrete shall be mixed and placed per ACI 304. Contractor shall refer to and follow the recommendations
in ACI 305R for hot weather concreting and ACI 306R for cold weather concreting.10. Contractor is not to backfill against retaining walls unless walls have achieved design strength or have been
shored. Contractor is not to backfill against basement walls without placement of the main floor diaphragm unless the walls have been shored or approval of the EOR has been granted, or it has been noted otherwise on the design drawings.
11. Construction activity or storage of materials shall not take place on newly placed concrete until the concrete achieves sufficient strength to provide adequate support.
MASONRY
1. Materials shall be as follows, unless noted otherwise:A. Design strength of all masonry shall be F'm=1900 psi at 28 days, unless noted otherwise. B. Concrete Masonry Units (CMU) shall be ASTM C-90, Grade N, Type 1, medium weight (115 pcf) with a
minimum unit strength of 1900 psi at 28 days for net area.C. Mortar shall be ASTM C270 Portland cement - lime, type “S”, with a minimum compression strength of 1800
psi at 28 days. See specifications for additives allowed. Masonry mortars and masonry cements are not allowed. Use type “M” mortar for masonry below grade (2500 psi).
D. Grout shall be ASTM C476, with a minimum compression strength at least equal to the design strength F'm at 28 days. Limit fly ash to 25% of the total cementitious material. Slump shall be between 8” and 11”.
E. Reinforcing bars shall be ASTM A615, grade 60, (Fy = 60 ksi) except only ASTM A706, grade 60, “low alloy”steel shall be used for reinforcing shown to be welded.
F. Joint Reinforcing shall be ASTM A951, galvanized, standard class, ladder type with #9 wire per ASTM A82.G. Deformed Bar Anchors (DBA) shall be ASTM A496.H. Headed Stud Anchors (HSA) shall be ASTM A108.I. Anchor Bolts shall be ASTM A307. Heavy hex nuts and hardened washers shall be ASTM A563 and ASTM
F436 respectively.J. Mechanical splice couplers shall be ASTM A1034 and shall be capable of developing 125% of the specified
yield strength of the bar.2. Construction Requirements
A. All masonry construction, workmanship, and materials shall comply with TMS 602/ACI 530.1/ASCE 6, “Specifications for Masonry Structures”.
B. All masonry units shall be stored under cover at the job site. Do not use any frozen materials.C. Prior to placing masonry, check with all trades to insure proper placement of openings, block outs, sleeves,
curbs, conduits, bolts, inserts, embeds, dowels, etc.D. During construction, cover and protect the top of all constructed masonry at the end of each day.E. All masonry walls, lintels, and columns shall be built with running bond, typical unless noted otherwise.F. Mortar joints for all hollow units, both vertical head joints and horizontal bed joints, shall be bedded for a
distance at least equal to the thickness of the face shells. The webs each side of cells to be grouted shall be bedded as well. Mortar joints for all solid masonry units, both vertical head joints and horizontal bed joints, shall be fully bedded.
G. Do not use mortar for grout.H. Grout pours shall be limited to 4'-0” in height and shall be placed in accordance with low lift procedures,
typical, unless noted otherwise.I. Grout pours shall terminate flush with the top of the uppermost unit except at cells with vertical reinforcing
where the grout shall be 1-1/2” below the top of the unit to provide a construction key.J. Grout shall be consolidated by mechanical vibration during placement and reconsolidated after excess
moisture has been absorbed but before workability is lost. Puddling or rodding of grout is not allowed.K. Grout solid all cells which contain reinforcing, bolts, anchors, etc., and as otherwise specified. Grout solid
all cells below grade. Grout solid all lintels and columns. Do not grout walls solid unless specifically noted as such. Grout solid around all joist and beam bearing pockets after installation of beams and joists, typical, unless noted otherwise.
L. Vertical cells to be filled with grout shall have vertical alignment sufficient to maintain a clear, unobstructed, vertical cell measuring not less than 2” x 3”.
M. Masonry control joint spacing shall not exceed 26'-0”. Control joints in reinforced masonry shall not occur at the face of masonry lintel supports. See architectural drawings for locations of control joints.
N. Penetrations shall not be allowed through any masonry lintel, column, pilaster, or jamb without the EOR's prior written approval. Penetrations shall be re-routed as required at these locations. Penetrations through masonry walls shall be built into the wall as the wall is being constructed and shall be reviewed by the EOR prior to installation.
O. Masonry walls and columns shall be securely braced until floor and/or roof systems have been installed and are capable of stabilizing the masonry.
P. Where horizontal reinforcing bars join concrete walls, columns, or pilasters, reinforcing shall be continuous. Also, a key shall be provided between the masonry and the concrete. Fill the key with grout.
Q. Bolt holes in face or end shells shall have a diameter two inches larger than the bolt diameter and the hole shall be filled with grout.
R. Post-installed anchor bolts shall only be installed with prior written approval of the EOR. When used, they shall be installed in solid material. Grout solid at cavity locations. All bolt holes to be filled with epoxy shall be wire brushed and cleaned with compressed air per manufacturer's recommendations.
3. Detailing RequirementsA. Reinforcing steel shall be free of loose flakey rust, scale, grease, oil, dirt, or other deleterious materials
which might affect or impair bond.B. Minimum grout coverage for reinforcing bars shall be one bar diameter, but not less than ¾”. When
masonry is exposed to soil, minimum coverage shall be 1-1/2”. Minimum mortar coverage for joint reinforcing shall be 5/8” from exposed face.
C. Reinforcing steel shall be placed prior to grouting and shall be placed, positioned, and located according to the structural drawings. It shall be secured against displacement by wire positioners or other suitable devices at intervals not to exceed 200 bar diameters or ten feet, and at all bar splice locations.
D. Lap all masonry reinforcing are as follow:1. One bar/cell, typical: #3=12”, #4=13”, #5=20”, #6=39”, #7=53”, #8=82”, #9=106”.2. Two bars/cell, typical: #3=12”, #4=22”, #5=35”, #6=70”, #7=84”, #8=96” and #9=109”.
E. Vertical reinforcing shall be doweled into the foundation wall, footing, or structure below with the same size bar, spacing, and in same core as the vertical reinforcing in the wall above.
F. Horizontal reinforcing shall be continuous through masonry walls, columns, and pilasters.G. Horizontal reinforcing at masonry control joints shall be continuous through the joint, typical, unless noted
otherwise.H. Reinforcing bars shall not be field bent, except as shown in the contract drawings or permitted by the EOR.I. Walls:
1. Masonry walls shall be built as an integral unit at corners and intersections. Reinforcing shall be continuous and back to back end shells shall be removed at each course.
2. Vertical reinforcing shall be placed in the center of the wall, typical, unless each face is specified or unless noted otherwise.
3. Vertical reinforcing shall be provided at each corner and intersection.4. Horizontal corner bars shall be provided at all wall intersections and corners. Use same size and
spacing as horizontal reinforcing. Provide proper lap lengths.5. Horizontal reinforcing shall terminate with a standard hook at the edge of openings and at ends of walls.6. Horizontal reinforcing shall occur at the top and bottom course of all masonry walls except the bottom
course horizontal reinforcing may be omitted when the wall is doweled to a concrete foundation wall below.
J. Lintels1. Masonry lintels shall be built as an integral part with the support. No “toothing” or doweling only will be
permitted. Masonry units with one open end (“A” blocks) shall be used in all masonry lintels. Back-to-back end shells are not allowed. Grout all masonry lintels solid for full depth and width shown in the masonry lintel schedule.
2. Reinforcing shown in the masonry lintel schedule is in addition to standard wall reinforcing.3. Horizontal reinforcing bars in the top of the lintel shall be placed in the top 4 inches of the lintel and shall
extend a minimum of 72 bar diameters beyond the face of the opening or shall be hooked if required.4. Horizontal reinforcing bars in the bottom of the lintel shall be placed in the bottom four inches of the lintel
and shall extend a minimum of 24 inches beyond the face of the opening or shall be hooked if required.5. Vertical reinforcing bars shall hook around the bottom horizontal reinforcing bars. They shall also hook
around the top horizontal reinforcing bars or extend into the wall above the lintel a minimum of 48 bar diameters.
6. Do not splice horizontal top or bottom bars of lintels, typical unless noted otherwise.7. For openings not shown, use similar lintel as shown in that wall or type of wall for similar length openings.
Verify with the EOR.8. Use the following masonry lintel sizes for openings in non-bearing masonry walls.
Width of Opening Lintel Depth Horizontal ReinforcingUp to 4'-0” 16” (2) #5 bottomUp to 8'-0” 24” (2) #5 top and bottomUp to 10'-0” 32” (2) #5 top and bottomFor wider openings contact the EOR. See the masonry lintel schedule for additional information.
K. Columns/Jambs1. All masonry column ties shall terminate with a 135 degree hook plus a 6 bar diameter extension (4”
minimum). Horizontal wall reinforcing shall be placed inside the column vertical reinforcing.2. Grout jambs solid for full height of wall (floor to floor and/or roof) at sides of openings; one cell for each
4'-0” of span or portion thereof. Reinforce with (2) #5 vertical bars in each grouted cell with one bar placed at each face of wall, typical unless noted otherwise. See contract documents for other reinforcing requirements.
L. Reinforcing shall not be welded unless specifically noted otherwise. In such cases, use AWS D1.4 standards. Do not substitute bars for DBA's or HSA's.
M. Epoxy Coated reinforcing shall only be used when specifically noted. Increase lap lengths as required by the IBC and ACI.
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A DIMENSIONS AND ELEVATIONS, AS THEY RELATE TO THE BUILDING IN GENERAL, i.e. GRID TO GRID DIMENSIONS OR DECK BEARING ELEVATIONS, ARE SUPPLIED BY THE ARCHITECT. THEY ARE PROVIDED ON THE STRUCTURAL PLANS AND DETAILS FOR THE CONVENIENCE OF THE CONTRACTOR. VERIFY DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.
NOTE: THESE STRUCTURAL DRAWINGS ARE BASED ON ARCHITECTURAL DRAWINGS DATED
This
dra
win
g, a
s an
inst
rum
ent o
f pro
fess
iona
l ser
vice
, is
the
prop
erty
of D
UN
N A
SSO
CIA
TES
INC
, and
sha
ll no
t be
used
, in
who
le o
r par
t for
any
oth
er p
roje
ct w
ithou
t the
writ
ten
perm
issi
on o
f an
auth
oriz
ed re
pres
enta
tive
of D
UN
N A
SSO
CIA
TES
INC
. Una
utho
rized
use
will
be p
rose
cute
d to
the
fulle
st e
xten
t of t
he la
w. C
opyr
ight
© 2
018
by D
UN
N A
SSO
CIA
TES
INC
.
11/2
0/2
01
8 2
:20:1
2 P
M
GENERAL
STRUCTURAL
NOTES
Author
2100 W
ES
T 1
1400 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
4095
SA
LT
LA
KE
CO
UN
TY
18142
11/20/2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
S001
Checker
11/20/2018PERMIT SET
11/15/2018
GENERAL STRUCTURAL NOTES
# Date Revision
11/20/2018
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PREFABRICATED WOOD TRUSSES
1. The prefabricated metal plate wood trusses shall be designed per the locally adopted building code and signed and sealed by a Professional Engineer registered in the same state as the project location. They shall be designed to support the concentrated and distributed loads shown on the framing plans in addition to the following uniform loads:Member-------------------------Dead--------------------Live*---------------Snow** Top Chord---------------------10 psf--------------------0 psf---------------30 psfBottom Chord-----------------10 psf-------------------10 psf---------------0 psf* The bottom chord live load is not concurrent with top chord live load.**Loads caused by drifting, unbalanced or sliding snow should be accounted for and are not included in uniform loads given.
Designs shall include additional Dead Load of 9 psf at all overbuild framing locations. Design all wood trusses and bearing attachments for wind uplift, assuming a dead load of 8 psf to resist uplift. The structural, mechanical, and architectural plans may show additional loading information (examples: snow drifts, point loads, drag strut loads, hanging partition walls, mechanical equipment weights, etc.). Loads shown on these other sheets shall be incorporated in the design of the trusses. Provide additional trusses as required.
2. The location of vertical and lateral supports for all trusses shall be compatible with the overall design of the building. In general, roof and/or floor decks shall provide the lateral restraint for trusses. The exception to this rule occurs at drag trusses in line with and directly over parallel shear walls labeled “PFT OVER SW” on plan. At these locations, horizontal diaphragm forces shall be applied to the truss top chord, conveyed to the truss bottom chord and transferred to the shear wall below. Uplift reactions from wind and/or seismic forces shall be provided at each end of the shear wall.
3. All trusses perpendicular to and vertically supported by exterior walls shall be designed to brace the exterior wall for wind and/or seismic forces normal to the wall. The horizontal wind and/or seismic forces on the upper half of the wall shall be applied to the truss at the vertical bearing support.
4. The deflection of all prefabricated wood trusses shall be limited to L/240 for total load and L/360 for live load at the roof and L/360 for total load and L/480 for live load at the floors, unless noted otherwise.
5. Use a load duration factor of 1.0 for live loads and for snow loads above 5000' elevation.6. All truss-to-truss and truss uplift connections shall be designed and provided by the truss manufacturer. See
wood schedules for a selection of uplift connector options.7. Steel connectors are specified at truss bearing locations in the typical details of these documents. Where truss
reactions exceed the capacity of specified connectors, the truss designer shall specify an appropriate alternate connector in the shop drawings.
8. Design, handling, erection, and permanent bracing of metal plate connected wood trusses shall be in accordance with ANSI/TPI-1, National Design Standard for Metal Plated Connected Wood Truss Construction.
9. All steel gusset plates shall be galvanized and shall be approved by the "Research Committee for the International Conference of Building Officials." Submit a copy of the ICC Report for the gusset used. Values established by this committee must be indicated on the shop drawings.
10. All gussets shall be located on the joint as the stresses require.11. Gussets shall be pressed or rolled into member to obtain full penetration without crushing the outer surfaces of
wood.12. No wane, knots, skips, or other defects shall occur in the plated contact area or scarfed area of web members.
Plates shall be centered with one required each side of wood truss.13. The trusses shall be handled and stored in a manner to prevent moisture from being absorbed by the wood.14. Requirements for truss stability and erection shall comply with the Truss Plate Institute publications entitled
"Commentary and Recommendations for Bracing Wood Trusses" and "Commentary and Recommendations for Handling and Erecting Wood Trusses." The contractor shall have copies of these publications on site and shall be familiar with their contents.
15. Shop Drawings: All loads included in the design of the trusses shall be shown on the truss layout plan. Complete calculations and shop drawings indicating all member forces, stresses, duration factors, lumber grades, truss to truss connections, steel gusset plate sizes and locations shall be submitted and reviewed by the engineer before fabrication. Each gusset shall be dimensioned on the shop drawings as to its exact location at the joint. Dimensions, roof slopes, overhangs, and ceiling elevations shall be shown in the shop drawings per the architectural drawings.
WOOD
1. Materials (Dry service conditions assumed for each type)A. Dimension Lumber and Timbers (Sawn Lumber)
1. All dimensioned lumber shall comply with USDOC PS20.2. Visually graded dimension lumber shall be Douglas Fir-Larch #2 or better. 3. Visually graded timbers (5" x 5" and larger) shall be Douglas Fir-Larch #1 or better.4. Machine stress rated (MSR) lumber shall be 1600f-1.6E or better.5. Approved end jointed lumber may be used interchangeably with solid sawn members of the same
species and grade.B. Wood Structural Panel Sheathing
1. Wood structural panels shall conform to the requirements for its type in USDOC PS1 or USDOC PS2. The panels must be identified by the trademarks of the approving testing and inspection agency.
2. Wood sheathing shall be APA rated sheathing Exposure 1 unless noted otherwise. See plans and schedules for thickness and span rating.
C. Nails1. All Nails shall conform to the requirements specified in ASTM F1667, "Standard Specification of Driven
Fasteners: Nails, Spikes and Staples."2. All nails shall be common nails with the following properties:
Nail------------------Shank Diameter--------------------------------Min. Penetration into Support6d--------------------0.113"--------------------------------------------1.25"8d--------------------0.131"--------------------------------------------1.50"10d-------------------0.148"--------------------------------------------1.63"12d-------------------0.148"--------------------------------------------1.63"16d-------------------0.162"--------------------------------------------1.75"Nails with properties less then those listed above shall not be used without prior written approval from Dunn Associates, Inc.
3. Nails with "T", brad, finish or casing heads are not permitted. Nails with Round (full), Offset, Oval, Clipped or Notched heads are acceptable.
4. Deformed shank nails shall have either a helical (screw) or an annular (ring) shank.D. Bolts
1. Anchor Bolts: ASTM F1554 Grade 36 (or A307 Grade A/C or A36)2. Connection Bolts: ASTM A307 Grade A/C or ANSI Standard B18.2.1.3. Bolt holes shall be a minimum of 1/32" to a maximum of 1/16" larger than the bolt diameter. Holes shall
be accurately aligned in main members and side plates or side members. Bolts shall not be forcibly driven.
4. At all bolted connections, provide a standard cut or larger washer or metal plate between the wood and the bolt head and between the wood and the nut.
E. Connection Hardware1. All connection hardware shown shall be supplied by Simpson Strong-Tie Incorporated. 2. Install all hardware per the manufacturer's guidelines.3. Connection hardware of equal design properties, including USP Structural Connectors or other
manufacturers may be substituted with written approval from Dunn Associates, Inc.2. All fasteners in contact with preservative-treated or fire-treated wood shall be hot-dipped zinc-coated
galvanized or stainless steel.3. All wood in contact with concrete, masonry or soil shall be preservative-treated or redwood.4. General framing and carpentary should be connected as per the "THE MINIMUM NAILING SCHEDULE"
unless noted otherwise.5. Provide solid shaped blocking at least 2" (nominal) thick and full depth of joist at ends and at each support of
joist. Provide approved bridging at an 8'-0" on center maximum between joist end supports. 6. Solid blocking at eaves may be omitted where required for ventilation (1 block in 5 blocks), UNO.
SPECIAL INSPECTION, TESTING AND STRUCTURAL OBSERVATION REQUIREMENTS
1. Special Inspections and TestingA. Special inspections and testing as required per the construction documents and per IBC Chapter 17 shall be
provided for this project unless waived by the Building Official.B. An independent agency/agencies employed by the Owner, shall perform the special inspection and testing
services required. C. The special inspection and testing requirements of this section of the General Structural Notes and the
special inspection tables serve as the Engineer of Record's statement of special inspections and structural observations required by IBC Chapter 17.
2. Contractor ResponsibilitiesA. Each Contractor responsible for the construction of a main wind or seismic force-resisting system, a
designated seismic system, or a wind or seismic force-resisting component shall submit a written statement of responsibility to the Building Official and Owner prior to commencing with the work involved. It shall contain acknowledgement of awareness of the special inspection and testing requirements.
B. The Contractor shall coordinate and cooperate with all the required inspections, testing, and/or structural observations required for the project. The Contractor shall not proceed with subsequent work until required inspections, testing, and/or structural observations have been provided.
C. The Contractor shall correct all work found to be deficient, and re-test at no additional cost to the Owner.D. The Contractor shall notify the Engineer of Record at least (7) days prior to any required structural
observations.E. Submit all required documentation to the Special Inspector for review.
3. Special Inspector ResponsibilitiesA. Each Special Inspector shall be a qualified person who shall demonstrate competence and relevant
experience or training, to the satisfaction of the Building Official, for the inspection of the particular type of construction or operation requiring special inspection.
B. Special Inspectors shall keep records of their inspections.C. Inspection reports shall indicate whether the work inspected was or was not completed in accordance with
the construction documents and the referenced building codes.D. Non-conforming work and/or discrepancies shall be brought to the Contractor's immediate attention for
correction.E. The Special Inspector shall notify the Architect/Engineer of any non-conforming work or discrepancies that
the Contractor cannot readily correct.F. Any uncorrected non-conforming work or discrepancies shall be brought to the attention of the
Architect/Engineer and the Building Official prior to completion of that phase of the work.G. Submit the following to the Building Official:
1. Special Inspections and Testing Reports.2. Certificates of Compliance for:
a. Fabrication of structural elements from approved fabricators.b. The seismic qualifications of nonstructural components, supports, and attachments.c. Designated Seismic Systems.
3. Reports of:a. Pre-construction tests for shotcrete.b. Material properties verifying compliance with the requirements of AWS D1.4 for weldability for
reinforcing bars other than ASTM A706.c. Mill tests for ASTM A615 reinforcing bars used to resist earthquake induced forces in special moment
frames, special structural walls or coupling beams in structures assigned to Seismic Design Category B, C, D, E, or F.
4. Special InspectionsA. Fabricated Items (1704.2.5): Where fabrication of structural, load bearing or lateral load-resisting members
or assemblies is being conducted on the premises of a fabricator's shop, special inspections of the fabricated items shall be performed during fabrication. Special inspections during fabrication are not required where the work is done on the premises of a fabricator registered and approved by the building official to perform such work without special inspection. At the completion of fabrication, the approved fabricators shall submit a certificate of compliance to the Owner for submittal to the Building Official.
B. Concrete (1705.3): Special inspections and tests of concrete construction shall be performed in accordance with Table 1705.3 in the construction documents.1. In the absence of sufficient data or documentation providing evidence of conformance to quality
standards for concrete materials, the building official shall require testing in accordance with the appropriate standards and criteria for the materials.
C. Masonry (1705.4): Special inspections and tests of masonry construction shall be performed in accordance with the Quality Assurance program requirements of ACI 530 and 530.1.1. Engineered masonry and vertical masonry foundation elements in Risk Categories I, II and III shall be
special inspected per Table 3.1.2- Masonry Level B Quality Assurance in the construction documents.D. Wood (1705.5): Special inspections of prefabricated wood structural elements and assemblies shall be
performed in accordance with the Fabricated Items section 4.A above. E. Soils (1705.6): Special inspections and tests of existing site soil conditions, fill materials, placement, and
load-bearing requirements shall be performed in accordance with the approved soils report and Table 1705.6 in the construction documents. The Special Inspector shall verify that proper materials and procedures are used. The approved geotechnical report and the construction documents shall be used to determine compliance
F. Post-Installed Anchors: Special inspections and tests shall be performed during installation of post-installed anchors according to the requirements of the ICC Evaluation Report and table 1705.3 in the construction documents. 1. Testing shall be done according to the more stringent requirements of the ICC Evaluation Report.
G. See architectural drawings for additional required inspections pertaining to sprayed fire-resistant materials (1705.14), mastic and intumescent fire-resistant coatings (1705.15), EIFS (1705.16), fire resistant penetrations and joints (1705.17), or smoke control systems (1705.18).
5. Special Inspections for Seismic Resistance (1705.12): Special inspections for seismic resistance are required for this project per IBC section 1705.12. Provide as follows:A. Structural Wood (1705.12.2): For the seismic force-resisting systems of structures assigned to Seismic
Design Category B, C, D, E, or F:1. Continuous special inspection shall be required during field gluing operations of elements of the seismic
force-resisting system.2. Periodic Special Inspection shall be required for nailing, bolting, anchoring and other fastening of
elements of the seismic force-resisting system, including wood shear walls, wood diaphragms, drag struts, braces, shear panels, and hold downs.Exception: Special inspections are not required for wood shear walls, shear panels, and diaphragms, including nailing, bolting, anchoring, and other fastening to other elements of the seismic force-resisting system, where the fastener spacing of the sheathing is more than 4” on center.
B. Designated Seismic Systems (1705.12.4): For structures assigned to Seismic Design Category C, D, E, or F, the Special Inspector shall examine designated seismic systems requiring seismic qualifications in accordance with ASCE7 Section 13.2.2, and verify that label, anchorage and mounting conforms to the certificate of compliance.
C. Architectural Components (1705.12.5): Periodic special inspection is required for the erection and fastening of exterior cladding, interior and exterior nonbearing walls and interior and exterior veneer in structures assigned to Seismic Design Category D, E, or F.1. Access Floors. Periodic special inspection is required for the anchorage of access floors in structures
assigned to Seismic Design Category D, E, or F.D. Plumbing, Mechanical, and Electrical Components (1705.12.6): Periodic special inspection of plumbing,
mechanical, and electrical components shall be required for the following:1. Anchorage of electrical equipment for emergency and standby power systems in structures assigned to
Seismic Design Category C, D, E, or F.2. Anchorage of other electrical equipment is structures assigned to Seismic Design Category E or F.3. Installation and anchorage of piping systems designed to carry hazardous materials and their associated
mechanical units in structures assigned to Seismic Design Category C, D, E, or F.4. Installation and anchorage of ductwork designed to carry hazardous materials in structures assigned to
Seismic Design Category C, D, E, or F.5. Installation and anchorage of vibration isolated systems in structures assigned to Seismic Design
Category C, D, E, or F where the approved construction documents require a nominal clearance of 1/4”or less between the equipment support frame and restraint.
6. Testing for Seismic Resistance (1705.13): Testing for seismic resistance is/is not required for this project per IBC section 1705.13. Provide as follows:A. Non-Structural Components (1705.13.2): For structures assigned to Seismic Design Category B, C, D, E, or
F where the requirements of ASCE 7 Section 13.2.1 for nonstructural components, supports or attachments are met by seismic qualification as specified in Item #2 therein, the registered design professional of the applicable discipline shall specify on the approved construction documents the requirements for seismic qualification by analysis, testing, or experience data. Certificates of Compliance for the seismic qualification shall be submitted to the Building Official.
B. Designated Seismic Systems (1705.13.3): For structures assigned to Seismic Design Category C, D, E, or F and with designated seismic systems that are subject to the requirements of ASCE 7 Section 13.2.2 for certification, the registered design professional of the applicable discipline shall specify on the approved contract documents the requirements to be met by analysis, testing, or experience data as specified therein. Certificates of Compliance documenting that the requirements are met shall be submitted to the Building Official.
7. Special Inspections for Wind Resistance (1705.11): Special inspections for wind resistance are/are not required for this project per IBC Section 1705.11.
8. Structural Observations/Site Observations (1704.6): Structural observations are not required for this project per IBC section 1704.6. 8.1 Site Observations are part of the Dunn Associates, Inc. contract with the Architect/Owner. The stages of
construction listed below will serve as suggested stages of construction to be observed. The Contractor shall notify (in writing) the Engineer of Record at least 7 days prior to the following stages of construction so that the Engineer may have the opportunity to review the work.1. Initial placing of any concrete, including but not limited to: footings, shear walls, moment frame beams,
post-tensioned slabs, slabs on grade or concrete over steel deck2. Initial grout pours for masonry walls3. Completion of structural roof deck
8.2 Structural observation/Site observation reports will be provided to the Architect. Distribution to the Contractor, Owner, and/or Building Official will be through the Architect.
9. Seismic/Wind Main Force Resisting Systems That Require Special InspectionsA. Masonry Shear WallsB. Wood Diaphragms
DEFERRED SUBMITTALS
1. Deferred submittals are items that are not part of our scope which require architectural and/or engineering review. Deferred submittals include plans, details, calculations and/or other relevant design information stamped by a Professional Engineer licensed in the state in which construction will occur.
2. Deferred submittals shall first be submitted to the project architect and/or engineer for review and coordination. Upon completion of the architect/engineer review, the architect/engineer will submit the deferred submittals to the Building Official for review and approval. The submittal to the Building Official shall include a letter stating that the architect/engineer review has been performed and that the plans and calculations for the deferred submittal items are found to be in general conformance with the design drawings with no exceptions.
3. Construction related to deferred submittals shall not commence until the Building Official has approved the submittal. Approved deferred submittals shall be available at the jobsite throughout construction.
4. Items requiring deferred submittals are listed below. These items shall be designed and fabricated by the manufacturer according to specifications given in the construction documents.A. Prefabricated Wood Trusses (by roof truss manufacturer)
ABBREVIATIONS
AB Anchor BoltABV AboveALT AlternateARCH ArchitectADD'L Additional
BFB Braced Frame BeamBFC Braced Frame ColumnBLDG BuildingBLKG BlockingBLW BelowBM BeamBN Boundary NailBOTT BottomBRB Buckling Restrained BraceBRDG BridgingBRG BearingBTWN BetweenBYND Beyond
CANT CantileveredCGS Center of Gravity of StrandCJ Control Joint CJP Complete Joint PenetrationCL Center LineCMU Concrete Masonry UnitCOL ColumnCONC ConcreteCONN ConnectionCONT ContinuousCOORD CoordinateCS Coil StrapCTR Center
DB Deck BearingDBA Deformed Bar AnchorDBL DoubleDCW Demand Critical WeldDET DetailDIA DiameterDIM DimensionDWG Drawing
(E) ExistingEA EachEF Each FaceEL ElevationELEC ElectricalEN Edge NailENGR EngineerEQ EqualEQUIP EquipmentEQ SP Equally SpacedEW Each WayEJ Expansion JointEXT Exterior
FLR FloorFND FoundationFTG Footing
ga GageGALV GalvanizedGLB Glued Laminated BeamGSN General Structural NotesGT Girder Truss
HD Hold-downHORIZ HorizontalHSA Headed Stud AnchorHSS Hollow Structural Section
IBC International Building CodeICC International Code CouncilINT Interior
JST Joist
K Kip(s) = 1000 PoundsKLF Kips Per Lineal FootKSF Kips Per Square Foot
LB Pounds (#)LOC LocationLSL Laminated Strand LumberLVL Laminated Veneer Lumber
MAS MasonryMAX MaximumMECH MechanicalMEZZ MezzanineMFB Moment Frame BeamMFC Moment Frame ColumnMFR ManufacturerMIN MinimumMISC MiscellaneousMTL Metal
NTS Not To Scale
oc On CenterOPNG OpeningOPP OppositeOSB Orientated Strand Board
PAF Power Actuated FastenerPCF Pounds per Cubic FootPEN Penetrate or PenetrationPERP PerpendicularPFT Pre-Fabricated TrussPJP Partial Joint PenetrationPL Plate PLF Pounds per Lineal FootPREFAB PrefabricatedPSF Pounds per Square FootPSI Pounds per Square InchPT Post TensionPT/DF Pressure Treated Douglas Fir
(or appropriate species for region)
REINF ReinforceREQD RequiredRTU Roof Top Unit
SCHED ScheduleSFRS Seismic Force Resisting SystemSHTG SheathingSIM SimilarSOG Slab on GradeSTD StandardSTIFF StiffenerSTL SteelSTRUCT StructuralSW Shear Wall
T&B Top and BottomT&G Tongue and GrooveTEMP TemperatureTHRU ThroughT/ Top ofTYP Typical
UNO Unless Noted Otherwise
VERT Vertical
W/ WithWWR Welded Wire ReinforcementWP Working Point
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
Architectural NEXUS, Inc.930 R StreetSacramento, CaliforniaT 916.443.5911 http://www.archnexus.com
DIMENSIONS AND ELEVATIONS, AS THEY RELATE TO THE BUILDING IN GENERAL, i.e. GRID TO GRID DIMENSIONS OR DECK BEARING ELEVATIONS, ARE SUPPLIED BY THE ARCHITECT. THEY ARE PROVIDED ON THE STRUCTURAL PLANS AND DETAILS FOR THE CONVENIENCE OF THE CONTRACTOR. VERIFY DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.
NOTE: THESE STRUCTURAL DRAWINGS ARE BASED ON ARCHITECTURAL DRAWINGS DATED
This
dra
win
g, a
s an
inst
rum
ent o
f pro
fess
iona
l ser
vice
, is
the
prop
erty
of D
UN
N A
SSO
CIA
TES
INC
, and
sha
ll no
t be
used
, in
who
le o
r par
t for
any
oth
er p
roje
ct w
ithou
t the
writ
ten
perm
issi
on o
f an
auth
oriz
ed re
pres
enta
tive
of D
UN
N A
SSO
CIA
TES
INC
. Una
utho
rized
use
will
be p
rose
cute
d to
the
fulle
st e
xten
t of t
he la
w. C
opyr
ight
© 2
018
by D
UN
N A
SSO
CIA
TES
INC
.
11/2
0/2
01
8 2
:20:1
2 P
M
GENERAL
STRUCTURAL
NOTES
Author
2100 W
ES
T 1
1400 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
4095
SA
LT
LA
KE
CO
UN
TY
18142
11/20/2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
S002
Checker
11/20/2018PERMIT SET
11/15/2018
# Date Revision
GENERAL STRUCTURAL NOTES
11/20/2018
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
TYPE
CONTINUOUSSPECIAL
INSPECTION
PERIODICSPECIAL
INSPECTION
TABLE 1705.6: REQUIRED SPECIAL INSPECTIONS AND TESTS OF SOILS
TYPE CONTINUOUS SPECIAL INSPECTION PERIODIC SPECIAL INSPECTION
TABLE 1705.3: REQUIRED SPECIAL INSPECTIONS AND TESTS OF CONCRETE CONSTRUCTION
REFERENCED STANDARD IBC REFERENCEa
TABLE 3.1.2: MASONRY LEVEL B QUALITY ASSURANCE(RISK CATEGORY I, II, AND III ENGINEERED MASONRY)
INSPECTION TASK FREQUENCY
PERIODIC
REFERENCE FOR CRITERIA
MINIMUM TESTS
MINIMUM SPECIAL INSPECTION
CONTINUOUS TMS 402 /ACI 530 /ASCE 5
TMS 602 /ACI 530.1 /
ASCE 6
- X -
- X -
- X -
XX -
-
- X
X -
X -
- X
X
X
-
- X
X
- X
-
X -
- X
- X1. Verify materials below shallow foundations are adequate to achieve the design bearing capacity.
2. Verify excavations are extended to proper depth and have reached propermaterial.
3. Perform classification and testing of compacted fill materials.
4. Verify use of proper materials, densities and lift thickness during placementand compaction of compacted fill.
5. Prior to placement of compacted fill, inspect subgrade and verify that site has been prepared properly.
1. Inspect reinforcement , including prestressing tendons, and verify placement
2. Reinforcing bar weldinga. Verify weldability of reinforcing bars other than
ASTM A 706;b. Inspect single-pass fillet welds, maximum
5/16"; andc. inspect all other welds
3. Inspect anchors cast in concrete.
5. Verify use of required design mix.
6. Prior to concrete placement, fabricate specimens for strength tests, perform slump and air content tests, and determine the temperature of the concrete.
7. Inspect concrete and shotcrete placement for proper application techniques.
8. Verify maintenance of specified curing temperature and techniques.
9. Inspect prestressed concrete for:a. Application of prestressing forces; andb. Grouting of bonded prestressing tendons.
10.Inspect erection of precast concrete members.
11.Verify in-situ concrete strength, prior to stressing of tendonsin post-tensioned concrete and prior to removal of shores and formsfrom beams and structural slabs.
12.Inspect formwork for shape, location and dimensions of the concretemember being formed.
ACI 318: 26.10.1(b)
ACI 318: 26.10.2
ACI 318: Ch. 26.8
ACI 318: 26.9.2.1ACI 318: 26.9.2.3
ACI 318: 26.4.7-26.4.9
ACI 318: 26.4.5
ASTM C 172ASTM C 31
ACI 318: 26.4.5, 26.12
ACI 318: Ch 19, 26.4.3, 26.4.4
AWS D1.4ACI 318: 26.5.4
ACI 318 Ch. 20, 25.2, 25.3, 26.5.1-26.5.3
1908.4
1904.1, 1904.2 1908.2, 1908.3
1908.10
1908.6, 1908.7, 1908.8
1908.9
ACI 318; 17.8.2
X
X
4. Inspect anchors post-installed in hardened concrete members.a. Adhesive anchors installed in horizontally or upwardly inclined orientations to resist sustained tension loadsb. Mechanical anchors and adhesive anchors not defined in 4.a.
ACI 318: 17.8.2.4
For SI: 1 inch = 25.4 mm.a. Where application, see also Section 1705.12. Special inspection for seismic resistance.b. Specific requirements for special inspection shall be included in the research report for the anchor issued by an approved source in accordance
with 17.8.2 in ACI 318 or other qualification procedures. Where specific requirements are not provided, special inspection requirements shallbe specified by the registered design professional and shall be approved by the building official prior to the commencement of the work.
Verification of Slump flow and Visual Stability Index (VSI) as delivered to the project site inaccordance with Specification Article 1.5 B.1.b.3 for self consolidating grout.
2. As masonry construction begins, verify that the following are in compliance:
b. Construction of mortar joints
a. Proportions of site-prepared mortar
1. Verify compliance with the approved submittals
c. Grade and size of prestressing tendons and anchorages
d. Location of reinforcement, connectors, and prestressing tendons and anchorages
e. Prestressing technique
f. Properties of thin-bed mortar for AAC masonry
3. Prior to grouting, verify that the following are in compliance:
a. Grout space
b. Grade, type, and size of reinforcement and anchor bolts, and prestressing tendons and anchorages
c. Placement of reinforcement, connectors, and prestressing tendons and anchorages
d. Proportions of site-prepared grout and prestressing grout for bonded tendons
e. Construction of mortar joints
4. Verify during construction:
a. Size and location of structural elements
b. Type, size, and location of anchors, including other details of anchorage of masonry to structural members, frames, or other construction
c. Welding of reinforcement
d. Preparation, construction, and protection of masonry during coldweather (temperature below 40°F (4.4°C)) or hot weather(temperature above 90°F (32.2°C))
e. Application and measurement of prestressing force
f. Placement of grout and prestressing grout for bonded tendons is in compliance
g. Placement of AAC masonry units and construction of thin-bed mortar joints
5. Observe preparation of grout specimens, mortar specimens, and/or prisms
(a) Frequency refers to the frequency of inspection, which may be continuous during the task listed or periodically during the listed task, as defined in the table.(b) Required for the first 5000 square feet (465 square meters) of AAC masonry.(c) Required after the first 5000 square feet (465 square meters) of AAC masonry.
X
X
X
X
X
X X
X
X
X
X
X
X
X
X
X
X
X
X X
X
X
(b) (c)
(b) (c)
Art. 3.3 F
Art. 1.8 C, 1.8 D
Art. 3.5, 3.6 C
Art. 3.3 B.9, 3.3F.1.b
Art. 3.6 B
Sec. 8.1.6.7.2, 9.3.3.4(c), 11.3.3.4(b)
Sec. 1.2.1(e), 6.1.4.3, 6.2.1
Art. 1.5
Art. 2.1, 2.6 A
Art. 3.3 B
Art. 2.4 B, 2.4 H
Art. 3.4, 3.6 A
Art. 3.6 B
Art. 2.1 C
Art. 3.2 D, 3.2 F
Art. 2.4, 3.4
Art. 3.2 E, 3.4, 3.6 A
Art. 2.6 B, 2.4 G.1.b
Art. 3.3 B
(a)
Sec. 6.1
Sec. 6.1, 6.2.1, 6.2.6, 6.2.7
Art. 1.4 B.2.a.3, 1.4 B.2.b.3, 1.4 B.2.c.3, 1.4 B.3, 1.4 B.4
Verification of f ' and f ' in accordance with Specification Article 1.4 B prior to construction, except wherespecifically exempted by this Code
-
-
m ACC
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
X
ACI 318: 17.8.2
-
X
-
-
-
-
b
-
-
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
Architectural NEXUS, Inc.930 R StreetSacramento, CaliforniaT 916.443.5911 http://www.archnexus.com
DIMENSIONS AND ELEVATIONS, AS THEY RELATE TO THE BUILDING IN GENERAL, i.e. GRID TO GRID DIMENSIONS OR DECK BEARING ELEVATIONS, ARE SUPPLIED BY THE ARCHITECT. THEY ARE PROVIDED ON THE STRUCTURAL PLANS AND DETAILS FOR THE CONVENIENCE OF THE CONTRACTOR. VERIFY DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.
NOTE: THESE STRUCTURAL DRAWINGS ARE BASED ON ARCHITECTURAL DRAWINGS DATED
This
dra
win
g, a
s an
inst
rum
ent o
f pro
fess
iona
l ser
vice
, is
the
prop
erty
of D
UN
N A
SSO
CIA
TES
INC
, and
sha
ll no
t be
used
, in
who
le o
r par
t for
any
oth
er p
roje
ct w
ithou
t the
writ
ten
perm
issi
on o
f an
auth
oriz
ed re
pres
enta
tive
of D
UN
N A
SSO
CIA
TES
INC
. Una
utho
rized
use
will
be p
rose
cute
d to
the
fulle
st e
xten
t of t
he la
w. C
opyr
ight
© 2
018
by D
UN
N A
SSO
CIA
TES
INC
.
11/2
0/2
01
8 2
:20:1
2 P
M
GENERAL
STRUCTURAL
NOTES
Author
2100 W
ES
T 1
1400 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
4095
SA
LT
LA
KE
CO
UN
TY
18142
11/20/2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
S003
Checker
11/20/2018PERMIT SET
11/15/2018
# Date Revision
GENERAL STRUCTURAL NOTES
11/20/2018
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
ML-
1M
L-1
ML-
1M
L-1
ML-
1M
L-1
ML-
1M
L-1
ML-
1M
L-1
ML-2ML-2ML-2ML-2ML-2ML-2ML-2ML-2ML-2ML-2
ML-1ML-1ML-1ML-1ML-1ML-1ML-1ML-1ML-1ML-1 ML-1ML-1ML-1ML-1ML-1ML-1ML-1ML-1ML-1ML-1 ML-1ML-1ML-1ML-1ML-1ML-1ML-1ML-1ML-1ML-1
ML-
1M
L-1
ML-
1M
L-1
ML-
1M
L-1
ML-
1M
L-1
ML-
1M
L-1
ML-
1M
L-1
ML-
1M
L-1
ML-
1M
L-1
ML-
1M
L-1
ML-
1M
L-1
ML-1ML-1ML-1ML-1ML-1ML-1ML-1ML-1ML-1ML-1
88
1010
K
K
L
L
(E) 15'-6" SQ FTG (E) 15'-6" SQ FTG
(E) 2'-0" CONT FTG
(E) 2'-0" CONT FTG
MC-1
MC-1MC-1
MC-1MC-1
MC-1
MC-1
MC-1
MC-1
MC-1MC-1
MC-1MC-1
TYP AT EXT, UNO
CW-08
CW-14
TYP AT INT, UNO
MW-08
CW-08
MW-06
CW-06
FC2.0 -2'-0"
4S502 TYP
5S502 TYP
6S502
7S502
TYP AT EXT WALL, UNO
TYP AT MAS COL, UNO
TYP AT DOOR OPNG, UNO
MC-1
TYP, UNO
8S502 TYP
MC-2MC-2
88
1010
K
K
L
L
2S701 TYP
2S701 TYP
3S701 TYP
3S701 TYP
PFT
AT 2
4"oc
2x10 OUTLOOKERS AT 24"oc
2x10 OUTLOOKERS AT 24"oc
DBL
DBL
S2013
7S701
FOOTING AND FOUNDATION PLAN NOTES:
MARKS AND SYMBOLS LEGEND
FTG DESIGNATIONTOF EL
FTG EL
1. COORDINATE LOCATION OF DEPRESSED SLABS, SLOPED SLABS, AND FLOOR DRAINS WITH ARCHITECTURAL AND MECHANICAL DRAWINGS.
2. SEE ARCHITECTURAL DRAWINGS AND CIVIL DRAWINGS FOR EXTERIOR CONCRETE WORK AT DOORS, SIDEWALKS, ETC.
3. CENTER ALL SPOT FOOTINGS UNDER COLUMNS AS SHOWN ON PLAN, TYPICAL UNLESS NOTED OTHERWISE.
4. SEE ARCHITECTURAL DRAWINGS FOR DIMENSIONS TO ALL STEEL COLUMNS.
5. SEE SCHEDULES ON (S300) SHEETS FOR:- FOOTINGS- CONCRETE WALLS- MASONRY WALLS- REINFORCING SPLICE LENGTHS
6. SEE TYPICAL FOOTING AND FOUNDATION DETAILS ON(S500) SHEETS FOR:- SLAB CONSTRUCTION AND CONTROL JOINTS- FOOTING STEPS- CORNER BARS- PIPES PERPENDICULAR AND PARALLEL TO FOOTINGS- DEPRESSED SLABS- REINFORCING AT MISCELLANEOUS MASONRY OPENINGS- REINFORCING AT SLAB DISCONTINUITIES- FROST COVER AND STRUCTURAL FILL- SOLE PLATE ANCHOR BOLTS- FLOOR OFFSETS- MASONRY CONTROL JOINTS- TERMINATION OF HORIZONTAL WALL REINFORCING AT
ENDS OF MASONRY WALLS7. SEE MASONRY LINTEL SCHEDULE (S301) FOR JAMB COLUMNS
AT SIDES OF OPENINGS.
DEPRESSED FND WALL,POUR SLAB OVER
CONC WALL, SEE SCHEDCW-X
CONC WALL BLW AND MAS WALL ABV, SEE SCHED
MW-X
CW-X
SECTION MARKSHEET NUMBER
MAS WALL, SEE SCHEDMW-X
ROOF FRAMING PLAN NOTES: MARKS AND SYMBOLS LEGEND
BRG WALL BLW
SECTION MARKSHEET NUMBER
MAS WALL
1. TYPICAL ROOF FRAMING IS WOOD TRUSSES AT 24"oc (MAX) UNO. SEE GENERAL STRUCTURAL NOTES FOR ADDITIONAL INFORMATION.
2. TRUSSES SHALL BE PER THE PRE-FABRICATED WOOD TRUSSNOTES SECTION OF THE GENERAL STRUCTURAL NOTES.
3. WEIGHTS AND LOCATIONS OF MECHANICAL EQUIPMENTSHALL BE SUBMITTED TO ARCHITECT IN WRITING FOR REVIEW PRIOR TO FABRICATION OF OR PLACEMENT OFTRUSSES OR OTHER FRAMING MEMBERS.
4. SEE ARCHITECTURAL DRAWINGS FOR ROOF SLOPES, DRAINS, PARAPETS, DECK BEARING ELEVATIONS, CEILINGELEVATIONS, AND SOFFIT ELEVATIONS.
5. SEE GENERAL STRUCTURAL NOTES FOR ADDITIONAL INFORMATION.
6. SEE SCHEDULES ON (S300) SHEETS FOR:- MINIMUM NAILING- ROOF SHEATHING- MASONRY WALLS AND LINTELS. LINTEL DEPTH BASED ON
ROUGH OPENINGSEE TYPICAL FRAMING DETAILS ON (S700) SHEETS FOR:- HOLES AND NOTCHES- SHEATHING JOINTS- FRAMING AT ROOF OPENINGS
PREFAB TRUSSES, SEE GSNPFT
ROOF OR FLOOR SHEATHING ORIENTATION, SEE SCHED
ML-x MAS LINTEL, SEE SCHED
2x10
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A DIMENSIONS AND ELEVATIONS, AS THEY RELATE TO THE BUILDING IN GENERAL, i.e. GRID TO GRID DIMENSIONS OR DECK BEARING ELEVATIONS, ARE SUPPLIED BY THE ARCHITECT. THEY ARE PROVIDED ON THE STRUCTURAL PLANS AND DETAILS FOR THE CONVENIENCE OF THE CONTRACTOR. VERIFY DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.
NOTE: THESE STRUCTURAL DRAWINGS ARE BASED ON ARCHITECTURAL DRAWINGS DATED
This
dra
win
g, a
s an
inst
rum
ent o
f pro
fess
iona
l ser
vice
, is
the
prop
erty
of D
UN
N A
SSO
CIA
TES
INC
, and
sha
ll no
t be
used
, in
who
le o
r par
t for
any
oth
er p
roje
ct w
ithou
t the
writ
ten
perm
issi
on o
f an
auth
oriz
ed re
pres
enta
tive
of D
UN
N A
SSO
CIA
TES
INC
. Una
utho
rized
use
will
be p
rose
cute
d to
the
fulle
st e
xten
t of t
he la
w. C
opyr
ight
© 2
018
by D
UN
N A
SSO
CIA
TES
INC
.
11/2
0/2
01
8 2
:20:1
2 P
M
FTG AND
ROOF
FRAMING
PLANS
Author
2100 W
ES
T 1
1400 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
4095
SA
LT
LA
KE
CO
UN
TY
18142
11/20/2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
S201
Checker
11/20/2018PERMIT SET
11/15/2018
NORTH
S201 SCALE: 1/8" = 1'-0"
1 FOOTING AND FOUNDATION PLAN
NORTH
S201 SCALE: 1/8" = 1'-0"
2 ROOF FRAMING PLAN
# Date Revision
NORTH
S201 SCALE: 1/8" = 1'-0"
3 MECHANICAL SUPPORT FRAMING
6" UNREINFORCED CONCRETE
11/20/2018
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
ML-1
MASONRY LINTEL NOTES:
1. LINTEL WIDTH AND MATERIAL TYPES SHALL BE THE SAME AS THE WALL IN WHICH THE LINTEL IS CONSTRUCTED.
2. GROUT MASONRY LINTELS MONOLITHICALLY WITH THE SUPPORT WALL OR COLUMN AT EA END.
3. MASONRY LINTELS ML-1 THRU ML-4 SHALL BE USED OVER OPENINGS IN MASONRY WALLS WHEN A SPECIFIC MASONRY LINTEL IS NOT OTHERWISE SPECIFIED. WHEN A LINTEL IS SPECIFIED ON THE PLANS, THE MAXIMUM SPAN AS NOTED IN THIS SCHEDULE SHALL NOT APPLY. CONSULT THE STRUCTURAL ENGINEER FOR LINTELS NOT SPECIFIED ON THE PLANS WHICH HAVE A SPAN GREATER THAN 10'-0".
4. MASONRY LINTELS ML-1 THRU ML-4 SHALL NOT BE LOCATED DIRECTLY BELOW FLOOR OR ROOF BEAMS OR GIRDERS UNLESS NOTED OTHERWISE ON THE PLANS. JOISTS SHALL NOT BEAR ON ANY LINTEL LESS THAN 16" DEEP. CONSULT THE STRUCTURAL ENGINEER FOR LINTELS NOT SHOWN ON THE PLANS WHICH ARE LOCATED DIRECTLY BELOW FLOOR OR ROOF BEAMS OR GIRDERS.
5. EXTEND ALL HORIZONTAL REINFORCING BEYOND THE EDGE OF ALL OPENINGS. IF HORIZONTAL REINFORCING CANNOT EXTEND LAP SPLICE LENGTH BEYOND EDGE OF OPENING, PROVIDE 90° STANDARD HOOK.
6. SPLICE TOP BARS AT MID-SPAN OF LINTEL ONLY AND BOTTOM BARS OVER SUPPORTS ONLY.
7. HORIZONTAL WALL REINFORCING SHALL CONTINUE THRU MASONRY LINTELS, WHERE BOTH HORIZONTAL WALL REINFORCING AND LINTEL REINFORCING OCCUR IN THE SAME COURSE, USE THE LARGER REINFORCING.
8. DOWEL VERTICAL REINFORCING OF WALL ABOVE LINTEL INTO THE FULL DEPTH OF LINTEL.
9. SEE GENERAL STRUCTURAL NOTES FOR ADDITIONAL REQUIREMENTS.
MASONRY LINTEL SCHEDULE
MARK LINTEL DEPTHHORIZONTAL STIRRUPS
REINFORCINGLINTEL SPAN (MAX)
COMMENTS
NONE(1) #7 BAR NONE(1) #7 BARML-1 24" (2) #5BAR CONT T&B4' - 0" MC-1 EA END
8"
ML-2
16"MASONRY WALL NOTES:
1. COORDINATE WITH ARCHITECTURAL DRAWINGS, MASONRY WALL FINISHES, TYPES OF MATERIAL, COURSING, ETC.2. DO NOT SOLID GROUT WALLS UNLESS NOTED OTHERWISE.3. ALL MASONRY BELOW GRADE SHALL BE GROUTED SOLID.4. VERTICAL REINFORCING SHALL BE CENTERED IN THE WALL UNLESS NOTED OTHERWISE.5. (1) VERTICAL BARS MINIMUM AT ALL CORNERS AND END OF WALLS.6. HORIZONTAL WALL REINFORCING SHALL BE PLACED BETWEEN VERTICAL MASONRY COLUMN REINFORCING BARS.7. HORIZONTAL WALL REINFORCING SHALL CONTINUE THRU MASONRY LINTELS, WHERE BOTH HORIZONTAL WALL REINFORCING
AND LINTEL REINFORCING OCCUR IN THE SAME COURSE, USE THE LARGER REINFORCING.8. MASONRY WALLS NOT DESIGNATED ON THE PLANS SHALL BE REINFORCED AS FOLLOWS:
9. SEE GENERAL STRUCTURAL NOTES FOR ADDITIONAL REQUIREMENTS.10. MASONRY SHALL BE SPECIAL INSPECTED SEE GENERAL STRUCTURAL NOTES.11. HORIZONTAL WALL REINFORCEMENT SPACING SHALL NOT EXCEED 48"oc OR 1/3 THE WALL LENGTH.
THICKNESS
6"8"
10"12"
VERTICAL REINFORCING
#5 BARS AT 32"oc#5 BARS AT 32"oc#6 BARS AT 32"oc#6 BARS AT 32"oc
HORIZONTAL REINFORCING
#4 BARS AT 48"oc#5 BARS AT 48"oc#6 BARS AT 48"oc
(2) #5 BARS AT 48"oc
MASONRY WALL SCHEDULE
TYPE 'A'(SINGLE MAT REINF)
HORIZ WALL REINF
VERT WALL REINF
MARK THICKNESSVERTICAL HORIZONTAL
REINFORCINGMATERIALS SOLID
GROUT TYPE JOINT
MW-08 8" CMU (1) #5 AT 32"oc (1) #5 AT 48"oc A NONO
MW-06 6" CMU (1) #5 AT 32"oc (1) #4 AT 48"oc A NONO
TYPICAL FOOTING SECTION
TYP FTG REINF
3" C
LR
3" CLR 3" CLREQ EQ EQ
CONCRETE FOOTING NOTES:
1. PLACE ALL FOOTING REINFORCING IN BOTTOM OF FOOTING WITH 3" CLEAR CONCRETE COVER, UNLESS NOTED OTHERWISE.2. TOP REINFORCING, WHERE SPECIFIED, SHALL BE PLACED IN THE TOP OF THE FOOTING WITH 2" MINIMUM CONCRETE COVER.3. IF FOOTINGS ARE EARTH FORMED, FOOTING WIDTH AND LENGTH SHALL BE 6" WIDER AND LONGER THAN SCHEDULED.4. SEE GENERAL STRUCTURAL NOTES FOR ALL OTHER REQUIREMENTS.5. NOT ALL FOOTINGS ARE USED, SEE FOUNDATION PLAN FOR FOOTING MARKS.6. RUN CONTINUOUS BARS IN 'FC' FOOTING THROUGH INTERSECTED 'FS' FOOTINGS.7. EXTEND CONTINUOUS FOOTINGS 1'-0" BEYOND END OF WALL, EXCEPT AT INTERSECTING CORNERS OR UNO ON PLAN.8. FOOTINGS MAY BE THICKER THAN THE SCHEDULED DEPTH IN AREAS SURROUNDING ANCHOR BOLTS OR HOLD DOWNS, SEE
ANCHORAGE AND HOLD DOWN DETAILS.9. IN FC FOOTINGS CROSSWISE BAR SHALL BE BELOW THE LENGTHWISE BAR
C3000-S1500
CONCRETE FOOTING SCHEDULE
MARK WIDTHNO SPACING
REINFORCING CROSSWISECOMMENTSLENGTH
SIZE LENGTH NO SPACING
REINFORCING LENGTHWISE
SIZE LENGTHDEPTH
CONT CONTFC2.0 2' - 0' 12" 3 #4 EQ
CONFIGURATION FOR MAS COL
4" TYPVERT COL REINF
MASONRY COLUMN NOTES:
1. HORIZONTAL WALL REINFORCEMENT SHALL BE LOCATED TO THE INSIDE OF VERTICAL BARS. THE CENTERLINE OF VERTICAL BARS SHALL BE LOCATED 2 1/2" FROM FACE OF THE MASONRY.
2. UNLESS NOTED OTHERWISE, VERTICAL REINFORCING AND TIES SHALL EXTEND TO FULL WALL HEIGHT.
3. VERTICAL MASONRY COLUMN REINFORCING SHALL EXTEND INTO FOOTING AND TERMINATE WITH A STANDARD 90° HOOK. FOR CONCRETE FOUNDATION WALLS OVER 5'-0" TALL, VERTICAL COLUMN REINFORCING SHALL DOWEL 4'-0" MINIMUM INTO THE FOUNDATION WALL.
4. IN CONCRETE FOUNDATION WALLS, VERTICAL MASONRY COLUMN REINFORCING SHALL BE TIED WITH #3 TIES AT THE SAME SPACING AND CONFIGURATION AS MASONRY COLUMNS ABOVE.5. SEE GENERAL STRUCTURAL NOTES FOR ADDITIONAL REQUIREMENTS.6. SPACE TIES AT 48"oc FROM A POINT 24" ABOVE OPENINGS TO THE TOP OF THE WALL.
RUN HORIZ REINF THRU COL
MARK COLUMN SIZEVERTICAL TIES
REINFORCING
TYPE
MC-1 8" x 16" (2) #5 NONE
MASONRY COLUMN SCHEDULE
MC-2 6" x 16" (2) #5 NONE NONE
NONE
TYPE "A" TYPE "B" TYPE "C"
EQ EQ
VERT REINF
HORIZ REINF
VERT REINF
HORIZ REINF
WALL REINFORCEMENT PLACEMENT TYPES:CONCRETE WALL NOTES:
1. SEE GENERAL STRUCTURAL NOTES FOR COVER AND OTHER REQUIREMENTS NOT NOTED IN SCHEDULE.2. CONCRETE WALLS NOT DESIGNATED ON THE PLANS SHALL BE REINFORCED AS FOLLOWS:
3. PLACE STEEL IN THE CENTER OF THE WALL (EXCEPT TYPE 'B' AND RETAINING WALLS). WALLS THICKER THAN 10" SHALL HAVE TWO CURTAINS OF REINFORCEMENT (PLACED NEAR EA FACE OF THE WALL), UNLESS NOTED OTHERWISE ON THE STRUCTURAL DRAWINGS.
THICKNESS
6"8"10"12"
VERTICAL REINFORCING
#4 BARS AT 18"oc#4 BARS AT 18"oc#4 BARS AT 16"oc
#4 BARS AT 18"oc EA FACE
HORIZONTAL REINFORCING
#4 BARS AT 16"oc#4 BARS AT 12"oc#5 BARS AT 15"oc
#4 BARS AT 16"oc EA FACE
CONCRETE WALL SCHEDULE
MARK THICKNESSREINFORCING
VERTICALCOMMENTS
HORIZONTAL TOP AND BOTTOMWALL TYPE
CW-08 8" (1) #4 AT 16"oc (1) #4 AT 12"oc (1) #4 A __
CW-14 14" (2) #4 AT 16"oc (2) #4 AT 12"oc (2) #4 C __
NOTES:
1. THIS SCHEDULE SHALL BE USED FOR ALL SPLICES, UNLESS NOTED OTHERWISE.2. HORIZONTAL BARS ARE CLASSIFIED AS TOP BARS WHERE 12", OR MORE, OF FRESH CONCRETE IS CAST BELOW
THE REINFORCING BARS.3. CLASS 'B' SPLICES SHALL BE USED FOR ALL SPLICES UNLESS NOTED OTHERWISE.4. TIES AND STIRRUPS SHALL NOT BE SPLICED.5. FOR ALL LIGHTWEIGHT CONCRETE, LAP LENGTHS SHALL BE MULTIPLIED BY 1.3.6. FOR ALL EPOXY COATED BARS, LAP LENGTHS SHALL BE MULTIPLIED BY 1.5 FOR BARS WITH CLEAR COVER LESS
THAN 3 BAR DIAMETERS OR CLEAR SPACING LESS THAN 6 BAR DIAMETERS, OTHERWISE MULTIPLY BY 1.2.7. LAP LENGTHS SHALL BE MULTIPLIED BY 1.25 AT SHEARWALL BOUNDARY ELEMENTS.8. DEVELOPMENT LENGTH 'Ld' IS EQUAL TO CLASS 'A' SPLICE.9. IF REINFORCING HAS CLEAR COVER LESS THAN ONE BAR DIAMETER, LAP LENGTHS SHALL BE MULTIPLIED BY 1.5.10. IF REINFORCING IS NOT ENCLOSED IN TIES OR STIRRUPS AND IS SPACED TIGHTER THAN 2 BAR DIAMETERS ON
CENTER, LAP LENGTHS SHALL BE MULTIPLIED BY 1.5.11. LAP LENGTHS SHALL BE MULTIPLIED BY 1.25 FOR GRADE 75 REBAR.12. WHERE BARS OF DIFFERENT SIZES ARE LAPPED, THE SPLICE LENGTH SHALL BE THE LARGER OF 'Ld' OF THE
LARGER BARS AND THE SPLICE LENGTH OF THE SMALLER BAR.
45° BEND
180° HOOK 135° HOOK(SEISMIC)
OFFSET
D
D
D
D
D4d OR 2 1/2" MIN
D
d
d
12
2
D
d
12d
6d O
R 3" M
IN
90° HOOK
D = 6d FOR #3 - #8D = 8d FOR #9 - #11D = 10d FOR #14 - #18
CONCRETE REINFORCING BAR LAP SPLICE SCHEDULE
REGULAR TOP
CLASS CLASS
A B A B
BAR SIZE
f'c = 3000 PSI
#3 17" 22"22" 28"
#4 22" 29"29" 38"
#5 28" 36"36" 47"
#6 33" 43"43" 56"
#7 48" 63"63" 81"
#8 55" 72"72" 93"
#9 62" 81"81" 105"
#10 70" 91"91" 118"
#11 78" 101"101" 131"
REGULAR TOP
CLASS CLASS
A B A B
f'c = 4000 PSI
15" 19"19" 25"
19" 25"25" 33"
24" 31"31" 41"
29" 37"37" 49"
42" 54"54" 71"
48" 62"62" 81"
54" 70"70" 91"
61" 79"79" 102"
67" 87"87" 114"
REGULAR TOP
CLASS CLASS
A B A B
f'c = 4500 PSI
14" 18"18" 23"
18" 24"24" 31"
23" 30"30" 38"
27" 35"35" 46"
40" 51"51" 67"
45" 59"59" 76"
51" 66"66" 86"
57" 74"74" 96"
64" 82"82" 107"
REGULAR TOP
CLASS CLASS
A B A B
f'c = 5000 PSI
13" 17"17" 22"
17" 23"23" 29"
22" 28"28" 36"
26" 34"34" 44"
38" 49"49" 63"
43" 56"56" 72"
48" 63"63" 81"
54" 71"71" 92"
60" 78"78" 102"
REGULAR TOP
CLASS CLASS
A B A B
f'c = 3500 PSI
16" 21"21" 26"
21" 27"27" 36"
26" 34"34" 44"
31" 40"40" 52"
45" 59"59" 75"
51" 67"67" 82"
58" 75"75" 98"
65" 85"85" 110"
73" 94"94" 122"
#3
BAR SIZE
9"
f'c = 3000 PSI
8"
f'c = 4000 PSI
7"
f'c = 4500 PSI
7"
f'c = 5000 PSI
6"
f'c = 6000 PSI
#4
#5
#6
#7
#8
#9
#10
#11
11" 10" 9" 9" 8"
14" 12" 12" 11" 10"
17" 15" 14" 13" 12"
20" 17" 16" 15" 14"
22" 19" 18" 17" 16"
25" 22" 21" 20" 18"
28" 25" 23" 22" 20"
31" 27" 26" 24" 22"
HOOKED BAR DEVELOPMENT LENGTHS, Ldh
NOTES:
1. FOR GRADE 75 REBAR, MULTIPLY LENGTHS BY 1.25.2. FOR LIGHTWEIGHT CONCRETE, MULTIPLY LENGTHS BY 1.3.3. FOR EPOXY COATED REINFORCEMENT, MULTIPLY LENGTHS BY 1.2.4. FOR HOOKS WITH 2.5" MINIMUM SIDE COVER PERPENDICULAR TO PLANE
OF HOOK, MULTIPLY LENGTHS BY 0.7.5. FOR LATERAL LOAD RESISTING ELEMENTS, CRITICAL SECTIONS SHALL BE TAKEN AS THE FACE OF TIE / HOOP AT CONFINED CORES OF COLUMN JOINTS OR SHEAR WALL BOUNDARY ZONE.
TYPICAL SECTION SECTION AT LATERAL LOAD RESISTING ELEMENT
2" MIN
2" MIN Ldh
FACE OF CONC
STANDARD HOOK
CRITICAL SECTION
Ldh
CRITICAL SECTION
FACE OF CONC
STANDARD HOOK
LATERAL LOAD RESISTING ELEMENT
REGULAR TOP
CLASS CLASS
A B A B
f'c = 6000 PSI
12" 16"16" 20"
16" 21"21" 27"
20" 26"26" 33"
24" 31"31" 40"
34" 45"45" 58"
39" 51"51" 66"
44" 57"57" 74"
50" 64"64" 84"
55" 71"71" 93"
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A DIMENSIONS AND ELEVATIONS, AS THEY RELATE TO THE BUILDING IN GENERAL, i.e. GRID TO GRID DIMENSIONS OR DECK BEARING ELEVATIONS, ARE SUPPLIED BY THE ARCHITECT. THEY ARE PROVIDED ON THE STRUCTURAL PLANS AND DETAILS FOR THE CONVENIENCE OF THE CONTRACTOR. VERIFY DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.
NOTE: THESE STRUCTURAL DRAWINGS ARE BASED ON ARCHITECTURAL DRAWINGS DATED
This
dra
win
g, a
s an
inst
rum
ent o
f pro
fess
iona
l ser
vice
, is
the
prop
erty
of D
UN
N A
SSO
CIA
TES
INC
, and
sha
ll no
t be
used
, in
who
le o
r par
t for
any
oth
er p
roje
ct w
ithou
t the
writ
ten
perm
issi
on o
f an
auth
oriz
ed re
pres
enta
tive
of D
UN
N A
SSO
CIA
TES
INC
. Una
utho
rized
use
will
be p
rose
cute
d to
the
fulle
st e
xten
t of t
he la
w. C
opyr
ight
© 2
018
by D
UN
N A
SSO
CIA
TES
INC
.
11/2
0/2
01
8 2
:20:1
2 P
M
SCHEDULES
R. SMITH
2100 W
ES
T 1
1400 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
4095
SA
LT
LA
KE
CO
UN
TY
18142
11/20/2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
S301
T.KETCHAM
11/20/2018PERMIT SET
11/15/2018
NO SCALE:S301
3 MASONRY LINTEL SCHEDULENO SCALE:S301
2 MASONRY WALL SCHEDULENO SCALE:S301
1 CONCRETE FOOTING SCHEDULE
NO SCALE:S301
4 MASONRY COLUMN SCHEDULENO SCALE:S301
5 CONCRETE WALL SCHEDULE
# Date Revision
NO SCALE:S301
6CONCRETE REINFORCING BAR LAP SCHEDULES ANDDIAGRAMS
ML-2 32" 12'-0" NONE MC-1 EA END(2) #5BAR CONT T&B
11/20/2018
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
b + 2d MIN
AS R
EQ'D
CONC FTG
STRUCT FILLSEE GSN
CONSULT THE PROJECT SPECIFICATIONS AND SOILS REPORT FOR EARTHWORK REQUIREMENTS. IN ABSENCE OF INFORMATION, REFER TO THE DTL ABV
b
2
1 BOTT OF TRENCH TO BE ABV THIS LINE
BACKFILL TRENCH PER GSN
CONC FTG
CONC WALL
PIPE
6"
IF THIS DIM EXCEEDS 1'-6", DO NOT THICKEN FTG
PIPE BELOW FOOTING
6" M
IN
PIPE THROUGH FOOTING
THICKEN FTG
THICKENED FTG
LAP SPLICE
PROVIDE ADDITIONAL LENGTHWISE REINF AS SHOWN TO MATCH BAR THAT IS CUT
PROVIDE SLEEVE FORALL PIPES PASSINGTHRU WALLS AND FTGS
CONC FTGPROVIDE SLEEVE FORALL PIPES PASSINGTHRU WALLS AND FTGS
1/2" CLEAR
12" MIN 3d 12" MIN
"d" = LARGEST PIPE DIAMETER
1/2" CLEAR
3d
"d" = LARGEST PIPE DIAMETER
12" MIN 12" MIN
CLR3"
8" M
IN
0" T
O 1
'-6"
VAR
IES
ADDITIONAL VERTBARS AT CORNER TYP
CORNER BARS TO MATCH WALL HORIZ BARS
CONC WALL
CORNER BARS TO MATCH WALL HORIZ BARS
CONC WALL
ADDITIONAL VERT BARSAT INTERSECTIONTYP
LAP LENGTH, TYP
LAP
LEN
GTH
, TYP
LAP
LEN
GTH
MAS WALL
ADDITIONAL VERT BAR AT INTERSECTION, TYP (4) PLACES
LAP LENGTH
MIN
LAP LENGTH
MIN
LAP LENGTH
MIN
LAP LENGTH
MIN
CORNER BAR TO MATCH WALL HORIZ BARS
CORNER BAR TO MATCH WALL HORIZ BARS
ADDITIONAL VERT BAR AT INTERSECTION, TYP (3) PLACES
MAS WALL
LAP LENGTH
PREFORMED "T" QUICK JOINT OR SAWCUT, USE TOOLED JOINTS AT EXT SLABS
4" SLAB ON GRADE
CONTROL JOINT
4" SLAB ON GRADE
CONSTRUCTION JOINT
t
THIC
KNES
S (t)
1/4"
SLA
B
INSTALL BACKER ROD IMMEDIATELY AFTER SAWCUTTING JOINTS
EDGE EA SIDE W/ 1/8" RADIUS
JOINT DOWEL; 5/8"Ø x 18" SLIP DOWEL AT 18"oc OR 4 1/2"x4 1/2" DIAMOND DOWEL AT 24"oc OR APPROVED EQ
DISCONTINUE BARS AT COLD CJ
2" C
LR
CONC FND WALL / CONC COL
CONC FTG
EXT FINAL GRADE
INT FINISH FLR
STRUCTURE ABV FINISHED FLR NOTE: CONTRACTOR SHALL
VERIFY AND COMPARE ALL FINAL EXT GRADE ELS W/ TOP OF FTG ELS NOTED TO INSURE MIN REQD FROST DEPTH IS PROVIDED
TYP AT EXT FND
PER
GSN
REQ
UIR
ED F
RO
ST D
EPTH
6" M
IN
1'-4" MIN
3d MIN
3d M
IN6"
MIN
END OF CONC WALL
6" M
AX
6" M
AX
PROVIDE TYP WALL HORIZ REINF
PROVIDE TYP HORIZ REINF BTWN SLEEVES
PROVIDE SLEEVE FOR ALL PIPES OR CONDUITS PASSING THRU WALLS. 8"Ø MAX
PROVIDE TYP WALL HORIZ REINF
d = DIAMETER OF PIPE SLEEVE
FOR PIPE SLEEVE DIAMETERS GREATER THAN 8", SEE TYP TRIM BARS AROUND MISCELLANEOUS CONCRETE WALL OPENINGS
IF SPACING REQUIREMENTS CANNOT BE MET, ENGINEER OF RECORD IS TO BE CONTACTED PRIOR TO SLEEVES BEING INSTALLED
BOTT/ CONC
WALL
TOP/ CONC
WALL
ADDITIONAL VERTBARS AT CORNER
CORNER BARS TO MATCH WALL HORIZ BARS
CONC WALL
CORNER BARS TO MATCH WALL HORIZ BARSCONC WALL
BENT NORMAL WALLREINF OR PROVIDEBAR OF SAME SIZEAND SPACING W/ LAPPER GSN
ADDITIONAL VERT BARSAT INTERSECTIONTYP (2) PLACES
LAP LENGTH, TYP
LAP
LEN
GTH
, TYP
FOR DOUBLE REINF WALL FRAMING TO SINGLE REINF WALL ONLY OUTER HORIZONTAL CORNER BAR IS REQD
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A DIMENSIONS AND ELEVATIONS, AS THEY RELATE TO THE BUILDING IN GENERAL, i.e. GRID TO GRID DIMENSIONS OR DECK BEARING ELEVATIONS, ARE SUPPLIED BY THE ARCHITECT. THEY ARE PROVIDED ON THE STRUCTURAL PLANS AND DETAILS FOR THE CONVENIENCE OF THE CONTRACTOR. VERIFY DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.
NOTE: THESE STRUCTURAL DRAWINGS ARE BASED ON ARCHITECTURAL DRAWINGS DATED
This
dra
win
g, a
s an
inst
rum
ent o
f pro
fess
iona
l ser
vice
, is
the
prop
erty
of D
UN
N A
SSO
CIA
TES
INC
, and
sha
ll no
t be
used
, in
who
le o
r par
t for
any
oth
er p
roje
ct w
ithou
t the
writ
ten
perm
issi
on o
f an
auth
oriz
ed re
pres
enta
tive
of D
UN
N A
SSO
CIA
TES
INC
. Una
utho
rized
use
will
be p
rose
cute
d to
the
fulle
st e
xten
t of t
he la
w. C
opyr
ight
© 2
018
by D
UN
N A
SSO
CIA
TES
INC
.
11/2
0/2
01
8 2
:20:1
3 P
M
FOOTING
AND
FOUNDATION
DETAILS
R. SMITH
2100 W
ES
T 1
1400 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
4095
SA
LT
LA
KE
CO
UN
TY
18142
11/20/2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
S501
T.KETCHAM
11/20/2018PERMIT SET
11/15/2018
NO SCALE:S501
1 TYPICAL SUBGRADE PREPARATION (AS REQ'D)NO SCALE:S501
3 TYPICAL PIPE PARALLEL TO FOOTINGNO SCALE:S501
4 TYPICAL PIPE PERPENDICULAR TO FOOTING
NO SCALE:S501
7TYPICAL CORNER BARS FOR SINGLE REINFORCEDCONCRETE WALLS (PLAN VIEW)
NO SCALE:S501
6TYPICAL CORNER BARS FOR SINGLE REINFORCEDMASONRY WALLS (PLAN VIEW)
NO SCALE:S501
9 TYPICAL SLAB ON GRADE JOINTS
NO SCALE:S501
2TYPICAL FOOTING DEPTH DETAIL FOR FROSTPROTECTION
NO SCALE:S501
5 TYPICAL SMALL PIPE OR CONDUIT THROUGH CONCRETE WALLNO SCALE:S501
8TYPICAL CORNER BARS FOR DOUBLE REINFORCEDCONCRETE WALLS (PLAN VIEW)
# Date Revision
11/20/2018
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
SEE MAS LINTEL SCHED FOR REINFABV RECESS
RECESS IN WALL
STD 180 DEG HOOK
VERT REINF FULLHEIGHT OF WALL ATEA SIDE OF RECESS
#5 HORIZ BAR BLWRECESS, EXTEND 48BAR Ø EA SIDEOF RECESSED OPNG
PLAN VIEW
SECTION CONDITION AT HORIZONTAL BOND BEAM AND JOINT REINFORCING
HORIZ REINF CONT THRU JOINT
CONT VERT CJ
(1) VERT BAR TO MATCH VERT WALL REINF, EA SIDE OF JOINT
JOINT MATERIAL DUR-O-WALL WF TYPE (OR APPROVED EQ) SIZE VARIES BASED ON WALL THICKNESS, VERIFY W/ ARCH
TYP VERT REINFIN LAST CELL
HORIZ REINF TO TERMINATE W/STD 180 DEG HOOK AT SINGLE LAYER OF VERT REINF
TYP VERT REINFIN LAST (2) CELLS
HORIZ REINF TO TERMINATE W/STD 90 DEG HOOK AT DBL LAYER OF VERT REINF EXTEND BYND VERT REINF
LAP LENGTH
LAP LENGTH
MAS WALL
SINGLE LAYER VERTICAL REINFORCING
DOUBLE LAYER VERTICAL REINFORCING
TIES SEE MAS COL SCHED
CONC SOG
CONC FTG
VERT WALL REINF
HORIZ WALL REINF
CONT BAR -#5 AT 8" MAS WALL#6 AT 10" MAS WALL
OPTION
SOLID GROUT ALL CELLS BLW GRADE
DOWEL TO MATCH VERTWALL REINF ABV
MAS WALL
HORIZ WALL REINF
HORIZ WALL REINF
ALTERNATE HOOK DIRECTION
8" T
YP
1/4" ROUGHENED SURFACE
CONC SOG
CONC FTG
BOTT CONT REINF
CONC WALL
HORIZ WALL REINF
VERT WALL REINF
TOP CONT REINF
CHAMFER, SEE ARCH
WHERE 'H' EXCEEDS 24"
DOWEL TO MATCH VERTWALL REINF ABV
MAS WALL
SILL OPTION
CONT #5 BAR
PRECAST CONC SILL, SEE ARCH MAS WALL BYND
24" 18"
#4 AT 24"oc
"H"
ALTERNATE HOOK DIRECTION1/4" ROUGHENED SURFACE
AT INTERIOR VENEER, WIDER WALL TO SUPPORT WHERE OCCURS
VENEER, WHERE OCCURS
HORIZ REINF
1'-4"
0'-00"
CONC SOG
CONC FTG
HORIZ WALL REINF
BOTT CONT REINF
TOP CONT REINF
CHAMFER, SEE ARCH
WHERE 'H' EXCEEDS 24"
CONC PIER
HORIZ WALL REINF CONT THRU PIER
24" 18"
#4 AT 24"oc
MAS COL
VERT COL REINF
DOWEL TO MATCH VERT COL REINF ABV
'H'
1/4" ROUGHENED SURFACE
CONC FTG
BOTT CONT REINF
CONC WALL
CONC SOG
DOWEL TO MATCH VERTWALL REINF ABV
WALL BEYOND
EXT SLAB OR GRADE
TOP CONT REINF
1
3 (MIN)
SEE ARCH FOR OPENING CONFIGURATION
8" T
YP
2x4 BEVELED KEYWAY,CONT OR INTERMITTENT
3" MIN
24" 18"
#4 AT 16"oc
1/4" ROUGHENED SURFACE
(E) CONC FTG
(E) CONC WALL
CONC SOG
MAS WALL
INTERIOR MAS WALL
CONC WALL
DOWEL 6" INTO (E) FTG
DOWEL 6" INTO (E) WALL
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A DIMENSIONS AND ELEVATIONS, AS THEY RELATE TO THE BUILDING IN GENERAL, i.e. GRID TO GRID DIMENSIONS OR DECK BEARING ELEVATIONS, ARE SUPPLIED BY THE ARCHITECT. THEY ARE PROVIDED ON THE STRUCTURAL PLANS AND DETAILS FOR THE CONVENIENCE OF THE CONTRACTOR. VERIFY DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.
NOTE: THESE STRUCTURAL DRAWINGS ARE BASED ON ARCHITECTURAL DRAWINGS DATED
This
dra
win
g, a
s an
inst
rum
ent o
f pro
fess
iona
l ser
vice
, is
the
prop
erty
of D
UN
N A
SSO
CIA
TES
INC
, and
sha
ll no
t be
used
, in
who
le o
r par
t for
any
oth
er p
roje
ct w
ithou
t the
writ
ten
perm
issi
on o
f an
auth
oriz
ed re
pres
enta
tive
of D
UN
N A
SSO
CIA
TES
INC
. Una
utho
rized
use
will
be p
rose
cute
d to
the
fulle
st e
xten
t of t
he la
w. C
opyr
ight
© 2
018
by D
UN
N A
SSO
CIA
TES
INC
.
11/2
0/2
01
8 2
:20:1
3 P
M
FOOTING
AND
FOUNDATION
DETAILS
R. SMITH
2100 W
ES
T 1
1400 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
4095
SA
LT
LA
KE
CO
UN
TY
18142
11/20/2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
S502
T.KETCHAM
11/20/2018PERMIT SET
11/15/2018
NO SCALE:S502
1TYPICAL MASONRY WALL RECESS DETAILS FOR SINGLEREINFORCED MASONRY WALLS (PLAN VIEW)
NO SCALE:S502
2TYPICAL CONTROL JOINT FOR SINGLE REINFORCEDMASONRY WALLS (PLAN VIEW)
NO SCALE:S502
3TYPICAL TERMINATION OF HORIZONTAL REINFORCINGFOR REINFORCED MASONRY WALLS (PLAN VIEW)
NO SCALE:S502
4TYPICAL SINGLE MAT REINFORCING MASONRY WALL ONINTERIOR CONCRETE FOOTING
NO SCALE:S502
6TYPICAL SINGLE MAT REINFORCING MASONRY WALL ONCONCRETE FOUNDATION WALL
NO SCALE:S502
7TYPICAL MASONRY COLUMN ON CONCRETE FOUNDATIONWALL
NO SCALE:S502
5 FOUNDATION WALL AT OPENING DETAIL
# Date Revision
NO SCALE:S502
8 DETAIL
11/20/2018
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
MAS WALL, SEE SCHED FOR REINF
3x TREATED SILL PL
SIMPSON H1 @ EA TRUSS
PREFABRICATED TRUSS
ROOF SHEATHING
5/8"Ø ANCHOR BOLTS AT 32" oc
2x BLKG BTWN TRUSSES
#5 x CONT
SIMPOSN A35 @ 24" OCE.N. SEE /(8 S701)
ROOF OUTLOOKER, SEE PLAN
ROOF SHEATHING
5/8"Ø ANCHOR BOLTS AT 32" oc
MAS WALL, SEE SCHED FOR REINF
HORIZ REINF
3x TREATED SILL PL
(4) 10d NAILS AT 8" oc
#5 x CONTSIMPSON H1 @ EA TRUSS
VARIES
ROOF PFT OR JOIST, SEE PLAN
SIMPSON LB TOP FLANGE HANGER
SEE ARCH
SIMPSON A35 @ 24" OC E.X
2X FOLL DEPTH BLOCKING
ROOF PURLIN, SEE PLAN
ROOF SHEATHING
5/8"Ø ANCHOR BOLTS AT 32" oc
MAS WALL, SEE SCHED FOR REINF
HORIZ REINF
3x TREATED SILL PL
TAPERED SHIM
TAPERED 2x BLKG BTWN JST
SIMPSON H1
SIMPSON A35 AT EA BLKG
AT SIM CONDITION, PURLIN OVERHANGS ON OPPOSITE SIDE
#5 x CONT 2x FRAMING
LVL BEAM
ROOF SHEATHING
SIMPSON JB210 TOP FLANGE HANGER
MAS WALL, SEE SCHED FOR REINF
3x TREATED SILL PL
SIMPSON H1
PREFABRICATED TRUSS
ROOF SHEATHING
5/8"Ø ANCHOR BOLTS AT 32" oc
TRUSS BLKG
#5 x CONT
MAS WALL, SEE SCHED FOR REINF
3x TREATED SILL PL
PREFABRICATED TRUSS
ROOF SHEATHING
5/8"Ø ANCHOR BOLTS AT 32" oc
#5 x CONT
SIMPSON JB210 TOP FLANGE HANGER
ROOF TRUSS
2x BRG WALL
ROOF SHTG
ROOF SHTG
2x BLKG, TYP
SIMPSON HANGER
TRUSS MANUF TO ADD ADDITIONAL VERT MEMBER
E.N. SEE /(8 S701) /(9 S701)
NOTES:1. NAILING SCHEDULE IS PER TABLE OF THE I.B.C.2. NAILING REQUIREMENTS SHOWN HERE DO NOT REPLACE HARDWARE ON THE PLANS OR DETAILS.3. ALL NAILS USED ARE COMMON NAILS, UNO.
MINIMUM NAILING SCHEDULECONNECTION NAILING
BRDG TO JST, TOE NAIL EA ENDSOLE PL TO JST OR BLK, FACE NAILTOP PL TO STUD, END NAILSTUD TO SOLE PL, END NAILDBL STUDS, FACE NAILDBL TOP PL, FACE NAILBLK BTWN JST OR RAFTERS TO TOP PL, TOE NAILRIM JST TO TOP PL, TOE NAILTOP PL, LAPS AT WALL INTERSECTION, FACE NAILCONT HEADER, TWO PIECESCEILING JST TO PL, TOE NAILCONT HEADER TO STUD, TOE NAILCEILING JST, LAPS OVER PARTITIONS, FACE NAILCEILING JST TO PARALLEL RAFTERS, FACE NAILRAFTER TO PL, TOE NAIL1" BRACE TO EA STUD AND PL, FACE NAILBUILT-UP CORNER STUDSBUILT-UP GIRDER AND BM
COLLAR TIE TO RAFTER, FACE NAILJACK RAFTER TO HIP, TOE NAIL
FACE NAILROOF RAFTER TO 2x RIDGE BM, TOE NAIL
FACE NAILJST TO BAND JST, FACE NAILLEDGER STRIP, FACE NAIL AT EA JOISTPLYWOOD AND PARTICLEBOARD:
SUBFLOOR, ROOF AND WALL SHEATHING (TO FRAMING)
1/2" AND LESS19/32" - 1"1 1/8" - 1 1/4
COMBINATION SUB FLOOR -UNDERLAYMENT (TO FRAMING)
3/4" AND LESS7/8" - 1"1 1/8" - 1 1/4"
NAILS SPACED AT 6 INCHES ON CENTER AT EDGES, 12 INCHES AT INTERMEDIATE SUPPORTS, EXCEPT 6" INCHES AT ALL SUPPORTS WHERE SPANS ARE 48 INCHES OR MORE. FOR NAILING OF DIAPHRAGMS AND SHEAR WALLS, REFER TO THE APPROPRIATE SCHEDULE.
(2) 8d16d AT 1'-4"oc(2) 16d(2) 16d16d AT 2'-0"oc16d AT 1'-4"oc(3) 8d8d AT 0'-6"oc(2) 16d16d AT 1'-4"oc ALONG EA EDGE(3) 8d(4) 8d(3) 16d(3) 16d(3) 8d(2) 8d16d AT 2'-0"oc3" x 0.131 AT 24"oc AT TOP AND BOTTAND STAGGERED, (3) 3" x 0.131 ATENDS AND AT EA SPLICE(3) 10d(3) 10d(2) 16d(2) 16d(2) 16d(3) 16d(3) 16d
8d8d OR 10d10d
8d8d OR 10d10d
SHEATHING SCHEDULE AT ROOF AND FLOOR
NOTES:1. ALL FLOOR SHEATHING SHALL BE APA RATED SHEATHING WITH A MINIMUM SPAN RATING OF 48/24. ALL ROOF SHEATHING SHALL BE APA RATED
SHEATHING WITH A MINIMUM SPAN RATING OF 40/20. USE OSB INSTEAD OF PLYWOOD UNLESS OTHERWISE APPROVED BY THE EOR.2. NAIL ROOF SHEATHING TO SUPPORTS. GLUE AND NAIL FLOOR SHEATHING TO SUPPORTS.3. USE COMMON NAILS (8d DIAMETER = 0.131”, 10d DIAMETER = 0.148”). RING SHANK NAILS WITH EQUAL OR GREATER DIAMETER MAY BE USED AT
FLOOR SHEATHING AT CONTRACTOR’S OPTION. MINIMUM NAIL PENETRATION INTO FRAMING MEMBERS, 8d = 1 1/2”, 10d = 1 5/8”.4. DRIVE NAILS WITH NAIL HEADS FLUSH WITH THE SURFACE OF THE SHEATHING. DO NOT OVER DRIVE OR UNDER DRIVE NAILS. EDGE NAILS SHALL BE PLACED 3/8” FROM EDGE OF PANEL.5. PANEL EDGES PERPENDICULAR TO SUPPORTS SHALL BE UNBLOCKED UNLESS FULLY BLOCKED IS SPECIFICALLY NOTED. PROVIDE PANEL EDGE
NAILING AS SPECIFIED ALONG ALL SUPPORTED EDGES (ALL EDGES IF FULLY BLOCKED), BOUNDARIES, TOP PLATES OF SHEAR WALLS, STRAPS, COLLECTORS, AND AT ALL OTHER LOCATIONS AS INDICATED AND/OR REQUIRED FOR A COMPLETE INSTALLATION.
6. PROVIDE FIELD NAILING AT 12”oc TYPICAL FOR ALL DIAPHRAGMS.7. ALL SHEATHING PANELS SHALL HAVE A MINIMUM WIDTH OF 2’-0”, UNLESS PANEL IS FULLY BLOCKED AND NAILED TO ADJACENT PANELS. 8. PLACE ALL SHEATHING PANELS JOINTS ALONG THE CENTER OF A SINGLE COMMON BACK-UP MEMBER, TYPICAL.9. ALL FLOOR SHEATHING TO BE TONGUE AND GROOVE. GLUE TONGUE AND GROOVE JOINT.10. EXTERIOR FLOOR SHEATHING SHALL BE PLYWOOD (NOT OSB) WHEN REQUIRED BY THE ARCHITECT.
OTHER EDGE
STAGGER JOINTS
CONT EDGE
FIELD NAILING
1/16
" GAP
AT
SID
E JO
INTS
EDGE OF PLYWOOD SHEETS CTR ON JSTS AND BLOCKS
1/8" GAP AT END JOINTS
LEDGER
BN
EN
EDGE BLK, WHERE NOTED IN SCHED, USE 2x4 FLAT BLK, UNO
LOCATIONWOOD
SHEATHING THICKNESS
NAIL SIZEEDGE NAIL
CONT EDGE OTHER EDGE
EDGE BLOCK
BOUNDARY NAIL
FIELD NAIL
ROOF __" __d __ __ ____ YES/NO
FLOOR __" __d __ __ ____ YES/NO
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A DIMENSIONS AND ELEVATIONS, AS THEY RELATE TO THE BUILDING IN GENERAL, i.e. GRID TO GRID DIMENSIONS OR DECK BEARING ELEVATIONS, ARE SUPPLIED BY THE ARCHITECT. THEY ARE PROVIDED ON THE STRUCTURAL PLANS AND DETAILS FOR THE CONVENIENCE OF THE CONTRACTOR. VERIFY DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.
NOTE: THESE STRUCTURAL DRAWINGS ARE BASED ON ARCHITECTURAL DRAWINGS DATED
This
dra
win
g, a
s an
inst
rum
ent o
f pro
fess
iona
l ser
vice
, is
the
prop
erty
of D
UN
N A
SSO
CIA
TES
INC
, and
sha
ll no
t be
used
, in
who
le o
r par
t for
any
oth
er p
roje
ct w
ithou
t the
writ
ten
perm
issi
on o
f an
auth
oriz
ed re
pres
enta
tive
of D
UN
N A
SSO
CIA
TES
INC
. Una
utho
rized
use
will
be p
rose
cute
d to
the
fulle
st e
xten
t of t
he la
w. C
opyr
ight
© 2
018
by D
UN
N A
SSO
CIA
TES
INC
.
11/2
0/2
01
8 2
:20:1
3 P
M
ROOF
FRAMING
DETAILS
R. SMITH
2100 W
ES
T 1
1400 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
4095
SA
LT
LA
KE
CO
UN
TY
18142
11/20/2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
S701
T.KETCHAM
11/20/2018PERMIT SET
11/15/2018
NO SCALE:S701
3 PREFABRICATED TRUSS TO MASONRY WALL CONNECTIONNO SCALE:S701
2 TYPICAL ROOF BLOCKING TO MASONRY WALLNO SCALE:S701
1 TYPICAL ROOF PURLIN TO MASONRY WALL CONNECTIONNO SCALE:S701
5 PREFABRICATED TRUSS TO TRUSS GIRDER CONNECTIONNO SCALE:S701
4 PREFABRICATED TRUSS AT MASONRY WALL OVERRUN
NO SCALE:S701
6 WOOD JOIST AT MASONRY WALL OVERRUN
# Date Revision
NO SCALE:S701
7 ROOF FRAMING A MECHANICAL SUPPORT
NO SCALE:S701
8 MINIMUM NAILING SCHEDULENO SCALE:S701
9 SHEATHING SCHEDULE AT ROOF AND FLOOR
11/20/2018
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
0.0
DUCTWORK/GRILLES PIPING PLUMBING LINETYPES LINETYPES CONT.
LEGEND OF MECHANICAL SYMBOLS AND ABBREVIATIONS
ANNOTATIONS
FIRE
EQUIPMENT
SD
A
M101
A
M-101
T
12X12
200
12X12
200
24X10200
24X10200
12X12200
22X22
200
12X12
200
N
LB/HR.GPM
3-1" SLOTS@ 48" 400
W R
12/12
6
45° D
FD
FSD
SD
OR
8/8
1.25D
AD
12/8 FO
ATC
CF
AW
AV
HP(NAME)
N20
(NAME)
R
12/8
12ø
UP
DN
12/12 12ø
1.5D
D
12∅ 12/12
HFR
HFS
FOR
FOS
HG
(NAME)
LPG
G(NAME)
GHR
HWR
HWS
E(NAME)
G
MUW
BF
BBD
HPS
MPS
LPS
HPC
LPC
P-1
OX
MA
MA 120
MV
N
C02
CA
LA
LV
B
CR
CS
CHWR
CHWS
IA
IA 120
MPC
1
BDD
SW
OX 120
RS
RL
V
RDO
RD
ROR
F
DI
DIR
RO
FOV
S
T
S
RPBP
EF
1
THERMOSTATIC MIXING VALVE
REDUCED PRESSURE BACKFLOWPREVENTOR W/ DRAIN PAN
FUEL OIL VENT
REVERSE OSMOSIS WATER SUPPLY
DEIONIZED WATER RETURN
DEIONIZED WATER SUPPLY
RISE OR DROP
FIRE SPRINKLER WATER
DRAIN PAN AND P-TRAP
FILL PORT
VALVE IN RISE
PRESSURE REDUCING VALVE SELF CONTAINED
COTG
FCO
MEDICAL OXYGEN AT PRESSUREINDICATED
REVERSE OSMOSIS WATER RETURN
SOFT DOMESTIC WATER
VENT (SEWER)
SEWER (ABOVE GRADE)
SEWER (BELOW GRADE)
ROOF DRAIN OVERFLOW
ROOF DRAIN
VACUUM
PUMPED CONDENSATE
REFRIGERANT LIQUID
REFRIGERANT SUCTION
UNIT HEATER
DUCT SMOKE DETECTOR
4-WAY BLOWPATTERN
3-WAY BLOWPATTERN
2-WAY BLOWPATTERN
2-WAY BLOWPATTERN
1-WAY BLOW PATTERN
NEGATIVE PRESSURE DUCT - RISE
POSITIVE PRESSURE DUCT - DROP
POSITIVE PRESSURE DUCT - RISE
BACK DRAFT DAMPER
CEILING RETURN AIR GRILEW/ SOUND BOOT
DOWNSPOUT NOZZLE
ROOF DRAIN
SENSOR
THERMOSTAT
SWITCH
HOSE BIBB
AIR VENT-AUTO
AIR VENT-MANUAL
FLOOR DRAIN
FLOOR SINK
SPRINKLER HEAD
FIRE RISER
BRANCH - TOP CONNECTION
BRANCH - BOTTOM CONNECTION
MEDIUM PRESSURE CONDENSATE
INSTRUMENT AIR AT PRESSUREINDICATED
INSTRUMENT AIR
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
FIXTURE FROM LEVEL ABOVE
BRINE
LAB VACUUM
LAB AIR
COMPRESSED AIR
CARBON DIOXIDE
NITROUS OXIDE
NITROGEN
MEDICAL VACUUM
MEDICAL AIR AT PRESSURE INDICATED
MEDICAL AIR
MEDICAL OXYGEN
HIGH PRESSURE DOMESTIC WATER
ACID VENT
ACID WASTE
KEYED NOTE IDENTIFICATION
EQUIPMENT IDENTIFICATION
DETAIL TAG - TOP FIGURE IS DETAIL NO. BOTTOM FIGURE IS SHEET NO.
SECTION TAG - TOP FIGURE IS SECTION NO. BOTTOM FIGURE IS SHEET NO.
POINT OF CONNECTION
PLUMBINGFIXTURES
DOMESTIC HOT WATER RETURN(DHWR)
DOMESTIC HOT WATER (DHW)
DOMESTIC COLD WATER (DCW)
FLOOR CLEAN-OUTOR CLEAN-OUT TOGRADE
HOSEVALVE
FLOW SWITCH
NRS GATE VALVE WITHSUPERVISION
BRANCH - SIDE CONNECTION
RISER - UP (ELBOW)
RISER - DOWN (ELBOW)
ARROW INDICATES DIRECTION OF FLOW INPIPE
NIGHT THERMOSTAT
45° ELBOW
90° ELBOW
CALIBRATED BALANCINGVALVE WITH GPM INDICATED
GLOBE VALVE
CHECK VALVE
GATE VALVE
RELIEF VALVE
ANGLE VALVE
PRESSURE REDUCING VALVE EXTERNAL PRESSURE
SOLENOID VALVE
FLOW SWITCH
REDUCER
LOW PRESSURE CONDENSATE
HIGH PRESSURE CONDENSATE
LOW PRESSURE STEAM
MEDIUM PRESSURE STEAM
HIGH PRESSURE STEAM
BOILER BLOW DOWN
BOILER FEED WATER
MAKE UP WATER
NATURAL GAS
EXISTING PIPING
HEATING HOT WATER SUPPLY
HEATING HOT WATER RETURN
GLYCOL HEAT RECOVERY PIPING
GLYCOL PIPING SOLUTION
LIQUIFIED PETROLEUM GAS
EXISTING PIPING TO BEREMOVED
HOT GAS
FUEL OIL SUPPLY
FUEL OIL RETURN
HELICOPTER FUEL SUPPLY
HELICOPTER FUEL RETURN
CHEMICAL FEED
DEMOLITION
TOP FIGURES INDICATENECK SIZE. BOTTOMFIGURE INDICATES CFM.
NEGATIVE PRESSURE DUCT - DROP
ROUND DUCT - RISE
ROUND DUCT - DROP
UNDER FLOOR DUCT
TURNING VANES
FRESH AIR LOUVER
RELIEF AIR OR EXHAUST AIR LOUVER
CEILING SUPPLY DIFFUSER
CEILING RETURN REGISTER
CEILING EXHAUST REGISTER,(BALANCE TO MATCH SUPPLY IFRETURN CFM IS NOT SHOWN)
SIDEWALL SUPPLYREGISTER
SIDEWALL EXHAUST ORRETURN REGISTER
CEILING SUPPLY DIFFUSERWITH FLEXIBLE DUCT
CEILING AIR GRILLE WITHFLEXIBLE DUCT
LINEAR DIFFUSER WITH PLENUM AND FLEXIBLE DUCTCONNECTION. NO. OF SLOTS & SIZE OF SLOT ON TOP,ACTIVE LENGTH AND CFM ON BOTTOM
FLEXIBLE DUCT CONNECTION
FLEXIBLE DUCT
FLAT OVAL DUCT WITH NET INSIDEDIMENSIONS SHOWN IN INCHES.
RECTANGULAR DUCT WITH NET INSIDEDIMENSIONS SHOWN IN INCHES.
ROUND DUCT WITH NET INSIDE DIMENSIONSSHOWN IN INCHES.
WITH RESPECT TO AIR FLOW 15°NOMINAL INCLINE WITH RADIUSTURNS=DEPTH OF DUCT.
INCLINED RISE
INCLINED DROP
R/W=1. ROUND DUCT SIMILAR TO RECTANGULAR
RECTANGULAR TO RECTANGULAR OR ROUND TO ROUNDDUCT TRANSFORMATION MAXIMUM 15° INCLUDED ANGLEEXCEPT WHERE SHOWN OTHERWISE.
RECTANGULAR TO ROUND DUCT TRANSFORMATION
BRANCH DUCT SPLIT WITH 6" WIDTH AND MIN.R=WIDTH OF BRANCH DUCT DOWNSTREAM.ELBOW TURNING VANE OPTIONAL.
TAP ENTRY AREA EQUALS 150% OF BRANCH AREA
HIGH EFFICIENCY FITTING
MANUAL VOLUME DAMPER
FIRE DAMPER IN DUCT, W/ ACCESS PANEL REQD.
COMBINATION FIRE/SMOKE DAMPER W/ ACCESS PANEL
SMOKE DAMPER W/ ACCESS PANEL
ATC DAMPER
ACCESS PANEL IN DUCT OR PLENUM
HEATING OR COOLING COIL IN DUCT
SINGLE DUCT AIR TERMINAL BOX VARIABLE ORCONSTANT VOLUME. MIN. 1-1/2 TERMINAL INLETSIZE STRAIGHT DUCT AT TERMINAL INLET.
LATERAL STRAINER WITH BLOW-OFF VALVE,PROVIDE HOSE END WITH CAP WHERE DISCHARGEIS NOT PIPED TO DRAIN
SHUT OFF VALVE
BALL VALVE
BUTTERFLY VALVE
MOTOR OPERATED BUTTERFLY VALVE
GATE VALVE - NON RISING STEM
PLUG VALVE
ATC - 2 WAY VALVE
ATC - 3 WAY VALVE
F&T=FLOAT & THERMOSTATIC
VENTURI FLOW METER
FLOW METER ORIFICE
PRESSURE SWITCH
TEMPERATURE AND PRESSURETEST PORT
THERMOMETER WELL
THERMOMETER - TEMP RANGE AS INDICATED
PRESSURE GAUGE WITHSHUT OFF PLUG VALVE
PRESSURE GAUGE WITH PIGTAIL
UNION
FLANGE
ECCENTRIC REDUCER
PIPE CAP
SHUT OFF PLUG VALVE FORFOR USE WITH PRESSURE GAUGE
LEADER INDICATES DOWNWORD SLOPE
FLEXIBLE EXPANSION JOINT
ALIGNMENT GUIDE
ANCHOR
VTR
WATER HAMMER ARRESTOR
VENT THRU ROOF
CLEAN-OUT
INLINE PUMP
FAN
INLINE PUMP
ICW
IHW
ISCW
IHWR
INDUSTRIAL SOFT COLD WATER
INDUSTRIAL HOT WATER RETURN
INDUSTRIAL HOT WATER
INDUSTRIAL COLD WATER
LW
LWR
LAB WATER
LAB WATER RETURN
TW
TWR TEMPERED WATER RETURN
TEMPERED WATER
FVS FLUSH VALVE SUPPLY
PC
OR
OR
OR
OR
OR
OR
OR
OR
OR
OR
OR
OR
OR
OR
OR
OR
OR
OR
OR
OR
RE
GIS
TER
E
DPROFESSIONA
L
EN
GIN
EE
R
No. 187737
S
TA
T E OF UTAH
JEFFREY S.
WATKINS
11.20.2018
W W W . V B F A . C O M
ASSOCIATES, INC.
VAN BOERUM& FRANK
801.530.3148 T
801.530.3150 F
CONSULTING ENGINEERS
330 South 300 East
Salt Lake City, UT 84111
Salt Lake City▪ Logan ▪ St. George ▪ Tempe
VBFA Project Number: 18532
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/20/2
01
8 8
:30
:32
AM
MECHANICALSYMBOLSANDLEGEND
KJM
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
409
5
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
M000
JSW
# Date Revision
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
MECHANICAL GENERAL NOTES
1. COORDINATE EXACT PLACEMENT OF DIFFUSERS, GRILLES, AND REGISTERS WITH ARCHITECTURAL REFLECTED CEILING PLAN, TYPICAL.
2. SEE DETAIL FOR DIFFUSER CONNECTIONS TO DUCTWORK, TYPICAL.
3. BRANCH DUCTWORK SHALL BE SIZED TO MATCH THE NECK INLET SIZE OF THE DIFFUSERS, REGISTER OR GRILLE IT SERVES UNLESS NOTED OTHERWISE, TYPICAL.
4. COORDINATE EXACT MOUNTING LOCATION OF ALL THERMOSTATS WITH LATEST REVISION OF ARCHITECTURAL ELEVATION AND FURNISHINGS PLANS, TYPICAL.
5. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR CAULKING AND SEALING ALL PENETRATIONS IN FIRE AND SMOKE RATED PARTITIONS TO MAINTAIN RATINGS. SEE SPECIFICATION, TYPICAL.
6. THE MECHANICAL CONTRACTOR SHALL PROVIDE FIRE, SMOKE OR COMBINATION FIRE/SMOKE DAMPERS AT ALL LOCATIONS SHOWN ON THE CONTRACT DOCUMENTS AND AS REQUIRED TO MEET THE INTEGRITY OF ALL SMOKE AND FIRE PARTITIONS. THE CONTRACTOR SHALL REFER TO THE LATEST ARCHITECTURAL LIFE SAFETY PLANS FOR ALL FIRE AND SMOKE PARTITION LOCATIONS. DAMPERS ARE TO BE PROVIDED WITH SHUTOFF/TEST SWITCH AT EACH LOCATION.
7. PROVIDE AND INSTALL TURNING VANES IN ALL SQUARE LOW PRESSURE DUCTWORK AT ELBOWS OR TEES, TYPICAL.
8. INSTALL ALL TERMINAL BOXES IN EASILY ACCESSIBLE AND SERVICEABLE LOCATIONS, MEETING ALL MANUFACTURERS REQUIRED CLEARANCES ON EACH SIDE, SEE DETAILS, TYPICAL.
9. CONTRACTOR SHALL OFF-SET, TRANSITION AND PROVIDE CHANGES AS REQUIRED FOR COORDINATION WITH OTHER TRADES, TYPICAL.
10. DUCTWORK SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS. REFER TO MECHANICAL SPECIFICATIONS FOR EXTENT OF DUCT INSULATION AND LINER.
11. PROVIDE AND INSTALL REMOTE DAMPER OPERATORS FOR ALL DAMPERS INSTALLED ABOVE INACCESSIBLE CEILINGS, SEE MECHANICAL SPECIFICATIONS FOR EQUIPMENT REQUIREMENTS, TYPICAL.
12. PROVIDE AND INSTALL HIGH EFFICIENCY TAKE-OFF FITTINGS AND BALANCING DAMPER AT ALL BRANCH CONNECTIONS TO LOW PRESSURE DUCTWORK.
13. PROVIDE AND INSTALL HIGH EFFICIENCY OR CONICAL TAKE-OFFS AT ALL BRANCH CONNECTIONS TO MEDIUM PRESSURE DUCTWORK.
14. WHERE DUCTWORK CROSSES, SUPPLY DUCTWORK IS USUALLY BELOW RETURN AND EXHAUST DUCT. RETURN DUCTWORK IS USUALLY BELOW EXHAUST DUCTS.
15. AT LOCATIONS WHERE DIFFUSERS OR GRILLES ARE UNDER DUCTWORK, CONTRACTOR TO FABRICATE TRANSITION BOOT FROM FLEX CONNECTION TO DIFFUSER OR GRILLE WITH BALANCING DAMPER, TYPICAL.
16. THE MECHANICAL CONTRACTOR SHALL PROVIDE CEILING MOUNTED ACCESS DOORS FOR ALL FIRE, SMOKE AND COMBINATION FIRE/SMOKE DAMPERS INSTALLED ABOVE INACCESSIBLE CEILING. FIELD VERIFY EXACT INSTALLATION LOCATIONS PRIOR TO COMMENCING WORK AND COORDINATE INSTALLATIONS WITH LATEST ARCHITECTURAL REFLECTED CEILING PLANS.
17. MECHANICAL CONTRACTOR SHALL ENSURE THAT ALL EQUIPMENT IS PROVIDED AND INSTALLED WITH CLEARANCES PER MANUFACTURERS RECOMMENDATIONS. THE CONTRACTOR SHALL MAINTAIN PROPER SERVICE SPACE FOR COIL PULLS, BAS DEVICES, MAINTENANCE ACCESS, ETC.
18. ALL VAV BOXES TO HAVE REHEAT COILS, EXCEPT AS NOTED. PROVIDE A MINIMUM OF TWO DUCT DIAMETERS OF STRAIGHT ROUND DUCT TO INLET OF VAV BOX. BOX SHALL BE HARD CONNECTED (CONICAL) TO MEDIUM PRESSURE DUCT, TYPICAL.
19. PROVIDE ACCESS DOORS TO ACCESS VAV BOX CONTROLS ABOVE HARD CEILINGS. PROVIDE MIN. 24" X 24".
20. ALL PIPE AND DUCT SIZES SHALL REMAIN THE SAME SIZE SHOWN, IN THE DIRECTION OF FLOW, UNTIL SHOWN OTHERWISE.
21. ALL DUCTWORK ABOVE HARD CEILINGS SHALL BE EXTENDED ALL THE WAY TO THE SUPPLY DIFFUSERS, RETURN GRILLS OR EXHAUST GRILLS WHETHER OR NOT HARD DUCT OR FLEX DUCT IS SHOWN ON PLANS. FLEX DUCT WILL NOT BE ALLOWED TO DIFFUSERS OR GRILLS ABOVE HARD CEILINGS. FLEX DUCT WILL BE REQUIRED IN AREAS ABOVE T-BAR CEILINGS.
22. NEW DUCTWORK, PIPING AND EQUIPMENT SHALL BE COORDINATED WITH STRUCTURE, LIGHTS, REFLECTED CEILING PLANS, CABLE TRAY, ELECTRICAL CONDUIT, PLUMBING, MECHANICAL AND FIRE PROTECTION PIPING, MEDICAL GASES, ALL OTHER TRADES AND ALL OTHER EXISTING CONDITIONS.
23. THE CONTRACTOR SHALL INFORM THE DESIGNER OF ANY PROPOSED DEVIATIONS FROM THE CONTRACT DOCUMENTS.
24. PROVIDE ACCESS TO ALL TEMPERATURE CONTROLS ABOVE CEILING. LOCATE IN ACCESSIBLE LOCATION. WHERE THERE ARE HARD CEILINGS THE CONTRACTOR SHALL PROVIDE 24"X24" ACCESS DOOR.
PLUMBING GENERAL NOTES
1. UNLESS OTHERWISE NOTED, SLOPE PIPE AS FOLLOWS: WASTE BRANCHES: 1/4" PER FOOT; WASTE MAINS: 1/4" PER FOOT; ROOF DRAIN/ROOF DRAIN OVERFLOW: 1/8" PER FOOT.
2. ALL WORK DONE SHALL BE PERFORMED WITH WATER CONTROL IN MIND. CONTAINMENT OF WATER IS NECESSARY TO PREVENT WATER FROM DAMAGING AREAS ON FLOORS BELOW.
3. PLUMBING DRAWINGS ARE SCHEMATIC IN NATURE. FIELD VERIFY EXACT PIPE ROUTING AND COORDINATE WITH ALL OTHER TRADES.
4. ALL PIPING IN PLUMBING CHASES SHALL BE ARRANGED TO ALLOW MAINTENANCE ACCESS.
5. NO PIPING TO RUN OVER ELECTRICAL PANELS, VFD'S OR MCC'S. PROTECT EQUIPMENT WITH A 42" DEEP ZONE IN FRONT OF PANELS, VFD'S, AND MCC'S.
6. COORDINATE FAN ROOM FLOOR DRAIN AND FLOOR SINK LOCATIONS WITH COOLING COIL, EVAPORATIVE SECTION, AND HEATING COIL LOCATIONS.
7. CONTRACTOR TO PROVIDE VALVE IDENTIFICATION AND LOCATION ON ALL CEILING TILES WHERE VALVES ARE LOCATED.
8. PIPING AND ROUTING SHOWN, INCLUDING ALL BELOW FLOOR DECK PIPING, IS APPROXIMATE. IT IS UP TO THE CONTRACTOR TO FIELD VERIFY THE EXACT LOCATION AND SIZE OF ALL PIPING.
9. REFER TO ARCHITECTURAL DRAWINGS FOR FIXTURE MOUNTING HEIGHTS, DIMENSIONS, AND OTHER REQUIREMENTS.
10. CONTRACTOR TO VERIFY CONNECTION SIDE OF ADA FIXTURES AND ADJUST ACCORDINGLY. INSTALL FLUSH VALVES HANDLES ON WIDE SIDE OF ALL FIXTURES.
11. LOCATE ALL VENTS MINIMUM 25' AWAY FROM AIR INTAKES.
12. INSTALL ALL DOMESTIC WATER LINES BELOW DUCTWORK.
13. INSTALL A 24" X 24" ACCESS DOOR BELOW ALL ISOLATION VALVES, BALANCING VALVES AND WATER HAMMER ARRESTORS WHERE MOUNTED ABOVE HARD CEILINGS.
14. MOUNT ALL ISOLATION VALVES, CONTROL VALVES, BALANCING VALVES, ETC. NEAR CEILING HEIGHT FOR ACCESSIBILITY.
15. INSTALL ALL EQUIPMENT WITH SUFFICIENT CLEARANCE FOR MAINTENANCE PER MANUFACTURERS RECOMMENDATION.
16. COORDINATE ALL FLOOR PENETRATIONS WITH STRUCTURAL AND PROVIDE SLEEVES AS NECESSARY.
17. COORDINATE EXACT LOCATION OF PLUMBING WITH STRUCTURAL MEMBERS, LIGHTS, REFLECTED CEILING, CABLE TRAY, DUCTWORK, MECHANICAL PIPING, MEDICAL GASES, FIRE PROTECTION AND OTHER TRADES, TYPICAL.
18. COORDINATE THE LOCATION OF THE FLOOR DRAIN, SHOWER DRAIN, OR FLOOR SINK WITH ARCHITECTURAL AND STRUCTURAL, TYPICAL.
19. ACCESS DOORS SHALL BE PROVIDED TO ALL WATER HAMMER ARRESTORS IN WALLS OR ABOVE CEILINGS.
20. SEE PLUMBING FIXTURE SCHEDULE FOR PIPE SIZES OF WASTE, VENT AND DOMESTIC WATER TO/FROM SINGLE FIXTURE.
21. HOSE BIBBS SHOWN AT LAVATORIES ARE TO BE MOUNTED AT AN ACCESSIBLE LOCATION UNDER THE LAVATORY.
22. COORDINATE EXACT LOCATION OF PLUMBING PIPING WITH STRUCTURAL MEMBERS, LIGHTS, REFLECTED CEILING PLANS, CABLE TRAY,ELECTRICAL CONDUITS, DUCTWORK, MECHANICAL AND FIRE PROTECTION PIPING, AND ALL OTHER TRADES AND ALL EXISTING CONDITIONS.
23. LOCATE CIRCUIT SETTERS, VALVES, WATER HAMMER ARRESTORS, ETC. IN ACCESSIBLE LOCATIONS. PROVIDE 24"X24" ACCESS PANEL WHERE ITEM IS LOCATED ABOVE A HARD CEILING.
24. ALL PIPE AND DUCT SIZES SHALL REMAIN THE SAME SIZE SHOWN, IN THE DIRECTION OF FLOW, UNTIL SHOWN OTHERWISE.
25. INSTALL CLEANOUTS IN DRAIN PIPING AS INDICATED, AND WHERE NOT INDICATED, ACCORDING TO THE FOLLOWING.
a) SIZE SAME AS DRAINAGE PIPING UP TO 4" NPS. USE 4" NPS FOR LARGER. DRAINAGE PIPING UNLESS LARGER CLEANOUT IS
INDICATED.
b) LOCATE AT MINIMUM INTERVALS OF 50 FT FOR PIPING 4" NPS AND SMALLER AND 100 FT FOR LARGER PIPING.
c) LOCATE AT THE BASE OF EACH VERTICAL STACK.
RE
GIS
TER
E
DPROFESSIONA
L
EN
GIN
EE
R
No. 187737
S
TA
T E OF UTAH
JEFFREY S.
WATKINS
11.20.2018
W W W . V B F A . C O M
ASSOCIATES, INC.
VAN BOERUM& FRANK
801.530.3148 T
801.530.3150 F
CONSULTING ENGINEERS
330 South 300 East
Salt Lake City, UT 84111
Salt Lake City▪ Logan ▪ St. George ▪ Tempe
VBFA Project Number: 18532
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/20/2
01
8 8
:30
:33
AM
MECHANICALGENERALNOTES
KJM
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
409
5
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
M001
JSW
# Date Revision
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
MEN'S TOILETS
S101
WOMEN'S TOILETS
S102
SHOWER ROOM
S106
MECH ROOM / CHASE
S107
SHOWER ROOM (ADA)
S103
SHOWER ROOM
S104
SHOWER ROOM
S105
K L
8
9
10
10ø CD-1175
10ø CD-1190
10ø CD-1185
6ø CD-155
6ø CD-145
6ø CD-145
6ø CD-175
6/6 EG-170
6/6 EG-160
6/6 EG-160
6/6 EG-190
10/10 EG-1200
10/10 EG-1190
10/10 EG-1205
ERV
1
14
/12
S.A
.
10/10 S.A.
10
/10
S.A
.
10/10 S.A.
10/10 E.A.
10
/10
E.A
.
8/8 E.A. 8/8 E.A.
16
/12
E.A
.
6/6 E.A. 6/6 E.A.
CU
1
14/12 S.A. UP
16/12 E.A. UP
12
3
10ø S.A. 10ø S.A.
DXC
1
EHC
14
T5
WH
1
RE
GIS
TER
E
DPROFESSIONA
L
EN
GIN
EE
R
No. 187737
S
TA
T E OF UTAH
JEFFREY S.
WATKINS
11.20.2018
W W W . V B F A . C O M
ASSOCIATES, INC.
VAN BOERUM& FRANK
801.530.3148 T
801.530.3150 F
CONSULTING ENGINEERS
330 South 300 East
Salt Lake City, UT 84111
Salt Lake City▪ Logan ▪ St. George ▪ Tempe
VBFA Project Number: 18532
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/20/2
01
8 8
:30
:35
AM
MECHANICALPLAN
KJM
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
409
5
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
M101
JSW
3/8" = 1'-0"M101
1 MECHANICAL PLAN
KEYED NOTES
1. INSTALL THE ERV UNIT ON A SLOPED CURB ON THE ROOF ABOVE. THE UNIT IS TO BE LEVEL WHEN IN OPERATION. POSITION THE UNIT SO THE OUTSIDE AIR AND EXHAUST AIR DUCTWORK CAN BE ROUTED INTO THE CEILING SPACE WHILE DISRUPTING THE ROOF FRAMING AS LITTLE AS POSSIBLE.
2. INSTALL THE CONDENSING UNIT ON AN OVERBUILD FLAT PLATFORM ON THE ROOF. REFER TO STRUCTURAL DRAWINGS FOR DETAILS ON THE OVERBUILD FLAT PLATFORM. PROVIDE 3/8" LIQUID AND 3/4" SUCTION REFRIGERANT PIPING BETWEEN THIS OUTDOOR UNIT AND THE INDOOR DUCT DX COIL. PROVIDE A WEATHER PROTECTION ENCLOSURE FOR ALL EXPOSED REFRIGERANT PIPING. WEATHER PROOF ALL ROOF PENETRATIONS.
3. INSTALL THE INDOOR DUCT-MOUNTED DX COOLING COIL IN THE OUTDOOR AIR DUCTWORK IN APPROXIMATELY THIS LOCATION. PROVIDE A 24" x 24" ACCESS PANEL THROUGH THE CEILING BELOW THE DUCT-MOUNTED COIL.
4. INSTALL THE INDOOR DUCT-MOUNTED ELECTRIC HEATING COIL IN THE OUTDOOR AIR DUCTWORK IN APPROXIMATELY THIS LOCATION. PROVIDE A 24" x 24" ACCESS PANEL THROUGH THE CEILING BELOW THE DUCT-MOUNTED COIL.
5. INSTALL A THERMOSTAT ON THE WALL IN THE WOMEN'S RESTROOM. THIS THERMOSTAT IS TO CONTROL THE ERV UNIT, THE OUTDOOR CONDENSING UNIT, THE DUCT-MOUNTED ELECTRIC HEATING COIL, AND THE DUCT-MOUNTED DX COOLING COIL.
# Date Revision
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
RE
GIS
TER
E
DPROFESSIONA
L
EN
GIN
EE
R
No. 187737
S
TA
T E OF UTAH
JEFFREY S.
WATKINS
11.20.2018
W W W . V B F A . C O M
ASSOCIATES, INC.
VAN BOERUM& FRANK
801.530.3148 T
801.530.3150 F
CONSULTING ENGINEERS
330 South 300 East
Salt Lake City, UT 84111
Salt Lake City▪ Logan ▪ St. George ▪ Tempe
VBFA Project Number: 18532
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/20/2
01
8 8
:30
:38
AM
MECHANICALDETAILS
KJM
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
409
5
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
M501
JSW
# Date Revision
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
RE
GIS
TER
E
DPROFESSIONA
L
EN
GIN
EE
R
No. 187737
S
TA
T E OF UTAH
JEFFREY S.
WATKINS
11.20.2018
W W W . V B F A . C O M
ASSOCIATES, INC.
VAN BOERUM& FRANK
801.530.3148 T
801.530.3150 F
CONSULTING ENGINEERS
330 South 300 East
Salt Lake City, UT 84111
Salt Lake City▪ Logan ▪ St. George ▪ Tempe
VBFA Project Number: 18532
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/20/2
01
8 8
:30
:40
AM
MECHANICALDETAILS
KJM
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
409
5
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
M502
JSW
# Date Revision
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
RE
GIS
TER
E
DPROFESSIONA
L
EN
GIN
EE
R
No. 187737
S
TA
T E OF UTAH
JEFFREY S.
WATKINS
11.20.2018
W W W . V B F A . C O M
ASSOCIATES, INC.
VAN BOERUM& FRANK
801.530.3148 T
801.530.3150 F
CONSULTING ENGINEERS
330 South 300 East
Salt Lake City, UT 84111
Salt Lake City▪ Logan ▪ St. George ▪ Tempe
VBFA Project Number: 18532
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/20/2
01
8 8
:30
:42
AM
MECHANICALDETAILS
KJM
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
409
5
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
M503
JSW
# Date Revision
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
RE
GIS
TER
E
DPROFESSIONA
L
EN
GIN
EE
R
No. 187737
S
TA
T E OF UTAH
JEFFREY S.
WATKINS
11.20.2018
W W W . V B F A . C O M
ASSOCIATES, INC.
VAN BOERUM& FRANK
801.530.3148 T
801.530.3150 F
CONSULTING ENGINEERS
330 South 300 East
Salt Lake City, UT 84111
Salt Lake City▪ Logan ▪ St. George ▪ Tempe
VBFA Project Number: 18532
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/20/2
01
8 8
:30
:44
AM
MECHANICALDETAILS
KJM
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
409
5
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
M504
JSW
# Date Revision
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
RE
GIS
TER
E
DPROFESSIONA
L
EN
GIN
EE
R
No. 187737
S
TA
T E OF UTAH
JEFFREY S.
WATKINS
11.20.2018
W W W . V B F A . C O M
ASSOCIATES, INC.
VAN BOERUM& FRANK
801.530.3148 T
801.530.3150 F
CONSULTING ENGINEERS
330 South 300 East
Salt Lake City, UT 84111
Salt Lake City▪ Logan ▪ St. George ▪ Tempe
VBFA Project Number: 18532
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/20/2
01
8 8
:30
:45
AM
MECHANICALDETAILS
KJM
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
409
5
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
M505
JSW
# Date Revision
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
RE
GIS
TER
E
DPROFESSIONA
L
EN
GIN
EE
R
No. 187737
S
TA
T E OF UTAH
JEFFREY S.
WATKINS
11.20.2018
W W W . V B F A . C O M
ASSOCIATES, INC.
VAN BOERUM& FRANK
801.530.3148 T
801.530.3150 F
CONSULTING ENGINEERS
330 South 300 East
Salt Lake City, UT 84111
Salt Lake City▪ Logan ▪ St. George ▪ Tempe
VBFA Project Number: 18532
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/20/2
01
8 8
:30
:48
AM
MECHANICALDETAILS
KJM
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
409
5
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
M506
JSW
# Date Revision
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
RE
GIS
TER
E
DPROFESSIONA
L
EN
GIN
EE
R
No. 187737
S
TA
T E OF UTAH
JEFFREY S.
WATKINS
11.20.2018
W W W . V B F A . C O M
ASSOCIATES, INC.
VAN BOERUM& FRANK
801.530.3148 T
801.530.3150 F
CONSULTING ENGINEERS
330 South 300 East
Salt Lake City, UT 84111
Salt Lake City▪ Logan ▪ St. George ▪ Tempe
VBFA Project Number: 18532
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/20/2
01
8 8
:30
:49
AM
MECHANICALSCHEDULES
KJM
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
409
5
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
M601
JSW
# Date Revision
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
MEN'S TOILETS
S101
WOMEN'S TOILETS
S102
SHOWER ROOM
S106
MECH ROOM / CHASE
S107
SHOWER ROOM (ADA)
S103
SHOWER ROOM
S104
SHOWER ROOM
S105
K L
8
9
10
DXC
1
WC-1
U-1
WC-2 WC-1 WC-1
WC-2
WC-2
SH-2
L-1
L-1L-1
L-1
SH-1
SH-1 SH-1
SS-1
L-1 L-1
EWC-1
L-1 L-1
WH
1
2" DCW
NFH-1
HY-1
2" DCW 1 1/2" DCW
1" DCW
1 1/2" DCW
1 1/4" DCW
3/4" DCW
1 1/4" DHW
1" DHW
1" DHW
1" DCW
3/4" DHW
GPM1.0
3/4" DCW
NFH-1
1
2
3
4 DET
1
RCP
1
1" DCW
1 1/4" DCW
1 1/4" DHW
3/4" DCW3/4" DHW 3/4" DCW
HB-1 HB-1
3/4" DCW1/2" DCW 1/2" DCW
RE
GIS
TER
E
DPROFESSIONA
L
EN
GIN
EE
R
No. 187737
S
TA
T E OF UTAH
JEFFREY S.
WATKINS
11.20.2018
W W W . V B F A . C O M
ASSOCIATES, INC.
VAN BOERUM& FRANK
801.530.3148 T
801.530.3150 F
CONSULTING ENGINEERS
330 South 300 East
Salt Lake City, UT 84111
Salt Lake City▪ Logan ▪ St. George ▪ Tempe
VBFA Project Number: 18532
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/20/2
01
8 8
:30
:52
AM
PLUMBINGSUPPLYPLAN
KJM
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
409
5
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
P101
JSW
3/8" = 1'-0"P101
1 PLUMBING SUPPLY PLAN
KEYED NOTES
1. CONNECT THIS NEW 2" DOMESTIC COLD WATER PIPING TO THE EXISTING 2" DOMESTIC COLD WATER PIPING RUNNING UNDERGROUND BETWEEN THE MAIN EQUESTRIAN ARENA AND THE SHOW BARN APPROXIMATELY 170 FEET TO THE SOUTHEAST. FIELD VERIFY THE EXACT TIE-IN LOCATION.
2. RAISE THE NEW DOMESTIC COLD WATER PIPING UP THROUGH THE MECHANICAL FLOOR IN APPROXIMATELY THIS LOCATION.
3. PROVIDE PRESSURE REDUCING WATER HEADER PIPING IN THIS LOCATION. REFER TO DETAIL 2 ON SHEET M501 FOR ADDITIONAL INFORMATION.
4. REFER TO DETAIL 8 ON SHEET M502 FOR ADDITIONAL INFORMATION ABOUT THE PIPING AND FITTINGS REQUIRED FOR THE WATER HEATER.
# Date Revision
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
K L
8
9
10
FD-2
SS-1
WH
1
U-1
3" W
4" W
4" W
L-1 L-1
FD-1
WC-1WC-2
EWC-1
4" W
2" W
FD-1
L-1
2" V
2" W 2" W 4" W 4" W
2" V
MEN'S TOILETS
S101
WOMEN'S TOILETS
S102
SHOWER ROOM
S106
MECH ROOM / CHASE
S107
SHOWER ROOM (ADA)
S103
SHOWER ROOM
S104
SHOWER ROOM
S105
2" V
3" V 2" V
2" V
3" V VTR
2" V
3" V
4" W
DXC
1
L-1 L-1
FD-1
WC-1 WC-1 WC-2
WC-2
L-1
L-1L-1
1
23
FCO
FCO
FCO
FD-3
FD-3 FD-3
FD-3
FD-1
FD-1 FD-1
2" V
2" V
RE
GIS
TER
E
DPROFESSIONA
L
EN
GIN
EE
R
No. 187737
S
TA
T E OF UTAH
JEFFREY S.
WATKINS
11.20.2018
W W W . V B F A . C O M
ASSOCIATES, INC.
VAN BOERUM& FRANK
801.530.3148 T
801.530.3150 F
CONSULTING ENGINEERS
330 South 300 East
Salt Lake City, UT 84111
Salt Lake City▪ Logan ▪ St. George ▪ Tempe
VBFA Project Number: 18532
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/20/2
01
8 8
:30
:54
AM
PLUMBINGDRAIN &VENT PLAN
KJM
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
409
5
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
P102
JSW
3/8" = 1'-0"P102
1 PLUMBING DRAIN & VENT PLAN
KEYED NOTES
1. CONNECT THIS NEW 4" SANITARY SEWER PIPING INTO THE EXISTING 6" SANITARY SEWER PIPING THAT IS JUST OFF THIS CORNER OF THE EXISTING BUILDING. FIELD VERIFY THE EXACT TIE-IN LOCATION.
2. CONNECT A 3/4" CONDENSATE DRAIN PIPE INTO THE DRIP PAN OF THE DX COOLING COIL IN THIS LOCATION.
3. DROP THE 3/4" CONDENSATE DRAIN PIPE DOWN INSIDE THE WALL IN THIS LOCATION AND COME OUT JUST ABOVE THE SERVICE SINK SO IT CAN DRAIN INTO IT.
# Date Revision
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
RE
GIS
TER
E
DPROFESSIONA
L
EN
GIN
EE
R
No. 187737
S
TA
T E OF UTAH
JEFFREY S.
WATKINS
11.20.2018
W W W . V B F A . C O M
ASSOCIATES, INC.
VAN BOERUM& FRANK
801.530.3148 T
801.530.3150 F
CONSULTING ENGINEERS
330 South 300 East
Salt Lake City, UT 84111
Salt Lake City▪ Logan ▪ St. George ▪ Tempe
VBFA Project Number: 18532
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
11
/20/2
01
8 8
:30
:55
AM
PLUMBINGSCHEDULES
KJM
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
409
5
SA
LT
LA
KE
CO
UN
TY
18142
11.20.2018
EQ
UE
ST
RIA
N C
EN
TE
R A
DD
ITIO
N
PERMIT SET
P601
JSW
# Date Revision
21
00
WE
ST
11
40
0 S
OU
TH
, S
OU
TH
JO
RD
AN
, U
TA
H 8
40
95
SA
LT
LA
KE
CO
UN
TY
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
TYPICAL ROUGH-IN DETAIL
NOTES:
1. IN ACCORDANCE W/ IBC 711.3.2, OUTLETS ON OPPOSITE SIDES OF FIRERATED WALLS OR PARTITIONS IN THE SAME STUD SPACE MUST BESEPARATED BY MIN. OF 24" HORIZONTAL DISTANCE.
1. TYP. FOR WOOD & METAL STUD ROUGH-IN.
2. PLASTER RINGS NOT SHOWN.
3. LOCATE ALL OUTLET BOXES IN ACCORDANCE W/ ARCH.& MECH. DWGS., AND W/ ALL APPLICABLE SHOP DWGS
TYPICAL DUPLEXOUTLET BOX
TYPICAL SWITCHOUTLET BOX
BAR STRAPS
BARSTRAPS
PROVIDE CONDUIT SUPPORTS INACCORDANCE W/ NEC SPACINGREQUIREMENTS FOR THE TYPE OFRACEWAY REQUIRED
AS REQUIRED FOR TYPE OFCONSTRUCTION
STEEL CITY NO.7501 BOX SUPPOR
A
B
NOTES:1. THE CONTRACTOR MUST COORDI NATE EXACT LOCATI ON OF THE DI SCONNECT WI TH THE MECHANI CALCONTRACTOR TO ELIMI NATE ANY OBSTACLE ( PIPE,CONCRETE PAD ETC.) IN FRONT OF THE DI SCONNECT. I FTHERE ARE ANY OBSTACLES, PROVI DE UNISTRUT AND INSTALL THE DI SCONNECT NEXT TO MECHANI CALEQUI PMENT IN ORDER TO PROVIDE THE REQUI RED CLEARANCE.
2. PROVIDE MI NI MUM CLEARANCE AS FOLLOWS:
SYSTEM VOLTAGE480
208
A B42"
36" 30"30"
DI SCONNECTSWI TCH
FLEXIBLE LIQUI DTI GHT METALLI CCONDUI T
MECHANI CALEQUI PMENTTYPICAL
CLEAREDSPACE
TYPICAL DISCONNECT CLEARANCE REQUIREMENTS
NOTE:TYPI CAL DETAI LS SHOWI NG GENERAL FI RESTOPPI NG PROCEDURE. ACTUAL PROCEDUREDEPENDS UPON ANNUL AR SPACE BETWEENPI PE AND/OR I NSULATI ON AND OPENI NG.FOLLOW MANUFACTURER' S I NSTRUCTI ONS.
DAMMI NG MATERI AL ( BACKER ROD,FI BERGLASS OR MI NERAL WOOL)
3M FI RE BARRI ERCP 25WB CAULKFI RE RATED CONCRETE
FLOOR SLAB
CONDUI T ORINSULATED CABLES
TYPICAL FIRESTOP FOR CABLES/CONDUITTHROUGH CONCRETE FLOORING
NOTE:TYPI CAL DETAI LS SHOWI NG GENERAL FI RESTOPPI NG PROCEDURE. ACTUAL PROCEDUREDEPENDS UPON ANNUL AR SPACE BETWEENPI PE AND/OR I NSULATI ON AND OPENI NG.FOLLOW MANUFACTURER' S I NSTRUCTI ONS.
CP 25WB CAULK ONBOTH SI DES OF WALL
INSULATED CABLES OR CONDUI T
FI RE RATED CONCRETE/ CONCRETEBLOCK WALL
DAMMI NG MATERI AL(BACKER ROD,FI BER-GLASSOR MI NERAL WOOL)
NON-METALLI C SLEEVE MAYEXTEND A MAX 2" ( 51 mm)BEYOND THE WALL SURFACE
TYPICAL FIRESTOP FOR CABLES/CONDUITTHROUGH CONCRETE WALLS
NOTE:1. TYPICAL DETAILS SHOWING GENERAL FIRESTOPPING PROCEDURE. ACTUAL PROCEDUREDEPENDS UPON ANNULAR SPACE BETWEENPIPE AND/OR INSULATION AND OPENING.FOLLOW MANUFACTURER'S INSTRUCTIONS.
1/4" MINIMUM DIAMETERBEAD OF 3M FIRE BARRIER CP25 CAULK OR MP MOLDABLEPUTTY
METALLICCONDUIT
1/4" MINIMUM DIAMETERBEAD OF 3M FIRE BARRIERCP 25 CAULK OR MPMOLDABLE PUTTY
1 OR 2 HOUR FIRE RATEDGYPSUM WALL BOARD
WOOD OR STEEL STUD
FIRESTOP FOR METAL CONDUITTHROUGH GYPSUM WALL BOARD
PULL
FIRE
WALL MOUNTED OCCUPANCY SENSOR:1. TO BE DUAL TECHNOLOGY2. TO HAVE TWO LEVEL SWITCHING. SWITCH "a"
INDICATED ON THE DRAWING SHALL BE OCCUPANCYSENSOR AND SWITCH "b" SHALL BE MANUAL ON.
3. TO HAVE BUILT IN PHOTO CELL4. TO HAVE MANUAL ON/OFF BUTTONS5. FOR SMALLER ROOMS (UP TO 300SF) SET TIME DELAY
TO 15 MINUTES AND SENSITIVITY TO MEDIUM. FORLARGER ROOMS (GREATER THAN 300SF) SET TIMEDELAY TO 25 MINUTES AND SENSITIVITY TO HIGH.
6. ONE CIRCUIT TO BE AUTO ON (TURN ON WHENLIGHT LEVEL IS LESS THAN 30FC) AND SECONDCIRCUIT TO BE MANUAL ON
7. TO BE RATED FOR 120/277 VOLT8. TO BE RATED FOR THE LOAD IT IS TIED TO9. REFER TO MANUFACTURERS WIRING DIAGRAM10. RE-PROGRAMMING OF OCCUPANCY SENSORS MAY BE
REQUIRED TO MEET OWNERS NEED11. TO HAVE BUILT-IN ADJUSTABLE SCREEN SO THE
SENSOR DOESN'T DETECT MOVEMENT OUTSIDETHE ROOM. ADJUST THE SENSOR FOR EACH ROOM.
12. APPROVED MANUFACTURERS: WATTSTOPPER, ACUITY, DOUGLAS, COOPER, LUTRON,LEVITON
SECONDARYLOAD
PRIMARYLOAD
LINE 1
LINE 2
NEUTRAL WHITE
NEUTRAL
NEUTRAL
GROUND GREEN
TWO CIRCUIT WIRING
WHITE
WHITE
CEILING MOUNTED OCCUPANCY SENSOR:1. TO BE DUAL TECHNOLOGY2. FOR SMALLER ROOMS (UP TO 300SF) SET TIME
DELAY TO 15 MINUTES AND SENSITIVITY TO MEDIUM.FOR LARGER ROOMS (GREATER THAN 300SF) SETTIME DELAY TO 25 MINUTES AND SENSITIVITY TOHIGH.
3. PROVIDE PROPER POWER PACK FOR THELOAD
4. SUPPLIER IS TO SUBMIT LAYOUT ANDPLACEMENT OF THE SENSORS TO PROVIDE A100% COVERAGE IN THE SPACE. PROVIDEADDITIONAL SENSORS AS NECESSARY FOR ATROUBLE FREE OPERATION.
5. REFER TO MANUFACTURERS WIRINGDIAGRAM
6. APPROVED MANUFACTURERS: WATTSTOPPER, ACUITY, DOUGLAS, COOPER, LUTRON,LEVITON
OCCUPANCY/VACANCY SENSOR DETAIL
LAST LIGHTFIXTURE OREQUIPMENT
LAST OUTLETOR EQUIPMENT
CIRCUIT LENGTH
(REFER TO THE CHART BELOW FOR WIRE SIZE,PROPERLY UPSIZE THE GROUND CONDUCTOR)UTILIZE THIS CHART FOR ALL 20 AMP CIRCUITSINCLUDING THREE PHASE EQUIPMENT)
MINIMUMCONDUCTOR SIZE
MAX CIRCUITLENGTH
(120 VOLT)
MAX CIRCUITLENGTH
(480 VOLT)
#12#10
#8#6
#4
75 FT
125 FT
205 FT
325 FT
440 FT
180 FT
260 FT
420 FT
660 FT900 FT
MAX CIRCUITLENGTH
(208 VOLT)
MAX CIRCUITLENGTH
(277 VOLT)
130 FT
215 FT
350 FT550 FT
750 FT
300 FT
500 FT
820 FT1300 FT
1600 FT
#3
#2
550 FT
660 FT
930 FT
1120 FT
1260 FT
1500 FT2200 FT
2600 FT
BRANCH PANEL
20A
BRANCH PANEL
20A
TYPICAL BRANCH CIRCUIT CONDUCTOR SIZE DETAIL(BASED ON DISTANCE AND VOLTAGE DROP)
36" FOR 208 V48" FOR 480 V
REQUIRED INDOOR INSTALLATIONSPACES FOR ELECTRICAL EQUIPMENT
WIDTH OF EQUIPMENT(MINIMUM 30")
HEIGHT OFEQUIPMENT
(6' MINIMUM)
6' OR CEILINGHEIGHT
EXHAUST DUCT
DEDICATEDELECTRICAL
SPACE
SPRINKLER ALLOWED
6 1/2 FT
WORKING SPACE
NOTES:1. THE WIDTH OF THE WORKING SPACE SHALL BE AT LEAST 30" OR THE WIDTH OF THE PANEL BOARD, WHICHEVER IS GREATER.
2. WORKING SPACE HEAD ROOM SHALL BE A MINIMUM OF 6.5'.3. THE MAXIMUM HEIGHT OF CIRCUIT BREAKERS/DISCONNECT SWITCH HANDLE SHALL NOT BE MORE THAN 6'6".
RECESSED TROFFER
FI XTURE CLAMP - PROVIDEONE PER SIDE OF EACHFI XTURE
LAY- I N GRI D SYSTEM
WI RE HANGER AT EACH CORNEROF FI XTURE ( TYP) INDEPENDENTOF CEI LI NG SUPPORT SYSTEM
TYPICAL RECESSED FIXTURE MOUNTING DETAIL
EXTERIOR PLYWOODOR BLOCK
EXTERIOR FINISHED MATERIAL
EXTERIOR FINISHED MATERIAL
ATTACH EXTERIOR BOXWITH SCREWS ATTHIS LOCATION (TYP. OF 4)
NOTES:1.RECESSED EXTERIOR BOX SHALL BE EQUAL TO ARLINGTON CAT #DSBVM1W-PAINTABLE. PROVIDE PROPER BOX FOR THE TYPE OF EXTERIOR BUILDING WALL MATERIAL.2.SEE MANUFACTURERS INSTALLATION INSTRUCTIONS.3.PAINT COVER TO MATCH EXTERIOR FINISH. COORDINATE WITH ARCHITECT.
EXTERIOR BUILDING MOUNTED OUTLET
OCCUPANCY SENSORREFER TO DETAIL D7/D7AFOR PRORAMMING
OCCUPANCY SENSOR LOCATION DETAIL
DOOR
ELEVATION
OFFICE
OCCUPANCY SENSORREFER TO DETAIL D7/D7AFOR PRORAMMING
LIGHT FIXTURE TO STAY ON AT NIGHT (NIGHT LIGHT). PROVIDE UNSWITCHED LIGHTING CIRCUIT.
LIGHT FIXTURE ON EMERGENCY POWER PROVIDE BATTERY AS REQUIRED
EXIT LIGHT. ARROWS SHOW EXIT DIRECTION
EMERGENCY BATTERY OPERATED LIGHT SINGLE OR TWIN BEAM
LIGHTING FIXTURE CALL OUT. NUMBER INDICATES A SUGGESTED QUANTITY- TO BE VERIFIED
REFERENCE NOTES CALL OUT
SINGLE POLE TOGGLE SWITCH - 20 AMP
SINGLE POLE TOGGLE SWITCH - 20 AMP LETTERS INDICATE SWITCH ASSIGNMENT
THREE WAY TOGGLE SWITCH - 20 AMP LETTERS INDICATE SWITCH ASSIGNMENT
SINGLE POLE PILOT SWITCH - 20 AMP, LETTER INDICATE SWITCH ASSIGNMENT
OVERRIDE SWITCH - 20 AMP
LOW PROFILE SLIDE DIMMER- SUITABLE FOR THE LOAD
LOW VOLTAGE BUTTON TO BE TIED TO LCP
DUPLEX CONVENIENCE OUTLET - 20 AMP
DUPLEX CONVENIENCE OUTLET - 20 AMP, GFCI PROTECTED.
RECESSED CLOCK-TYPE OUTLET - 20 AMP
DUPLEX CONVENIENCE OUTLET - 20 AMP ELECTRIC WATER COOLER
FOUR - PLEX CONVENIENCE OUTLET - 20 AMP
DUPLEX OUTLET WITH TWO BUILT IN USB PORTS. 20 AMP. EQUAL TO PASS AND SEYMOUR#5362USBSCBA*.
JUNCTION BOX - SIZE AND FUNCTION AS REQUIRED
EACH ARROW INDICATES A HOME RUN. RUN GROUND CONDUCTOR REGARDLESS OF CONDUIT TYPE.NUMBER OF CONDUCTORS AS REQUIRED
FUSED DISCONNECT SWITCH - SIZE AS REQUIRED-STANDARD HEIGHT TO BE 66" AFF TO THE TOP
FLUSH TELEPHONE, DATA OUTLET
FLUSH TELEPHONE OUTLET
FLUSH DATA OUTLET
MOTOR LOCATION
MECHANICAL EQUIPMENT CALL OUT
MANUAL DISCONNECT WITH THERMAL OVERLOAD PROTECTION
ELECTRICAL PANEL LOCATION
DUAL TECH WALL MOUNTED OCCUPANCY SENSOR TO CONTROL LIGHTING IN THE ROOM
TWO CIRCUIT, DUAL TECH WALL MOUNTED OCCUPANCY SENSOR TO CONTROL LIGHTING IN THE ROOM
DUAL TECH WALL MOUNTED OCCUPANCY SENSOR WITH BUILT IN 0-10V DIMMER AND PHOTOCELL TOCONTROL LIGHTING IN THE ROOM.PROVIDE SNAP ON COVER PLATE.
DUAL TECH CEILING MOUNTED OCCUPANCY SENSOR TO CONTROL LIGHTING IN THE ROOM
ELECTRICAL METER LOCATION
INDICATES WEATHER PROOF EQUIPMENT
INDICATES DEVICE IS ABOVE COUNTER TOP-42" AFF REFER TO ARCHITECTURAL ELEVATION
INDICATES DEVICES WITH LOW PROFILE WIRE GUARD. SUBMIT FOR APPROVAL
INDICATES DEVICES MOUNTED ON THE CEILING, COORDINATE LOCATION WITH THE ARCHITECT.
ABOVE CEILING. COORDINATE EXACT LOCATION.
DEDICATED OUTLET FOR PRINTER/FAX
HAND DRYER- COORDINATE LOCATION AND HEIGHT WITH ARCHITECT
DOOR OPENER-INSTALL AND WIRE CONTROL SWITCHES
DISPOSAL-PROVIDE WALL MOUNTED CONTROL SWITCH
DC
DS
CARD READER ROUGH IN DETAIL
DOUBLE GANGBOX, FLUSH
CARDREAD ER
DOO RSTRI KE
DOORCONTACT
SI NGLE GANGBOX
3/ 4" CONDUI T
ASSESSABLE CEI LI NGON THE SAME FLOOR
JUNCTI ON BOX(DOUBLE GANG)
NOTES:1. COORDI NATE EXACT LOCATI ON
WI TH THE OWNER PRIOR TOROUGH-I N.
2. PROVI DE ADDITI ONAL CONDUI T,ETC AS NECESSARY.
3. PROVI DE PULL STRI NG IN ALLEMPTY CONDUI TS.
4. PROPERLY LABEL BOTH ENDS OFCONDUI TS.
5. PROVI DE COVER PLATE FORJ- BOXES.
1. ALL NEW WORK MUST MEET THE CURRENT ADOPTED NATIONAL ELECTRICAL CODE (NEC) AND ALL THE LOCAL CODES.
2. NOT MORE THAN THREE (3) CIRCUITS SHALL BE INSTALLED IN A 3/4" CONDUIT.3. RUN A NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR. DO NOT SHARE THE NEUTRAL CONDUCTOR IN
HOMERUNS. (NEC 210.4).4. THE MINIMUM SIZE OF THE CONDUCTORS SHALL BE A NO. 12 AWG, THHN COPPER. UNLESS INDICATED OTHERWISE
ON THE DRAWINGS.5. LIGHT FIXTURES, RACEWAYS AND OTHER ELECTRICAL DEVICES SHALL BE SUPPORTED FROM THE STRUCTURE NOT
FROM METAL OR WOOD CEILING DECK. UTILIZE UNISTRUTS IN BETWEEN STRUCTURE AS NEEDED.6. WHERE CIRCUIT CONDUCTORS ARE TO BE INCREASED IN SIZE TO MEET THE VOLTAGE DROP REQUIREMENT, THE
EQUIPMENT GROUNDING CONDUCTORS MUST BE INCREASED ACCORDINGLY (NEC 250.122)7. ALL J-BOXES SHALL HAVE A MINIMUM DEPTH OF 2-1/8" UNLESS OTHER WISE SPECIFIED. SECURE ALL J-BOXES AS
SHOWN IN THE DETAILS. FURNISH AND INSTALL PROPER MUD RINGS.8. ALL THE HOMERUNS MUST BE ACCESSIBLE. DO NOT CARRY A HOMERUN FROM ONE DEVICE TO ANOTHER WHICH IS
TIED TO A SEPARATE HOMERUN INSIDE THE WALL. MARK ON ALL THE J-BOXES THE CIRCUIT NAMES AND NUMBERS.9. ALL DISCONNECTS SHALL BE OF A HEAVY DUTY TYPE.10. ALL DISCONNECTS, J-BOXES, AND CONDUITS EXPOSED TO THE OUTSIDE WEATHER AND MECHANICAL ROOMS
SHALL BE OF A NON-CORROSIVE, WEATHER PROOF TYPE.11. ALL NEW EXPOSED CONDUITS MUST RUN AGAINST THE WALL OR CEILING. DO NOT PENDANT MOUNT ANY CONDUIT
FROM THE CEILING. 12. ALL MATERIALS USED IN INSTALLATION SHALL BE U.L. APPROVED AND NEW.13. ALL ELECTRICAL WIRING MUST BE IN A CONDUIT (ROMEX NOT PERMITTED).14. ALL EXTERIOR RECEPTACLES SHALL BE OF WEATHER-RESISTANT TYPE AS PER NEC 406.8.15. NO CONDUITS SHALL RUN IN DUCT WORK.16. CABLES OR RACEWAYS INSTALLED IN EXPOSED OR CONCEALED LOCATIONS UNDER METAL-CORRUGATED SHEET
ROOF DECKING SHALL BE INSTALLED AND SUPPORTED SO THAT THE NEAREST OUTSIDE SURFACE OF THE CABLE OR RACEWAY IS NOT LESS THAN 38 MM ( 1 1/2 IN.) FROM THE NEAREST SURFACE OF THE ROOF DECKING.
17. SWITCHBOARDS, PANELBOARDS, AND MOTOR CONTROL CENTERS SHALL BE FIELD MARKED TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS. THE MARKING SHALL BE LOCATED SO AS TO BE CLEARLY VISIBLE TO QUALIFIED PERSON'S BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF THE EQUIPMENT. THE WARNING SHALL BE SPECIFIC TO EACH PANEL AND TO MEET NEC 110-16.
18. PROVIDE LATERAL AND LONGITUDINAL BRACING FOR ALL CONDUIT RACKS, CABLE TRAYS, ETC., EXCEEDING 20 FEET IN LENGTH.
19. MINIMUM SIZE CONDUIT SHALL BE 3/4" FOR INTERIOR APPLICATION, AND 1" FOR CONDUIT BURIED BELOW GRADE IN EXTERIOR APPLICATION.
20. LABELING IS REQUIRED FOR ALL PANELBOARDS, SWITCHBOARDS, MOTOR CONTROL CENTERS, MOTOR STARTERS, TRANSFORMERS, MAJOR JUNCTION BOXES, DISCONNECT SWITCHES, BREAKERS, PUSH BUTTONS, ETC., INTERLOCKS AND RELAY PANELS.
21. USE RIGID STEEL, SET SCREW TYPE FITTINGS ONLY. DIE CAST FITTING SHALL NOT BE USED.22. USE EPOXY ANCHORS TO SUPPORT THE ELECTRICAL EQUIPMENT. EXPANSION ANCHOR BOLTS ARE NOT
ACCEPTABLE. 23. AT THE END OF THE JOB, PROVIDE BLANK, MATCHING COVER PLATES FOR ALL J-BOXES WHERE DEVICES HAVE NOT
YET BEEN INSTALLED.24. SEAL AROUND ALL CONDUIT PENETRATIONS THROUGH WALLS AND CEILINGS WITH A FIRE RATED MATERIAL. 3M IS
AN APPROVED MANUFACTURER.25. PRIOR TO SUBMITTAL FOR A BID THE ELECTRICAL CONTRACTOR SHALL INSPECT THE SITE AND INCLUDE IN THEIR
BID PACKAGE ALL CHARGES RELATED TO EXISTING CONDITIONS AND DEMOLITION WORK. PROVIDE SHOP DRAWINGS AS REQUIRED BY CONSTRUCTION DOCUMENTS. ALL LABOR, MATERIALS AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF 1 YEAR FROM THE DATE OF ACCEPTANCE BY THE TENANT. REPLACE OR REPAIR ALL DEFECTS DURING THE GUARANTEED PERIOD.
26. THE ELECTRICAL CONTRACTOR SHALL TERMINATE THE ELECTRICAL CONNECTIONS TO ALL THE EQUIPMENT BY PROVIDING THE NECESSARY MALE/ FEMALE CONNECTOR, RECEPTACLE, PLUG, ETC.
27. THE ELECTRICAL CONTRACTOR SHALL NOTIFY AND COORDINATE WITH THE MECHANICAL CONTRACTOR SO THAT NO PIPING, DUCTS, OR OTHER EQUIPMENT SHALL BE INSTALLED IN THE ENTRY, PASS THROUGH ELECTRICAL ROOM OR SPACES ABOVE OR BELOW ELECTRICAL PANELS.
28. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL ELECTRICAL LOADS (VOLTAGE, PHASE, CONNECTION REQUIREMENT, ETC.) OF EQUIPMENT FURNISHED UNDER OTHER DIVISIONS WITH APPROVED SHOP DRAWINGS.
29. THE CONTRACTOR SHALL INFORM THE ARCHITECT/ ENGINEER, IN WRITING, OF ANY DISCREPANCIES FOUND BETWEEN THE INTENDED FUNCTION OF EQUIPMENT AND EQUIPMENT SPECIFIED IN THE CONTRACT DOCUMENTS WITH A MINIMUM OF FIVE (5) WORKING DAYS PRIOR TO ISSUANCE OF THE FINAL ADDENDUM. FAILURE TO REPORT ANY DISCREPANCY(CATALOG NUMBERS, DISCONTINUED ITEMS, ETC.) DOES NOT RELIEVE THE CONTRACTOR FROM PROVIDING EQUIPMENT WHICH SHALL CONFORM TO AND FULFILL THE INTENT OF THE CONTRACT DOCUMENTS. NOR SHALL IT BE USED AS A CONDITION TO OBTAIN ADDITIONAL FUNDS FROM THE OWNER AFTER THE CONTRACT IS AWARDED. THE CONTRACTOR SHALL REQUEST ALL CLARIFICATIONS OF CONTRACT DOCUMENT REQUIREMENTS, IN WRITING, TO THE ARCHITECT/ ENGINEER WITH A MINIMUM OF FIVE (5) WORKING DAYS PRIOR TO ISSUANCE OF THE FINAL ADDENDUM.
30. CONTRACT DOCUMENTS SHALL TAKE PRECEDENCE OVER SHOP DRAWINGS UNLESS SPECIFICALLY NOTED OTHERWISE.
31. DETAILS ARE SHOWN ON DIFFERENT SHEETS. THE CONTRACTOR SHALL REFER TO THOSE DETAILS WHETHER OR NOT CALLED IN REFERENCE NOTES.
32. PROVIDE MANUAL THERMAL SWITCHES WITH PILOT LIGHT. 33. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLANS FOR THE EXACT LOCATION OF LIGHT FIXTURES.34. COORDINATE WITH THE OWNER AND ARCHITECT FOR THE EXACT LOCATION OF THE OUTLETS PRIOR TO ROUGH-
INS.35. LIGHT SWITCHES INSTALLED ADJACENT TO EACH OTHER, SHALL BE GANGED TOGETHER WITH A ONE PIECE COVER
PLATE. 36. PROVIDE A TYPED LABEL FOR ALL DUPLEX OUTLETS AND LIGHT SWITCHES TO INDICATE WHICH CIRCUIT THEY ARE
TIED TO.37. FEEDERS SHALL HAVE TYPE THHN/THWN INSULATION EXCEPT WHERE EXTREME HEAT OR WATER CONDITIONS
EXIST REQUIRING SPECIAL INSULATION.38. CONTRACTOR MUST PAY FOR HIS OWN ELECTRICITY DURING CONSTRUCTION. COORDINATE WITH THE LOCAL
POWER COMPANY FOR SETTING UP TEMPORARY POWER.39. THE OWNER MUST SCHEDULE INTERRUPTIONS OF SERVICE WHEN CONTRACTOR WISHES TO MAKE UTILITY
CONNECTIONS. NOTIFY IN WRITING, THE OWNER'S REPRESENTATIVE 72 HOURS PRIOR TO TIME WHEN INTERRUPTION IS DESIRED. INTERRUPTION MUST BE AT THE COUNTY'S CONVENIENCE. OVERTIME, IF REQUIRED FOR THIS WORK, IS TO BE AT CONTRACTORS EXPENSE.
40. RIGID METAL CONDUIT (RMC): PROVIDED ZINC-COATED, HOT-DIPPED GALVANIZED, RIGID METALLIC CONDUIT IN WET LOCATIONS OR AREAS SUBJECT TO DAMAGE.
41. FLEXIBLE METAL CONDUIT: PROVIDE ZINC-COATED, FLEXIBLE METAL CONDUIT FOR CONNECTIONS TO MOTORS, TRANSFORMERS, OR OTHER EQUIPMENT SUBJECT TO MOVEMENT OR VIBRATION.
42. ALL HOMERUNS SHALL BE IN CONDUIT. MC CABLES ARE ONLY ALLOWED IN CONCEALED AREA FROM HOME RUNS TO THE DEVICES.
43. MARK BURIED CONDUIT WITH MAGNETIC YELLOW MAKER RIBBON 8" TO 12" BELOW FINISHED SURFACE.44. ALL UNDERGROUND CONDUITS SHALL BE BURIED 24 INCHES MINIMUM UNDER THE GROUND.45. THE FIRST 10 FEET OF ALL BURIED CONDUITS, 1 INCH AND OVER IN DIAMETER, ARE TO BE RIGID GALVANIZED STEEL
WHERE THEY ARE ENTERING OR LEAVING THE BUILDING, MAN-HOLE, VAULT, ETC. ALL METALLIC UNDERGROUND CONDUITS SHALL HAVE PVC COATING.
46. ALL METALLIC CONDUITS, JOINTS, FITTINGS, ETC. IN CONTACT WITH THE GROUND SHALL BE SPIRAL WRAPPED WITH 3M SCOTCHRAP-51, 20 MIL TAPE (OR APPROVED EQUAL). 1/2" OVERLAP IS REQUIRED.
47. PROVIDE TYPED PANEL INDEX FOR EXISTING ELECTRICAL PANELS AFFECTED BY THE SCOPE OF THIS WORK. EXISTING/UNAFFECTED CIRCUITS IN THE PANEL SHALL BE ITALICIZED AND CHANGED/ADDED CIRCUITS SHALL BE TYPED BOLD.
GENERAL NOTES:
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
12/3
/201
8 3:
50:5
8 P
M
GENERALNOTES &DETAILS
LH
2100
WE
ST
114
00 S
OU
TH
, SO
UTH
JO
RD
AN
, UT
AH
840
95
SA
LT
LA
KE
CO
UN
TY
18142
11.30.2018
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PERMIT SET
EE-001
MA
# Date Revision
12/03/2018
Architect.© Architectural Nexus, Inc. 2014
121121122112221221222222212221222222222221221221222222122212122212212222122122212122222212212211111111111111111111111111111111111111111111111111111111111111111111111111111111111111 0/000003/2018
LIGHT FIXTURE SCHEDULE
SYMBOL TYPE DESCRIPTION
REQUIREMENTS (ABSOLUTE DELIVEREDLUMENS)
MANUFACTURERS CATALOG NUMBERS
LUM
EN
S
WA
TTA
GE
VO
LTA
GE
DIM
MIN
G
CO
LOR
TE
MP
MIN
IMU
MC
RI
MO
UN
TIN
G
BE
AM
AN
GLE
3" ROUND APERTURE LEDRECESSED DOWN LIGHT. TOBE RATED FOR SHOWER.SOME LIGHTS TO HAVEEMERGENCY BATTERY PACK.
1,50
0 LU
ME
NS
15W
LE
D
MU
LTI V
OL
T
0-10
V T
O 1
0%
3000
K
90 C
RI
FLA
NG
ED
50D
ALPHABET NU3RD-XTM19-20LM-30K-98-D50-120-DIM10-NC-SCBA-SCBA
Gotham
Contech
Lightolier Inc. 4RN / C4L15930MZ10U / C4RSLWH
EXTERIOR WALL MOUNTEDLIGHT FIXTURE . TO HAVE ABUILT IN OCCUPANCYSENSOR WITH PHOTOCELL.THE FIXTURE SHALL DIMDOWN TO 50% LIGHTOUTPUT 30 MINUTES AFTERMOTION IS DETECTED.
3,00
0 LU
ME
NS
30W
LE
D
MU
LTI V
OL
T
0-10
V T
O 1
0%
3000
K
85 C
RI
WA
LL
TY
PE
IV
McGraw GWC-AF-01-LED-E1-T4FT-SCBA-600-MS/DIM-LXX
Lithonia DSXW2 LED 30C 1000 30K T4M MVOLTPIR DDBXD
Kim
GARDCO 101L-16L-1200-NW-G1-4-EBPC-UNVPCB-IMRI2-STANDARD FINISH
LINEAR 3" WIDE RECESSEDLIGHT FIXTURE OVER THEMIRROR. SOME TO BE ROWMOUNTED. LENS SHALL BESNAP-ON WITH NO GAP ANDNO VISIBLE LED'S. REFER TODRAWINGS FOR EXACTLENGTH. TO HAVE THICKLENS RATED FOR PUBLICRESTROOM. 1,
000
LUM
EN
S/L
F
10W
LE
D/L
F
MU
LTI V
OL
T
0-10
V T
O 1
0%
3000
K
90 C
RI
FLA
NG
ED
N/A
Metalumen RM4D0D-1L30K-XX-G-MB-SCBA-L41-R-4
ALW
Lumenwerx
Pinnacle EV3-WET-CL930/??LPF-??-IND-FL-UOL1-1-0-STANDARD FINISH
LED 4'/8' STRIP LIGHT.ADJUSTABLE CABLE HUNG.REFER TO THE DRAWINGFOR LENGTH.
4,00
0 LU
ME
NS
/4'
40W
LE
D
MU
LTI V
OL
T
0-10
V T
O 1
0%
3000
K
90 C
RI
SU
RFA
CE
/CH
AIN
N/A
Metalux 4SNLED-LD5-41SL-LW-UNV-L830-CD1-UAYC-CHAIN/SET
Lithonia ZL1D L48 5000LM FST MVOLT 30K 90CRIWH / ZACVH
Columbia CSL4/8-4035 / GLH5
DayBrite FSS440L830-UNV-DIM
NOTES:
1. THE WRITTEN CRITERIA OF THE FIXTURE DESCRIPTION/REQUIREMENT TAKES PRECEDENCE OVER THE CATALOG NUMBER.
2. ALL LED FIXTURES SHALL HAVE 5 YEAR MINIMUM WARRANTY, REPLACEABLE AND UP-GRADEABLE MODULES AND DRIVERS, AND 50,000 HOUR LED LIFE.FIXTURE SHALL BE TESTED USING LM 79 AND LM 80 PROCEDURE. ALL LED FIXTURES SHALL BE IN THE DESIGNLIGHTS CONSORTIUM QUALIFIED LIST. LUMENOUTPUT INDICATED IS ABSOLUTE DELIVERED LIGHT.3. FIELD VERIFY ALL LIGHTING VOLTAGES PRIOR TO PLACING ANY ORDER.4. LUMEN OUTPUT INDICATED UNDER THE REQUIREMENTS COLUMN SHALL BE THE OUTPUT OF THE FIXTURE NOT THE LED MODULE.5. REFER TO ARCHITECTURAL ELEVATIONS FOR PENDANT MOUNTING HEIGHTS. DO NOT CUT EXCESS PENDANT CABLES UNTIL PENDANT HEIGHT HAS BEENAPPROVED BY ARCHITECT AND ENGINEER.
D-1
EW-1
LR-1
S-1
MECHANICAL EQUIPMENT SCHEDULE
NAME OFMECHANICALEQUIPMENT
EN
ER
GY
RE
CO
VE
RY
VE
NT
ILA
TO
R
CO
ND
EN
SIN
GU
NIT
ELE
CT
RIC
HE
AT
ING
CO
IL
WA
TE
R H
EA
TE
R
DO
ME
ST
IC P
UM
P
MO
TO
R D
AT
A
EQUIPMENT NO. ERV-1 CU-1 EHC-1 WH-1 RCP-1
RATING/WATTS 0.75 HP 24 KW 1_6 HP
VOLTAGE 208 208 480 480 120
PHASE 3 1 3 3 1
AMPS 5.20 15.40 12 28.90 4.40
WIRE SIZE 3 # 12 2 # 12 3 # 12 3 # 8 2 # 12
GROUND WIRE 1 # 12 1 # 12 1 # 12 1 # 10 1 # 12
CONDUIT SIZE 3/4" 3/4" 3/4" 3/4" 3/4"
FUSE DISC. SW. 30 30 30 60
TYPE RKI FUSES 6 20 15 35 6
BREAKER SIZE 20 20 20 40 20
NOTES 1 1, 3 1 2 2
NOTES:
1 STARTER IS FURNISHED WITH THE UNIT. PROVIDE SITE DISCONNECT.
2 PROVIDE THERMAL OVERLOAD SWITCH.
3RUN 3#12 WIRES IN 3/4" CONDUIT FROM THE INDOOR UNIT TO THE OUTDOOR UNIT. COORDINATEWITH SUPPLIER.
*THE ELECTRICAL CONTRACTOR IS TO COORDINATE WITH THE MECHANICAL CONTRACTOR FOREXACT LOCATIONS AND PROVIDE FUSE/BREAKER SIZE FOR EACH EQUIPMENT PERMANUFACTURER'S RECOMMENDATIONS.
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
12/3
/201
8 3:
50:5
9 P
M
LIGHT FIXTURE/MECHANICAL/PANELSCHEDULES
LH
2100
WE
ST
114
00 S
OU
TH
, SO
UTH
JO
RD
AN
, UT
AH
840
95
SA
LT
LA
KE
CO
UN
TY
18142
11.30.2018
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PERMIT SET
EE-002
MA
1. PROVIDE NEW BREAKERS AS NECESSARY. NEW BREAKERS SHALL MATCH AIC RATING OF EXISTING BREAKERS.
NOTES:
Power 24027 VA 100.00% 24027 VA
Other 95 VA 100.00% 95 VA Total Est. Demand: 45 AMotor 9977 VA 125.00% 12471 VA Total Conn.: 42 ALighting - Exterior 200 VA 125.00% 250 VA Total Est. Demand: 37370 VALighting - Dwelling Unit 380 VA 100.00% 380 VA Total Conn. Load: 34793 VALighting 150 VA 125.00% 188 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 41 A 41 A 44 AAIC: Total Load: 11335 VA 11335 VA 12125 VA-- -- Space -- -- 41 0 VA / 0 VA 42 -- -- Space -- ---- -- Space -- -- 39 0 VA / 0 VA 40 -- -- Space -- ---- -- Space -- -- 37 0 VA / 0 VA 38 -- -- Space -- ---- -- Space -- -- 35 0 VA / 0 VA 36 -- -- Space -- ---- -- Space -- -- 33 0 VA / 0 VA 34 -- -- Space -- ---- -- Space -- -- 31 0 VA / 0 VA 32 -- -- Space -- --
20 A 1 Spare -- 29 0 VA / 0 VA 30 -- Spare 1 20 A20 A 1 Spare -- 27 0 VA / 0 VA 28 -- Spare 1 20 A20 A 1 Spare -- 25 0 VA / 0 VA 26 -- Spare 1 20 A
23 8009 VA / 821... 24 N Po... LIGHTING - RESTROOM BLDG 1 20 A21 8009 VA / 0 VA 22 -- EXISTING - EXTERIOR WALL PACKS 1 20 A40 A 3 WH-1 - WATER HEATER
Power N
19 8009 VA / 0 VA 20 -- EXISTING - LCP 1 20 A17 3326 VA / 0 VA 18 -- EXISTING - LIGHTS 1 20 A15 3326 VA / 0 VA 16 -- EXISTING - LIGHTS 1 20 A20 A 3 EHC-1-ELECTRIC HEATING COIL
Power N
13 3326 VA / 0 VA 14 -- EXISTING - LIGHTS 1 20 A11 0 VA / 0 VA 12 -- EXISTING - LIGHTS 1 20 A9 0 VA / 0 VA 10 -- EXISTING - LIGHTS 1 20 A20 A 3 EXISTING - EH1 --7 0 VA / 0 VA 8 -- EXISTING - LIGHTS 1 20 A5 0 VA / 0 VA 6 -- EXISTING - LIGHTS 1 20 A3 0 VA / 0 VA 4 -- EXISTING - LIGHTS 1 20 A20 A 3 EXISTING - P1 --1 0 VA / 0 VA 2 -- EXISTING - LIGHTS 1 20 A
BREAKER
A PDESCRIPTION TYPE E/
NCIR.
# A B C CIR.#
E/N TYPE DESCRIPTION
BREAKER
P A
AMPS: 225 A MAIN: Volts: 480/277 Wye PHASE: 3 # OF WIRES: 4 MOUNTING: Surface LOCATION:
EXISTING PANEL H1
1. PROVIDE NEW BREAKERS AS NECESSARY. NEW BREAKERS SHALL MATCH AIC RATING OF EXISTING BREAKERS.
NOTES:
Total Est. Demand: 31 ATotal Conn.: 28 A
Receptacle 2120 VA 100.00% 2120 VA Total Est. Demand: 11025 VAPower 2500 VA 100.00% 2500 VA Total Conn. Load: 10225 VAMotor 5605 VA 114.29% 6405 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 20 A 39 A 29 AAIC: Total Load: 2372 VA 4546 VA 3306 VA-- -- Space -- -- 41 0 VA / 0 VA 42 -- -- Space -- ---- -- Space -- -- 39 0 VA / 0 VA 40 -- -- Space -- ---- -- Space -- -- 37 0 VA / 0 VA 38 -- -- Space -- ---- -- Space -- -- 35 0 VA / 180 VA 36 N Po... OUTLET - ROOFTOP 1 20 A-- -- Space -- -- 33 0 VA / 600 VA 34 N Po... DAMPERS 1 20 A-- -- Space -- -- 31 0 VA / 528 VA 32 N Po... RCP-1 -DOMESTIC PUMP 1 20 A
29 1602 VA / 624... 3020 A 2 CU-1 - CONDENSING UNIT Po... N
27 1602 VA / 624 VA 2820 A 1 EXISTING - UPPER LOFT -- 25 0 VA / 624 VA 26
N Power
ERV-1 - ENERGY RECOVERYVENTILATOR 3 20 A
20 A 1 EXISTING - LOWER LOFT -- 23 0 VA / 180 VA 24 N Po... HAND DRYER - WEST SHOWER 1 20 A20 A 1 EXISTING - UTILITY - RECEPT -- 21 0 VA / 1000 VA 22 N Po... HAND DRYER - WEST/MID SHOWER 1 20 A20 A 1 EXISTING - W WALL - N RECEPT -- 19 0 VA / 180 VA 20 N Po... HAND DRYER - EAST/MID SHOWER 1 20 A20 A 1 EXISTING - N WALL - W RECEPT -- 17 0 VA / 180 VA 18 N Po... HAND DRYER - ADA SHOWER 1 20 A20 A 1 EXISTING - N WALL - E RECEPT -- 15 0 VA / 360 VA 16 N Po... OUTLETS - WEST SHOWER/MECH 1 20 A20 A 1 EXISTING - E WALL - N RECEPT -- 13 0 VA / 360 VA 14 N Po... OUTLETS - MIDDLE 2 SHOWERS 1 20 A20 A 1 EXISTING - W WALL - N MIDDLE -- 11 0 VA / 360 VA 12 N Po... OUTLETS - EAST EXT./ADA SHOWER 1 20 A20 A 1 EXISTING - W WALL - S MIDDLE -- 9 0 VA / 180 VA 10 N Po... HAND DRYER - WOMENS RESTROOM 1 20 A20 A 1 EXISTING - W WALL - S RECEPT -- 7 0 VA / 180 VA 8 N Po... OUTLET - MENS RESTROOM 1 20 A20 A 1 EXISTING - E WALL - S RECEPT -- 5 0 VA / 180 VA 6 N Po... HAND DRYER - MENS RESTROOM 1 20 A20 A 1 EXISTING - S WALL - E RECEPT -- 3 0 VA / 180 VA 4 N Po... OUTLET - WOMENS RESTROOM 1 20 A20 A 1 EXISTING - S WALL - W RECEPT -- 1 0 VA / 500 VA 2 N Po... EXTERIOR OUTLET - EWC 1 20 A
BREAKER
A PDESCRIPTION TYPE E/
NCIR.
# A B C CIR.#
E/N TYPE DESCRIPTION
BREAKER
P A
AMPS: 225 A MAIN: Volts: 120/208 Wye PHASE: 3 # OF WIRES: 4 MOUNTING: Surface LOCATION:
EXISTING PANEL P1
# Date Revision
12/03/2018
Architect.© Architectural Nexus, Inc. 2014
122212221212222221222222221222222212222212121211111111111111111111111111111111111111111111111111111111111111111111111111111111111 /03/2018
WHJ
TJ
J
T
J
T
JJ
J J J
J
CR CRCR CR
WH
MEN'S TOILETS
S101
WOMEN'S TOILETS
S102
MECH ROOM / CHASE
S107
SHOWER ROOM
S106
SHOWER ROOM
S105 SHOWER ROOM
S104
SHOWER ROOM (ADA)
S103
A
A
AA
AA
EWC
ERV-1
P1-27,29P1-26,28,30
P1H1
75 KVALCP
H1-19,21,23
ELECTRICAL ROOM IS APPROXIMATELY 50 FEET FROM THE NEW RESTROOM. FIELD VERIFY PRIOR TO BID.
P1-2,4,6
EHC-1
H1-13,15,17
CU-1WH-1
P1-32
RCP-1
DAMPER
DAMPER
ON ROOF
P1-34
P1-34
P1
WP
P1-12,14,16
P1-36
WP
P1-8,10
P1-18,20P1-22,24
H.D. H.D.
H.D.
H.D.H.D.H.D.
FUTURE ACCESS CONROL PANELP1
P2 P2 P2 P2
WOMEN'S TOILETS
S102
MEN'S TOILETS
S101
MECH ROOM / CHASE
S107
SHOWER ROOM
S106
SHOWER ROOM
S105 SHOWER ROOM
S104
SHOWER ROOM (ADA)
S103
LR-1TYP
D-1TYP
D-1TYP
LR-1TYP
TYPL2
TYPL2
TYPL2
L1S-1
TYP
EW-1TYP EW-1
TYP
EW-1TYP
a
H1 P1LCP 75 KVA
ELECTRICAL ROOM IS APPROXIMATELY 50 FEET FROM THE NEW RESTROOM. FIELD VERIFY PRIOR TO BID.
L3
H1-24
E E
E,NLE,NL
ba,b
E E
LR-1TYP
h
h
h
k
k
k
c c
c
d
d d f
f
f
g g
g
g
SHEET NOTES - POWER1 PROVIDE NEW DUCT DETECTORS AS INDICATED ON THE MECHANICAL
EQUIPMENT SCHEDULE ON SHEET EE-002.
REFERENCE NOTES
L1 FURNISH AND INSTALL A WALL MOUNTED DUAL-TECHNOLOGY AND TWOCIRCUIT (WHERE SHOWN) OCCUPANCY SENSOR WITH INTEGRATEDPHOTOCELL AND VANDAL-RESISTANT LENS TO CONTROL THE LIGHTFIXTURES IN THE ROOM. REFER TO DETAIL D7 ON SHEET EE-001 FORPROGRAMMING.
L2 FURNISH AND INSTALL A CEILING MOUNTED DUAL-TECHNOLOGY ANDMULTI CIRCUIT (WHERE SHOWN) OCCUPANCY SENSOR WITHINTEGRATED PHOTOCELL AND VANDAL-RESISTANT LENS TO CONTROLTHE LIGHT FIXTURES IN THE ROOM. THE LIGHT SWITCHES SHOWN INTHE ROOM SHALL BE ON THE LOAD SIDE OF THE OCCUPANCY SENSOR.THE OCCUPANCY SENSOR SUPPLIER SHALL PROVIDE A LAYOUT TOENSURE A 100% COVERAGE IN EACH ROOM. PROVIDE ADDITIONALPOWER PACKS, RELAYS, ETC. FOR A COMPLETE INSTALLATION. REFERTO DETAIL D7 ON SHEET EE-001 FOR PROGRAMMING.
L3 TIE EXTERIOR LIGHT FIXTURES TO THE NEAREST 277 VOLT LIGHTINGCIRCUIT THROUGH THE EXISTING LIGHTING CONTROL PANEL. PROVIDEADDITIONAL RELAY, PROGRAMING, SOFTWARE, ETC AS REQUIRED FORA COMPLETE INSTALLATION.
P1 TIE THE DAMPER TO THE CORRESPONDING EXHAUST FAN SO THAT THEDAMPERS WILL OPEN WHEN THE EXHAUST FAN IS ON. PROVIDE PROPERINTERLOCKING RELAY AS NECESSARY. COORDINATE THIS WORK WITHTHE MECHANICAL SUB-CONTRACTOR.
P2 FURNISH AND INSTALL A RECESSED, DEEP, SINGLE GANGE J-BOX IN THEAPPROXIMATE LOCATION SHOWN FOR FUTURE CARD READER. RUN A 1"CONDUIT FROM THE J-BOX TO THE FUTURE ACCESS CONTROL PANEL INTHE MECH ROOM S107. ALSO RUN A 3/4" CONDUIT FROM THE DOORSTRIKE AND DOOR CONTACT TO THE J-BOX. COORDINATE THIS WORKWITH THE GC/OWNER PRIOR TO ROUGH-IN. PROPERLY CAP AND LABELTHE CONDUITS. PROVIDE PULL STRING IN THE CONDUITS.
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
54321
D
C
B
A
12/3
/201
8 3:
51:0
1 P
M
MAIN FLOORPLAN -LIGHTING &POWER
LH
2100
WE
ST
114
00 S
OU
TH
, SO
UTH
JO
RD
AN
, UT
AH
840
95
SA
LT
LA
KE
CO
UN
TY
18142
11.30.2018
EQ
UE
ST
RIA
N C
EN
TE
RR
ES
TR
OO
M/S
HO
WE
R B
UIL
DIN
G
PERMIT SET
ELP-101
MA
SHEET NOTES - LIGHTING1 TIE ALL FIXTURES INDICATED WITH A LOWER CASE LETTER TO ITS
CORRESPONDING SWITCH(ES). PROVIDE CONDUITS, CONDUCTORS,LIGHTING CONTACTORS, ETC. FOR A COMPLETE INSTALATION.
2 LIGHT FIXTURES INDICATED WITH THE LETTERS "NL" (NIGHT LIGHT) SHALLSTAY ON AT ALL TIMES. PROVIDE CONDUITS, CONDUCTORS, ETC. FOR ACOMPLETE INSTALLATION.
3 EMERGENCY LIGHT FIXTURES INDICATED WITH THE LETTER "E" SHALL BEPROVIDED WITH AN EMERGENCY BATTERY PACK AND TURN ON WHEN THECOMMERCIAL POWER FAILS REGARDLESS OF THE POSITION OF THECONTROL SWITCH. THE FIXTURE SHALL BE CONTROLLED BY THEINDICATED SWITCH. PROVIDE CONDUITS, CONDUCTORS, ETC. FOR ACOMPLETE INSTALLATION. PROVIDE AN UNSWITCHED LIGHTING CIRCUITFROM THE SAME CIRCUIT AS THE LIGHT FIXTURE TO THE BATTERY PACK.
# Date Revision
12/03/2018
Architect.© Architectural Nexus, Inc. 2014
1212222122222212122222121222222212122222122222221222212212222122212222221222121221212122222222222222221222122221222222212222222222212222122222221222222222212222212212122221222222221111111111111111111111111111111111111111111111111111111111 /0000/000/00/0/00/000/0///////////////////////////////////////////////////////// 3/2018