smart meter goodwe smart meter is designed with high ... meter user manual.pdf · goodwe smart...

2
PACKING LIST USER MANUAL Smart Meter Kun Lun Shan Road 189, Suzhou, Jiangsu, China 215000 [email protected] | www.goodwe.com 1* Smart Meter 1* Screw Driver 1* USB Seal 1* CT (Current Transformer) [1] 4* Cable Connection Terminals 1* RJ45-to-Pin Cable [2] NOTE: [1] A three-phase Meter will contain 3 CT clamps. Specifications are subject to the physical product. [2] Only suitable for RS485 cable connection on RJ45 port of GoodWe hybrid inverters. OVERVIEW 02 2.1 SMART METER OVERVIEW 66.5mm 85mm 36mm 9 N 10 L1(A) 11 L2(B) 12 L3(C) 3 -(IC-) 4 +(IC+) 8 +(IA+) 7 -(IA-) 5 -(IB-) 6 +(IB+) 2 A(485A+) 1 B(485B-) Power LED Energy Consumption LED Communications LED Reset Switch USB Port 2.2 CT OVERVIEW 2M 32mm 45mm 35mm 16mm INSTALLATION INSTRUCTION 03 3.1 INSTALLATION ENVIRONMENT Protection Class: IP20 (for indoor use) Operating Temperature: -20~603.2 INSTALLATION with DIN trackPull to release the retaining clip Mount the Meter on the track and push the retaining clip up (a click sound indicates it is installed well) 01 02 03 Any fault or damage caused by misoperation or disobeyal against the rules on manual is beyond GoodWe warrenty cover range. GoodWe Smart Meter is designed with high precision small dimensions, convenient operation and installation. It is available for both single-phase and three-phase grid system connection to detect voltage, current, power and energy, for working with inverters including SEMS systems for the purpose energy management.

Upload: others

Post on 03-Feb-2020

71 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Smart Meter GoodWe Smart Meter is designed with high ... Meter User Manual.pdf · GoodWe Smart Meter is designed with high precision small dimensions, convenient operation and installation

PACKING LIST

USER MANUAL

Smart Meter

Kun Lun Shan Road 189, Suzhou, Jiangsu, China [email protected] | www.goodwe.com

1* Smart Meter

1* Screw Driver

1* USB Seal

1* CT (Current Transformer)[1]

4* Cable Connection Terminals

1* RJ45-to-Pin Cable[2]

NOTE:

[1] A three-phase Meter will contain 3 CT clamps.

Specifications are subject to the physical product.

[2] Only suitable for RS485 cable connection on RJ45 port of

GoodWe hybrid inverters.

OVERVIEW02

2.1 SMART METER OVERVIEW

66.5mm

85m

m

①②③④

36mm

9 N

10 L

1(A)

11 L

2(B)

12 L

3(C

)

3 -(

IC-)

4 +

(IC+

)

8 +

(IA+

)7

-(IA

-)

5 -(

IB-)

6 +

(IB+

)

2 A(

485A

+)

1 B(

485B

-)

① Power LED

② Energy Consumption LED

③ Communications LED

④ Reset Switch

⑤ USB Port

2.2 CT OVERVIEW

2M 32mm

45m

m

35mm

16mm

INSTALLATION INSTRUCTION03

3.1 INSTALLATION ENVIRONMENT

Protection Class: IP20 (for indoor use)

Operating Temperature: -20~60℃

3.2 INSTALLATION (with DIN track)

① Pull to release the retaining clip

② Mount the Meter on the

track and push the retaining

clip up (a click sound indicates

it is installed well) ①

01

02 03

Any fault or damage caused by misoperation or disobeyal against the rules on manual is beyond GoodWe warrenty cover range.

GoodWe Smart Meter is designed with high precision

small dimensions, convenient operation and installation.

It is available for both single-phase and three-phase grid

system connection to detect voltage, current, power

and energy, for working with inverters including SEMS

systems for the purpose energy management.

Page 2: Smart Meter GoodWe Smart Meter is designed with high ... Meter User Manual.pdf · GoodWe Smart Meter is designed with high precision small dimensions, convenient operation and installation

Load

Inverter

RS485

N L1 L2 L3

Main Meter

Grid

NLA

LBLC

B A LC﹣

LB﹣

LB﹢

LA﹣

LA﹢

LC﹢

CT×3

RS485

GridInverter

N L1

CT

Main Meter

Grid

NL

Load

Smart MeterFUSES 0.5A

3.3 WIRING CONNECTION

3.3.1 WIRING FOR SINGLE-PHASE METER

• Correct direction of CT: House (K)→Grid (L).

Incorrect connection or direction will cause incorrect data.

3.3.2 WIRING FOR THREE-PHASE METER

Smart Meter

FUSES 0.5A

ELECTRICAL DATA04

APPLICATION Three-phaseSingle-phase

Active/Reactive Power Energy

Voltage

MODEL GM3000GM1000

Voltage/Current/Active Power/Reactive Power/Power Factor/Frequency

Nominal Voltage

Voltage Range

Frequency

Nominal Current

Current Range

CurrentInput

Self-Consumption

Data Detection

Energy Calculation

Precision

Voltage/Current

Active Power

Reactive Power

With InverterComm.

Class 1

Class 1

Class 2

RS485 (Bund Rate 9600 / ModBus Protocol / communication cable max. length 100m)

3W max

0.48A~120A

CT in:120A/40mA

50Hz/60Hz

0.7~1.2Un 0.7~1.2Un

3L+N/400Vac230Vac

INTERFACE05

5.1 INDICATORS

* Power LED :

Normal operation: ON

* Energy Consumption LED:

Consuming: On

Generating: Blinking

* Communication LED:

Transmitting data: Blinking

Resetting: Blink 5 times

5.2 RESET BUTTON

Press Function

<3s Meter Reset

5s Meter Settings Initialization

>10s Meter Initialize settings and clear energy data

5.3 USB PORT

For after-sales maintenance

340-00133-01

04 05

06 07

• Correct direction of CT: House (K)→Grid (L).

• Ensure CT and corresponding supply cable are connected to

the same phase.

Incorrect connection or direction will cause incorrect data and

may damage the meter.