slt installation & operation manual 253031934-a

99
SAGEM-LINK T SDH Microwave Trunk Network Solution Installation & Operation Manual 3000299570-R11-000-01 Edition 01 : October 2007

Upload: ledungvms

Post on 26-Oct-2014

135 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK TSDH Microwave

Trunk Network Solution

Installation & Operation Manual

3000299570-R11-000-01Edition 01 : October 2007

Page 2: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 2/99

Sagem Communications closely follows all technological changes and is continually striving to improve itsproducts for the benefit of its customers. It therefore reserves the right to change its documentation accordinglywithout notice.All trademarks are registered by their owners.

Sagem Communication document. Reproduction and disclosure prohibited.

Page 3: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 3/99

HANDBOOK CHANGE LIST

(Each new edition supersedes the previous edition)

No. Editions(No., date)

ChangeDescription

ChangedPages

01 October 2007 Document creation All pages

Page 4: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 4/99

SAGEM-LINK T

INSTALLATION & OPERATION MANUAL

Table of Contents

CHAPTER 1 - PRODUCT DESCRIPTION ...........................................................................................................8

1.1 - GENERAL.....................................................................................................................................................81.2 – SYSTEM OVERVIEW.....................................................................................................................................81.3 – SLT SYSTEM DIAGRAM ...............................................................................................................................91.4 – SLT MAIN FEATURES ..................................................................................................................................91.5 – APPLICATIONS...........................................................................................................................................101.6 – SYSTEM CONFIGURATIONS ........................................................................................................................111.7 – FREQUENCY BANDS ..................................................................................................................................121.8 – SAGEM-LINK T DIAGRAMS AND ILLUSTRATIONS .......................................................................................131.9 – SAGEM-LINK T COMPONENTS ................................................................................................................19

1.9.1 - RFU Subrack Components ...............................................................................................................191.9.2 – Baseband Indoor Components ........................................................................................................221.9.3 – Power Supply ...................................................................................................................................23

1.10 – AUXILIARY CHANNELS .............................................................................................................................241.11 – RADIO PROTECTION SWITCHING ..............................................................................................................25

1.11.1 – Channel Priorities ...........................................................................................................................261.11.2 – Revertive Mode ..............................................................................................................................271.11.3 – Upgrade / Downgrade ....................................................................................................................271.11.4 – Link Topologies ..............................................................................................................................27

1.12 – MANAGEMENT.........................................................................................................................................28

CHAPTER 2 - SAGEM-LINK T SPECIFICATIONS............................................................................................29

2.1 – SAGEM-LINK T SPECIFICATIONS (STM-1) ...............................................................................................292.2 – FREQUENCY CHANNELS ............................................................................................................................33

CHAPTER 3 - SAGEM-LINK T INSTALLATION ...............................................................................................45

3.1 – GENERAL..................................................................................................................................................453.2 - REQUIRED PARTS AND TOOLS ....................................................................................................................453.3 – TRANSPORTATION AND HANDLING..............................................................................................................463.4 – INSTALLATION PROCEDURES......................................................................................................................47

3.4.1 - ICC to ICB Assembly ........................................................................................................................473.4.2 – Configuration Tables ........................................................................................................................513.4.3 – Rack Installation ...............................................................................................................................543.4.4 – Securing to Floor ..............................................................................................................................553.4.5 – Securing to Wall ...............................................................................................................................553.4.6 – Rack Concatenation .........................................................................................................................573.4.7 - Connecting the Power Supply...........................................................................................................583.4.8 - Installing the RFUs............................................................................................................................583.4.9 - Connecting the IDMs.........................................................................................................................583.4.10 - Connecting the Bends.....................................................................................................................583.4.11 – Switching the System On ...............................................................................................................58

CHAPTER 4 - INITIAL SYSTEM SETUP ...........................................................................................................59

4.1 – GENERAL..................................................................................................................................................594.2 – INITIAL SETUP STEPS FOR UP TO 4+1 CONFIGURATION ...............................................................................594.3 – INITIAL SETUP USING THE CRAFT TERMINAL ...............................................................................................60

4.3.1 - Connecting to the IDU via Serial Port ...............................................................................................604.4 – INITIAL SETUP STEPS FOR UP TO 9+1 CONFIGURATION ...............................................................................61

4.4.1 - To set the cascading mode:..............................................................................................................614.5 – DEFINING IP ADDRESSES ..........................................................................................................................614.6 – SETUP OPTIONS IN THE TERMINAL PROGRAM .............................................................................................654.7 – ADDITIONAL SETUP USING LINKPILOT ........................................................................................................65

Page 5: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 5/99

CHAPTER 5 - SAGEM-LINK T ACCEPTANCE & COMMISSIONING PROCEDURES ...................................75

5.1 – GENERAL..................................................................................................................................................755.2 – SITE ACCEPTANCE PROCEDURE ................................................................................................................76

5.2.1 - Site Acceptance Checklist.................................................................................................................765.2.2 - Site Acceptance Checklist Notes ......................................................................................................79

5.3 – N+0 COMMISSIONING PROCEDURE............................................................................................................815.3.1 - Scope ................................................................................................................................................815.3.2 - Commissioning Tests........................................................................................................................81

5.4 – N+1 COMMISSIONING PROCEDURE............................................................................................................825.4.1 - Scope ................................................................................................................................................825.4.2 - Commissioning Tests........................................................................................................................82

5.5 – XPIC COMMISSIONING PROCEDURE ..........................................................................................................835.5.1 - Scope ................................................................................................................................................835.5.2 - XPIC Installation Guidelines .............................................................................................................835.5.3 - XPIC Commissioning Tests ..............................................................................................................84

5.6 – SAGEM-LINK T COMMISSIONING LOG......................................................................................................86

APPENDIX A - CONNECTORS PINOUT ...........................................................................................................90

A.1 – GENERAL .................................................................................................................................................90A.2 – INPUT EXTERNAL ALARMS CONNECTOR .....................................................................................................91A.3 – OUTPUT EXTERNAL ALARMS CONNECTOR..................................................................................................92A.4 – PROTECTION CONNECTOR PINOUT ............................................................................................................93A.5 – 8XE1/T1 CONNECTOR PINOUT..................................................................................................................94A.6 – MODEM – PPP CROSS CABLE PINOUT .....................................................................................................95A.7 – WAYSIDE CHANNEL CONNECTOR PINOUT ..................................................................................................96

APPENDIX B - PPP/SLIP DRIVER INSTALLATION.........................................................................................97

B.1 - INSTALLATION FOR WINDOWS 2000............................................................................................................97B.2 - CONFIGURING PPP ...................................................................................................................................97

Page 6: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 6/99

Safety Precautions

Fiber Optic Line Precautions

!! Before turning on the equipment, make sure that the fiber optic cable isintact and is connected to the transmitter

!! Do not attempt to adjust the laser drive current.

!!Do not use broken or non-terminated fiber optic cables/connectors orlook straight at the laser beam. ATTENTION : The laser beam isinvisible!

!! The use of optical devices with the equipment will increase eye hazard.

CLASS 1 LASER PRODUCTComplies with IEC 60 825-1:1993 + A1:1997 + A2:2001, and EN 60825-1:1994 + A1:1996 + A2:2001.

General Equipment Precautions

!! Use of controls, adjustments, or performing procedures other thanthose specified herein, may result in hazardous radiation exposure.

!!When working with a SLT IDU, note the following risk of electric shockand energy hazard: Disconnecting one power supply disconnects onlyone power supply module. To isolate the unit completely, disconnectall power supplies..

!!Machine noise information order - 3. GPSGV, the highest soundpressure level amounts to 70 dB (A) or less, in accordance with ISO EN7779.

Page 7: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 7/99

Safety Precautions(Continued)

Static electricity may cause body harm, as well as harm to electroniccomponents inside the device.

Anyone responsible for the installation or maintenance of the SLT IDUmust use an ESD Wrist Strap.

ESD protection measures must be observed when touching the IDU.

To prevent damage, before touching components inside the device, allelectrostatic must be discharged from both personnel and tools.

Page 8: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 8/99

Chapter 1Product Description

1.1 - General

Constant network expansion in this day of fast-paced communication has brought with it the need forincreased capacity, long distance links, simplicity of installation, and more robust backbone and long-haulinfrastructure.

SAGEM-LINK T is a low frequency, high capacity, N+1 trunk radio system that was designed to respond tothose needs.

1.2 – System Overview

SAGEM-LINK T system supports multiple capacities, frequencies, modulation schemes, and configurationsfor various network requirements.

SAGEM-LINK T operates in the frequency range of 6-11 GHz, and its capacities support up to 10 x 155 Mbps.In addition, a redundant channel provides backup in the event of equipment failure or degradation on specificfrequency channels.

SAGEM-LINK T was designed to provide maximum protection and availability for backbone networks.Featuring N+1 switching protection, embedded space diversity, and ultra high power, operators can greatlyimprove hop length, system performance and availability.

The SAGEM-LINK T long haul trunk solution includes value-added features, such as full TDM and IPcapabilities and unique flexibility options. The same hardware is used for both split-mount and all-indoorinstallations, providing the customer with maximum flexibility to meet their wide range of requirements.

SAGEM-LINK T has an ultra high power transmitter, which reaches longer distances and helps reduce systemcost due to the usage of smaller antennas. Thus, high quality communication is achieved, with less cost.

For installation flexibility, the SAGEM-LINK T Trunk Radio system can be assembled in one of twoconfigurations:

• All-Indoor installation, with the entire system installed in a rack

• Split-Mount installation, with the Radio Frequency Units installed near the antenna

SAGEM-LINK T specifications are in accordance with the relevant ITU, ETSI, and IEC international standards.

Page 9: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 9/99

1.3 – SLT System Diagram

The following illustration shows the SLT system structure and components.

As shown in the block diagram, the SAGEM-LINK A IDU includes the following sections and functions:

1.4 – SLT Main Features

• Operates in the frequency range of 6-11 GHz

• N+1 carrier protection

• Two possible installation types:

- SLT All-Indoor: 1+0 to 9+1/10+0- SLT Split-Mount: 1+0 to 5+1/6+0

• Protected Configurations: 1+1 Hot Standby, 1+1 to 9+1 Frequency Diversity, Co-channel operationwith XPIC (CCDP)

Note: all configurations are available with Space Diversity, using an innovative digital multi-mode IFcombiner.

• High transmit power

- SLT All-Indoor: 32/33 dBm- SLT Split-Mount: 29dBm

• Capacity: up to 10 x 155 Mbps

• Modulation 64/128 QAM

• Channel bandwidth: 28/29.65/30/40 MHz

• Two receivers and one transmitter in a single transceiver unit, for built-in Diversity capability

Page 10: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 10/99

• Innovative digital multi-mode IF combiner

• Both configurations, All-Indoor and Split-Mount, use the same hardware

• Simple and flexible installation

• Light weight system

• Different capacities and interfaces, using different indoors: SLT or SAGEM-LINK A units

• Compliant with ETSI, FCC, ITU-T, and ITU-R standards for worldwide operation

• Advanced LinkPilot - Java-based SNMP element manager, and IONOS-NMS - open interface networkmanagement system.

• SLT baseband indoor can operate with SAGEM-LINK A ODUs (6-38 GHz).

1.5 – Applications

SLT can be used for a variety of applications, as a flexible and cost-effective trunk network solution.

In addition to trunk N+1 x 155 Mbps configurations, for maximum link optimization, all SAGEM-LINK A indoorunit types can be connected to the RFU subrack for all-indoor configurations.The following SAGEM-LINK A indoor units can be configured for 1+0, 1+1, 2+0, and east-west communication,in an all-indoor installation:

• DS3/STM-1/OC-3 interfaces

• FE/GbE + 8xE1/T1

In addition, the SLT baseband indoor can operate with all SAGEM-LINK A ODUs (6-38 GHz).

The following are the types of applications for which SAGEM-LINK T is optimally suited.

Long Distance Connectivity

For both fixed line and mobile operators, SAGEM-LINK T trunk networks provide long distanceconnectivity.

Use of lower frequencies, which require high transmit power and Space Diversity, together with STM-1/OC-3 capacity and N+1 carriers, enables SAGEM-LINK T to facilitate backbone long-haul networkbuilding.

Mobile and Fixed Infrastructure

Quickly deployed and optimized for long-haul trunk applications, SAGEM-LINK T is ideal for growingnetworks that demand very high capacities with multiple STM-1/OC-3 carriers. With scaleable capacity ofup to N+1 carriers, operators can easily expand their networks to meet the huge increase in users, cellsites, and bandwidth-hungry applications.

The SLT system offers smooth migration from PDH to SONET/SDH networks and next generation IP, withcapacities of n x DS3, FE, 2 x FE, and GbE. Applications include voice, Internet, PABX, DSL, video, VoIP,and others.

Page 11: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 11/99

Broadcast Networks

With very high capacity and ultra-long distance radio hop capability, SAGEM-LINK T is an economicchoice for cross-country digital broadcast connectivity. The scalability and reliability of the SLT solution areideal for high-quality transport of contribution and distribution services. Applications include Digital VideoBroadcast, TV, radio, and telemedicine.

Utilities & Private Networks

SAGEM-LINK T provides high-capacity connectivity for enterprise LAN and PBX systems. Its hardwareoptimization significantly reduces equipment requirements for low frequency long haul radio hops, resultingin lower operation and maintenance costs. SAGEM-LINK T is ideal for utility operators, corporateenterprises, education campuses, hospitals, banks, and others.

Applications include TDM connectivity, IP LAN connectivity, (FE/GbE), VoIP, client-server application,remote storage, video conferencing, infrastructure redundancy, and more.

1.6 – System Configurations

SAGEM-LINK T is an N+1 Trunk Radio system that includes transceivers and Baseband Indoorunits. The radio is a regenerator, RST (Regenerator Section Termination), in accordance with ITU-TRec. G.783.

The following configurations are supported:

Unprotected

Data is transmitted through N channels, without redundancy (protection).

- All-Indoor: 1+0 to 10+0- Split-Mount: 1+0 to 6+0

Hot Standby (both configurations)

Two RFUs (RF Units) use the same RF channel, whereby one channel transmits and the other actsas a backup (standby).

N+1 Frequency Diversity

Data is transmitted through N channels, and an additional RF channel protects the data bytransmitting in a different frequency.

Frequency Diversity configurations can be expanded to up to 9+1. The system is mechanicallyprepared for traffic channel expansion.

In addition, in N+1 Frequency Diversity systems, a low priority traffic channel can be transmitted onthe protection channel (Occasional Traffic), without the need for additional equipment.

- All-Indoor: 1+1 to 9+1- Split-Mount: 1+1 to 5+1

Page 12: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 12/99

Notes: The N+1 Frequency Diversity (N>1) is not applicable for SAGEM-LINK A indoors.

Space Diversity can be used in each of the configurations (HSB, N+0, and N+1).

1.7 – Frequency Bands

The frequency bands supported by SAGEM-LINK T are listed in the following table.

Page 13: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 13/99

1.8 – SAGEM-LINK T Diagrams and Illustrations

The SAGEM-LINK T system is composed of three main components:

• Branching System

• Baseband Indoor

• RFUs

System Block Diagrams

The following are block diagrams of the SAGEM-LINK T system and its main components.

SLT 4+1 Single Polarization System Block Diagram

RST

RST

RST

RST

RST

RST

RST

MODEM

MODEM

MODEM

MODEM

MODEM

MODEM

MODEM

MODEM

MODEM

RST

RST

RFU

s

N+1

Sw

itchi

ng

SLT 9+1 Dual Polarization System Block Diagram

Page 14: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 14/99

Ω50Ω

50

ICC 1

WG

Subrack 1

Subrack 2Ω50

Ω50

ICC 2

WG

Tx1Tx2 Tx3 Tx Tx4

Tx6 Tx7 Tx8

Tx

R x1R x2R x3Rx4R x

R x6R x8 R x7

Rx5

T x9T x10

T x5

R x9R x10

SLT Branching System Electrical Diagram

Page 15: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 15/99

MODEM

IF

MODEM

IF

MODEM

IF

MODEM

IF

EXT. Alarm

SupervisoryBoards

OH

LineInterface

RSOH

RX

TX

OH

LineInterface

RSOH

RX

TX

OH

LineInterface

RSOH

RX

TX

OH

LineInterface

RSOH

RX

TX

RXControl

N+1 SWITCH

AuxiliaryBoard

WSUC

EOW

MNG

To RFU

NMS

To RFU

To RFU

To RFU +1

TX

SLT 3+1 Baseband Indoor Block Diagram

Page 16: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 16/99

SLT Single Carrier Block Diagram

Page 17: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 17/99

All-Indoor Illustration

The following illustration shows the SAGEM-LINK T All-Indoor N+1 Trunk Radio system in a 9+1/10+0configuration that includes the N+1 Baseband Indoor and All-Indoor RFUs in their respective enclosures, intheir respective enclosures.

SAGEM-LINK T All-Indoor 9+1 System

Page 18: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 18/99

Rack and Subrack Dimensions

Page 19: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 19/99

1.9 – SAGEM-LINK T Components

1.9.1 - RFU Subrack Components

FibeAir 3200T RFU Subrack

Subrack

The subrack hosts all the RFU components and connections, as shown in the illustration below.The subrack includes:

ICBs – up to five ICBs per subrack

ICCs - up to two ICCs per subrack

ICCDs - if space diversity is used, the ICC will include two output ports, main and diversity

RFUs - up to five RFUs per subrack (each RFU connects to an ICB)

Filters - up to three filters per subrack (Tx and 2 x Rx), connected to each ICB

Patch Panel - part of the subrack; IF and XPIC cables are connected to the panel

Fan Tray - contains eight controlled and monitored fans, which cool the RFU heat dissipations

RFU

IBN

ICB

Page 20: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 20/99

RFU - RF Unit

The RFU handles the main radio processing. It includes the following radio components: signal receiving,signal transmission, IF processing, and power supply.IF processing is a module that combines two signals, main and diversity, and uses the combined signal toovercome multi-path phenomenon (for Space Diversity configurations).The RFU has different versions, depending on the frequency band.

IBN - Indoor Branching Network

The IBN is a branching network for N+1 radio systems. It provides the electrical and mechanical interfacebetween the RFU and the antenna waveguides.The IBN has several versions, depending on the frequency and application.The Branching Network contains N+1 x ICBs (Indoor Circulator Blocks), ICC (Indoor Combiner Circulator),RF filters, and other WG components, which are connected in accordance with the system configuration(1+1, N+1, N+0, etc.).IBN components are integrated with the RFUs.

ICB - Indoor Circulator Block

Each RFU is connected to one ICB, and several ICBs are chained to each other. The chained ICBs carrydifferent RF channels and are connected to a single ICC, which sums the RF signals.The main ICB functions include:

- Hosts the circulators and filters.- Routes the RF signals in the correct direction, via the filters and circulators.- Facilitates RFU connection to the main and diversity antennas.

The ICB is a modular stand-alone unit. When system expansion is necessary, additional ICBs will beadded and chained with the existing ICBs.

ICC

Subrack

Filters

Patch PanelFan Tray

Radio and ICB

ICC

Subrack

Filters

Patch PanelFan Tray

Radio and ICB

Page 21: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 21/99

ICC - Indoor Combiner Circulator

The ICC sums the Rx and Tx signals and combines the N channels to the output ports (one or two, inaccordance with the configuration).

There are two types of ICCs:

- ICC - does not perform summing of space diversity ICBs (single output port)

- ICCD - performs space diversity ICB summing (two output ports)

Within these types, there are two sub-types:

ICC3/ICCD3 - sums up to three ICBs

ICC5/ICCD5 - sums up to five ICBs

For example:We will assume a SLT system in a 4+1 dual polarization configuration, as shown in the illustration below.

In this configuration, three ICBs are chained together and connected to a vertical ICC, and two ICBs arechained together and connected to a horizontal ICC.

The RF components will include:- Five RFUs- Five ICBs- Two ICCs

Horizontal ICC

Vertical ICC

Horizontal ICC

Vertical ICC

Page 22: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 22/99

RF Filters

The RF Filters are used for specific frequency channels and Tx/Rx separation. The filters are attachedto the ICB, and each RFU contains one Rx and one Tx filter.

In a Space Diversity configuration, each RFU contains two Rx filters (to combine the IF signals) and oneTx filter.

1.9.2 – Baseband Indoor Components

SLT Indoor Unit

IDC - IDU Controller

The IDC card is responsible for the management of the Baseband Indoor. Management includes all FCAPSfunctionality (Fault, Configuration, Accounting, Provisioning, and Security).The indoor is equipped with up to five IDMs that can be installed in three floors:

- Floor 1 - 2 IDMs- Floor 2 - 1 IDM and XC card- Floor 3 - 2 IDMs

Each IDC manages the relevant floor, according to its location.

IDM - Indoor Module

The IDM is the data carrier, which consists of two independent drawers:- Multiplexer drawer- Modem drawer (IF)

The Multiplexer drawer is a standard SDH/SONET regenerator. It receives standard SDH/SONET data fromits line interface and transfers the data to the Modem drawer.

The line interface can be one of the following:- Optical interface, single-mode,1300 nm, SC connector- Optical interface, multi-mode,1300 nm, SC connector

- Electrical interface, CMI/1.0-2.3

The Modem drawer is a multi-constellation modem that performs data conversion from the basebandfrequency to the IF frequency, and vice versa.The Multiplexer and the IF drawer are hot swappable cards that can be replaced while the indoor isoperating.

Page 23: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 23/99

XC - Switching Board

The XC board is responsible for the N+1 functionality.When a radio problem occurs in one of the N links, the XC board builds an alternative path between thelocal and remote Multiplexer drawers. The switch between the paths is performed using the Hitless method.

Connection Panel

The fourth floor of the Baseband Indoor is responsible for most of the sub-rack connectivity. It includes theAuxiliary board, N-type connectors, and two power supply feeding boards.

N-Type Connectors

These are IF cable connectors located on the Connection Panel, which connect the Baseband Indoor andthe RFUs.

Power Supply Feeding Board

This board is responsible for the power distribution in the Baseband Indoor. There are two power supplyinput boards for power input redundancy.

Auxiliary

This board is responsible for all auxiliary traffic, including the Wayside Channel (E1, T1, Ethernet),management port interface, 64 Kbyte User Channel (V.11, RS232, Ethernet), and Engineering OrderWire.

1.9.3 – Power Supply

SAGEM-LINK T operates on DC power, which feeds the baseband indoor.A dual power source feeds two power distributor cards at the fourth level of the baseband indoor. Thesepower feeds back up each other and distribute the power to the different IDMs, which, in turn, feed theRFUs.The operational power supply range is -40.5V to 60V.

Page 24: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 24/99

1.10 – Auxiliary Channels

The following Auxiliary channels are available:

Wayside Channels

Up to four wayside channels can be used per baseband indoor. Each channel is dedicated to a singlecarrier.

The wayside channel type can be:

1. E1/Ethernet, software configurable

2. T1/Ethernet, software configurable

User Channels

Up to four user channels can be used per baseband indoor. The rate of each channel is up to 64 kbps.

The user channel type can be selected and configured via the LinkPilot management application.

Each user channel can be individually configured (as shown in the LinkPilot window below).

The user channel type can be:

• Asynchronous - RS-232 or V-11 (up to four channels)

• Synchronous - co/contra directional (up to four channels)

• Ethernet (up to four channels)

Note that an optional VoiP phone can be connected to the user channel Ethernet port, to enable dialingfrom one terminal to another terminal.

LinkPilot Auxiliary Channel Configuration

Page 25: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 25/99

Other Auxiliary Channels

Additional auxiliary channels include the following:

• EOW - 64 kbps connection for a headset (earphone + microphone), enabling voice (broadcast) fromone terminal to another terminal.

• External alarms - 8 inputs, 5 outputs

1.11 – Radio Protection Switching

The following is a description of the radio protection switching concept and functionality.

The N+1 radio protection system protects N carriers using an additional (+1) carrier (using diversefrequency channel or diverse polarization). When a fault is detected on one of the N carriers, a request fora protection path is sent to the remote side. The remote side then sends the traffic of the faulty carrier viaboth the regular and protected paths.

The transaction between the normal and diversity traffic is hitless, ensuring continuity of the data frameand clock. The faulty period is less than 10 ms.

Errorless switching is configured when setting up the switching criteria (“Switch on early warning”).

If the system detects more than one fault, the N+1 system will service the most severe fault first, wherebythe severity is defined in accordance with the following table.

Fault Priority Table

# Event Priority Remark

1 LockOut 1 (high) No switching is allowed, userconfiguration

2 Force Switch 2 Force protection of requiredchannel, user configuration

3 Radio (BB) LOF 3BB LOF indication from modemcard, or recognized by XC (loss offrame), or missing modem card

4 BB Excessive BER 4 High BER (>10e-6), XC calculation

5 BB SignalDegrade 5 Low BER (<10e-6), XC calculation

6 Early Warning(MSE) 6

Degradation of MSE underrequired reference; errorlessswitching

7 Manual 7 Protect required channel ifavailable, user configuration

8 None 8 (low) No protection switching required

Radio protection switching is performed by the XC card, through which all carrier traffic passes through, asshown in the following illustration.

The XC card supports up to a 4+1 configuration. For additional carrier protection, an additional basebandindoor is added, and two XC cards are chained, enabling support for up to a 9+1 configuration.

Page 26: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 26/99

One IDU in the chain is configured as the primary and the other as the secondary. The chaining modeenables the addition of five carriers for a 9+1 configuration.

Chaining is done using the XC chaining connector, and requires an SFP cable.

IF

IF

IF

IF

IFNMS & WAYSIDE POWER

IDM

Switch Matrix(XC)

IDM

IDMSTM-1

STM-1

STM-1IDC

IDC

IDC IDMSTM-1

IF

IF

IF

IF

IFNMS & WAYSIDE POWER

Switch Matrix(XC)

IDMSTM-1

IDC

IDC

IDMSTM-1

IDC

IDMSTM-1

IDMSTM-1

IDMSTM-1

IDMSTM-1

1.11.1 – Channel PrioritiesThe user can configure two priority groups:

• High priority

• Normal priority

Another associated configuration is the high priority threshold.

The following rules define the XC selection algorithm:

• If two carriers report a fault with a similar severity, the first channel will be serviced first.

• If two carriers from the same priority group report a fault, the channel with the most severefault will be serviced first.

• If two carriers from different priority groups report a fault, and the fault severity of the highpriority channel is greater than the high priority threshold, that channel will be serviced first.Otherwise, the previous rule will define the preferred channel.

• If the system detects more than one fault with the same severity, the link with the higherpriority will be serviced first, whereby the link priority is configured by the user.

Page 27: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 27/99

1.11.2 – Revertive ModeThe user can work in revertive or non-revertive mode. In revertive mode, the system automaticallyreturns the data to its original path when a fault situation is resolved.

In non-revertive mode, the system continues to protect the last channel (errorless protection) untila new higher priority fault occurs.

1.11.3 – Upgrade / DowngradeThe user can add a carrier to the N+1 group by inserting the module and setting a configurationcommand. When a new carrier is added to the N+1 group, the XC receives its status and handlesits requests, as with all other carriers.

All cards are hot-swappable (can be inserted during live traffic).

In the RF subrack, a new ICB with its filters and RFU will be chained to the existing ICBs.

1.11.4 – Link Topologies

The following configurations of SLT drawers were defined for various topologies. Note that theseconfigurations should be implemented exactly as described, for proper system functionality.

1+1HSB

1+1FD

2+1FD

Page 28: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 28/99

1.12 – ManagementSagem provides state-of-the-art management based on SNMP. Our management applications are writtenin Java code and can control Sagem units at both the element and network levels. The applications run onWindows 2000/XP systems.

The LinkPilot software enables the operator to perform element configuration, performance monitoring,remote diagnostics, alarm reports, and more. This software can be integrated with different NMS platformsto provide more comprehensive system management.

Example of LinkPilot Main Window

3+1FD

4+1FD

Page 29: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 29/99

Chapter 2SAGEM-LINK T Specifications

2.1 – SAGEM-LINK T Specifications (STM-1)

RF Parameters

Frequency 6L GHz 6H GHz 7 GHz 8 GHz 11 GHz

Standards ETSI/FCC ETSI/FCC ETSI ETSI ETSI/FCC

RF ChannelSpacing(MHz)

28/30 40 28/29.65 28/29.65/40 30/40

Tx Out(dBm)

33 dBm @ 64 QAM

32 dBm @ 128 QAM

29 dBm @ 64 QAM29 dBm @ 128 QAM

System Gain(dB)

104 dB @ 64 QAM

102 dB @ 128 QAM100 dB @ 64 QAM98 dB @ 128 QAM

ATPC(dB) > 20 dB

Capacity N+1 x 155 Mbps

Modulation 64/128 QAM

SystemConfigurations

Unprotected: 1+0 to 10+0

Protected:

1+1 Hot Standby, 1+1 to 9+1, Frequency Diversity, co-channel operation with XPIC(CCDP)

All configurations are available with Space Diversity

WaysideChannels

NxE1/T1, Ethernet Bridge 10BaseT

User Channels V.11, RS-232, 10BaseT, G.703 (optional)

ExternalAlarms

8 inputs, TTL-level contact closure to ground, 5 outputs, form C contacts, softwareconfigurable

EOW 64 Kbps Engineering Order Wire

InterfaceModules

STM-1/OC-3: Electrical - CMI/BNC, Optical - SM/SC, SM/MM

Switching Hitless

Payload Types TDM: SDH STM-1, SONET OC-3, DS3

ATM: ATM over SONET/SDH

Page 30: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 30/99

Waveguide Flanges

The radio output port (C') is frequency dependent, and is terminated with the following waveguide flanges:

Frequency Band (GHz) Waveguide Flange

6L CPR1376H CPR1377 CPR1128 CPR11211 CPR90

Branching Loss

The following table lists the system branching loss, measured at C'.

ICC3 has a 0 dB loss, since the RFU was calibrated to Pmax, together with the filter and 1+0 branchingloss.

Dual Polarization Configuration

Configuration 1+1FD 2+1 3+1 4+1 5+1 6+1 7+1 9+1

Losses (dB) 0.2 0.6 0.6 1 1.4 1.9 1.9 2.3

Single Polarization Configuration

Configuration 1+0 1+1 HSB 1+1 FD 2+1 3+1 4+1Losses

(dB) 0.2 1.6 0.6 1 1.5 1.9

Page 31: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 31/99

Power Consumption

The following table lists the total system power consumption for each card/unit, perspecific configuration (All-Indoor only). Power Supply from -40.5 to -60 VDC.

Card/UnitWatts

perUnit

1+0 1+1 2+1 3+1 4+1 5+1 6+1 7+1 8+1 9+1

RFU 100 1 2 3 4 5 6 7 8 9 10

Fan Tray 30 0.5 0.5 1 1 1 2 2 2 2 2

IDC 12 1 2 2 3 3 5 5 5 6 6

XC 4 1 1 1 1 1 2 2 2 2 2

IDM 20 1 2 3 4 5 6 7 8 9 10

Aux 3 1 1 1 1 1 2 2 2 2 2

Total PowerConsumption (W) 154 286 421 553 673 854 974 1094 1226 1346

The following table lists the power consumption for an N+1 split-mount system (Split-Mountconfigurations only, whereby the RFUs are installed outdoors near the antennas). PowerSupply from -40.5 to -60 VDC.

Card/Unit Wattsper Unit 1+0 1+1 2+1 3+1 4+1 5+1

RFU 80 1 2 3 4 5 6

IDC 12 1 2 2 3 3 5

XC 4 1 1 1 1 1 2

IDM 20 1 2 3 4 5 6

Aux 3 1 1 1 1 1 2

Total PowerConsumption (W) 119 231 331 443 543 674

Page 32: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 32/99

Network Management

Type SNMP, in compliance with RFC 1213, RFC 1595 (SONET MIB)

Local or RemoteNMS Station

LinkPilot with advanced GUI for Windows 2000/XP, integrated with SAGEMIONOS-NMS Platform

NMS Interface Ethernet bridge 10Base-T, RS-232 (PPP, SLIP), built-in Ethernet hub

LocalConfigurationand Monitoring

Standard ASCII terminal, serial RS-232

In-BandManagement DCCr, DCCm, media-specific, proprietary

TMN NMS functions are in accordance with ITU-T recommendationsfor TMN

PerformanceMonitoring

Integral with onboard memory per ITU-T G.828

Mechanical

TransceiverDimensions(withouthandles)

One sub rack:Height: 445 mmWidth: 432 mmDepth: 280 mm

N+1 BasebandSubrackDimensions

Height: 172 mmWidth: 432 mmDepth: 240 mm

Rack Type ETSI 300 mm depth

Environmental

RFUETS 300 019-1-4 class 4.1, with an operating temperature range of -50°Cto 55°C

Indoor Units Operating temperature range of -5°C to +45°C

Storage ETS 300 019-2-2 class 1.2, with a maximum temperature limit of +85°C

Transportation ETS 300 019-2-2 class 2.2

EMC and Safety

EMC compliant with the conditions specified in EN 300 385 [9], for class B.

Safety The system complies with the UL 1950 and EN 60950 safety standards.

Page 33: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 33/99

MTBF

The following table lists the calculated MTBF-values for each SAGEM-LINK T unit.

MTBF of a 1+0 terminal = 35.3 years

MTBF (availability) of a 1+1 terminal = > 90 years

Cards/Units MTBF (Years)

IDC 100XC 100IDM 50RFU 120

2.2 – Frequency Channels

6L GHz (5.85-6.45 GHz)

ITU-R F.383-7 [1-3]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 5955.00 1 6195.002 5995.00 2 6235.003 6035.00 3 6275.004 6075.00 4 6315.005 6115.00 5 6355.00

240

6 6155.00 6 6395.00

ITU-R F.383-7 [0] / FCC 101.147(i8)

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 5945.20 1 6197.242 5974.85 2 6226.893 6004.50 3 6256.544 6034.15 4 6286.195 6063.80 5 6315.846 6093.45 6 6345.497 6123.10 7 6375.14

252.04

8 6152.75 8 6404.79

Page 34: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 34/99

FCC 101.147(i7)

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz

1 5935.32 1 6187.362 5945.2 2 6197.243 5955.08 3 6207.124 5964.97 4 6217.015 5974.85 5 6226.896 5984.73 6 6236.777 5994.62 7 6246.668 6004.5 8 6256.549 6014.38 9 6266.4210 6024.27 10 6276.3111 6034.15 11 6286.1912 6044.03 12 6296.0713 6053.92 13 6305.9614 6063.8 14 6315.8415 6073.68 15 6325.7216 6083.57 16 6335.6117 6093.45 17 6345.4918 6103.33 18 6355.3719 6113.22 19 6365.2620 6123.1 20 6375.1421 6132.98 21 6385.0222 6142.87 22 6394.9123 6152.75 23 6404.79

252.04

24 6162.63 24 6414.67

Page 35: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 35/99

ITU-R F.384-7

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 5955.00 1 6215.002 6015.00 2 6275.003 6075.00 3 6335.00

260

4 6135.00 4 6395.00

ITU-R F.497-6 [0]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 5941.00 1 6207.002 5969.00 2 6235.003 5997.00 3 6263.004 6025.00 4 6291.005 6053.00 5 6319.006 6081.00 6 6347.007 6109.00 7 6375.00

266

8 6137.00 8 6403.00

6H GHz (6.45-7.1 GHz)

ITU-R F.384-7

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 6460.00 1 6800.002 6500.00 2 6840.003 6540.00 3 6880.004 6580.00 4 6920.005 6620.00 5 6960.006 6660.00 6 7000.007 6700.00 7 7040.00

340

8 6740.00 8 7080.00

Page 36: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 36/99

FCC 101.147(k7)

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 6545 1 67152 6555 2 67253 6565 3 6735170

4 6585 4 67451 6595 1 67552 6605 2 67653 6615 3 67754 6625 4 67855 6635 5 67956 6645 6 68057 6655 7 68158 6665 8 68259 6675 9 683510 6685 10 684511 6695 11 6855

160

12 6705 12 686540 1 6535 1 6575

7 GHz (7.1-7.9 GHz)

ITU-R 385-7 [1]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 7442 1 75962 7470 2 76243 7498 3 76524 7526 4 7680

154A

5 7554 5 7708

Page 37: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 37/99

ITU-R 385-7 [1]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 7456 1 76102 7484 2 76383 7512 3 76664 7540 4 7694

154B

5 7568 5 7722

ITU-R 385-7 [0]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 7138.5 1 7299.52 7226 2 73873 7428 3 7589

161

4 7526 4 7687

ITU-R 385-7 [1]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 7442 1 76872 7470 2 77153 7498 3 77434 7526 4 77715 7554 5 77996 7582 6 78277 7610 7 7855

245

8 7638 8 7883

Page 38: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 38/99

ITU-R 385-7 [0]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 7138.5 1 7299.52 7166.5 2 7327.53 7194.5 3 7355.54 7222.5 4 7383.55 7250.5 5 7411.511 7145.5 11 7306.512 7173.5 12 7334.513 7201.5 13 7362.514 7229.5 14 7390.521 7152.5 21 7313.522 7180.5 22 7341.523 7208.5 23 7369.524 7236.5 24 7397.531 7159.5 31 7320.532 7187.5 32 7348.533 7215.5 33 7376.5

161A

34 7243.5 34 7404.5

ITU-R 385-7 [0]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 7263.5 1 7424.52 7291.5 2 7452.53 7319.5 3 7480.54 7347.5 4 7508.55 7375.5 5 7536.511 7270.5 11 7431.512 7298.5 12 7459.513 7326.5 13 7487.514 7354.5 14 7515.521 7277.5 21 7438.522 7305.5 22 7466.523 7333.5 23 7494.524 7361.5 24 7522.531 7284.5 31 7445.532 7312.5 32 7473.533 7340.5 33 7501.5

161B

34 7368.5 34 7529.5

Page 39: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 39/99

ITU-R 385-7 [0]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 7438.5 1 7599.52 7466.5 2 7627.53 7494.5 3 7655.54 7522.5 4 7683.55 7550.5 5 7711.511 7445.5 11 7606.512 7473.5 12 7634.513 7501.5 13 7662.514 7529.5 14 7690.521 7452.5 21 7613.522 7480.5 22 7641.523 7508.5 23 7669.524 7536.5 24 7697.531 7459.5 31 7620.532 7487.5 32 7648.533 7515.5 33 7676.5

161C

34 7543.5 34 7704.5

ITU-R 385-7 [0]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 7563.5 1 7724.52 7591.5 2 7752.53 7619.5 3 7780.54 7647.5 4 7808.55 7675.5 5 7836.511 7570.5 11 7731.512 7598.5 12 7759.513 7626.5 13 7787.514 7654.5 14 7815.521 7577.5 21 7738.522 7605.5 22 7766.523 7633.5 23 7794.524 7661.5 24 7822.531 7584.5 31 7745.532 7612.5 32 7773.533 7640.5 33 7801.5

161D

34 7668.5 34 7829.5

Page 40: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 40/99

ITU-R 385-7 [3]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 7457 1 76252 7485 2 76533 7513 3 76814 7541 4 7709

168B

5 7569 5 7737

ITU-R 385-7 [1]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 7428 1 76102 7456 2 76383 7484 3 76664 7512 4 7694

182

5 7540 5 7722

ITU-R 385-7 [3]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 7121 1 73172 7149 2 73453 7177 3 73734 7205 4 7401

196

5 7233 5 7429

Page 41: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 41/99

ITU-R 385-7 [4]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 7442 1 76872 7470 2 77153 7498 3 77434 7526 4 77715 7554 5 77996 7582 6 78277 7610 7 7855

245

8 7638 8 7883

8 GHz (7.8-8.5 GHz)

ITU-R 386-6 [4]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 7926 1 81922 7954 2 82203 7982 3 82484 8010 4 82765 8038 5 83046 8066 6 83327 8094 7 8360

266

8 8122 8 8388

Page 42: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 42/99

ITU-R 386-6 [1]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 7747.70 1 8059.022 7777.35 2 8088.673 7807.00 3 8118.324 7836.65 4 8147.975 7866.30 5 8177.626 7895.95 6 8207.277 7925.60 7 8236.92

311.32A

8 7955.25 8 8266.57

ITU-R 386-6 [1]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 7732.875 1 8044.1952 7762.525 2 8073.8453 7792.175 3 8103.4954 7821.825 4 8133.1455 7851.475 5 8162.7956 7881.125 6 8192.4457 7910.775 7 8222.095

311.32B

8 7940.425 8 8251.745

ITU-R 386-6 [3]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 8293 1 84122 8307 2 84263 8321 3 84404 8335 4 84545 8349 5 8468

119

6 8363 6 8482

Page 43: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 43/99

11 GHz (10.4-11.7 GHz)

ITU-R 387-8[0] / CEPT 12-6 E

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 10715 1 112452 10755 2 112853 10795 3 113254 10835 4 113655 10875 5 114056 10915 6 114457 10955 7 114858 10995 8 115259 11035 9 1156510 11075 10 1160511 11115 11 11645

530

12 11155 12 11685

ITU-R 387-8[0,2] & FCC 101.147 [7]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 10735 1 112252 10775 2 112653 10815 3 113054 10855 4 113455 10895 5 113856 10935 6 114257 10975 7 114658 11015 8 115059 11055 9 1154510 11095 10 1158511 11135 11 11625

490

12 11175 12 11665

Page 44: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 44/99

CEPT 12-6 E

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz1 10715 1 112052 10755 2 112453 10795 3 112854 10835 4 113255 10875 5 113656 10915 6 114057 10955 7 114458 10995 8 114859 11035 9 1152510 11075 10 11565

490

11 11115 11 11605

FCC 101.147 [6]

T/RSeparation

n(L)

CenterFrequency

MHz

n(H)

CenterFrequency

MHz

500 1 10715 1 112152 10755 2 112453 10795 3 112854 10835 4 113255 10875 5 113656 10915 6 114057 10955 7 114458 10995 8 114859 11035 9 1152510 11075 10 1156511 11115 11 11605

490

12 11155 12 11645500 13 11185 13 11685

Page 45: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 45/99

Chapter 3SAGEM-LINK T Installation

3.1 – General

This guide provides instructions for SAGEM-LINK T system installation at the customer site.

SAGEM-LINK T is an All-Indoor system, designed for simple installation and quick upgrade.

The equipment is generally supplied mounted, except for the RFUs, which are provided in a separatepackage, unless otherwise specified by the customer.

3.2 - Required Parts and Tools

An installation kit is supplied with the system.

The kit contains the following parts:

Part Description Quantity Comments

Offset hexagon key wrenches for M10 1 -

Offset hexagon key wrenches 3/16 1 -

Offset hexagon key wrenches 5/32 1 -

Screw socket head #8 or #6 and washer 8 or 12 Per ICC

Screw socket head #10 and washer 2 Per ICB

Coupling nut 3 Per ICB

Screw socket head M10 3 Per ICB

Washer spring M10 3 Per ICB

Screw socket head #8 or #6 and washer 8 or 12 Pertermination

Page 46: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 46/99

Required Tools

• Hammer drill

• Masonry bit, Ø12 mm

• Small hammer

• Tape measure

• Pencil

• Adjustable wrench

3.3 – Transportation and Handling

PackingThe equipment rack is packed at the factory, and sealed moisture-absorbing bags are inserted.

TransportationThe equipment is prepared for public transportation. The cargo must be kept dry during transportation, inaccordance with ETS 300 019-1-2, Class 2.3.

It is recommended to transport the equipment to the installation site in its original packing case.

If intermediate storage is required, the packed equipment must be stored in dry and cool conditions and outof direct sunlight, in accordance with ETS 300 019-1-1, Class 1.2.

InspectionCheck the packing lists, and ensure that the correct part numbers and quantities of components arrived.

Page 47: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 47/99

3.4 – Installation Procedures

The sections below describe the SLT installation procedures.

3.4.1 - ICC to ICB AssemblyThis section explains how the ICC (Indoor Combining Circulator) is assembled to the ICB (Indoor CirculatorBlock).

To assemble the ICC to the ICB, do the following:

1. Connect the ICB to ICC, as shown in the illustrations below, before mounting the assembled parts inthe sub-rack. Fasten the screws and washers in accordance with the specific configuration.

ICB-ICC Assembly

2. For N+1 configurations (ICB concatenation), insert three coupling nuts in the appropriate grooves,as shown in the illustration below.

Page 48: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 48/99

Coupling Nut Insertion

3. Place the assembled part in the sub-rack, in accordance with its final configuration, and fasten twoscrews and washers using the supplied key.

ICC-ICB Mounting on Subrack

Page 49: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 49/99

4. Concatenate the ICB units in accordance with the final configuration, and fasten three screws andwashers using the supplied socket key, in accordance with the described order.Tighten the screws to 35 Nm.

ICB Concatenation

5. If this is to be the last concatenated ICB, assemble 50 ohm terminations on its left ports (two or threeterminations for Space Diversity). Fasten the screws and spring washers.

Termination Mounting

Page 50: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 50/99

6. Connect the WA-0223-X (location recognition and fan control) cable to the selected 16-pin connectoron the back plane (this connection sets the RFU sub-rack slot location for the managementapplication).The cable should be connected to the 16-pin connector immediately below the ICB.Configure SW2 on the back plane to position 1 for the upper subrack, and position 2 for the lowersubrack.

Cable Connection to Backplane

Connect WA-0233-X (TNC cable) to the selected location in the patch panel.Connect WA-0233-X (N-type cable) to the selected location in the patch panel.

Page 51: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 51/99

Cable Connection

7. Insert the RFU in the ICB, and fasten the two screws using the supplied key.Tighten the screws to 18-20 Nm.

RFU Mounting

3.4.2 – Configuration Tables

The tables below list ICB-ICC installations according to the different configurations.

E-W = East-West

SD = Space Diversity

HSB = Hot Standby

Page 52: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 52/99

Placement on Upper Subrack

ConfigurationICB-ICC

Placement onSubrack

ICB Placementon Subrack

1+1 HSB 1/5 -

1+1 HSB SD 1/5 -

1+1 HSB E-W 1/5/8/12 -

1+1 HSB E-W SD 1/5/8/12 -

2+1 XPIC 1/10 3

2+1 XPIC SD 1/10 3

3+1 XPIC 1/10 3/6

3+1 XPIC SD 1/10 3/6

4+1 XPIC 1/10 3/6/12

4+1 XPIC SD 1/10 3/6/12

1+1/2+0 2 4

1+1/2+0 SD 2 4

2+1/3+0 2 4/7

2+1/3+0 SD 2 4/7

3+1/4+0 2 4/7/9

3+1/4+0 SD 2 4/7/9

4+1/5+0 2 4/7/9/11

4+1/5+0 SD 2 4/7/9/11

Page 53: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 53/99

Placement on Lower Subrack

ConfigurationICB-ICC

Placement onSubrack

ICB Placementon Subrack

2+2 HSB E-W 1/5 -

2+2 HSB E-W SD 1/5 -

2+1 XPIC E-W 1/10 3

2+1 XPIC E-W SD 1/10 3

3+1 XPIC E-W 1/10 3/6

3+1 XPIC E-W SD 1/10 3/6

4+1 XPIC E-W 1/10 3/6/12

4+1 XPIC E-W SD 1/10 3/6/12

2+1 XPIC 1/10 3/6/12

2+1 XPIC - -

N+1 XPIC 1/10 3/6/12

1+1 HS 1/5 -

1+1 HS E-W 1/5/8/12 -

2+0 XPIC 1/5 -

2+0 XPIC E-W 1/5/8/12 -

Page 54: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 54/99

3.4.3 – Rack Installation

The sections below explain the methods used to install the SAGEM-LINK T rack. It is possible to use someof the methods together, depending on the layout plan.

The following illustration shows the rack dimensions and the system layout in the rack.

Width = 600 mm, Depth: 300 mm

AUX. SUBRACK

SUBRACKTOP

SUBRACKBOTTOM

BASEBAND INDOOR

BASEBAND INDOOR

Page 55: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation ManSagem Communications document. Reproduction and

3.4.4 – Securing to Floor

1. Place the rack upright, and position it according to the layout plan, using its adjustable legs.

2. Mark the places through the holes, remove the rack, and drill 4 corresponding holes in the floor.

3. Place the rack back in its position, and align it in the correct vertical position by adjusting the legs.

4. Remove the flanged nuts from 4 expansion plugs (item 9 in the table above). Place expansion plugsin the holes, and gently hammer them into place. Place the flanged nuts back in their positions andtighten them to 30 (Nm).

Mounting to Floor

3.4.5 – Securing to Wall

1. Mount the 2 support brackets (item 4 in the table above) on the re(item 6) and 2 washers (items 7 and 8) for each support bracket.

2. Align the rack to its correct vertical position by adjusting the legs.

3. Draw marks through the 2 holes, remove the rack, and drill corres

4. Place the rack back in its position.

5. Remove the flanged nuts from 2 expansion plugs (item 9), place gently hammer into place. Place the flanged nuts back in their po

Adjustable Leg(x4)

ual 3000299570-R11-000-01 disclosure prohibited Page 55/99

ar side of the rack, using 2 screws

ponding holes in the wall.

expansion plugs in the holes, andsitions and tighten them to 30 (Nm).

Page 56: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 56/99

Mounting to Wall

Page 57: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 57/99

3.4.6 – Rack Concatenation

It is possible to concatenate racks in order to increase the N+1 system for up to 10 RFU units.

1. Fix a single rack using at least one method described in the section above.

2. Place an additional rack against the fixed rack, side-by-side.

3. Insert 2 screws (item 1) and 2 washers (items 2 and 3) from one rack, and fasten them on the otherrack using 2 nuts (item 4) and 2 washers (items 2 and 3). Tighten the screws to 40 (Nm).

Note: You can use the supplied wrench socket key (item 11).

Rack Concatenation

Page 58: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 58/99

3.4.7 - Connecting the Power SupplyConnect the GND and -48 VDC terminals of power supplies A and B to the terminal strip, as shown in thefollowing illustration:

PSU A -48 VDC

PSU B -48 VDC

PSU A Neutral

PSU B Neutral

Site GND

3.4.8 - Installing the RFUs1. Remove the RFU from its package, and insert it in the ICB assembly.

2. Using the supplied wrench socket key (item 10), tighten the 2 captive screws to 18-20 (Nm).

3. Repeat this procedure for the remaining RFUs.

3.4.9 - Connecting the IDMs1. Remove the IDM from its package, and insert it in the SLT Baseband unit.

2. Tighten the 2 captive screws.

3. Repeat this procedure for the remaining IDMs.

3.4.10 - Connecting the Bends1. Connect the waveguide bends to the waveguide outputs at the top of the rack, for easier connection

to the elliptical waveguides (if necessary).

2. Make sure flanges are aligned correctly and all 8 screws are tightened.

3.4.11 – Switching the System OnAfter all waveguides are connected to their respective elliptical waveguides, turn the system on by poweringon all installed IDMs.

Powering ON the system while waveguides are open ishazardous. You may be subjected to electro-magnetic radiationeffects!

Page 59: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 59/99

Chapter 4Initial System Setup

4.1 – General

After the system is installed and antenna alignment is performed, the next step is initial IDU setup andconfiguration.

Initial setup procedures are performed on a craft terminal via a serial port connection. Additional setupprocedures are performed using the LinkPilot software supplied with SAGEM-LINK T.

For a complete description of LinkPilot, refer to the SAGEM-LINK A installation and user manual (providedin the CDROM).

Note: The craft terminal should be used only to perform the initial setup procedures described in thischapter. Once the system is up and running, use LinkPilot to maintain and operate the system on a regularbasis.

4.2 – Initial Setup Steps for up to 4+1 Configuration

The following initial setup procedure refers to one SLT IDU at each site, which allows the user to reach aconfiguration of up to 4+1 (five carriers).

The procedure includes the following steps:

Procedures Performed using a Craft Terminal:

• Connecting to the IDU via serial port. The SLT IDU consists of three levels (IDCs) that need to beconnected to.

• Defining IP addresses for each one of the three IDCs.

• Setup options.

Procedures Performed using Link Pilot :

• Connecting to the Ethernet ports (two ports on the top panel of the IDU)

• Installing the software

• Starting LinkPilot and connecting to the unit, specifying the IP address of the middle level (IDC)

• Setting the local Tx frequency channel for the five carriers

Note: The protected carrier is the one connected to the upper left drawer.• Specifying system information

• Configuring the local/remote transport

• Configuring trap forwarding

• Setting up external alarms

Connecting the Line Interfaces

Page 60: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 60/99

4.3 – Initial Setup Using the Craft Terminal

The following procedures are performed after the ODU/RFU and antenna are installed.

4.3.1 - Connecting to the IDU via Serial PortTurn the IDU power switch ON, and note the following:

• Make sure that the color of the main power LED on the IDU front panel is blue. (Note that there aretwo main power inputs to the IDU.)

• On the front panel of each of the five IDMs, make sure the color of the power LED is green.

To set up the HyperTerminal connection:

1. Connect the RS-232 port of your computer to the RS-232 (9-pin) port on the IDU front panel. Thisport is labeled “Terminal”.

2. Select Start, Programs, Accessories, Communication, HyperTerminal.

3. Double-click the HyperTerminal application icon.

4. For Connection Description, type Terminal, and click OK.

5. In the Connect Using field (Phone Number), select Direct to Com 1, and click OK.

6. In the Port Settings tab (Com 1 Properties), specify the following settings:

• Bits per second - 19,200

• Data bits - 8

• Parity - None

• Stop bits - 1

• Flow control - Hardware

7. Click OK.

8. After you connect to the terminal, to enter the terminal setup program, press Enter.

9. For password, use admin.

Page 61: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 61/99

4.4 – Initial Setup Steps for up to 9+1 Configuration

Cascading two SLT IDUs at each site will enable a configuration of up to 9+1 (10 carriers), or XPIC 7+1with two additional carriers.

The setup steps for a configuration of up to 9+1, are identical to those of the configuration of up to 4+1 (seeabove) except for the following differences:

• You must configure all six IDCs using the HyperTerminal.

• You must specify if you are using cascading mode, using the HyperTerminal

• You must specify in which IDU the protected link will be defined.

4.4.1 - To set the cascading mode:1. In the main terminal program menu, select Configuration.

2. Select System configuration.

3. Select Cluster configuration.

Specify the number of sub-racks in the system. 1 for stand alone, or 2 for cascading mode.

Specify either 1 or 2 for the sub-rack number. The protected carrier will be in sub-rack 1.

4.5 – Defining IP Addresses

Before you can configure the SLT system, you need to define four IP addresses using the craft terminal.

SAGEM-LINK T includes three levels of two IP interfaces: an Ethernet interface, and a serial interface.Each interface has its own IP address and IP mask.

You must configure an IP address for each of the three IDCs - a unique shelf number for each shelf in thecluster.

Page 62: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 62/99

In addition, you must define same base IP address for every SLT IDC. The address is a four digit numberseparated by decimal points. Each IP address is a pair netid-hostid, where netid identifies a network, andhostid identifies a host on the network. The IP mask separates between the netid and hostid.

For example, if the IP address is 192.114.35.12 (11000000 01110010 00100011 00001100), and the IPmask is 255.255.255.0 (11111111 11111111 11111111 00000000), the netid is 192.114.35, and the hostidis 12.

An IP interface can only communicate with hosts that are on the same net (have the same netid). In theexample above, the interface can communicate only with hosts that have netid 192.114.35 (for 1 to 255).

If SLT has a frame to send to a host that is not on the Ethernet IP netid or the serial IP netid, the frameshould be sent to an intelligent device (usually a gateway) on the network. Such a device, known as a"default router", will know how to send the frame over the internet. The default gateway should be a host onone of the SLT interface netids.

The SLT cluster is managed as a single Network Element (NE) by the LinkPilot software.

The following figure illustrates a SLT management model from an EMS/NMS point of view.

LinkPilot

SLT GNE A SLT NE B

SLA NE C

SLA NE D

Each IDC calculates its own IP address, considering cascade shelf# and floor#:##*3 floorshelfIPbaseIP ++= ,

where:

IPbase is dividable by 8 (i.e. = IPbase & 0xfffffff8),

shelf# = 0, which is the cascade master (the one with the protected carrier), or 1 for cascade slave,

floor# = 1, 2, or 3 (the number of the floor within the SLT shelf)

In-Band Management

In-band management of the SLT link chain must be configured carefully due to a large number of public IPaddress allocations. In addition, it should be noted that in-band management becomes a limiting factor forchain length when only the Class C DCN is used.

The figure below illustrates the largest Class C in-band subnet (with CIDR = 26 bits, i.e. subnet mask255.255.255.192).

Page 63: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 63/99

The DCN shown in the figure makes use of the 192.168.1.64 in-band subnet. This subnet allows 62 nodes192.168.1.65 - 192.168.1.126, and has a broadcast address of 192.168.1.127.

It is assumed that the SLT at site A has a single GNE 1 assigned to one of the IDCs.

All three IDCs at site A have direct out-of-band IP connectivity with remote management applications(LinkPilot, IONOS-NMS...). The remaining SLT chain IP addresses are accessed via the GNE IDC.

LinkPilot

SLT GNE 1 SLT NE 2

SLT NE 3

SLT NE 6

SLT NE 7SLT NE 8SLT NE 8

SLT NE 5

SLT NE 4

Note that the Inband bytes run through the upper level of the cluster.

The Ethernet interface of every Network Element (NE) is assigned the CIDR=/29 subnet, i.e. subnet mask255.255.255.248. This allows 6 elements to be communicated over the interface. These addresses can befully utilized when two SLT shelves are cascaded for 7+1 group protection.

The figure above shows “back-to-back” connected SLT shelves at the same sites: B, C, and D, forEast/West chaining. Two NE IDCs (NE 2 and NE 3), at the same site, are connected over a PPPoE link.

This scheme allows four links of up to 7+1 (eight SLT shelves, as shown, or sixteen SLT shelves cascadedin pairs) chained through the same LinkPilot management, when IP addresses are allocated as describedabove.

Notes:

1. The CIDR=/29 subnet allows external element communication (such as a laptop connected to thesite B LAN) only if there are less than six IDCs operating on two cascaded SLT shelves. The subnetis not sufficient for three SLT cascading shelves. Three cascaded shelves require CIDR=/28 nodes(subnet mask 255.255.255.240). This reduces the available number of chained links to 50%.

2. High protocol timing constraints (SNMP/TFTP) are expected in SLT link chains due to the largenumber of hops (each East/West site adds two in-band routing hops), and a large number ofmanaged IDC nodes.

The following slight optimization may be useful for a chain topology (but not for a ring):

One of the in-band NE management channels is configured as a Default GNE Direction, assumingthe channel leads to the nearest GNE under normal conditions. Then, in-band routing chooses thischannel as a first priority for every “in-band packet” generated internally, or received from theEthernet interface.

To define IP Addresses:1. In the main terminal program menu, select Configuration.

Page 64: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 64/99

2. Select System configuration.

3. Select IDC configuration.

4. Select IDC Basic configuration.

5. Select IP.

6. Define the addresses as described above: element IP and basic IP of the units.

Important: After you set up IP addresses, restart the IDUs to activate them.

7. Repeat the steps above for the remaining IDCs in the SLT IDU.

Page 65: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 65/99

4.6 – Setup Options in the Terminal Program

The main menu in the terminal setup program includes the following options:

Configuration (1) - the main setup section in which you can configure the IDC, the right and left drawers,protection, SNMP management, in-band routing, and other such parameters.

System Status (2) - used to obtain information about the different software versions currently used in thesystem.

Maintenance (3) - used to perform software upload, download, and reset.

Diagnostics (4) - used to perform loopbacks and obtain system information.

Logs (5) - used to view alarm and configuration log reports.

4.7 – Additional Setup Using LinkPilot

After you perform initial setup via the terminal, some additional procedures should be performed viaLinkPilot software.

Note: The information in this section is provided only for basic initial setup. More detailed information aboutLinkPilot can be found in the SAGEM-LINK A Installation and Operation manual (provided in the CDROM).

Connecting to the Ethernet Port1. Connect a crossed Ethernet cable from your PC to the Ethernet Port. If the connection is to a LAN

(wall connection), use the standard Ethernet cable.

2. Make sure the IP address on your PC is on the same sub-net as the one you defined for the SLT IDU(in most cases, the first three numbers of the IP address must be identical, depending on the sub-netmask).

LinkPilot PC RequirementsBefore you install the LinkPilot software, verify that your PC has the following minimum requirements:

Windows

Processor: Pentium 4, 2.8 GHz (minimum)

Memory (RAM): 256 MB minimum

Operating System: Windows 2000 or above

Serial Port: RS-232 (Hyper-Terminal)

Installing the LinkPilot Management Software1. Insert the LinkPilot CD in the CD drive.

2. In Windows Explorer, double-click the setup.exe file.

The installation program begins.

3. Follow the instructions displayed.

Page 66: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 66/99

Starting LinkPilot1. Select Start, Programs, LinkPilot, LinkPilot Element Manager.

The LinkPilot Login window appears.

LinkPilot Login Window2. Enter the IP address of the second IDC, and the SNMP community (for SNMP protocol access). If

you are working in cascading mode, select the IP address of the second IDC in the master unit.

3. For User Name use “admin” and for Password use “admin”.

4. Select Save Password if you want LinkPilot to remember the password you entered.

Note that there are two types of passwords, each with a different security level for authorized activities:Read Only - user can perform monitoring activities only.

Read/Write - user can change system configuration and system administrator parameters, andperform monitoring activities.

After you log in, the Main LinkPilot window appears.

Page 67: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 67/99

Starting the Local Tx Frequency ChannelIf the Tx frequency was previously defined using the HyperTerminal, use the frequency window in LinkPilotonly to verify that the correct frequency was set.

Note that the concept of N+1 system configuration is to first configure all the carriers separately to work asa stand alone system. After all the carriers are set up as an N+0 configuration, including the XPIC links,then the protection type is configured.

1. Select Configuration, RFU, RFU Configuration, or click the RFU icon in the tool bar.

At the top of the window, the system displays Tx/Rx ranges, the gap between them, and the channelbandwidth.

RFU Configuration Window2. In the Frequency Control section, set the Tx Channel to the required channel. By default, it is set to

the first channel. If you are unsure of the required channel, refer to Chapter 2 for channelallocations.

The frequency of the selected Tx channel appears in the Tx Frequency field.

3. If you prefer, you can set the Tx frequency by entering a frequency, in MHz, in the Tx Frequencysection. If the frequency is not available, a warning message will appear to enable the enteredfrequency, or to change it to the nearest available channel.

4. Select the XPIC option (which appears under the RFU illustration) to activate the XPIC mechanism.The mechanism is used to cancel cross polar interference in a dual polarization system.

Page 68: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 68/99

5. Select the Local Only option. By default, the Local + Remote option is selected. However, since thereis no connection to the remote unit at this time, the Local + Remote option is not available.

6. Click Apply to save the settings.

7. Click Close.

Setting up the N+1 Configuration1. Select Protection, H/W protection, H/W protection type.

H/W Protection Type Window

2. Click the Protection Topology drop-down list and select the required configuration, as follows:

HSB 1+1 - the upper level is activated with two drawers that protect each other, while the standbydrawer is muted.

HSB 2+2 - levels one and three of the IDU are activated. Each level protects the other when thestandby IDU is muted. Each level operates in XPIC mode. External protection cablesneed to be connected between levels one and three.

1+1 - the +1 algorithm is activated. The upper level includes two carriers, whereby the left one isprotected.

2+1 - three separate carriers with one protected.

3+1 - four separate carriers with one protected.

4+1 - five separate carriers with one protected.

5+1 - cascade mode, six separate carriers with one protected.

6+1 - cascade mode, seven separate carriers with one protected.

7+1 - cascade mode, eight separate carriers with one protected.

8+1 - cascade mode, nine separate carriers with one protected.

9+1 - cascade mode, ten separate carriers with one protected.

3. Select Protection, H/W protection, H/W protection configuration.

The following window will appear if the protection type you selected was between 1+1 and 9+1.

Page 69: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 69/99

H/W Protection Configuration Window

4. Select Protection Enabled.

5. Select Switch On Early Warning if you want the switch to occur when the system reaches an MSEof -28.

6. For Revertive Link, select the carrier that will be connected to the +1 modem. Your selection will beused in cases where a switch occurs and then the system returns to normal operation.

Examples

Revertive = Extra TrafficIf a major alarm occurs at site A, a request is sent to site B to transmit through the Extra Trafficchannel. The switch that is performed is Hitless (up to 10 mS), and the Extra Traffic channel will nolonger exist on both sides by definition (generally, the system can protect up to two faults at differentsides). The moment the alarm is cleared, the +1 (Extra Traffic) modem will refer to the input from the+1 MUX.

Revertive = NoneEach carrier MUX will receive two inputs: its own modem, and the +1 modem. The Extra Trafficchannel will not exist. Data to the MUX (for each of the defined carriers) will be received from its ownmodem until the first hitless fault. When the fault is cleared, the MUX will receive data from twosources: the +1 modem, and its own modem, meaning the next fault in this channel will be errorless(if other carriers will fail, the data will be hitless).

Revertive = Carrier#XMUX number X will always receive two sources: the +1, and its own, unless there is a fault in anothercarrier. If MUX number X receives two sources, and a fault occurs, the switch is errorless. In all theother cases, the switch is hitless.

7. For Revertive Switch Timeout, specify the period (in seconds) after which the revertive mode willbe activated.

8. For High Priority Threshold, click the drop-down list and select the criteria upon which the systemwill perform a switch to the channel you chose as high priority.

Page 70: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 70/99

The options include: Baseband Loss of Frame, Baseband Excessive BER, Baseband SignalDegrade, and Early Warning

9. In the priority table, designate the high priority channel(s). A high priority channel will be switched firstwhen the criteria chosen for the threshold is met, even if a major fault occurs in a different channel.

The Priority Level options include:

• Normal - regular operation according to the N+1 mechanism

• High Priority

• Not Protected – stand-alone channel without protection

Specifying System InformationNote: To specify system information, you must perform the following steps in all three IDCs in the SLT IDU:

1. Select File, System, Information., or click the System Information icon.

System Information Window2. In the Current Time area, click Date/Time Configuration and set the date and time (in the format

HH:MM:SS).

3. The read-only Description field provides information about the system.

4. (Optional) In the Name field, enter a name for this link. By convention, this is the node’s fully-qualified domain name.

5. (Optional) In the Contact field, enter the name of the person to be contacted when a problem withthe system occurs. Include information on how to contact the designated person.

6. (Optional) In the Location field, enter the actual physical location of the node or agent.

7. The Up Time field is read-only and shows how long the system has been operating continuously.

Page 71: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 71/99

8. For Left/Right Carrier Name, specify the name you want to give the carrier for identificationpurposes.

9. Click Apply. The settings are saved.

10. Click Close.

Local/Remote Transport ConfigurationThe Local/Remote Transport Configuration window allows you to change threshold levels for the radio andalarms, and to configure special transmission parameters. This is recommended for advanced users onlyand should be done in all of the three IDCs in the SLT IDU.

Note: You will need to restart LinkPilot if you change the transport protocol.

1. Select Configuration, IDU, Transport.

The Transport Configuration window appears.

Transport Configuration Window2. The Protocol field displays the current data transfer protocol. To change the protocol, click the drop

down list and select SDH, SONET, or SONET-C.

3. Click Apply to save the settings.

4. Click Close.

Trap Forwarding ConfigurationThis section explains how to set up a trap forwarding plan. If your application does not require trapforwarding, you can skip the following procedure.

1. Select Configuration, Management System, Traps Configuration, or click the Traps Configurationicon.

The Trap Forwarding Configuration window appears.

Page 72: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 72/99

Trap Forwarding Configuration Window

2. In the Managers IP Address area, specify the IP addresses of the managers to which you wanttraps to be sent. For each manager IP you specify, specify the Trap Port, and for Send Trap forAlarms with Severity, select the severity filter to determine which types of alarms will be forwarded.

3. In the Send Trap for Alarms of Group section, you determine which alarms will be sent as SNMPtraps to each manager. In each manager column, select the alarm types you want to include for thatmanager.

4. In the Trap Options area, select Standard traps include serial number if you want trap messagesto include the IDU serial number.

Select Report local traps of far end IDU if you want remote IDU trap messages to be reportedlocally.

Select Use different ID for each alarm type if you want each type of alarm to receive a unique ID.

Select Send “clear” traps with zero severity if you want a trap with a “clear” severity (instead ofthe alarm's original severity) to be sent to the IP addresses you specified.

5. For CLLI (Common Language Location Identifier), enter up to 18 characters that will represent yoursystem ID when traps are sent.

6. For Heartbeat Period, a heartbeat signal will be generated every x minutes (the number you enter)to tell your system that the trap mechanism is working.

7. Click Apply to save the settings.

Page 73: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 73/99

External Alarms SetupThe procedure detailed in this section is required only if alarms generated by external equipment areconnected to the IDU, or if the IDU alarm outputs are connected to other equipment (using the alarms I/Oconnector).

The SLT IDU has eight external alarm inputs and five external alarm outputs. Since each of the three levelssupport five outputs, the system uses the OR function between the outputs of each floor, and accordinglygenerates the alarm.

1. Select the middle floor of the SLT IDU, and select Configuration, IDU, External Alarms.

Or, click the External Alarms icon.

Or, click the EXT ALARM IN icon on the IDU front panel.

The Input / Output External Alarms window appears.

Input / Output External Alarms WindowFollow the steps below for both the Local and Remote sides.

The microcontroller in the IDU reads alarm inputs (dry contact) and transmits them to the LinkPilotmanagement system. This allows SLT to report external alarms that are not related to its ownsystem.

For each alarm on the left side of the window, do the following:

2. Click the box next to the alarm number to enable/disable the alarm.

3. If you enable an alarm, enter a description of the alarm in the text field.

4. Select the alarm’s severity level from the drop-down list (Major, Minor, Warning, or Event).

5. SLT provides five alarm outputs that can be used by other systems to sense SLT alarms. Theoutputs are configured on the right side of the window.

Page 74: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 74/99

The alarm outputs are Form C Relays. Each output relay provides three pins, as follows:

• Normally Open (NO)• Normally Closed (NC)• Common (C)

Output alarms can be defined as any of the following:

• Major• Minor• Warning• External• Power• BER• Line• Loopback• LOF• IDU• ODU• Cable• Remote

The default alarm output setting for each relay is “Power”.

The relays may be connected to customer-specific applications. Refer to Appendix B for detailsconcerning the alarm connector pin assignments.

6. After you complete the configuration, click Apply to save the settings.

7. Click Close.

Exiting LinkPilotTo exit LinkPilot, select File, Exit in the main window.

Connecting Line InterfacesAfter configuring the system in accordance with the previous sections, the line interfaces can be connectedto the IDU.

For a description of the line interfaces, see the SAGEM-LINK A installation and operation manual.

Page 75: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 75/99

Chapter 5SAGEM-LINK T Acceptance & Commissioning Procedures

5.1 – General

This chapter provides Sagem's recommended Acceptance and Commissioning Procedure for the SAGEM-LINK T.

Acceptance and commissioning should be performed after initial setup is complete.

The purpose of this procedure is to verify correct installation and operation of the installed link and theinteroperability with customer end equipment.

Sagem's Acceptance and Commissioning procedure includes the following stages:

• Site Acceptance Procedure

• Commissioning of radio link in N+0 configuration

• Commissioning of radio link in N+1 configuration

• Commissioning of radio link in XPIC configuration

The Site Acceptance Procedure is a checklist that summarizes the installation requirements of the site at whichthe product is installed.

The commissioning tests cover the required configuration information that should be recorded, and the teststhat should be performed on the radio link in N+0, N+1, and XPIC configurations.

Page 76: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 76/99

5.2 – Site Acceptance Procedure

The purpose of the following procedures is to verify that all installation requirements were noted and checked.Following this procedure will ensure proper, long-lasting, and safe operation of the product.

The checklist below summarizes the installation requirements of the site.

5.2.1 - Site Acceptance ChecklistThe following checklist should be filled in at each site.

SITE ACCEPTANCE CHECKLIST

1. SITE INFORMATION

Customer:

Radio model:

Site name:

Site code:

Mount is of sufficient height to clear local obstructions

Site address:

2. ANTENNA MOUNTING

Antenna mount type:

Mount is due to tower construction OK

Mount is due to Antenna weight and tower load OK

Mount is assembled and installed with its segments due to manufacturers instructions OK

Mount is on sufficient height to clear local obstructions OK

Mount is safely positioned to not cause a safety hazard OK

Mount is anchored and perpendicular OK

Mount is grounded as per site specifications OK

All steelwork is Galvanized or Stainless Steel as appropriate, and due to mechanical design OK

3. ANTENNA

Antenna type (model and size):

Antenna assembled due to manufacturers instructions OK

Antenna installed and anchored to the mount and due to manufacturers instructions OK

Antennas struts are assembled , installed, attached to the tower due to manufacturersinstructions OK

Antennas Feeder assembled due to manufacturer instructions, and port polarization is as perlink requirements OK

Page 77: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 77/99

SITE ACCEPTANCE CHECKLIST(continued)

4. OUT-DOOR UNIT: Split Mount Configuration

Type of RFU mount: (Direct or Remote mount)

RFU is securely mounted to the antenna or pole OK

RFU is grounded as per installation instructions OK

RFU‘s polarization is as per link requirements OK

RFU is installed properly and has no physical damage OK

For Remote-Mount Only:

Remote mount kit is securely mounted to the pole OK

Waveguide has no physical damage and connectors aresealed OK

All waveguide bolts are secured using washers and lock-washers, as appropriate OK

Flexible waveguide is secured to the pole OK

5. OUT-DOOR UNIT: All Indoor Configuration

RFU is securely mounted on the ICB OK

RFU is grounded as per installation instructions OK

RFU‘s polarization is as per link requirements OK

RFU is installed properly and has no physical damage OK

6. COAX CABLE

Overall cable length:

Cable type:

N-Type connectors assembled properly on the cable OK

Cable connected securely to RFU and IDU OK

Cable connector is weather-proofed (sealed) at the RFU OK

At the RFU, cable has a service/drip loop to preventmoisture from entering the connector OK

Cable is secured using suitable restraints to fixed points atregular intervals (0.5 m recommended) OK

Cable has no sharp bends, kinks, or crushed areas. Allbends are per manufacturer specifications OK

Grounding/lightning protection is as per site specifications OK

Lightning protection type and model:

Cable point-of-entry to building/shelter is weather-proof OK

Cable ends are properly labeled OK

Page 78: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 78/99

SITE ACCEPTANCE CHECKLIST(continued)

7. WAVEGUIDE

Overall waveguide length:

Waveguide type:

Waveguide is connected securely to C port and antenna OK

Waveguide connectors are assembled in accordance with manufacturer instructions OK

Waveguide is grounded to Main Ground Bar, and as per regulations OK

Waveguide is anchored using suitable clamps to fixed points, at regular intervals (asper frequency band recommendation) OK

Waveguide is installed in accordance with manufacturer instructions. All bends andtwists are per manufacturer specifications OK

Waveguide point-of-entry to building/shelter is weather-proof OK

Waveguide runs to the rack directly, with no cross-lining OK

Waveguide run takes into account future expansion OK

Waveguide ends are properly labeled OK

Waveguide pressure window is assembled in accordance with frequency band andmanufacturer instructions OK

Waveguide is connected to the dehydrators in accordance with manufacturerinstructions OK

8. IN-DOOR UNIT

IDU is securely mounted to the rack OK

IDU is located in a properly ventilated environment OK

IDU fans are functional and air flow to the fans is notdisrupted OK

IDU and rack are grounded as per site specifications OK

Traffic cables and connections are properly terminated asper manufacturer/cable instructions OK

All cabling is secured, tidy, and visibly labeled OK

9. DC POWER SUPPLY - Two Inputs

Measured DC voltage input to the IDU: (-40.5 to -72 VDC)

Power supply maximum current: (at least 3 Ampere)

Power supply is properly grounded OK

DC power backup type:

IDU DC connector is secure and the DC input leads arecorrectly terminated (no bare wires are visible) OK

IDU DC connector (+) and (GND) leads are shorted andGND is grounded OK

Page 79: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 79/99

10. RACK INSTALLATION

Rack is mounted to the shelter floor with four screws OK

Rack is mounted to the shelter wall with two screws OK

Racks are secured properly to each other, in concatenation(All Indoor) OK

11. REMARKS/NOTES

12. GENERAL INFORMATION

Name:

Title:

Company:

Signature:

Site accepted by:

Date:

Name:

Title:

Company:

Signature:

Site approved by:

Date:

5.2.2 - Site Acceptance Checklist Notes

The following notes provide important additional information about the Site Acceptance Checklist.

1. Antenna Mounting

• Mounting pole is of sufficient height to clear local obstructions, such as parapets, window cleaninggantries, and lift housings.

• Mounting Pole is of sufficient height, and is safely positioned, so as not to cause a safety hazard. Noperson should be able to walk in front of, or look directly into the path of the microwave radio beam.Where possible, the pole should be away from the edge of the building.

• Mounting pole is secure and perpendicular. A pole that is not perpendicular may cause problems duringantenna alignment.

• Mounting pole is grounded as per site specifications. All operators and site owners have specificrequirements regarding the grounding of installations. As a minimum, typical requirements are suchthat any metal structure must be connected to the existing lightning protection ground of the building.Where it extends beyond the 45 degree cone of protection of existing lightning conductors, additionallightning protectors should be installed.

• All steelwork is Galvanized or Stainless Steel, as appropriate to prevent corrosion.

Page 80: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 80/99

2. Antenna

• Antenna is grounded as per site specifications. See the third point in the Antenna Mounting sectionabove.

• Antenna sway braces are fitted and installed correctly, where applicable. Typically, for an antenna of 1.2m or larger, an extra sway brace is fitted to the mounting frame of the antenna. This sway braceshould not be mounted to the same pole as the antenna, but should be installed directly back to thetower or an alternative point.

• Antenna Water Drain Plugs are fitted and removed, where appropriate. Some antennas have moisturedrain plugs installed at various points around the antenna. The purpose of these plugs is to allow anymoisture that forms on the inside of the antenna or radome to drip out and prevent a pool within theantenna. Only the plugs at the bottom of the antenna, after installation, should be removed. All otherplugs should be left in position.

3. RFU (RF Unit)

• The RFU is grounded as per installation instructions. See the third point in the Antenna Mountingsection above.

• The RFU Polarization is as per link requirements and matches the polarization of the antenna.

4. Indoor Unit

• The main traffic connections (STM-1 tributaries) are correctly terminated and crimped as per cable andconnector manufacturer instructions. All fiber optic patch leads should be routed carefully andefficiently, using conduits to prevent damage to the cables.

All other user terminations are secure and correctly terminated.

• All labeling is complete as per site requirements. Labeling is specific to each customer. At a site withonly one installation, labeling may be unnecessary. However, at sites with multiple installations,correct and adequate labeling is essential for future maintenance operations.

Typical labeling requirements include:

Antenna labels - for link identity and bearingRFU labels - for link identity, frequency, and polarizationCoax cable labels - for link identity, close to the RFU, IDU, and either end of any jointIDU labels - for link identity

Page 81: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 81/99

5.3 – N+0 Commissioning Procedure

5.3.1 - ScopeThis section describes the recommended commissioning tests for a SAGEM-LINK T radio link in an N+0configuration.

The purpose of the commissioning tests is to verify correct and proper operation of the product.

The SLT system can work with up to 10 separate carriers in a 10+0 configuration. The following stepsshould be performed for each of the N carriers independently.

5.3.2 - Commissioning TestsThe following tests should be performed on each installed link.

Link Verification• “Radio” LED on the IDM front panel is green, indicating the radio link is up.

• Received Signal Level (RSL) is up to +/- 4 dB from the expected (calculated) level at both ends ofthe link.

• Radio Bit Error Rate (BER) is 10-11 or higher.

• If working with ATPC, ATPC is operating as expected (RSL = reference level).

• After connecting test equipment or end equipment to the line interfaces, all LEDs on the front panelof the IDM are green.

Line Interfaces Test• 155 Mbps Interface

Connect SDH/SONET/ATM test equipment to the 155 Mbps interface and verify error-free operationfor at least 1 hour. Use physical or software loop at the far end.

• 2 Mbps or 1.5 Mbps Interface

Connect PDH test equipment to the E1/T1 interface of an ADM connected to the IDU, and verifyerror-free operation for at least 1 hour. Use physical or software loop at the far end.

Interoperability Verification• Connect customer end equipment to the line interfaces, and verify correct operation.

• Further interoperability tests should be performed in accordance with the specific requirements of theconnected end equipment.

Management Verification• Install LinkPilot software on the PC, and launch the program.

• Verify that you can manage the link and that you are able to perform changes to the linkconfiguration (frequency channel, Tx power, system name, time & date, etc.) via LinkPilot.

• Verify that LinkPilot reports the correct parameters when performing the above.

• Verify that there are no active alarms on the link.

• If the management station is located at a remote site (Network Operation Center), verify that themanagement station can manage the link and receive traps.

Loopback OperationPerform line loopback, IDU loopback, RFU loopback, and Remote loopback, and verify that the systemoperates accordingly.

Page 82: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 82/99

5.4 – N+1 Commissioning Procedure

5.4.1 - ScopeThis section describes the recommended commissioning tests for a SAGEM-LINK T radio link in an N+1and Space Diversity (SD) or Frequency Diversity (FD) configuration.

The purpose of the commissioning tests is to verify correct and proper operation of the product.

The SLT system can work with up to a 9+1 configuration (two systems in concatenation mode).

The +1 carrier protects the other N carriers, and in normal operation of the system (no errors or faults),carries extra traffic.

The first tests should be performed on all carriers, including the extra traffic channel, separately.

When testing protection using switching tests, there is a difference if a channel is a preferred channel(errorless, no errors at switching time at all), or if it is a regular channel (hitless, errors are detected within10 ms).

5.4.2 - Commissioning TestsThe following tests should be performed on each installed link.

Link VerificationThe following steps should be repeated for each of the N+1 RFUs.

• “Radio” LED on the IDM front panel is green, indicating the radio link is up.

• Received Signal Level (RSL) is up to +/- 4 dB from the expected (calculated) level at both ends ofthe link.

• Radio Bit Error Rate (BER) is 10E-11 or higher.

• If working with ATPC, ATPC is operating as expected (RSL = reference level).

• After connecting test equipment or end equipment to the line interfaces, all LEDs on the front panelof the IDM are green.

Line Interfaces Test• 155 Mbps Interface

Connect SDH/SONET/ATM test equipment to the 155 Mbps interfaces using splitters. Verify error-free operation for at least 1 hour. Use physical loop between the splitters at the far end.

• 2 Mbps/1.5 Mbps Interface

Connect PDH test equipment to the E1/T1 interfaces of an ADM connected to the IDU using splitters.Verify error-free operation for at least 1 hour. Use physical loop between the splitters at the far end.

Switching Tests

Define each of the N channels as preferred (one at a time) for errorless switching to the +1 channel. Theregular channel supports hitless switching to the +1 channel.

155 Mbps Interface• Connect SDH/SONET/ATM test equipment to the

155 Mbps interfaces using splitters. Use physical loop between the splitters at the far end. Verify thatthere are no alarms.

Page 83: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 83/99

• Perform the following switching tests from one IDMto the other, and verify the system switches automatically.

- Power: power off the active IDM

- Radio: disconnect the coax cable of the active IDM

- Line: disconnect the 155 Mbps line input of the active IDM

- Management: force a switch using LinkPilot

• For diversity configurations, verify that eachreceiver is receiving its own signal, and then mute the active RFU. Verify that the receiver at the farend still receives from the diversity path. Verify that there are no errors in the test equipment.

Interoperability Verification• Connect the customer end equipment to

the line interfaces and verify correct operation.

• Further interoperability tests should be performed inaccordance with the specific requirements of the connected end equipment.

Management Verification• Install LinkPilot software on the PC and launch the program.

• Verify that you can manage the link and that you are able to performchanges to the link configuration (frequency channel, Tx power, system name, time & date, etc.) viaLinkPilot.

• Verify that LinkPilot reports the correct parameters when performing the above.

• Verify that there are no active alarms on the link.

If the management station is located at a remote site (Network Operation Center), verify that themanagement station can manage the link and receive traps.

5.5 – XPIC Commissioning Procedure

5.5.1 - ScopeThis section describes the recommended commissioning tests for a SAGEM-LINKT radio link in an XPICCo-Channel-Dual-Polarization configuration.

The purpose of the commissioning tests is to verify correct and proper operation of the product.

Important! Since operation of the XPIC system depends on correct installation, make sure the guidelinesfor XPIC system installation provided below are followed correctly.

The SLT system can carry up to two XPIC links per IDU. The XPIC mode runs between drawers 1-2 and 4-5 in the IDU.

All tests described below should be performed separately for each XPIC pair in the IDU.

5.5.2 - XPIC Installation Guidelines

Antenna and RFU Installation

1. Install the dual polarization antenna and point it in the direction of the other site.

2. Install the two RFUs on a rack, and mark them with V and H respectively.

Page 84: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 84/99

IDU-RFU Cable Installation

1. Connect two cables between the RFUs and the drawers (IDMs). Note that the cable lengthdifference should not exceed 10 meters.

2. Mark the cables with V and H respectively, and make sure V is connected to the right drawer and His connected to the left drawer.

3. Mark the drawers respectively.

Antenna Alignment

1. Power up drawer V on both ends of the link and configure it to the desired frequency channel andmaximum power.

2. Align the antennas, one at a time, until expected RSL is achieved. Make sure achieved RSL is nogreater than +/-4 dB from the expected level.

Polarization Alignment

Polarization alignment is required to verify that the antenna feeds are adjusted, to ensure that the antennaXPD (Cross Polarization Discrimination) is achieved.

Polarization adjustment should be done on one antenna only.

1. Power up drawer V on both ends of the link and record the RSL reading on one end.

2. Power off drawer V on that end, and power on drawer H.

3. Check the RSL obtained on this RFU on H pol, and compare it to the RSL obtained by the RFUinstalled on the V pol.

4. Verify that the XPI (Cross Polarization Interference) is at least 25 dB

where:

XPI = RSLPOL – RSLXPOL

RSLPOL corresponds to the RSL with the same polarization used at both sitesRSLXPOL corresponds to the RSL with orthogonal polarization used at both sites

5. If the XPI is less than 25 dB, adjust the feed polarization by opening the polarization screw andgently rotating the feed to minimize the RSLXPOL.

Note that polarization alignment is not always possible since the RSLXPOL may fall below thesensitivity threshold of the RFU.

It is also recommended to try to maximize the XPI as much as possible, by aligning the polarization.

5.5.3 - XPIC Commissioning Tests

Individual Link Verification

Before operating in XPIC configuration, each of the links (V and H) should be commissioned individually inorder to verify its proper operation.

1. Power up only drawer V at both ends and verify its frequency channel and Tx power configuration.

2. Verify that the RSL is no more than +/-4 dB from the expected level.

3. Run BER stability test on the link for at least 15 minutes to ensure error-free operation.

4. Power up only drawer H at both ends and verify its frequency channel and Tx power configuration.

Page 85: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 85/99

5. Verify that the RSL is no more than +/-4 dB from the expected level.

6. Run BER stability test on the link for at least 15 minutes to ensure error-free operation.

XPIC Configuration Verification

1. Using the XPIC cable, connect the two RFUs at each end to the TNC connectors. Make sure thecable is no longer than 3 meters.

2. Configure the drawers to work in XPIC mode.

3. Verify that the RSL at all four RFUs is no more than +/-4 dB from the expected level.

4. Verify that no alarms exist (if a 155 Mbps line is connected).

5. Run BER stability test on each of the 155 Mbps links for at least 1 hour to ensure error-freeoperation.

XPIC Recovery Verification

In order to verify XPIC operation, simulate the faults described below.

1. Disconnect the IDU-RFU cable for each of the drawers (one at a time), and verify that theother link is operating.

2. Disconnect the XPIC cable and check that the relevant alarms are generated.

3. Power down each of the drawers and verify that the other link is operating.

4. Swap the V and H cables and check that the relevant alarm is generated.

5. Mute and then un-mute one RFU at a time and verify that the other link is operating.

Page 86: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 86/99

5.6 – SAGEM-LINK T Commissioning Log

The Commissioning Log is an integral part of the commissioning procedure and should be filled in for eachinstalled link.

In an N+1 system, a commissioning log should be recorded for each of the five carriers (per IDU), includingthe extra traffic channel.

The Commissioning Log gathers all relevant information regarding the installed link and contains a checklist ofall recommended commissioning tests.

Maintaining the Commissioning Log is important for tracking your installations, and to provide essential datafor Sagem Communications.

SAGEM-LINK T LINK COMMISSIONING LOG

1. GENERAL INFORMATION

Customer:

Radio model:

Configuration:

Radio link code:

Site 1 name & add:

Site 2 name & add:

2. IN-DOOR UNITSite 1

Drawer 1-NSite 2

Drawer 1-N

IDC model:

Wayside channel:

IDC p/n:

IDC1 s/n:

IDC2 s/n:

IDC3 s/n:

SW IDC:

Drawer model:

Main channel:

Drawer p/n:

Drawer s/n:

Modem s/n:

Mux s/n:

XC s/n:

Page 87: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 87/99

SAGEM-LINK T LINK LINK COMMISSIONING LOG(continued)

FW Mux:

FW Modem:

Cfg Modem:

3. RFUSite 1

Drawer 1-NSite 2

Drawer 1-N

RFU model:

RFU p/n:

RFU Main s/n:

SW RFU:

Tx frequency (MHz):

Rx frequency (MHz):

Link ID:

Tx power (dBm):

ATPC on/off:

ATPC ref level:

RFU Polarization:

4. ANTENNA Site 1 Site 2

Antenna model:

Antenna size:

Manufacturer:

Mounting type:

Mounting losses:

5. LINK PARAMETERSSite 1

Drawer 1-NSite 2

Drawer 1-N

Link distance:

Rain zone:

Expected RSL (dBm):

Expected Diversity RSL (dBm):

RSL Main (dBm):

RSL Diversity (dBm):

Deviation from exp?

RSL ≤4 dB?

Page 88: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 88/99

SAGEM-LINK T LINK LINK COMMISSIONING LOG(continued)

6. COMMISSIONING TESTSSite 1

Drawer 1-NSite 2

Drawer 1-N

Front panel LEDs: All green All green

Line loopback: Pass Pass

IDU loopback: Pass Pass

RFU loopback: Pass Pass

Radio BER: Pass Pass

STM-1 test: Pass Pass

Fast Ethernet test: Pass Pass

8 x E1/T1 test: Pass Pass

E3/DS3 test: Pass Pass

Wayside E1 test: Pass Pass

Wayside Eth test: Pass Pass

XPIC test: Pass Pass

Switching test: Pass Pass

7. MANAGEMENT CONFIGURATION Site 1 Site 2

Eth Main IP address:

Eth Coupled IP address:

Eth IP mask:

Serial IP address:

Serial IP mask:

Default router:

In-band enabled?

Gateway/NE:

In-band channel 1:

In-band channel 2:

Ring IP address:

Ring IP mask:

Network ID:

8. REMARKS/NOTES

Page 89: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 89/99

SAGEM-LINK T LINK LINK COMMISSIONING LOG(continued)

9. INSTALLATION INFORMATION

Name:

Company:

Date:Installed by:

Signature:

Name:

Company:

Date:Commissioned by:

Signature:

Page 90: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 90/99

Appendix AConnectors Pinout

A.1 – General

This chapter provides connectors pinout for SAGEM-LINK T. It includes the following :

• Input External Alarms Connector

• Output External Alarms Connector

• Protection Connector

• 8 x E1/T1 Connector

• Modem-PPP Cross Cable

• Wayside Channel Connectors

Page 91: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 91/99

A.2 – Input External Alarms Connector

The Input External alarms connector which is a high density male 15-pin D Sub connectorincludes 8 inputs (normally open type).

1

106

5

1511

DB 15 HD Male ConnectorView from the pin side

Pin Signal Signal Description1 EXT IN1 External Alarm Input #12 EXT IN2 External Alarm Input #23 EXT IN3 External Alarm Input #34 EXT IN4 External Alarm Input #45 EXT IN5 External Alarm Input #56 EXT IN6 External Alarm Input #67 EXT IN7 External Alarm Input #78 EXT IN8 External Alarm Input #89 GND Ground

10 NC11 NC12 NC13 NC14 NC15 NC

Page 92: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 92/99

A.3 – Output External Alarms Connector

The Output External alarms connector which is a high density male 15-pin D Sub connectorincludes 5 outputs (normally open type).

1

106

5

1511

DB 15 HD Male ConnectorView from the pin side

Pin Signal Signal Description1 RELAY_5_NC Relay #5 normally closed2 RELAY_5_C Relay #5 common3 RELAY_5_NO Relay #5 normally opened4 RELAY_4_C Relay #4 common5 RELAY_4_NO Relay #4 normally opened6 RELAY_3_C Relay #3 common7 RELAY_3_NO Relay #3 normally opened8 RELAY_2A_NO Relay #2 normally opened9 RELAY_4_NC Relay #4 normally closed

10 RELAY_1A_NC Relay #1 normally closed11 RELAY_3_NC Relay #3 normally closed12 RELAY_2A_C Relay #2 common13 RELAY_2A_NC Relay #2 normally closed14 RELAY_1A_C Relay #1 common15 RELAY_1A_NO Relay #1 normally opened

Page 93: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 93/99

A.4 – Protection Connector Pinout

The protection connector is a RJ-45 8-pin type.

Pin

Left RightFunction

1 1 GND

2 5 E_SLF_OUT

3 6 IDC TXD

4 7 Cable Echo

5 2 E_MT_IN

6 3 IDC RXD

7 4 NA

8 8 GND

Page 94: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 94/99

A.5 – 8xE1/T1 Connector Pinout

Connector: 36pin SCSI type

Used with: Multi conductor cable (Twisted Pairs)

Protocols supported: E1/T1

Range: 100 m

Impedance: 120 Ω/ 100 Ω

8E1/T1 Connector PinoutPin Signal

1 IN-TIP 119 IN-RING 1

2 IN-TIP 220 IN-RING 2

3 IN-TIP 321 IN-RING 3

4 IN-TIP 422 IN-RING 4

5 IN-TIP 523 IN-RING 5

6 IN-TIP 624 IN-RING 6

7 IN-TIP 725 IN-RING 7

8 IN-TIP 826 IN-RING 8

9 GND27 N.C.

10 GND28 N.C.

11 OUT-TIP 129 OUT-RING 1

12 OUT-TIP 230 OUT-RING 2

13 OUT-TIP 331 OUT-RING 3

14 OUT-TIP 432 OUT-RING 4

15 OUT-TIP 533 OUT-RING 5

16 OUT-TIP 634 OUT-RING 6

17 OUT-TIP 735 OUT-RING 7

18 OUT-TIP 836 OUT-RING 8

Page 95: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 95/99

A.6 – Modem – PPP Cross Cable Pinout

This section provides pin-outs for the cross cable installed between the dial-up modem and the SLT PPPinterface

DB9 to DB9 Cross Cable

DB9 Male Connection DB9 Male

TX 2 2 RX

RX 3 3 TX

DTR 4 1 DCD

CTS 8 7 RTS

RTS 7 8 CTS

DCD 1 4 DTR

GND 5 5 GND

DB9 to DB25 Cross Cable

DB9 DB25

1 20

2 2

3 3

4 8

5 7

7 5

8 4

Notes:

1. Shell is connected to IDU chassis GND.2. The following pins are not connected: 6, 7, 8, 9, 15, 23, 36, 37, 38, 39

Page 96: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 96/99

A.7 – Wayside Channel Connector Pinout

E1/T1 Connector Pinout

RJ 45 Type

Pin Signal

1 Ch1_Rx+, Receive Positive - Primary

2 Ch1_Rx-, Receive Negative - Primary

3 Ch2_Rx+, Receive Positive - Secondary

4 Ch1_Tx+, Transmit Positive- Primary

5 Ch1_Tx-, Transmit Negative - Primary

6 Ch2_Rx-, Receive Negative - Secondary

7 Ch2_Tx+, Transmit Positive - Secondary

8 Ch2_Tx-, Transmit Negative - Secondary

10BaseT Connector Pinout

Pin Signal

1

2Twisted Pair, Out - Tx Ch2 (Right)

3

6Twisted Pair, In - Rx Ch2 (Right)

4

5Twisted Pair, Out - Ch1 Tx (Left)

7

8Twisted Pair, In - Ch1 Rx (Left)

Page 97: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 97/99

Appendix BPPP/SLIP Driver Installation

B.1 - Installation for Windows 2000 1. Click Start, Setting, Network and Dialup, Make New Connection.

2. Click Next. 3. Mark Connect directly to another computer. 4. Click Next. 5. Mark Guest. 6. Click Next. 7. Select Communication cable between two computers.

8. Click Next. 9. Select For all user. 10. Click Next. 11. Type The connection Name.

12. Click Finish.

B.2 - Configuring PPP 1. Click START , Setting, Network and Dialup.

2. Select The connection Name.

3. In the General tab click Configure, and set the speed to 38400.

4. Check Enable Hardware flow control. 5. Uncheck Modem Error control, Modem Compression.

6. Select Network tab.

7. Select Type PPP.

8. Select Internet protocol (TCP/IP) and click Properties.

9. Uncheck all options except TCP/IP.

10. Check Use the following IP.

11. Insert IP Address (the same subnet as the Indoor).

12. Click OK.

13. Click OK.

Page 98: SLT Installation & Operation Manual 253031934-A

SAGEM-LINK T Installation and Operation Manual 3000299570-R11-000-01Sagem Communications document. Reproduction and disclosure prohibited Page 98/99

ENVIRONMENTPreservation of the environment as part of a sustainable development logic is an essential concern of SagemCommunications. The desire of Sagem Communications is to operate systems observing the environmentand consequently it has decided to integrate environmental performances in the life cycle of its products, frommanufacturing to commissioning, use and elimination.

PACKAGING

The presence of the logo (green dot) means that a contribution is paid to an approved nationalorganisation to improve packaging recovery and recycling infrastructures.

To facilitate recycling, please respect the sorting rules set up locally for this kind of waste.

BATTERIES

If your product contains batteries, they must be disposed of at appropriate collection points.

THE PRODUCT

The crossed-out waste bin stuck on the product or its accessories means that the product belongs tothe family of electrical and electronic equipment.

In this respect, the European regulations ask you to dispose of it selectively : At sales points in the event of the purchase of similar equipment. At the collection points made available to you locally (drop-off centre, selective collection, etc.).

In this way you can participate in the re-use and upgrading of Electrical and Electronic Equipment Waste,which can have an effect on the environment and human health.

Page 99: SLT Installation & Operation Manual 253031934-A

Siège social : 27, rue Leblanc - 75512 PARIS CEDEX 15 - FRANCETél. : +33 1 58 11 77 00 - Fax : +33 1 58 11 77 50http://www.sagem.com

Société Anonyme au capital de 300 272 000 € - 480 108 158 RCS Paris