GOLD
We reserve the right to alter specifications. 20191209104
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
Sizing, Installation, Dimensions and Weights
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -254 -2 -3 -5 -13 -13 -14 -20 -25
To inlet duct* 1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -434 -9 -11 -16 -28 -38 -41 -44 -44
To air handling unit surroun-dings**
1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -564 -13 -17 -28 -34 -46 -47 -54 -56
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s004 288 0.08 1620 0.45
Lw,tot 75
8580
70dB
2.5
2.0
1.5
1
23
4
123
4
70dBLw,tot75
8580
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
MTE MPE
70dBLw,tot
75
85 80
2.5
2.0
1.5
Lw,tot
75
85 80
70dB
1
23
4
12
4
3
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The air handling unit complies with requirements to Ecodesign 2016/2018.
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
GOLD PX, counterflow heat exchanger, size 004, common casing
20191209 We reserve the right to alter specifications.
GOLD
105
Power connection1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanMotor shaft power: 0.8 kW (0.41 kW)* motor control system, 1 x 230 V, 50 Hz *The motor control system limits the power of the take-off to the value specified.
Clear Space for InspectionA clear space of 900 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.
Size A B C D F G H J L Ø Weight, kg
004 822 825 240 345 230 460 920 579 2333 315 349-387
Right-hand version
Left-hand version
Delivery and transport within the siteThe GOLD PX 004 is produced in one single variant. All of its components are arranged at their given physical loca-tions inside the air handling unit.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
The air handling unit is supplied on a wooden pallet.
The set of support legs, for mounting the base beams, is available as an accessory.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units).
Outdoor air Supply air Extract air Exhaust air
PX
76
72
14
52*380 18
52284 284
76
45 45J
72
øø= =
Power connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
Sizing, Installation, Dimensions and Weights
GOLD PX, counterflow heat exchanger, size 004, common casing
GOLD
We reserve the right to alter specifications. 20191209106
GOLD PX, counterflow heat exchanger, size 004, split version
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
Sizing, Installation, Dimensions and Weights
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -254 -2 -3 -5 -13 -13 -14 -20 -25
To inlet duct* 1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -434 -9 -11 -16 -28 -38 -41 -44 -44
To air handling unit surroun-dings**
1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -564 -13 -17 -28 -34 -46 -47 -54 -56
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s004 288 0.08 1620 0.45
Lw,tot 75
8580
70dB
2.5
2.0
1.5
1
23
4
123
4
70dBLw,tot75
8580
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
MTE MPE
70dBLw,tot
75
85 80
2.5
2.0
1.5
Lw,tot
75
85 80
70dB
1
23
4
12
4
3
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The air handling unit complies with requirements to Ecodesign 2016/2018.
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
20191209 We reserve the right to alter specifications.
GOLD
107
D
52
PX
76
K
76
K
14 52*
380 18
72284
ø
284
ø
45 45J
72
= =
Sizing, installation, dimensions and weights
GOLD PX, counterflow heat exchanger, size 004, split version
Power connection1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanMotor shaft power 0.8 kW (0.41 kW)*, Motor control system: 1 x 230 V, 50 Hz *The motor control system limits the output power to the value speci-fied.
Delivery and transport within the siteThe GOLD PX 004 can be supplied as one single unit, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit/Delivery Configuration RX/PX/CX, sizes 004-080.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: Specify right-hand or left-hand version when ordering. B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units).
Power connection
Right-hand version
Left-hand version
Outdoor air Supply air Extract air Exhaust air
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 88-112 kg, D = 262-266 kg.
Division into sections for transport
A AD
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
Size A B C D F G H J K L Ø Weight, kg
004 617 825 240 1300 230 460 920 579 345 2534 315 438-490
GOLD
We reserve the right to alter specifications. 20191209108
GOLD PX Top, counterflow heat exchanger, size 004
Sizing, installation, dimensions and weights
2.5
2.0
1.5
65dBLw,tot701 23
4
75
80
65dBLw,tot70
75
1
23
4 80
2.5
2.0
1.5
65dBLw,tot701 23
4
75
80
65dBLw,tot70
75
1
23
4 80
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s004 288 0.08 1620 0.45
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The air handling unit complies with requirements to Ecodesign 2016/2018.
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 1 -4 -4 -9 -13 -15 -22 -332 1 -6 -8 -4 -10 -13 -18 -273 2 -2 -5 -14 -18 -20 -28 -414 -10 -16 -21 -35 -41 -42 -45 -47
To inlet duct* 1 -7 -9 -19 -34 -38 -43 -43 -502 -9 -17 -22 -28 -36 -39 -43 -483 -8 -11 -25 -41 -44 -48 -54 -574 -10 -16 -21 -35 -41 -42 -45 -47
To air handling unit surroun-dings**
1 -10 -18 -27 -30 -46 -48 -56 -642 -10 -20 -31 -25 -43 -46 -52 -583 -9 -16 -28 -35 -51 -53 -62 -724 -21 -30 -44 -56 -74 -75 -79 -78
MTE MPE
20191209 We reserve the right to alter specifications.
GOLD
109
GOLD PX Top, counterflow heat exchanger, size 004
Sizing, installation, dimensions and weights
D
52
PX
52
380 18
ø
ø
45 45
J 76
7614
ø
ø
FE
FE
I
I
Delivery and transport within the siteGOLD PX Top 004 can be supplied as one single unit or in an optional division of sections. Extra air handling unit sections cannot be ordered due to the deviating height measurement. Filter/fan sections for height adapted PX (side fed) and PX Top can be combined, see the section: Description of the Air Han-dling Unit.The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.The air handling unit/unit sections is/are delivered on wooden beams.The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors).
B: Specify right-hand or left-hand version when ordering.
Power connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
Size A B D E F H I J L Ø Weight, kg
004 617 825 1300 334 798 1085 238 579 2534 315 480-484
Outdoor air Supply air Extract air Exhaust air
Right-hand version
Left-hand version
Electrical connection1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanMotor shaft power 0.8 kW (0.41 kW)*, motor control system: 1 x 230 V, 50 Hz *The motor control system limits the output power to the value speci-fied.
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 109 kg, D = 262-266 kg.
Division into sections for transport
Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
ADA
GOLD
We reserve the right to alter specifications. 20191209110
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
Sizing, Installation, Dimensions and Weights
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -254 -2 -3 -5 -13 -13 -14 -20 -25
To inlet duct* 1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -434 -9 -11 -16 -28 -38 -41 -44 -44
To air handling unit surroun-dings**
1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -564 -13 -17 -28 -34 -46 -47 -54 -56
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s005 288 0.08 2340 0.65
70dBLw,tot 75 80
85
9095
2.5
2.0
1.5
70dBLw,tot 75 80
85
9095
1
23
4
1
23
4
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The limit lines for Ecodesign are calculated with capacity variant 2. The mean value for supply air and extract air must be within the limit line.
Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
MTE MPE
70dBLw,tot 75 80
85
9095
2.5
2.0
1.5
70dBLw,tot 75 80
85
9095
1
23
4
1
23
4
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
GOLD PX, counterflow heat exchanger, size 005, common casing
20191209 We reserve the right to alter specifications.
GOLD
111
Sizing, Installation, Dimensions and Weights
Clear Space for InspectionA clear space of 900 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.
Power connection1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A (capacity variant 1) alt. 16 A (capacity variant 2) or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanMotor shaft power: 0.8 kW alt. 1.15 kW, motor control system: 1 x 230 V, 50 Hz
Size A B C D F G H J L Ø Weight, kg
005 822 825 240 345 230 460 920 579 2333 315 349-387
Outdoor air Supply air Extract air Exhaust air
Delivery and transport within the siteThe GOLD PX 005 is produced in one single variant, in which all the components are arranged at their given physical locations inside the air handling unit.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
The air handling unit is supplied on a wooden pallet.
The set of support legs, for mounting the base beams, is available as an accessory.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units).
Right-hand version
Left-hand version
PX
76
72
14
52*380 18
52284 284
76
45 45J
72
øø= =
Power connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
GOLD PX, counterflow heat exchanger, size 005, common casing
GOLD
We reserve the right to alter specifications. 20191209112
GOLD PX, counterflow heat exchanger, size 005, split version
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
Sizing, Installation, Dimensions and Weights
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -254 -2 -3 -5 -13 -13 -14 -20 -25
To inlet duct* 1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -434 -9 -11 -16 -28 -38 -41 -44 -44
To air handling unit surroun-dings**
1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -564 -13 -17 -28 -34 -46 -47 -54 -56
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s005 288 0.08 2340 0.65
70dBLw,tot 75 80
85
9095
2.5
2.0
1.5
70dBLw,tot 75 80
85
9095
1
23
4
1
23
4
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The limit lines for Ecodesign are calculated with capacity variant 2. The mean value for supply air and extract air must be within the limit line.
Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
MTE MPE
70dBLw,tot 75 80
85
9095
2.5
2.0
1.5
70dBLw,tot 75 80
85
9095
1
23
4
1
23
4
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
20191209 We reserve the right to alter specifications.
GOLD
113
Sizing, installation, dimensions and weights
GOLD PX, counterflow heat exchanger, size 005, split versionDelivery and transport within the siteThe GOLD PX 005 can be supplied as one single unit, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit/Delivery Configuration RX/PX/CX, sizes 004-080.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units). Outdoor air Supply air Extract air Exhaust air
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 88-112 kg, D = 262-266 kg.
Division into sections for transport
A AD
Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
Size A B C D F G H J K L Ø Weight, kg
005 617 825 240 1300 230 460 920 579 345 2534 315 438-490
Power connection1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A (capacity variant 1) or 16 A (capacity variant 2) or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanMotor shaft power: 0.8 kW alt. 1.15 kW, motor control system: 1 x 230 V, 50 Hz
Right-hand version
Left-hand version
D
52
PX
76
K
76
K
14 52*
380 18
72284
ø
284
ø
45 45J
72
= =
Power connection
GOLD
We reserve the right to alter specifications. 20191209114
2.5
2.01.5
65dB 70 80
80
75Lw,tot
1
23
4
1
23
4
90
85
65dB70
75Lw,tot
9085
2.5
2.01.5
65dB70
80
80
75Lw,tot
1
23
4
1
23
4
90
85
65dB70
75Lw,tot
9085
Cap. var 1
Cap. var 2
Cap. var 1
Cap. var 2
Cap. var 1
Cap. var 2
Cap. var 1
Cap. var 2
GOLD PX Top, counterflow heat exchanger, size 005
Sizing, installation, dimensions and weights
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).Limit line, Ecodesign, 2018
MTE MPE
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s005 288 0.08 2340 0.65
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 1 -4 -4 -9 -13 -15 -22 -332 1 -6 -8 -4 -10 -13 -18 -273 2 -2 -5 -14 -18 -20 -28 -414 -10 -16 -21 -35 -41 -42 -45 -47
To inlet duct* 1 -7 -9 -19 -34 -38 -43 -43 -502 -9 -17 -22 -28 -36 -39 -43 -483 -8 -11 -25 -41 -44 -48 -54 -574 -10 -16 -21 -35 -41 -42 -45 -47
To air handling unit surroun-dings**
1 -10 -18 -27 -30 -46 -48 -56 -642 -10 -20 -31 -25 -43 -46 -52 -583 -9 -16 -28 -35 -51 -53 -62 -724 -21 -30 -44 -56 -74 -75 -79 -78
For Ecodesign, the mean value for supply air and extract air must be within the limit line.
20191209 We reserve the right to alter specifications.
GOLD
115
GOLD PX Top, counterflow heat exchanger, size 005
Sizing, installation, dimensions and weights
D
52
PX
52
380 18
ø
ø
45 45
J 76
7614
ø
ø
FE
FE
I
I
Delivery and transport within the siteGOLD PX Top 005 can be supplied as one single unit or in an optional division of sections. Extra air handling unit sections cannot be ordered due to the deviating height measurement. Filter/fan sections for height adapted PX (side fed) and PX Top can be combined, see the section: Description of the Air Han-dling Unit.The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.The air handling unit/unit sections is/are delivered on wooden beams.The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors).
B: Specify right-hand or left-hand version when ordering.
Power connectiontion
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
Size A B D E F H I J L Ø Weight, kg
005 617 825 1300 334 798 1085 238 579 2534 315 480-492
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 109-113 kg, D = 262-266 kg.
Division into sections for transport
Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Electrical connection1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A (capacity variant 1) or 16 A (capacity variant 2) or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanMotor shaft power: 0.8 kW alt. 1.15 kW, motor control system: 1 x 230 V, 50 Hz
Outdoor air Supply air Extract air Exhaust air
Right-hand version
Left-hand version
ADA
GOLD
We reserve the right to alter specifications. 20191209116
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors, KOK , dB.
Sizing, installation, dimensions and weights
Rangein
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outletduct
1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -254 -2 -3 -5 -13 -13 -14 -20 -25
To the inletduct*
1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -434 -9 -11 -16 -28 -38 -41 -44 -44
To unit’s surroundings**
1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -564 -13 -17 -28 -34 -46 -47 -54 -56
Size Min. airflow (for airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s007 288 0.08 2700 0.75
2.5
2.0
1.5
70dBLw,tot 80 85
90
75
70dBLw,tot 8085
90
75
1
24
1
24
3
3
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The limit line for Ecodesign 2018 is calculated with capacity variant 2. The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016.
Limit line, Ecodesign, 2018
MTE MPE
2.5
2.0
1.5
70dBLw,tot 80 85
90
75
70dBLw,tot 80
85
90
75
12
4
1
24
3
3
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
GOLD PX, counterflow heat exchanger, size 007, common casing
20191209 We reserve the right to alter specifications.
GOLD
117
Sizing, installation, dimensions and weights
Power connectionCapacity variant 1: 1-phase, 3-conductor, 230 V -10/+15%, 50 Hz, 10 A or 3-phase, 5-conductor, 400 V -10/+15%, 50 Hz, 10 A
Capacity variant 2: 1-phase, 3-conductor, 230 V -10/+15%, 50 Hz, 16 A or
3-phase, 5-conductor, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanCapacity variant 1: Motor shaft power: 0.8 kW, motor control system: 1 x 230 V, 50 Hz
Capacity variant 2: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz
Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Size A B C D F G H J L Ø Weight, kg
007 911,5 995 277,5 440 271 543 1085 749 2503 400 435-492
Delivery and transport within the siteThe GOLD PX 007 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
The air handling unit is supplied on a wooden pallet.
The set of support legs, for mounting the base beams, is available as an accessory.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units).
Outdoor air Supply air Extract air Exhaust air
PX
76
72
16
52*380 18
52305 305
76
45 45J
72
øø= =
Power connection
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
Right-hand version
Left-hand version
GOLD PX, counterflow heat exchanger, size 007, common casing
GOLD
We reserve the right to alter specifications. 20191209118
GOLD PX, counterflow heat exchanger, size 007, split version
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors, KOK , dB.
Sizing, installation, dimensions and weights
Rangein
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outletduct
1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -254 -2 -3 -5 -13 -13 -14 -20 -25
To the inletduct*
1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -434 -9 -11 -16 -28 -38 -41 -44 -44
To unit’s surroundings**
1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -564 -13 -17 -28 -34 -46 -47 -54 -56
Size Min. airflow (for airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s007 288 0.08 2700 0.75
2.5
2.0
1.5
70dBLw,tot 80 85
90
75
70dBLw,tot 8085
90
75
1
24
1
24
3
3
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The limit line for Ecodesign 2018 is calculated with capacity variant 2. The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016.
Limit line, Ecodesign, 2018
MTE MPE
2.5
2.0
1.5
70dBLw,tot 80 85
90
75
70dBLw,tot 80
85
90
75
12
4
1
24
3
3
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
20191209 We reserve the right to alter specifications.
GOLD
119
D
52
16 52*
380 18
PX
7676
K72
305
ø
305
ø
K
45 45J
72
= =
GOLD PX, counterflow heat exchanger, size 007, split version
Sizing, installation, dimensions and weights
Delivery and transport within the siteThe GOLD PX 007 can be supplied as one single unit, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit/Delivery Configuration RX/PX/CX, sizes 004-080.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units). Outdoor air Supply air Extract air Exhaust air
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 103-138 kg, D = 341-347 kg.
Division into sections for transport
A AD
Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Power connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
Size A B C D F G H J K L Ø Weight, kg
007 647 995 277.5 1517 271 543 1085 749 440 2811 400 547-623
Power connectionCapacity variant 1: 1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Capacity variant 2: 1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanCapacity variant 1: Motor shaft power: 0.8 kW, motor control system: 1 x 230 V, 50 Hz Capacity variant 2: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz
Right-hand version
Left-hand version
GOLD
We reserve the right to alter specifications. 20191209120
2.5
2.0
1.5
65dBLw,tot 70 75 80
80
65dBLw,tot 70 75 80
80
1
2
4
1
2
4
3
3
85
85
2.5
2.0
1.5
65dBLw,tot 70 75 80
80
65dBLw,tot 70 75 80
80
1
2
4
1
2
4
3
3
85
85
GOLD PX Top, counterflow heat exchanger, size 007
Sizing, installation, dimensions and weights
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors, KOK , dB.
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Rangein
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outletduct
1 -1 -5 -5 -11 -12 -11 -19 -292 -3 -7 -11 -4 -9 -10 -16 -243 1 -1 -8 -16 -19 -19 -28 -394 -9 -14 -22 -31 -38 -36 -37 -41
To the inletduct*
1 -11 -13 -23 -30 -35 -33 -36 -462 -13 -19 -27 -25 -34 -32 -34 -413 -11 -11 -27 -38 -43 -40 -43 -554 -9 -14 -22 -31 -38 -36 -37 -41
To unit’s surroundings**
1 -12 -19 -28 -32 -45 -44 -53 -602 -14 -21 -34 -25 -42 -43 -50 -553 -10 -15 -31 -37 -52 -52 -62 -704 -20 -28 -45 -52 -71 -69 -71 -72
Size Min. airflow (for airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s007 288 0,08 2700 0,75
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
MTE MPE
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).Limit line, Ecodesign, 2018
For Ecodesign, the mean value for supply air and extract air must be within the limit line.
20191209 We reserve the right to alter specifications.
GOLD
121
16
PX
380 18
76
D
52 45 45
J 76
52
FE
FE
I
K
ø
ø ø
ø
GOLD PX Top, counterflow heat exchanger, size 007
Sizing, installation, dimensions and weights
Delivery and transport within the siteGOLD PX Top 007 can be supplied as one single unit or in an optional division of sections. Extra air handling unit sections cannot be ordered due to the deviating height measurement. Filter/fan sections for height adapted PX (side fed) and PX Top can be combined, see the section: Description of the Air Han-dling Unit.The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.The air handling unit/unit sections is/are delivered on wooden beams.The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors). B: Specify right-hand or left-hand version when ordering.
Electrical connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
Size A B D E F H I J K L Ø Weight, kg
007 647 995 1517 350 878 1295 288 749 278 2811 400 599-613
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 129-133 kg, D = 341-347 kg.
Division into sections for transport
Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
A
Electrical connectionCapacity variant 1: 1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Capacity variant 2: 1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanCapacity variant 1: Motor shaft power: 0.8 kW, motor control system: 1 x 230 V, 50 Hz Capacity variant 2: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz
Outdoor air Supply air Extract air Exhaust air
Right-hand version
Left-hand version
ADA
GOLD
We reserve the right to alter specifications. 20191209122
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
Sizing, Installation, Dimensions and Weights
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -254 -2 -3 -5 -13 -13 -14 -20 -25
To inlet duct* 1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -434 -9 -11 -16 -28 -38 -41 -44 -44
To air handling unit surroun-dings**
1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -564 -13 -17 -28 -34 -46 -47 -54 -56
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s008 720 0.20 3600 1.00
2.5
2.0
1.5
70dBLw,tot80 85
90
75
70dBLw,tot 80
85
90
75
1
23
4
1
23
4
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The limit lines for Ecodesign are calculated with capacity variant 2. The mean value for supply air and extract air must be within the limit line.
Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
2.5
2.0
1.5
70dBLw,tot 85
90
75
70dBLw,tot80
85
75
1
234
1
23
4
80
90 Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
MTE MPE
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
GOLD PX, counterflow heat exchanger, size 008, common casing
20191209 We reserve the right to alter specifications.
GOLD
123
Sizing, Installation, Dimensions and Weights
Clear Space for InspectionA clear space of 900 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.
Power connectionCapacity variant 1: 1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Capacity variant 2: 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Rated data per fanCapacity variant 1: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz Capacity variant 2: Motor shaft power: 1.6 kW, motor control system: 3 x 400 V, 50 Hz
Delivery and transport within the siteThe GOLD PX 008 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
The air handling unit is supplied on a wooden pallet.
The set of support legs, for mounting the base beams, is available as an accessory.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units).
Outdoor air Supply air Extract air Exhaust air
Size A B C D F G H J L Ø Weight, kg
008 911,5 995 277,5 440 271 543 1085 749 2503 400 449-506
Right-hand version
Left-hand version
PX
76
72
16
52*380 18
52305 305
76
45 45J
72
øø= =
Power connection
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
GOLD PX, counterflow heat exchanger, size 008, common casing
GOLD
We reserve the right to alter specifications. 20191209124
GOLD PX, counterflow heat exchanger, size 008, split version
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
Sizing, Installation, Dimensions and Weights
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -254 -2 -3 -5 -13 -13 -14 -20 -25
To inlet duct* 1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -434 -9 -11 -16 -28 -38 -41 -44 -44
To air handling unit surroun-dings**
1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -564 -13 -17 -28 -34 -46 -47 -54 -56
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s008 720 0.20 3600 1.00
2.5
2.0
1.5
70dBLw,tot80 85
90
75
70dBLw,tot 80
85
90
75
1
23
4
1
23
4
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The limit lines for Ecodesign are calculated with capacity variant 2. The mean value for supply air and extract air must be within the limit line.
Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
2.5
2.0
1.5
70dBLw,tot 85
90
75
70dBLw,tot80
85
75
1
234
1
23
4
80
90 Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
MTE MPE
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
20191209 We reserve the right to alter specifications.
GOLD
125
GOLD PX, counterflow heat exchanger, size 008, split version
Sizing, installation, dimensions and weights
Delivery and transport within the siteThe GOLD PX 008 can be supplied as one single unit, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit/Delivery Configuration RX/PX/CX, sizes 004-080.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units). Outdoor air Supply air Extract air Exhaust air
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 110-142 kg, D = 341-347 kg.
Division into sections for transport
A AD
Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Power connectionCapacity variant 1: 1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Capacity variant 2: 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanCapacity variant 1: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz Capacity variant 2: Motor shaft power: 1.6 kW, motor control system: 3 x 400 V, 50 Hz
Size A B C D F G H J K L Ø Weight, kg
008 647 995 277.5 1517 271 543 1085 749 440 2811 400 561-631
Right-hand version
Left-hand version
D
52
16 52*
380 18
PX
7676
K72
305
ø
305
ø
K
45 45J
72
= =
Power connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
GOLD
We reserve the right to alter specifications. 20191209126
2.5
2.01.5
65dBLw,tot 70 75 80
65dBLw,tot 7075
80
1
2
4
1
2
4
3
3
85
85
2.5
2.01.5
65dBLw,tot 70 75 80
65dBLw,tot 7075
80
1
2
4
1
2
4
3
3
85
85
GOLD PX Top, counterflow heat exchanger, size 008
Sizing, installation, dimensions and weights
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors, KOK , dB.
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Rangein
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outletduct
1 -1 -4 -5 -10 -12 -12 -20 -282 -2 -6 -10 -4 -10 -12 -19 -263 0 -2 -7 -15 -18 -20 -29 -374 -13 -14 -23 -34 -40 -39 -40 -46
To the inletduct*
1 -12 -13 -21 -31 -36 -37 -40 -502 -14 -17 -25 -27 -35 -37 -40 -493 -13 -12 -26 -38 -43 -41 -42 -524 -13 -14 -23 -34 -40 -39 -40 -46
To unit’s surroundings**
1 -12 -18 -28 -31 -45 -45 -54 -592 -13 -20 -33 -25 -43 -45 -53 -573 -11 -16 -30 -36 -51 -53 -63 -684 -24 -28 -46 -55 -73 -72 -74 -77
Size Min. airflow (for airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s008 720 0,20 3600 1,00
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
MTE MPE
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).Limit line, Ecodesign, 2018
For Ecodesign, the mean value for supply air and extract air must be within the limit line.
20191209 We reserve the right to alter specifications.
GOLD
127
GOLD PX Top, counterflow heat exchanger, size 008
Sizing, installation, dimensions and weights
Delivery and transport within the siteGOLD PX Top 008 can be supplied as one single unit or in an optional division of sections. Extra air handling unit sections cannot be ordered due to the deviating height measurement. Filter/fan sections for height adapted PX (side fed) and PX Top can be combined, see the section: Description of the Air Han-dling Unit.The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.The air handling unit/unit sections is/are delivered on wooden beams.The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors). B: Specify right-hand or left-hand version when ordering.
Size A B D E F H I J K L Ø Weight, kg
008 647 995 1517 350 878 1295 288 749 278 2811 400 613-621
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 136-137 kg, D = 341-347 kg.
Division into sections for transport
Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Electrical connectionCapacity variant 1: 1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Capacity variant 2: 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanCapacity variant 1: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz Capacity variant 2: Motor shaft power: 1.6 kW, motor control system: 3 x 400 V, 50 Hz
16
PX
380 18
76
D
52 45 45
J 76
52
FE
FE
I
K
ø
ø ø
ø
Electrical connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
Outdoor air Supply air Extract air Exhaust air
Right-hand version
Left-hand version
ADA
GOLD
We reserve the right to alter specifications. 20191209128
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
Sizing, installation, dimensions and weights
Size Min. flow (for airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s011 720 0.20 3960 1.10
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -254 -2 -3 -5 -13 -13 -14 -20 -25
To inlet duct* 1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -434 -9 -11 -16 -28 -38 -41 -44 -44
To air handling unit surroun-dings**
1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -564 -13 -17 -28 -34 -46 -47 -54 -56
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
GOLD PX, counterflow heat exchanger, size 011
2.5
2.0
1.5
1
23
4
1
234
70dBLw,tot 80 8575
90
70dBLw,tot 80 8575
90 Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).Limit line, Ecodesign, 2018
2.5
2.0
1.5
1
23
4
1
23
4
70dBLw,tot 80 8575
90
70dBLw,tot 80 8575
90 Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
MTE MPE
The limit line for Ecodesign 2018 is calculated with capacity variant 2. The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016.
20191209 We reserve the right to alter specifications.
GOLD
129
Sizing, installation, dimensions and weights
Power connectionCapacity variant 1: 1-phase, 3-conductor, 230 V -10/+15%, 50 Hz, 16 A or
3-phase, 5-conductor, 400 V -10/+15%, 50 Hz, 10 A Capacity variant 2: 3-phase, 5-conductor, 400 V -10/+15%, 50 Hz, 10 A Rated data per fanCapacity variant 1: Motor shaft power: 1.15 kW,
motor control system: 1 x 230 V, 50 Hz Capacity variant 2: Motor shaft power: 1.6 kW, motor control system: 3 x 400 V, 50 Hz
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 135-175 kg, D = 444-454 kg.
Division into sections for transport
Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
PX
76 76
K K
16 52*
380 18
D
E E52
72
øø
350 350
= =
45 45J
72
GOLD PX, counterflow heat exchanger, size 011
Power connection
Delivery and transport within the siteThe GOLD PX 011 can be supplied as one single unit, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit. Filter/fan sections for PX and PX Top can be combined, see the section: Description of the Air Handling Unit. The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.The air handling unit/unit sections is/are delivered on wooden beams.The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: Specify right-hand or left-hand version when ordering. B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units).
Right-hand version
Left-hand version
Outdoor air Supply air Extract air Exhaust air
Size A B C D E F G H J K L Ø Weight, kg
011 647 1199 324 1631 471 324 647 1295 953 551 2925 500 714-804
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
A AD
GOLD
We reserve the right to alter specifications. 20191209130
2.5
2.0
1.5
65dBLw,tot 70 75 80
65dBLw,tot 70 75 80
1
2
4
1
2
4
3
3
2.5
2.0
1.5
65dBLw,tot 70 75 80
65dBLw,tot 70 75 80
1
2
4
1
2
4
3
3
GOLD PX Top, counterflow heat exchanger, size 011
Sizing, installation, dimensions and weights
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors, KOK , dB.
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Size Min. airflow (for airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s011 720 0,20 3960 1,10
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Rangein
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outletduct
1 0 -11 -2 -11 -11 -12 -20 -292 1 -10 -11 -3 -8 -10 -16 -223 7 -2 -6 -13 -15 -16 -27 -354 -5 -15 -22 -32 -35 -36 -40 -40
To the inletduct*
1 -8 -18 -20 -31 -33 -36 -44 -442 -10 -21 -29 -25 -32 -34 -41 -463 -2 -9 -21 -35 -34 -38 -45 -474 -5 -15 -22 -32 -35 -36 -40 -40
To unit’s surroundings**
1 -11 -25 -25 -32 -44 -45 -54 -602 -10 -24 -34 -24 -41 -43 -50 -533 -4 -16 -29 -34 -48 -49 -61 -664 -16 -29 -45 -53 -68 -69 -74 -71
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
MTE MPE
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).Limit line, Ecodesign, 2018
For Ecodesign, the mean value for supply air and extract air must be within the limit line.
20191209 We reserve the right to alter specifications.
GOLD
131
16 52
D
52 45 45
J
FE
FE
I
Iø
ø
ø
ø
PX
380 1876
72
GOLD PX Top, counterflow heat exchanger, size 011
Sizing, installation, dimensions and weights
Delivery and transport within the siteThe GOLD Top PX 011 can be supplied as two units, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit. Filter/fan sections for PX and PX Top can be combined, see the section: Description of the Air Handling Unit.The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.The air handling unit/unit sections is/are delivered on wooden beams.The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors). B: Specify right-hand or left-hand version when ordering.
Electrical connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
Size A B D E F H I J L Ø Weight, kg
011 827 1199 1631 332 500 1295 332 953 3285 500 814-826
Outdoor air Supply air Extract air Exhaust air
Right-hand version
Left-hand version
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 185-186 kg, D = 444-454 kg.
Division into sections for transport
Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
ADA
Electrical connectionCapacity variant 1: 1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Capacity variant 2: 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanCapacity variant 1: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz Capacity variant 2: Motor shaft power: 1.6 kW, motor control system: 3 x 400 V, 50 Hz
GOLD
We reserve the right to alter specifications. 20191209132
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
Sizing, Installation, Dimensions and Weights
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -25
To inlet duct* 1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -43
To air handling unit surroun-dings**
1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -56
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s012 720 0.20 5040 1.40
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
GOLD PX, counterflow heat exchanger, size 012
2.5
2.0
1.5
1
23
1
23
70dBLw,tot 80 8575
90
70dBLw,tot 8085
75
90Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The limit lines for Ecodesign are calculated with capacity variant 2. The mean value for supply air and extract air must be within the limit line.
Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
MTE MPE
2.5
2.0
1.5
1
2
3
1
23
70dBLw,tot 80 8575
90
70dBLw,tot 80 8575
90Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Cap. var. 2
20191209 We reserve the right to alter specifications.
GOLD
133
Sizing, Installation, Dimensions and Weights
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 146-189 kg, D = 444-454 kg.
Division into sections for transport Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanMotor shaft power: 1.6 kW alt. 2.4 kW, motor control system: 3 x 400 V, 50 Hz
GOLD PX, counterflow heat exchanger, size 012Delivery and transport within the siteThe GOLD PX 012 can be supplied as one single unit, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit. Filter/fan sections for PX and PX Top can be combined, see the section: Description of the Air Handling Unit. The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.The air handling unit/unit sections is/are delivered on wooden beams.The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units). Outdoor air Supply air Extract air Exhaust air
Size A B C D E F G H J K L Ø Weight, kg
012 647 1199 324 1631 471 324 647 1295 953 551 2925 500 736-832
PX
76 76
K K
16 52*
380 18
D
E E52
72
øø
350 350
= =
45 45J
72
Power connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
A AD
Right-hand version
Left-hand version
GOLD
We reserve the right to alter specifications. 20191209134
2.5
2.01.5
65dBLw,tot 70 75 80
65dBLw,tot 70 75 80
1
2
1
23
3
85
85
2.5
2.0
1.5
65dBLw,tot 70 75 80
65dBLw,tot 70 75 80
1
2
1
23
385
85
GOLD PX Top, counterflow heat exchanger, size 012
Sizing, installation, dimensions and weights
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors, KOK , dB.
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Rangein
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outletduct
1 2 -7 -3 -10 -12 -14 -20 -262 3 -7 -6 -5 -9 -13 -17 -223 3 -3 -6 -11 -13 -17 -25 -31
To the inletduct*
1 -7 -15 -22 -34 -35 -38 -46 -492 -8 -17 -25 -29 -33 -37 -44 -493 -3 -13 -21 -37 -36 -39 -44 -45
To unit’s surroundings**
1 -9 -21 -26 -31 -45 -47 -54 -572 -8 -21 -29 -26 -42 -46 -51 -533 -8 -17 -29 -32 -46 -50 -59 -62
Size Min. airflow (for airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s012 720 0,20 5040 1,40
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Cap. var. 2
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
MTE MPE
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).Limit line, Ecodesign, 2018
For Ecodesign, the mean value for supply air and extract air must be within the limit line.
20191209 We reserve the right to alter specifications.
GOLD
135
GOLD PX Top, counterflow heat exchanger, size 012
Sizing, installation, dimensions and weights
16 52
D
52 45 45
J
FE
FE
I
Iø
ø
ø
ø
PX
380 1876
72
Delivery and transport within the siteThe GOLD Top PX 012 can be supplied as two units, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit. Filter/fan sections for PX and PX Top can be combined, see the section: Description of the Air Handling Unit.The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.The air handling unit/unit sections is/are delivered on wooden beams.The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors).
B: Specify right-hand or left-hand version when ordering.
Electrical connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
Size A B D E F H I J L Ø Weight, kg
012 827 1199 1631 332 500 1295 332 953 3285 500 836-854
Outdoor air Supply air Extract air Exhaust air
Right-hand version
Left-hand version
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 196-200 kg, D = 444-454 kg.
Division into sections for transport Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Electrical connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanMotor shaft power: 1.6 kW alt. 2.4 kW, motor control system: 3 x 400 V, 50 Hz
ADA
GOLD
We reserve the right to alter specifications. 20191209136
Sizing, Installation, Dimensions and Weights
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s014 720 0.20 5940 1.65
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -25
To inlet duct* 1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -43
To air handling unit surroun-dings**
1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -56
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
GOLD PX, counterflow heat exchanger, size 014
1
2
3
1
2
3
75dBLw,tot 85 8580
90
70dBLw,tot 80 8575
90
2.5
2.0
1.5
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The limit line for Ecodesign 2018 is calculated with capacity variant 2. The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016.
Limit line, Ecodesign, 2018
MTE MPE
1
2
3
1
2
3
75dBLw,tot 85 8580
90
70dBLw,tot 80 8575
90
2.5
2.0
1.5
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
20191209 We reserve the right to alter specifications.
GOLD
137
Sizing, Installation, Dimensions and Weights
Clear Space for InspectionA clear space of 900 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.
Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanMotor shaft power: 1.6 kW alt. 2.4 kW, motor control system: 3 x 400 V, 50 Hz
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 190-244 kg, D = 549-561 kg.
Division into sections for transport
GOLD PX, counterflow heat exchanger, size 014Delivery and transport within the siteThe GOLD PX 014 can be supplied as two units, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit. Filter/fan sections for PX and PX Top can be combined, see the section: Description of the Air Handling Unit.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units).
Outdoor air Supply air Extract air Exhaust air
Size A B D E F G H I J K L M N Weight, kg
014 757,5 1400 1836 528 400 1000 1551 375 1154 200 3351 205 188 929-1049
Right-hand version
Left-hand version
D
E E 5252
PX
M M
L
380 18
N76
N
724545
Power con-nection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
A AD
GOLD
We reserve the right to alter specifications. 20191209138
GOLD PX Top, counterflow heat exchanger, size 014
Sizing, installation, dimensions and weights
1
2
3
1
2
3
70dBLw,tot 85
90
8075
70dBLw,tot 85
90
8075
2.5
2.0
1.5
1
2
3
1
2
3
70dBLw,tot 85
90
8075
70dBLw,tot 85
90
8075
2.5
2.0
1.5
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s014 720 0,20 5940 1,65
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -10 -16 -2 -9 -9 -13 -16 -212 -9 -16 -9 -3 -6 -12 -15 -193 -1 -6 -4 -9 -10 -15 -21 -26
To inlet duct* 1 -14 -21 -25 -31 -33 -33 -26 -272 -16 -22 -28 -29 -32 -31 -25 -263 -9 -14 -30 -35 -38 -38 -33 -35
To air handling unit surroun-dings**
1 -21 -30 -25 -30 -42 -46 -50 -522 -20 -30 -32 -24 -39 -45 -49 -503 -12 -20 -27 -30 -43 -48 -55 -57
MTE MPE
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).Limit line, Ecodesign, 2018
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
For Ecodesign, the mean value for supply air and extract air must be within the limit line.
20191209 We reserve the right to alter specifications.
GOLD
139
GOLD PX Top, counterflow heat exchanger, size 014
Sizing, installation, dimensions and weights
Clear space for inspectionA clear space of 1000 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Electrical connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fanMotor shaft power: 1.6 kW alt. 2.4 kW, motor control system: 3 x 400 V, 50 Hz
45 72
45
J
100
21
B
5252 K K
PX
380 18 76
G
O P
N
MFE I M F EI
45 72
45
J
100
21
B
5252 K K
PX
380 18 76
G
O P
N
MFE I M F EI
Delivery and transport within the siteThe GOLD Top PX 014 can be supplied as two units, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit. Filter/fan sections for PX and PX Top can be combined, see the section: Description of the Air Handling Unit.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors).
B: Specify right-hand or left-hand version when ordering.
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 267-285 kg, D = 549-561 kg.
Division into sections for transport
Electrical connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
Size A B D E F G H I J K L M N O P Weight, kg
014 1039 1400 1836 120 400 1000 1551 106 1154 528 3914 300 1200 200 100 1083-1131
Outdoor air Supply air Extract air Exhaust air
Right-hand version
Left-hand version
View from the above.
ADA
GOLD
We reserve the right to alter specifications. 20191209140
Sizing, Installation, Dimensions and Weights
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s020 1080 0.30 7560 2.10
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11
2 2 -4 -7 -7 -10 -12 -16 -17
To inlet duct* 1 -11 -16 -14 -27 -33 -37 -38 -34
2 -6 -9 -14 -28 -35 -39 -43 -39
To air handling unit surroun-dings**
1 -15 -23 -30 -26 -41 -42 -45 -42
2 -9 -18 -30 -28 -43 -45 -50 -48
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
GOLD PX, counterflow heat exchanger, size 020
2.5
2.0
1.5
12
12
65dBLw,tot 75 80 8570
90
65dBLw,tot 75 80 8570
90 Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The limit lines for Ecodesign 2018 are calculated with capacity variant 2. The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016.
Limit line, Ecodesign, 2018
MTE MPE
2.52.0
1.5
12
12
65dBLw,tot 75 80 8570
65dBLw,tot 75 80 8570
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
20191209 We reserve the right to alter specifications.
GOLD
141
Sizing, Installation, Dimensions and Weights
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 200-264 kg, D = 549-561 kg.
Division into sections for transport Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A (capacity variant 1) alt. 16 A (capacity variant 2)
Rated data per fanMotor shaft power: 2.4 kW alt. 3.4 kW, motor control system: 3 x 400 V, 50 Hz
D
E E 5252
PX
M M
L
380 18
N76
N
724545
GOLD PX, counterflow heat exchanger, size 020
Power con-nection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
Size A B D E F G H I J K L M N Weight, kg
020 757,5 1400 1836 528 400 1000 1551 375 1154 200 3351 205 188 949-1089
Outdoor air Supply air Extract air Exhaust air
Right-hand version
Left-hand version
Delivery and transport within the siteThe GOLD PX 020 can be supplied as two units, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit. Filter/fan sections for PX and PX Top can be combined, see the section: Description of the Air Handling Unit.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units).
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
A AD
GOLD
We reserve the right to alter specifications. 20191209142
12
12
75dBLw,tot 85 90
95
80
75dBLw,tot 85
95
80 90
2.5
2.0
1.5
12
12
75dBLw,tot 85 90
95
80
75dBLw,tot 85
95
80 90
2.5
2.0
1.5
GOLD PX Top, counterflow heat exchanger, size 020
Sizing, installation, dimensions and weights
MTE MPE
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).Limit line, Ecodesign, 2018
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
For Ecodesign, the mean value for supply air and extract air must be within the limit line.
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s020 1080 0,30 7560 2,10
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -10 -15 -2 -8 -10 -17 -22 -28
2 -2 -6 -3 -8 -11 -19 -26 -31
To inlet duct* 1 -18 -24 -29 -33 -36 -35 -29 -30
2 -13 -17 -32 -38 -40 -41 -36 -37
To air handling unit surroun-dings**
1 -21 -29 -25 -29 -43 -50 -56 -59
2 -13 -20 -26 -29 -44 -52 -60 -62
20191209 We reserve the right to alter specifications.
GOLD
143
45 72
45
J
100
21
B
5252 K K
PX
380 18 76
G
O P
N
MFE I M F EI
45 72
45
J
100
21
B
5252 K K
PX
380 18 76
G
O P
N
MFE I M F EI
GOLD PX Top, counterflow heat exchanger, size 020
Sizing, installation, dimensions and weights
Clear space for inspectionA clear space of 1000 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Electrical connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A (capacity variant 1) or 16 A (capacity variant 2)
Rated data per fanMotor shaft power: 2.4 kW alt. 3.4 kW, motor control system: 3 x 400 V, 50 Hz
Delivery and transport within the siteThe GOLD Top PX 020 can be supplied as two units, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit. Filter/fan sections for PX and PX Top can be combined, see the section: Description of the Air Handling Unit.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors).
B: Specify right-hand or left-hand version when ordering.
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 277-307 kg, D = 549-561 kg.
Division into sections for transport
Electrical connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
Size A B D E F G H I J K L M N O P Weight, kg
020 1039 1400 1836 120 400 1000 1551 106 1154 528 3914 300 1200 200 100 1103-1175
Outdoor air Supply air Extract air Exhaust air
Right-hand version
Left-hand version
View from the above.
ADA
GOLD
We reserve the right to alter specifications. 20191209144
Sizing, Installation, Dimensions and Weights
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s025 1080 0.30 9000 2.50
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11
2 2 -4 -7 -7 -10 -12 -16 -17
To inlet duct* 1 -11 -16 -14 -27 -33 -37 -38 -34
2 -6 -9 -14 -28 -35 -39 -43 -39
To air handling unit surroun-dings**
1 -15 -23 -30 -26 -41 -42 -45 -42
2 -9 -18 -30 -28 -43 -45 -50 -48
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
GOLD PX, counterflow heat exchanger, size 025
2.52.0
1.5
65dBLw,tot 75 80 8570
65dBLw,tot 75 80 8570
12
12
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
The limit lines for Ecodesign 2018 are calculated with capacity variant 2. The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016.
MTE MPE
2.5 2.0
1.5
65dBLw,tot 7570 80 85
65dBLw,tot 75 80 8570
12
12
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).Limit line, Ecodesign, 2018
20191209 We reserve the right to alter specifications.
GOLD
145
Sizing, Installation, Dimensions and Weights
Clear space for inspectionA clear space of 900 mm should be provided in front of the unit.
Power connection3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 10 A (capacity variant 1) alt. 16 A (capacity variant 2)
Rated data per fanMotor shaft power: 2.4 kW alt. 3.4 kW, motor control system: 3 x 400 V, 50 Hz
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 249-333 kg, D = 737-761 kg.
Division into sections for transport
GOLD PX, counterflow heat exchanger, size 025Delivery and transport within the siteThe GOLD PX 025 can be supplied as two units, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit. Filter/fan sections for PX and PX Top can be combined, see the section: Description of the Air Handling Unit.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units).
Size A B D E F G H I J K L M N Weight, kg
025 847,5 1600 2130 675 500 1200 1811 405 1354 200 3825 200 203 1235-1427
Outdoor air Supply air Extract air Exhaust air
Right-hand version
Left-hand version
PX
M M
L
D
E E 5252
N
N
8245
45
Power connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
A AD
GOLD
We reserve the right to alter specifications. 20191209146
GOLD PX Top, counterflow heat exchanger, size 025
Sizing, installation, dimensions and weights
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
12
12
75dBLw,tot 85
90
80
75dBLw,tot 80
90
2.0
2.5
1.5
85
12
12
75dBLw,tot 85
90
80
75dBLw,tot 80
90
2.5
2.0
1.5
85
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s025 1080 0,30 9000 2,50
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -9 -13 -6 -6 -6 -12 -16 -19
2 -4 -5 -4 -8 -10 -18 -25 -28
To inlet duct* 1 -11 -13 -15 -26 -30 -31 -36 -36
2 -8 -9 -21 -31 -36 -37 -40 -40
To air handling unit surroun-dings**
1 -20 -27 -29 -27 -39 -45 -50 -50
2 -15 -19 -27 -29 -43 -51 -59 -59
MTE MPE
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).Limit line, Ecodesign, 2018
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
For Ecodesign, the mean value for supply air and extract air must be within the limit line.
20191209 We reserve the right to alter specifications.
GOLD
147
GOLD PX Top, counterflow heat exchanger, size 025
Sizing, installation, dimensions and weights
Clear space for inspectionA clear space of 1,000 mm should be provided in front of the unit.
Electrical connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A (capacity variant 1) or 16 A (capacity variant 2)
Rated data per fanMotor shaft power: 2.4 kW alt. 3.4 kW motor control system: 3 x 400 V, 50 Hz
45 82
45
J
100
21B
5252 K K
G
O P
N
MFE I M F EI
PX
Delivery and transport within the siteThe GOLD Top PX 025 can be supplied as two units, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit. Filter/fan sections for PX and PX Top can be combined, see the section: Description of the Air Handling Unit.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors).
B: Specify right-hand or left-hand version when ordering.
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 319-364 kg, D = 737-761 kg.
Division into sections for transport
Electrical connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
Size A B D E F G H I J K L M N O P Weight, kg
025 1039 1600 2130 120 400 1200 1811 106 1354 675 4208 300 1400 200 100 1375-1489
Outdoor air Supply air Extract air Exhaust air
Right-hand version
Left-hand version
A AD
45 82
45
J
100
21B
5252 K K
G
O P
N
MFE I M F EI
PX
View from the above.
GOLD
We reserve the right to alter specifications. 20191209148
Sizing, Installation, Dimensions and Weights
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s030 1800 0.50 11520 3.20
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11
2 2 -4 -7 -7 -10 -12 -16 -17
To inlet duct* 1 -11 -16 -14 -27 -33 -37 -38 -34
2 -6 -9 -14 -28 -35 -39 -43 -39
To air handling unit surroun-dings**
1 -15 -23 -30 -26 -41 -42 -45 -42
2 -9 -18 -30 -28 -43 -45 -50 -48
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
GOLD PX, counterflow heat exchanger, size 030
12
12
2.5
2.0
1.5
70dBLw,tot 80 8575
90
70dBLw,tot 80 8575
90
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The limit lines for Ecodesign are calculated with capacity variant 2. The mean value for supply air and extract air must be within the limit line.
Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
MTE MPE
12
12
2.5
2.0
1.5
70dBLw,tot 80 8575
90
70dBLw,tot 80 8575
90
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
20191209 We reserve the right to alter specifications.
GOLD
149
Sizing, Installation, Dimensions and Weights
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 275-345 kg, D = 737-761 kg.
Division into sections for transport Clear space for inspectionA clear space of 900 mm should be provided in front of the unit.
Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 16 A (capacity variant 1) alt. 20 A (capacity variant 2)
Rated data per fanMotor shaft power: 4.0 kW alt. 5.0 kW, motor control system: 3 x 400 V, 50 Hz
PX
M M
L
D
E E 5252
N
N
8245
45
GOLD PX, counterflow heat exchanger, size 030Delivery and transport within the siteThe GOLD PX 030 can be supplied as two units, or in a num-ber of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit. Filter/fan sections for PX and PX Top can be combined, see the section: Description of the Air Handling Unit. .
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units).
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
Size A B D E F G H I J K L M N Weight, kg
030 847,5 1600 2130 675 500 1200 1811 405 1354 200 3825 200 203 1287-1451
Outdoor air Supply air Extract air Exhaust air
Right-hand version
Left-hand version
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
Power connection
A AD
GOLD
We reserve the right to alter specifications. 20191209150
GOLD PX Top, counterflow heat exchanger, size 030
Sizing, installation, dimensions and weights
Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.
Correction factors KOK , dB
* The integral attenuation of filters and counterflow heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
2.5
2.0
1.5
12
12
75dBLw,tot 80 85 90
95
75dBLw,tot 80 85 90
95
12
12
75dBLw,tot 85 90
95
80
75dBLw,tot 80
95
2.0
2.5
1.5
85 90
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s030 1800 0,50 11520 3,20
Range in the
diagram
Octave band, No. / mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To outlet duct 1 -9 -13 -3 -6 -10 -15 -17 -17
2 -3 -5 -4 -8 -10 -18 -23 -24
To inlet duct* 1 -15 -17 -17 -28 -33 -34 -40 -40
2 -8 -8 -20 -31 -35 -36 -38 -39
To air handling unit surroun-dings**
1 -20 -27 -26 -27 -43 -48 -51 -48
2 -14 -19 -27 -29 -43 -51 -57 -55
MTE MPE
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).Limit line, Ecodesign, 2018
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
For Ecodesign, the mean value for supply air and extract air must be within the limit line.
20191209 We reserve the right to alter specifications.
GOLD
151
45 82
45
J
100
21B
5252 K K
G
O P
N
MFE I M F EI
PX
GOLD PX Top, counterflow heat exchanger, size 030
Sizing, installation, dimensions and weights
Delivery and transport within the siteThe GOLD Top PX 030 can be supplied as two units, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit. Filter/fan sections for PX and PX Top can be combined, see the section: Description of the Air Handling Unit.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors).
B: Specify right-hand or left-hand version when ordering.
Clear space for inspectionA clear space of 1,000 mm should be provided in front of the unit.
Electrical connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 16 A (capacity variant 1) alt. 20 A (capacity variant 2)
Rated data per fanMotor shaft power: 4.0 kW alt. 5.0 kW, motor control system: 3 x 400 V, 50 Hz
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 345-376 kg, D = 737-761 kg.
Division into sections for transport
Electrical connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
Size A B D E F G H I J K L M N O P Weight, kg
030 1039 1600 2130 120 400 1200 1811 106 1354 675 4208 300 1400 200 100 1427-1513
Outdoor air Supply air Extract air Exhaust air
Right-hand version
Left-hand version
A AD
45 82
45
J
100
21B
5252 K K
G
O P
N
MFE I M F EI
PX
View from the above.
GOLD
We reserve the right to alter specifications. 20191209152
Sizing, Installation, Dimensions and Weights
GOLD PX, counterflow heat exchanger, size 035
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held terminal. The practical flow limits are determined by the external pressure drop.
* The integral attenuation of filters and coil heat exchangers has been taken into account.** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Correction factors, KOK , dB
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s035 1800 0,50 14040 3,90
Range in the
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outlet duct
1 -4 -9 -7 -5 -8 -9 -11 -11
2 2 -4 -7 -7 -10 -12 -16 -17
To the inlet duct*
1 -10 -10 -8 -21 -28 -30 -35 -32
2 -5 -3 -8 -22 -30 -32 -40 -37
To air handling unit surround-ings**
1 -15 -23 -30 -26 -41 -42 -45 -42
2 -9 -18 -30 -28 -43 -45 -50 -48
2.5
2.0
1.5
75dBL w,tot 80 85 90
75dBL w,tot 80 85 90
12
12
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
MTE MPE
12
12
2.5
2.0
1.5
L w,tot 80 8575
L w,tot 80 85
90
9075
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels.
Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
20191209 We reserve the right to alter specifications.
GOLD
153
Sizing, Installation, Dimensions and Weights
PX
L
D
E E 5252
N
N
8245
45
245 245
GOLD PX, counterflow heat exchanger, size 035Delivery and transport within the siteThe GOLD PX 035 can be supplied as three units, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit/Delivery Configuration RX/PX/CX, sizes 011-080.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units).
Clear space for inspectionA clear space of 1,000 mm should be provided in front of the unit.
Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 16 A (capacity variant 1) alt. 20 A (capacity variant 2)
Rated data per fanMotor shaft power: 4.0 kW alt. 5.0 kW, motor control system, 3 x 400 V, 50 Hz
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 377-482 kg, D = 1038-1074 kg.
Division into sections for transport
Outdoor air Supply air Extract air Exhaust air
Right-hand version
Left-hand version
A AD
Power connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
Size A B D E F G H I J K L N Weight, kg
035 1038.5 1990 2400 806 600 1400 2159 479 1744 295 4477 240 1792-2038
GOLD
We reserve the right to alter specifications. 20191209154
2.5
2.0
1.5
75dBLw,tot 80 85 90
75dBLw,tot 80 85 90
12
12
2.5
2.0
1.5
75dBLw,tot 85 9080
75dBLw,tot 85 9080
12
12
Sizing, Installation, Dimensions and Weights
GOLD PX, counterflow heat exchanger, size 040
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held terminal. The practical flow limits are determined by the external pressure drop.
Correction factors, KOK , dB
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s040 2700 0,75 18000 5,00
* The integral attenuation of filters and coil heat exchangers has been taken into account.** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Range in the
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outlet duct
1 -4 -9 -7 -5 -8 -9 -11 -11
2 2 -4 -7 -7 -10 -12 -16 -17
To the inlet duct*
1 -10 -10 -8 -21 -28 -30 -35 -32
2 -5 -3 -8 -22 -30 -32 -40 -37
To air handling unit surround-ings**
1 -15 -23 -30 -26 -41 -42 -45 -42
2 -9 -18 -30 -28 -43 -45 -50 -48
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
MTE MPE
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).Limit line, Ecodesign, 2018
20191209 We reserve the right to alter specifications.
GOLD
155
Sizing, Installation, Dimensions and Weights
GOLD PX, counterflow heat exchanger, size 040Delivery and transport within the siteThe GOLD PX 040 can be supplied as three units, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit/Delivery Configuration RX/PX/CX, sizes 011-080.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (does not apply to outdoor units).
Clear space for inspectionA clear space of 1,000 mm should be provided in front of the unit.
Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 25 A (capacity variant 1) alt. 40 A (capacity variant 2)
Rated data per fanMotor shaft power: 6.5 kW alt. 10 kW, motor control system, 3 x 400 V, 50 Hz
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 390-504 kg, D = 1038-1074 kg.
Division into sections for transport
Outdoor air Supply air Extract air Exhaust air
A AD
Size A B D E F G H I J K L N Weight, kg
040 1038.5 1990 2400 806 600 1400 2159 479 1744 295 4477 240 1818-2082
Right-hand version
Left-hand version
PX
L
D
E E 5252
N
N
8245
45
245 245
Power connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
GOLD
We reserve the right to alter specifications. 20191209156
Sizing, Installation, Dimensions and Weights
GOLD CX, coil heat exchangers, size 035
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held terminal. The practical flow limits are determined by the external pressure drop.
* The integral attenuation of filters and coil heat exchangers has been taken into account.** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Correction factors, KOK , dB
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s035 1800 0,50 14040 3,90
Range in the
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outlet duct
1 -4 -9 -7 -5 -8 -9 -11 -11
2 2 -4 -7 -7 -10 -12 -16 -17
To the inlet duct*
1 -10 -10 -8 -21 -28 -30 -35 -32
2 -5 -3 -8 -22 -30 -32 -40 -37
To air handling unit surround-ings**
1 -15 -23 -30 -26 -41 -42 -45 -42
2 -9 -18 -30 -28 -43 -45 -50 -48
2.5
2.0
1.5
75dBL w,tot 80 85 90
75dBL w,tot 80 85 90
12
12
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The limit line for Ecodesign 2018 is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels.
Limit line, Ecodesign, 2018
20191209 We reserve the right to alter specifications.
GOLD
157
Sizing, Installation, Dimensions and Weights
5245
4552
200 700145
B**
CX
GOLD CX, coil heat exchangers, size 035
Size A B C D E F G H I J K L Weight, kg
035 1038.5 1990 1744 900 245 600 1400 2159 479 240 295 2977 1934-2144
Right-hand version
Left-hand version
Upward UpwardForwardForward
Upward Upward
ForwardForward
Outdoor air Supply air Extract air Exhaust air
Clear space for inspectionA clear space of 1,000 mm should be provided in front of the unit.
Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 20 A (capacity variant 1) alt. 25 A (capacity variant 2)
Rated data per fanMotor shaft power: 4.0 kW alt. 5.0 kW, motor control system, 3 x 400 V, 50 Hz
Power connection
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 377-482 kg, D = 1,180 kg.
Division into sections for transport
A AD
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose. Applies to right-hand version with the supply air fan to the upper right and to left-hand version with the supply air fan to the upper left.* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).** Width of centre section's casing = B + 200 mm.
Delivery and transport within the siteThe GOLD CX 035 is supplied in three units, or in a number of differ-ent combinations of unit sections from the factory, see the section: Description of the Air Handling Unit/Delivery Configuration RX/PX/CX, sizes 011-080.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The coil heat exchanger system is filled with liquid from the factory.
Duct connection optionsA: Specify right-hand or left-hand version when ordering. If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site using the hand-held terminal.
B: The arrangement of the functional sections can be vertically reversed. To be specified when placing an order, see the illustration to the right.
C: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
D: Specify whether the unit shall have an air intake from above for outdoor air or extract air when placing orders (Does not apply to units installed outdoors).
Supply air fan, right, lower level
Supply air fan, right, upper level
Supply air fan, left, upper level
Supply air fan, left, lower level
GOLD
We reserve the right to alter specifications. 20191209158
2.5
2.0
1.5
75dBLw,tot 85 9080
75dBLw,tot 85 9080
1
2
12
Sizing, Installation, Dimensions and Weights
GOLD CX, coil heat exchangers, size 040
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels.
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held terminal. The practical flow limits are determined by the external pressure drop.
Correction factors, KOK , dB
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s040 2700 0,75 18000 5,00
* The integral attenuation of filters and coil heat exchangers has been taken into account.** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Range in the
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outlet duct
1 -4 -9 -7 -5 -8 -9 -11 -11
2 2 -4 -7 -7 -10 -12 -16 -17
To the inlet duct*
1 -10 -10 -8 -21 -28 -30 -35 -32
2 -5 -3 -8 -22 -30 -32 -40 -37
To air handling unit surround-ings**
1 -15 -23 -30 -26 -41 -42 -45 -42
2 -9 -18 -30 -28 -43 -45 -50 -48
Cap. var. 1
Cap. var. 2
Cap. var. 1Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).Limit line, Ecodesign, 2018
20191209 We reserve the right to alter specifications.
GOLD
159
Sizing, Installation, Dimensions and Weights
GOLD CX, coil heat exchangers, size 040
Size A B C D E F G H I J K L Weight, kg
040 1038.5 1990 1744 900 245 600 1400 2159 479 240 295 2977 1960-2188
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 390-504 kg, D = 1,180 kg.
Division into sections for transport
A AD
** Width of centre section's casing = B + 200 mm.
Delivery and transport within the siteThe GOLD CX 040 is supplied in three units, or in a number of differ-ent combinations of unit sections from the factory, see the section: Description of the Air Handling Unit/Delivery Configuration RX/PX/CX, sizes 011-080.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The air handling unit/unit sections is/are delivered on wooden beams.
The coil heat exchanger system is filled with liquid from the factory.
Duct connection optionsA: Specify right-hand or left-hand version when ordering. If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site using the hand-held terminal.
B: The arrangement of the functional sections can be vertically reversed. To be specified when placing an order, see the illustration to the right.
C: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
D: Specify whether the unit shall have an air intake from above for outdoor air or extract air when placing orders (Does not apply to units installed outdoors).
Clear space for inspectionA clear space of 1,000 mm should be provided in front of the unit.
Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 32 A (capacity variant 1) alt. 40 A (capacity variant 2)
Rated data per fanMotor shaft power: 6.5 kW alt. 10 kW, motor control system: 3 x 400 V, 50 Hz
5245
4552
200 700145
B**
CX
Right-hand version
Left-hand version
Upward UpwardForwardForward
Upward Upward
ForwardForward
Outdoor air Supply air Extract air Exhaust air
Power connection
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose. Applies to right-hand version with the supply air fan to the upper right and to left-hand version with the supply air fan to the upper left.* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. The AHU can also be supplied with full face end connection panel (accessory).
Supply air fan, right, lower level
Supply air fan, right, upper level
Supply air fan, left, upper level
Supply air fan, left, lower level
GOLD
We reserve the right to alter specifications. 20191209160
2.5
2.0
1.5
75dBLw,tot 80 85 90
75dBLw,tot 80 85 90
12
12
Sizing, Installation, Dimensions and Weights
GOLD CX, coil heat exchangers, size 050
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held terminal. The practical flow limits are determined by the external pressure drop.
* The integral attenuation of filters and coil heat exchangers has been taken into account.** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Correction factors, KOK , dB
Rangein
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outletduct
1 -4 -9 -7 -5 -8 -9 -11 -11
2 2 -4 -7 -7 -10 -12 -16 -17
To the inletduct*
1 -10 -10 -8 -21 -28 -30 -35 -32
2 -5 -3 -8 -22 -30 -32 -40 -37
To unit’s surroundings**
1 -15 -23 -30 -26 -41 -42 -45 -42
2 -9 -18 -30 -28 -43 -45 -50 -48
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s050 2700 0,75 18000 5,00
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The air handling units, with capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018. Other values in diagrams are calculated for air handling units with standard end connection panels.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
20191209 We reserve the right to alter specifications.
GOLD
161
146M
B** 200 741
52
52*CX
10078
123 835 835402782162
45
N O
Sizing, Installation, Dimensions and Weights
GOLD CX, coil heat exchangers, size 050Delivery and transport within the siteThe GOLD CX 050 is supplied in three units, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit/Delivery Configu-ration RX/PX/CX, sizes 011-080.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors
The unit is supplied on 100 mm high support feet made of steel.
The coil heat exchanger system is filled with liquid from the factory.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: The arrangement of the functional sections can be vertically reversed. To be specified when placing an order, see the illustra-tion to the right.
C: Specify upper fan outlet for upward air discharge when plac-ing orders (not for outdoor units).
D: Specify whether the unit shall have an air intake from above for outdoor air or extract air when placing orders (Does not apply to units installed outdoors). N.B.! Duct connection size: 2,000 x 600 mm.
Upward Upward
ForwardForward
Upward Upward
ForwardForward
Right-hand version
Left-hand version
Outdoor air Supply air Extract air Exhaust air
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 444-572 kg, D = 1458 kg.
Clear space for inspectionA clear space of 1,100 mm should be provided in front of the unit.
Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 32 A (capacity variant 1) alt. 40 A (capacity variant 2)
Rated data per fanMotor shaft power: 6.5 kW alt. 10 kW, motor control system: 3 x 400 V, 50 Hz
Power connection
Division into sections for transport
* If the duct accessory is housed in an insu-lated casing, the AHU is supplied without the end connection panel. The AHU can also be supplied with full face end connection panel (accessory).
** Width of centre sec-tion's casing = B + 200 mm.
A AD
Supply air fan, right, lower level
Supply air fan, right, upper level
Supply air fan, left, upper level
Supply air fan, left, lower level
Supplied on 100 mm high transport feet. Removed when the unit is at its final location. If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Adjustable support feet (accessories) can be appropriately fitted to the base beams for this purpose. Applies to right-hand version with the supply air fan to the upper right and to left-hand version with the supply air fan to the upper left.
Size A B D E F G H I J K L M N O Weight, kg
050 1038,5 2318 900 145 800 1600 2288 344 172 359 2977 600 159 2000 2346-2602
GOLD
We reserve the right to alter specifications. 20191209162
Sizing, Installation, Dimensions and Weights
GOLD CX, coil heat exchanger, size 060
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held terminal. The practical flow limits are determined by the external pressure drop.
Correction factors, KOK , dB
* The integral attenuation of filters and coil heat exchangers has been taken into account.** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Rangein
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outletduct
1 -4 -9 -7 -5 -8 -9 -11 -11
2 2 -4 -7 -7 -10 -12 -16 -17
To the inletduct*
1 -10 -10 -8 -21 -28 -30 -35 -32
2 -5 -3 -8 -22 -30 -32 -40 -37
To unit’s surroundings**
1 -15 -23 -30 -26 -41 -42 -45 -42
2 -9 -18 -30 -28 -43 -45 -50 -48
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s060 3600 1,00 23400 6,50
2.5
2.0
1.5
75dBL w,tot 80 85 90
75dBL w,tot 80 85 90
12
12
95
95
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels.
Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
20191209 We reserve the right to alter specifications.
GOLD
163
146M
B** 200 741
52
52*CX
10078
123 835 835402782162
45
N O
Size A B D E F G H I J K L M N O Weight, kg
060 1038,5 2318 900 145 800 1600 2288 344 172 359 2977 600 159 2000 2480-2718
Sizing, Installation, Dimensions and Weights
GOLD CX, coil heat exchanger, size 060Delivery and transport within the siteThe GOLD CX 060 is supplied in three units, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit/Delivery Configu-ration RX/PX/CX, sizes 011-080.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors
The unit is supplied on 100 mm high support feet made of steel.
The coil heat exchanger system is filled with liquid from the factory.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: The arrangement of the functional sections can be vertically reversed. To be specified when placing an order, see the illustra-tion to the right.
C: Specify upper fan outlet for upward air discharge when plac-ing orders (not for outdoor units).
D: Specify whether the unit shall have an air intake from above for outdoor air or extract air when placing orders (Does not apply to units installed outdoors). N.B.! Duct connection size: 2,000 x 600 mm.
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 511-630 kg, D = 1458 kg.
Clear space for inspectionA clear space of 1,100 mm should be provided in front of the unit.
Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 40 A (capacity variant 1) or 50 A (capacity variant 2)
Rated data per fanMotor shaft power: 2 x 4.0 kW alt. 2 x 6.5 kW, motor control system: 3 x 400 V, 50 Hz
Power connection
Division into sections for transport
* If the duct accessory is housed in an insu-lated casing, the AHU is supplied without the end connection panel. The AHU can also be supplied with full face end connection panel (accessory).
** Width of centre sec-tion's casing = B + 200 mm.
A AD
Upward Upward
ForwardForward
Upward Upward
ForwardForward
Right-hand version
Left-hand version
Outdoor air Supply air Extract air Exhaust air
Supply air fan, right, lower level
Supply air fan, right, upper level
Supply air fan, left, upper level
Supply air fan, left, lower level
Supplied on 100 mm high transport feet. Removed when the unit is at its final location. If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Adjustable support feet (accessories) can be appropriately fitted to the base beams for this purpose. Applies to right-hand version with the supply air fan to the upper right and to left-hand version with the supply air fan to the upper left.
GOLD
We reserve the right to alter specifications. 20191209164
GOLD CX, coil heat exchangers, size 070
Sizing, Installation, Dimensions and Weights
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held terminal. The practical flow limits are determined by the external pressure drop.
Correction factors, KOK , dB
* The integral attenuation of filters and coil heat exchangers has been taken into account.** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Rangein
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outletduct
1 -4 -9 -7 -5 -8 -9 -11 -11
2 2 -4 -7 -7 -10 -12 -16 -17
To the inletduct*
1 -10 -10 -8 -21 -28 -30 -35 -32
2 -5 -3 -8 -22 -30 -32 -40 -37
To unit’s surroundings**
1 -15 -23 -30 -26 -41 -42 -45 -42
2 -9 -18 -30 -28 -43 -45 -50 -48
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s070 3600 1,00 27000 7,50
75dBL w,tot 80 85 90
75dBL w,tot 80 85 90
95
95
2.5
2.0
1.5
12
12
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1Cap. var. 2
Cap. var. 1
Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels.
Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
20191209 We reserve the right to alter specifications.
GOLD
165
CX
52*
52
200B**743146M N O
121 1200115076 2485 76
45
GOLD CX, coil heat exchangers, size 070
Sizing, Installation, Dimensions and Weights
Delivery and transport within the siteThe GOLD CX 070 is supplied in three units, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit/Delivery Configu-ration RX/PX/CX, sizes 011-080.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The coil heat exchanger system is filled with liquid from the factory.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: The arrangement of the functional sections can be vertically reversed. To be specified when placing an order, see the illustra-tion to the right.
C: Specify upper fan outlet for upward air discharge when plac-ing orders (not for outdoor units).
D: Specify whether the unit shall have an air intake from above for outdoor air or extract air when placing orders (Does not apply to units installed outdoors). N.B.! Duct connection size: 2,400 x 750 mm.
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 786-911 kg, D = 1882 kg.
Clear space for inspectionA clear space of 1,100 mm should be provided in front of the unit.
Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 40 A (capacity variant 1) or 63 A (capacity variant 2)
Rated data per fanMotor shaft power: 2 x 4.0 kW alt. 2 x 6.5 kW, motor control system: 3 x 400 V, 50 Hz
Power connection
Division into sections for transport
* If the duct accessory is housed in an insu-lated casing, the AHU is supplied without the end connection panel. The AHU can also be supplied with full face end connection panel (accessory).
** Width of centre sec-tion's casing = B + 200 mm.
A AD
Upward Upward
ForwardForward
Upward Upward
ForwardForward
Right-hand version
Left-hand version
Outdoor air Supply air Extract air Exhaust air
Supply air fan, right, lower level
Supply air fan, right, upper level
Supply air fan, left, upper level
Supply air fan, left, lower level
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Adjustable support feet (accessories) can be appropriately fitted to the base beams for this purpose. Applies to right-hand version with the supply air fan to the upper right and to left-hand version with the supply air fan to the upper left.
Size A B D E F G H I J K L M N O Weight, kg
070 1273,5 2637 900 162 1000 1800 2640 320 160 418,5 3447 750 118,5 2400 3454-3704
GOLD
We reserve the right to alter specifications. 20191209166
80dBLw,tot 85 90
80dBLw,tot 85 90
95
95
2.5
2.01.5
12
12
GOLD CX, coil heat exchangers, size 080
Sizing, Installation, Dimensions and Weights
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held terminal. The practical flow limits are determined by the external pressure drop.
Correction factors, KOK , dB
* The integral attenuation of filters and coil heat exchangers has been taken into account.** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Rangein
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outletduct
1 -4 -9 -7 -5 -8 -9 -11 -11
2 2 -4 -7 -7 -10 -12 -16 -17
To the inletduct*
1 -10 -10 -8 -21 -28 -30 -35 -32
2 -5 -3 -8 -22 -30 -32 -40 -37
To unit’s surroundings**
1 -15 -23 -30 -26 -41 -42 -45 -42
2 -9 -18 -30 -28 -43 -45 -50 -48
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s080 5400 1,50 34200 9,50
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).Limit line, Ecodesign, 2018
20191209 We reserve the right to alter specifications.
GOLD
167
CX
52*
52
200B**743146M N O
121 1200115076 2485 76
45
GOLD CX, coil heat exchangers, size 080
Sizing, Installation, Dimensions and Weights
Delivery and transport within the siteThe GOLD CX 080 is supplied in three units, or in a number of different combinations of unit sections from the factory, see the section: Description of the Air Handling Unit/Delivery Configu-ration RX/PX/CX, sizes 011-080.
The unit sections are jointed together/split by means of bolts. The electrical and control cables between the unit sections have quick-fit connectors.
The coil heat exchanger system is filled with liquid from the factory.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: The arrangement of the functional sections can be vertically reversed. To be specified when placing an order, see the illustra-tion to the right.
C: Specify upper fan outlet for upward air discharge when plac-ing orders (not for outdoor units).
D: Specify whether the unit shall have an air intake from above for outdoor air or extract air when placing orders (Does not apply to units installed outdoors). N.B.! Duct connection size: 2,400 x 750 mm.
The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 813-956 kg, D = 1882 kg.
Clear space for inspectionA clear space of 1,100 mm should be provided in front of the unit.
Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 63 A (capacity variant 1) or 80 A (capacity variant 2)
Rated data per fanMotor shaft power: 2 x 6.5 kW alt. 2 x 10 kW, motor control system: 3 x 400 V, 50 Hz
Division into sections for transport
A AD
Upward Upward
ForwardForward
Upward Upward
ForwardForward
Right-hand version
Left-hand version
Outdoor air Supply air Extract air Exhaust air
Supply air fan, right, lower level
Supply air fan, right, upper level
Supply air fan, left, upper level
Supply air fan, left, lower level
Power connection
* If the duct accessory is housed in an insu-lated casing, the AHU is supplied without the end connection panel. The AHU can also be supplied with full face end connection panel (accessory).
** Width of centre sec-tion's casing = B + 200 mm.
If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Adjustable support feet (accessories) can be appropriately fitted to the base beams for this purpose. Applies to right-hand version with the sup-ply air fan to the upper right and to left-hand version with the supply air fan to the upper left.
Size A B D E F G H I J K L M N O Weight, kg
080 1273,5 2637 900 162 1000 1800 2640 320 160 418,5 3447 750 118,5 2400 3508-3794
GOLD
We reserve the right to alter specifications. 20191209168
2.5
2.0
1.5
12
12
80dBLw,tot 85 90 95
80dBLw,tot 85 9095
GOLD CX, coil heat exchangers, size 100
Sizing, installation, dimensions and weights
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held terminal. The practical flow limits are determined by the external pressure drop.
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s100 5400 1,50 39 600 11,0
Correction factors, KOK , dB
* The integral attenuation of filters and coil heat exchangers has been taken into account.
** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Range in the
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outlet duct
1 -4 -9 -7 -5 -8 -9 -11 -11
2 2 -4 -7 -7 -10 -12 -16 -17
To the inlet duct**
1 -10 -10 -8 -21 -28 -30 -35 -32
2 -5 -3 -8 -22 -30 -32 -40 -37
To air handling unit surround-ings**
1 -15 -23 -30 -26 -41 -42 -45 -42
2 -9 -18 -30 -28 -43 -45 -50 -48
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1Cap. var. 2
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
The limit line for Ecodesign 2018 is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels.
Limit line, Ecodesign, 2018
20191209 We reserve the right to alter specifications.
GOLD
169
GOLD CX, coil heat exchangers, size 100
Sizing, installation, dimensions and weights
56*M
P
P
N O N
180200B**
56
77 3186 77
1048 1000 1048122
45
Delivery and transport within the siteThe GOLD CX 100 is supplied as six separate sections: Two fan sections, two filter sections and two coil heat exchanger sections. The six sections must be fitted together at the building site. The pipework package including the control box can be ordered as accessories and are supplied in unassembled condition for floor or wall mounting (see TBXZ pipework package under Acces-sories).
The three sections are to be jointed together by bolts and the electrical and control cables are simple to connect.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: The arrangement of the functional sections can vary. Specify this by selecting fan arrangement 1, 2, 4 or 5 when placing orders. For fan arrangement 4 and 5, you should also specify: supply air in upper or lower level.
C: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units). N.B.! Duct connec-tion size: 2,500 x 800 mm.
* If the duct accessory is housed in an insu-lated casing, the AHU is supplied without the end connection panel. The AHU can also be supplied with full face end connection panel (accessory).
Upward UpwardForwardForward
Upward Upward
ForwardForward
Right-hand version
Fan arrangement 1 Fan arrangement 2
Outdoor air Supply air Extract air Exhaust air
Filter and fan sections See dimensions A and P in the table above. Weight: fan section = 644-720 kg, filter section = 402-540 kg.
Heat exchanger sectionsSee dimensions D and P in the table above. Weight: Heat exchanger section = 1101-1126 kg.
Clear space for inspectionA clear space of 1,000 mm should be provided in front of the unit.
Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 50 A (capacity variant 1) or 80 A (capacity variant 2)
Rated data per fanMotor shaft power: 2 x 6.5 kW alt. 2 x 10 kW, motor control system: 3 x 400 V, 50 Hz
Transport, dimensions and weights
Fan arrangement 5, supply air – upper level
Fan arrangement 5, supply air - lower level
Upward UpwardForwardForward
Upward UpwardForward
Forward
Left-hand version
Fan arrangement 1 Fan arrangement 2
Fan arrangement 4, supply air – upper level
Fan arrangement 4, supply air - lower level
Size A B D E F G H I J K L M N O P Weight, kg
100 1126 3340 1070 190 1200 2400 3440 520 210 470 3322 800 420 2500 1720 4294-4772
Power connection
If extract air flows through the lower level: The air handling unit must be raised at least 50 mm (Higher than the upper edge of the base beams) to provide space for the water trap.
** Width of centre sec-tion's casing = B + 200 mm.
GOLD
We reserve the right to alter specifications. 20191209170
2.5
2.01.5
12
12
80dBLw,tot 85 90 95
80dBLw,tot 85 90 95
GOLD CX, coil heat exchangers, size 120
Sizing, installation, dimensions and weights
Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held terminal. The practical flow limits are determined by the external pressure drop.
Size Min. airflow (on airflow regulation)
Max. airflow
m3/h m3/s m3/h m3/s120 9000 2,50 50 400 14.0
Correction factors, KOK , dB
* The integral attenuation of filters and coil heat exchangers has been taken into account.
** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
Range in the
diagram
Octave band, no./mid-frequency, Hz
Sound path 1 2 3 4 5 6 7 8
63 125 250 500 1000 2000 4000 8000
To the outlet duct
1 -4 -9 -7 -5 -8 -9 -11 -11
2 2 -4 -7 -7 -10 -12 -16 -17
To the inlet duct**
1 -10 -10 -8 -21 -28 -30 -35 -32
2 -5 -3 -8 -22 -30 -32 -40 -37
To air handling unit surround-ings**
1 -15 -23 -30 -26 -41 -42 -45 -42
2 -9 -18 -30 -28 -43 -45 -50 -48
Supply air fan
Extract air fan
SFPv
Air flow, m3/s
Ava
ilab
le t
ota
l pre
ssu
re r
ise,
Pa
Air flow, m3/h
The lower limit for the air flow when the unit is operating in the air flow regulation mode.
Cap. var. 1
Cap. var. 2
Cap. var. 1
Cap. var. 2
The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the air flow when the unit is operating in the air flow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the air flow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).Limit line, Ecodesign, 2018
20191209 We reserve the right to alter specifications.
GOLD
171
Size A B D E F G H I J K L M N O P Weight, kg
120 1126 3340 1070 190 1200 2400 3440 520 210 470 3322 800 420 2500 1720 4494-4990
GOLD CX, coil heat exchangers, size 120
Sizing, installation, dimensions and weights
56*M
P
P
N O N
180200B**
56
77 3186 77
1048 1000 1048122
45
Delivery and transport within the siteThe GOLD CX 120 is supplied as six separate sections: Two fan sections, two filter sections and two coil heat exchanger sections. The six sections must be fitted together at the building site. The pipework package including the control box can be ordered as accessories and are supplied in unassembled condition for floor or wall mounting (see TBXZ pipework package under Acces-sories).
The three sections are to be jointed together by bolts and the electrical and control cables are simple to connect.
Duct connection optionsA: Specify right-hand or left-hand version when ordering.
B: The arrangement of the functional sections can vary. Specify this by selecting fan arrangement 1, 2, 4 or 5 when placing orders. For fan arrangement 4 and 5, you should also specify: supply air in upper or lower level.
C: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units). N.B.! Duct connec-tion size: 2,500 x 800 mm.
* If the duct accessory is housed in an insu-lated casing, the AHU is supplied without the end connection panel. The AHU can also be supplied with full face end connection panel (accessory).
Outdoor air Supply air Extract air Exhaust air
Power connection
If extract air flows through the lower level: The air handling unit must be raised at least 50 mm (Higher than the upper edge of the base beams) to provide space for the water trap.
** Width of centre sec-tion's casing = B + 200 mm.
Filter and fan sections See dimensions A and P in the table above. Weight: fan section = 744-829 kg, filter section = 402-540 kg.
Heat exchanger sectionsSee dimensions D and P in the table above. Weight: Heat exchanger section = 1101-1126 kg.
Clear space for inspectionA clear space of 1,000 mm should be provided in front of the unit.
Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 80 A (capacity variant 1) or 125 A (capacity variant 2)
Rated data per fanMotor shaft power: 3 x 6.5 kW or 3 x 10 kW, motor control system: 3 x 400 V, 50 Hz
Transport, dimensions and weights
Upward UpwardForwardForward
Upward Upward
ForwardForward
Right-hand version
Fan arrangement 1 Fan arrangement 2
Fan arrangement 5, supply air – upper level
Fan arrangement 5, supply air - lower level
Upward UpwardForwardForward
Upward UpwardForward
Forward
Left-hand version
Fan arrangement 1 Fan arrangement 2
Fan arrangement 4, supply air – upper level
Fan arrangement 4, supply air - lower level