24.00-00A DWG. ABSORPTION BED FOR TRANSFORMER PADS 24.01-01 SECTION 24 - PADS, PULL BOXES TABLE OF CONTENTS 24.01-07 SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA 24.01-09 THREE-PHASE TRANSFORMER PAD FOR 75-300 KVA THREE-PHASE TRANSFORMER PAD FOR 500-3000 KVA 24.01-13 ADAPTER PLATE FOR THREE-PHASE TRANSFORMER PAD FOR 500-3000KVA 0 3 2 APPR. REVISED BY CK'D 1 24.01-11 AND PAD-MOUNTED CAPACITOR THREE-PHASE SECONDARY ENCLOSURE PAD 24.03-01 THREE-PHASE SECONDARY ENCLOSURE MOUNTING BOX 24.03-03 (SMALL SPLICE BOX) (24" X 43" X 18") MOUNTING BOX FOR PME 9, 10, 11 & AUTO TRANSFER 24.05-01 24.05-03 MOUNTING BOX FOR PME 4 (200 & 600 AMP) 24.05-05 MOUNTING BOX PMH 9, 10 & 11, AUTO TRANSFER & TRAYER 9, 10 & 11 24.05-07 MOUNTING BOX FOR COOPER 15KV VFI-5 24.05-09 MOUNTING BOX FOR 15 KV, 12.5 KA, VISTA AND NEXT GENERATION VISTA SMALL PULL & SPLICE BOX (30" X 48" X 24") 24.07-03 24.07-07 LIDS FOR SMALL PULL & SPLICE BOX 24.07-09 LARGE PULL BOX, BOTTOM HALF (6.5' X 4' X 2') 24.07-11 LARGE PULL BOX, TOP HALF (6.5' X 4' X 3') STEEL LIDS FOR LARGE PULL BOX 24.07-13 24.07-15 CONCRETE LIDS FOR LARGE PULL BOX LARGE PULL BOX ASSEMBLY 24.07-01 10/4/10 CECCONI GUINN ELKINS 24.05-11 CABLE AND CONDUIT PLACEMENT FOR TRAYER ATS VFI 5/24/12 KATIGBAK BURLISON ELKINS 24.01 TRANSFORMERS 24.03 ENCLOSURES 24.05 SWITCHGEAR 24.07 PULL BOXES

Upload: others

Post on 12-Jul-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

24.00-00A

DWG.

ABSORPTION BED FOR TRANSFORMER PADS 24.01-01

SECTION 24 - PADS, PULL BOXES

TABLE OF CONTENTS

24.01-07SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA

24.01-09THREE-PHASE TRANSFORMER PAD FOR 75-300 KVA

THREE-PHASE TRANSFORMER PAD FOR 500-3000 KVA

24.01-13ADAPTER PLATE FOR THREE-PHASE TRANSFORMER PAD FOR 500-3000KVA

0

3

2

APPR.REVISED BY CK'D

1

24.01-11AND PAD-MOUNTED CAPACITOR

THREE-PHASE SECONDARY ENCLOSURE PAD 24.03-01

THREE-PHASE SECONDARY ENCLOSURE MOUNTING BOX

24.03-03(SMALL SPLICE BOX) (24" X 43" X 18")

MOUNTING BOX FOR PME 9, 10, 11 & AUTO TRANSFER 24.05-01

24.05-03MOUNTING BOX FOR PME 4 (200 & 600 AMP)

24.05-05MOUNTING BOX PMH 9, 10 & 11, AUTO TRANSFER & TRAYER 9, 10 & 11

24.05-07MOUNTING BOX FOR COOPER 15KV VFI-5

24.05-09MOUNTING BOX FOR 15 KV, 12.5 KA, VISTA AND NEXT GENERATION VISTA

SMALL PULL & SPLICE BOX (30" X 48" X 24")

24.07-03

24.07-07

LIDS FOR SMALL PULL & SPLICE BOX

24.07-09

LARGE PULL BOX, BOTTOM HALF (6.5' X 4' X 2')

24.07-11

LARGE PULL BOX, TOP HALF (6.5' X 4' X 3')

STEEL LIDS FOR LARGE PULL BOX

24.07-13

24.07-15

CONCRETE LIDS FOR LARGE PULL BOX

LARGE PULL BOX ASSEMBLY

24.07-01

10/4/10

CECCONI GUINN ELKINS

24.05-11CABLE AND CONDUIT PLACEMENT FOR TRAYER ATS VFI

5/24/12

KATIGBAK BURLISON ELKINS

24.01 TRANSFORMERS

24.03 ENCLOSURES

24.05 SWITCHGEAR

24.07 PULL BOXES

Page 2: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

4"

4"

TRANSFORMER

PAD

PLAN VIEW

3Ø 500-3000 28" 82" 87"

TRANSFORMER

KVA

ALL

75-300

PHASE

A

12"

18"

45"

60"

B

APPROXIMATE

WEIGHT/LBS

C

40"

75" 2150

3000

470

24.01-01

DWG.

10/4/10

DANNA GUINN ELKINS

A

A C A

A

B

CONTINUOUS

CONCRETE CURB OR

EDGE OF ASPHALT

CURBING AND ABSORPTION BED ARE REQUIRED WHEN TRANSFORMER IS LOCATED IN OR IMMEDIATELY ADJACENT

TO PAVEMENT, NEAR BODIES OR WATER, STORM DRAINS, RETENTION AREAS, OR LOCATIONS WHERE OIL RUNOFF

IS LIKELY TO ENTER WATER, STORM OR SEWER SYSTEMS.

CRUSHED STONE

(1/2" MIN. DIA.)

AROUND PAD

CUSTOMER PROVIDE

AND INSTALLED

CONCRETE CURB

AROUND PAD

FINISHED GRADE

4"

4"12" MIN. 4"

2"

CRUSHED STONES

TRAFFIC BARRIERS

NOTES:

1. ALL UNDERGROUND FACILITIES MUST BE LOCATED PRIOR TO INSTALLATION OF TRAFFIC BARRIERS.

ABSORPTION BED FOR TRANSFORMER PADS

FOR TRAFFIC BARRIER DETAILS.

R

0

3

2

1

APPR.REVISED BY CK'D

TRAFFIC BARRIERS ARE TO BE USED WHEN TRANSFORMER IS EXPOSED TO VEHICLE TRAFFIC. SEE DWG. 27.06-06

Page 3: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

DWG.

24.01-07

SINGLE-PHASE TRANSFORMER PAD

FOR 25 - 167 KVA

PLAN VIEW

SIDE VIEW

3/4" LIFTING

INSERT

5/8" INSERT

NOTES:

1. THE GROUND SHALL BE LEVELED AND THOROUGHLY COMPACTED BEFORE PAD IS INSTALLED.

4. CUT OFF ALL CONDUITS FLUSH WITH TOP OF PAD AND CAP CONDUIT.

5. SOD MAY BE REQUIRED AROUND PAD TO PREVENT SOIL EROSION.

3. MAINTAIN CLEARANCES PER DWG. 27.06-05.

R

2. USE FIRE ANT CONTROL UNDER ENTIRE PAD INCLUDING PAD OPENINGS.

0

2

1

APPR.REVISED BY CK'D

3

10/4/10

ELKINSDANNA GUINN

40"

45"

6-3/8"

1-5/8" 12"12" 1-5/8"

6-3/8"27-1/4"

6"

14"

6-1/2"

13-1/2"

1"

1"

4"

2"

PRIMARY

D8.0 X D8.0

(TYP. 2 LOCATIONS)

WELDED WIRE MESH

SECONDARY

1 PAD1P40X45CF

BILL OF MATERIALS

CATALOG

327703 25 - 167 KVA SINGLE-PHASE PAD

DESCRIPTION

1

QTY

1

PER

CU

NUMBER

MACRO UNIT

-

CU

ITEM

NO.

COMPATIBLE

UNIT

QTY

REQ'D

1

Page 4: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

DWG.

24.01-09

THREE-PHASE TRANSFORMER

PAD FOR 75-300 KVA

NOTES:

1. THE GROUND SHALL BE LEVELED AND THOROUGHLY COMPACTED BEFORE PAD IS INSTALLED.

2. USE GENEROUS AMOUNT OF FIRE ANT KILLER UNDER ENTIRE PAD.

4. CUT OFF ALL CONDUITS FLUSH WITH TOP OF PAD AND CAP CONDUIT.

5. SOD MAY BE REQUIRED AROUND PAD TO PREVENT SOIL EROSION.

3. MAINTAIN CLEARANCES PER DWG. 27.06-05.

PLAN VIEW

3/4" LIFTING

INSERT

0

3

2

1

APPR.REVISED BY CK'D

SIDE VIEW

60"

33-1/2"

3"

16" 4" 4@7-1/2"=30" 4"

75"

4-1/2"

8@8-1/4"=66"

4-1/2"

PRIMARY

SECONDARY

3/4" LIFTING

INSERT

3"

TRADEMARK

1"

1"

7"

3-1/2"

12-3/4"

13-1/2"

48"

12-3/4"

10/4/10

ELKINSDANNA GUINN

1 PAD3P60X75CF

BILL OF MATERIALS

CATALOG

327707 60" X 75" 75 - 300 KVA THREE-PHASE PAD

DESCRIPTION

1

QTY

1

PER

CU

NUMBER

MACRO UNIT

-

CU

ITEM

NO.

COMPATIBLE

UNIT

QTY

REQ'D

1

7/9/13

ADCOCKKATIGBAK GUINN

Page 5: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

DWG.

24.01-11

10/4/10

DANNA GUINN ELKINS

THREE-PHASE TRANSFORMER

PAD FOR 500-3000 KVA

AND PAD-MOUNTED CAPACITOR

NOTES:

1. THE GROUND SHALL BE LEVELED AND THOROUGHLY COMPACTED BEFORE PAD IS INSTALLED.

4. CUT OFF ALL CONDUITS FLUSH WITH TOP OF PAD AND CAP CONDUIT.

5. SOD MAY BE REQUIRED AROUND PAD TO PREVENT SOIL EROSION.

3. MAINTAIN CLEARANCES PER DWG. 27.06-05.

PLAN VIEW

GALVANIZED COIL INSERT

(TYPICAL 2 LOCATIONS)

PAD3P82X87CF

R

0

3

2

1

APPR.REVISED BY CK'D

SIDE VIEW

OPENING

1"

1"

7"

3-1/2"

87"

82"

6@6-5/8"=39-3/4"

3@7-1/2"=22-1/2"

5@7=35"

3@7-1/2"=22-1/2"

60"13-1/2"

2. USE FIRE ANT CONTROL UNDER ENTIRE PAD INCLUDING PAD OPENINGS.

327712

32"

4"

2"

4"

13-1/2"

26"

4 - #4 BARS @ 24" LONG

(TYPICAL 4 LOCATIONS)

#4 BAR REINFORCING

TYPICAL

1 - EXTRA #4 BAR BETWEEN

EDGE OF PAD AND WINDOW

OPENING (TYPICAL EACH SIDE)

1

BILL OF MATERIALS

CATALOG

82" X 87" 500 - 3000 KVA 3 PH. PAD

DESCRIPTION

1

QTY

1

PER

CU

NUMBER

MACRO UNIT

-

CU

ITEM

NO.

COMPATIBLE

UNIT

QTY

REQ'D

1

3-1/2" 3-1/2"

Page 6: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

DWG.

24.01-13

10/4/10DANNA GUINN ELKINS

ADAPTER PLATE FOR THREE-PHASE

TRANSFORMER PAD FOR 500-3000 KVA

NOTES:

R

59"

1"

12"

12"

64"

2"

1/2-13 BONDING PAD WITH

ANDERSON GROUND LUG

MOUNTED ON BOTTOM OF

THE PLATE

1/4-1X59 BACKSTOP BAR

CENTERED ON PLATE BOTTOM

DESIGNS WITH THE LARGE 500-3000KVA PADMOUNT CONCRETE PAD.

12 GAUGE 304L SS PLATE IS TO BE USED AS AN ADAPTER PLATE FOR USE WITH 18" DEEP CABINET TRANSFORMER

1. USE ADAPTER PLATE TO REDUCE PAD OPENING AS NEEDED WHEN INSTALLING TRANSFORMER WITH 18" DEEP

CABINET.

2. GROUND ADAPTER PLATE WITH #4 BC USING GROUND LUG INSTALLED ON BOTTOM.

3. PLACE ADAPTER PLATE IN PAD OPENING WITH BACKSTOP AGAINST THE REAR OF THE OPENING AS SHOWN.

0

3

2

1

APPR.REVISED BY CK'D

1 PADADAPTERLTF

BILL OF MATERIALS

CATALOG

9220119264 64" X 12" TRANSFORMER PAD ADAPTER PLATE

DESCRIPTION

1

QTY

1

PER

CU

NUMBER

MACRO UNIT

-

CU

ITEM

NO.

COMPATIBLE

UNIT

QTY

REQ'D

1

Page 7: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

DWG.

24.03-01

10/4/10

DANNA GUINN ELKINS

THREE-PHASE SECONDARY ENCLOSURE PAD

NOTES:

1. THE GROUND SHALL BE LEVELED AND THOROUGHLY COMPACTED BEFORE PAD IS INSTALLED.

PLAN VIEW

SIDE VIEW

3. MAINTAIN 8' CLEARANCE FROM FRONT AND REAR DOORS AND 3' FROM SIDES.

4. CUT OFF ALL CONDUITS FLUSH WITH TOP OF PAD AND CAP CONDUIT.

5. SOD MAY BE REQUIRED AROUND PAD TO PREVENT SOIL EROSION.

29"

56"

5"

1/2" CHAMFER

18"

50" 23"

1/2"

THREADED

INSERTS

SECONDARY ENCLOSURE

OUTLINE OF 3 PHASE

3/4" LIFTING

INSERTS

1/2"

TRADEMARK

1/2"

R

0

3

2

1

APPR.REVISED BY CK'D

2. USE FIRE ANT CONTROL UNDER ENTIRE PAD INCLUDING PAD OPENINGS.

1

1 PADS50X56CF

BILL OF MATERIALS

CATALOG

327704 50" X 56" SECONDARY ENCLOSURE PAD

DESCRIPTION

1

QTY

1

PER

CU

NUMBER

MACRO UNIT

-

CU

ITEM

NO.

COMPATIBLE

UNIT

QTY

REQ'D

Page 8: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

2. WHEN USED AS A SPLICE BOX, USE 1/0 PRIMARY CONDUCTOR MAXIMUM.

1. BELOW GRADE INSTALLATION REQUIRES ELECTRONIC POWER MARKER.

NOTES:

24.03-03

DWG.

3. CAN BE USED AS THREE-PHASE SECONDARY ENCLOSURE MOUNTING BOX. SEE DWG. 25.03-01.

4. CAN BE USED AS A SINGLE-PHASE TRANSFORMER MOUNTING BOX.

THREE-PHASE SECONDARY ENCLOSURE

MOUNTING BOX (SMALL SPLICE BOX)

(24" X 43" X 18")

5. CUT OFF CONDUITS (IF PRESENT) 6" ABOVE BOTTOM OF BOX AND CAP.

6. DO NOT FILL INTERIOR OF BOX WITH SOIL.

24"

12"

20-1/2"

2-1/2"

2-1/2"

29"

24"

18"

32"

2-1/2"

48"

11 7/8"

R

7. USE FIRE ANT CONTROL UNDER ENTIRE PAD INCLUDING PAD OPENINGS.

0

3

2

1

APPR.REVISED BY CK'D

1

BILL OF MATERIALS

CATALOG

320154

24" X 32" LID

BOX

12.875" X 32" LID

DESCRIPTION

PADTMT48X32CF 320162

320166

1

QTY

1

1

1

PER

CU

NUMBER

MACRO UNIT

-

CU

ITEM

NO.

COMPATIBLE

UNIT

QTY

REQ'D

1

8/10/10DANNA GUINN ELKINS

Page 9: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

1. THE GROUND SHALL BE LEVELED AND THOROUGHLY COMPACTED BEFORE PAD IS INSTALLED.

NOTES:

24.05-01

DWG.

4. CUT OFF ALL CONDUITS 6" ABOVE BOTTOM OF BOX AND CAP.

MOUNTING BOX FOR PME 9, 10, 11

& AUTO TRANSFER

10/4/10DANNA GUINN ELKINS

5. DO NOT FILL INTERIOR OF BOX WITH SOIL.

6. SOD MAY BE REQUIRED AROUND PAD TO PREVENT SOIL EROSION.

SIDE VIEW

PLAN VIEW

6'-5"

LOCATION OF

49 1/2"

INSERT FOR

PME 9

LOCATION OF

PME 10 & 11

INSERT FOR

55 1/2"

5/8"

THREADED

INSERTS

6'-3"

69 1/2"

(LOCATION OF INSERT)

6"

5" 5"

6"

13/16" HOLE FOR LIFTING BOLT.

ONE ON EACH SIDE

6"

GROUND

12"

LINE

1/2" X 1/2"

CHAMFER

3. MAINTAIN 10' CLEARANCE FROM FRONT AND REAR DOORS AND 3' FROM SIDES.

7. TO DEFER SWITCH INSTALLATION, USE LID ( CN 327375).

FOR PME 9

OUTLINE OF CABINET

24"

R

0

3

2

1

APPR.REVISED BY CK'D

2. USE FIRE ANT CONTROL UNDER ENTIRE PAD INCLUDING PAD OPENINGS.

1 PADSWGCPME9F

BILL OF MATERIALS

CATALOG

327723 BOX, FOR MOUNTING PME GEAR

DESCRIPTION

1

QTY

1

PER

CU

NUMBER

MACRO UNIT

-

CU

ITEM

NO.

COMPATIBLE

UNIT

QTY

REQ'D

1

Page 10: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

DWG.

24.05-03

10/4/10

DANNA GUINN ELKINS

MOUNTING BOX FOR PME 4 (200 & 600 AMP)

PLAN VIEW

SIDE VIEW

12"

24"

5"

5"

5"

5"

48"

43"

LOCATION OF INSERT

LOCATION OF INSERT

40 1/2"

65"

ONE ON EACH SIDE

13/16" HOLE FOR LIFTING BOLT.

CHAMFER

1/2' X 1/2"

GROUND

LINE

3. MAINTAIN 10' CLEARANCE FROM FRONT AND REAR DOORS AND 3' FROM SIDES.

6. SOD MAY BE REQUIRED AROUND PAD TO PREVENT SOIL EROSION.

4. CUT OFF ALL CONDUITS 6" ABOVE BOTTOM OF BOX AND CAP.

1. THE GROUND SHALL BE LEVELED AND THOROUGHLY COMPACTED BEFORE PAD IS INSTALLED.

5. DO NOT FILL INTERIOR OF BOX WITH SOIL.

NOTES:

6"

R

0

3

2

1

APPR.REVISED BY CK'D

2. USE FIRE ANT CONTROL UNDER ENTIRE PAD INCLUDING PAD OPENINGS.

1 PADSWGCPME4F

BILL OF MATERIALS

CATALOG

327724 BOX, MOUNTING ALL PME-4

DESCRIPTION

1

QTY

1

PER

CU

NUMBER

MACRO UNIT

-

CU

ITEM

NO.

COMPATIBLE

UNIT

QTY

REQ'D

1

5/8" X 2"

THREADED INSERT

Page 11: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

DWG.

24.05-05

10/4/10

DANNA GUINN ELKINS

MOUNTING BOX PMH 9, 10 & 11,

AUTO TRANSFER & TRAYER 9, 10 & 11

5/8" X 2" THREADED INSERT

TRADEMARK

1/2" X 1/2" CHAMFER

69"

1-1/2"

71"

6"

6"

24"

HOLE IF NECESSARY

REINFORCING ROD

13/16" HOLE FOR

TO CLEAR BOLT

(ONE EACH SIDE)

LIFTING BOLT

OFFSET VERTICAL

PLAN VIEW

SIDE VIEW

13/16" HOLE FOR LIFTING

BOLT ONE ON EACH SIDE

6"

7. TO DEFER SWITCH INSTALLATION, USE LID ( CN 327381).

NOTES:

6. SOD MAY BE REQUIRED AROUND PAD TO PREVENT SOIL EROSION.

1. THE GROUND SHALL BE LEVELED AND THOROUGHLY COMPACTED BEFORE PAD IS INSTALLED.

5. DO NOT FILL INTERIOR OF BOX WITH SOIL.

4. CUT OFF ALL CONDUITS 6" ABOVE BOTTOM OF BOX AND CAP.

3. MAINTAIN 10' CLEARANCE FROM FRONT AND REAR DOORS AND 3' FROM SIDES.

8. OLD 70" X 62" PADS MAY BE USED.

9. APPROXIMATE WEIGHT IS 3150 LBS.

8"

R

0

3

2

1

APPR.REVISED BY CK'D

2. USE FIRE ANT CONTROL UNDER ENTIRE PAD INCLUDING PAD OPENINGS.

1 PADSWGCPMHF

BILL OF MATERIALS

CATALOG

152199 BOX, MOUNTING PMH SWITCHGEAR

DESCRIPTION

1

QTY

1

PER

CU

NUMBER

MACRO UNIT

-

CU

ITEM

NO.

COMPATIBLE

UNIT

QTY

REQ'D

1

Page 12: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

DWG.

24.05-07

10/4/10

DANNA GUINN ELKINS

MOUNTING BOX FOR

COOPER 15KV VFI-5

28"

C

L L

C

12"

GROUND LINE

24"

6"

FRONT VIEW

PLAN VIEW

5"W X 6-1/4"D X 3"L

BEAM POCKET

1/2" X 1/2"

CHAMFER (TYP.)

C

L

L

C

5"

75"

14"

5"

37-3/4"

68"

13/16"Ø HOLE

FOR LIFTING

BOLT (TYP.)

W6 X 16 X 37"L

GALV. STEEL BEAM

5/8" X 3" THREADED

INSERT (4 TYP.)

COMPATIBLE UNITITEM NO.

1 PADSWGCVFIF

BILL OF MATERIALS

QUANTITYCATALOG NUMBER

9220109880 1 MOUNTING BOX

DESCRIPTION

NOTES:

1. THE GROUND SHALL BE LEVELED AND COMPACTED TO THAT OF UNDISTURBED EARTH BEFORE MOUNTING

BOX IS INSTALLED. SOIL AROUND THE MOUNTING BOX IS TO BE FREE OF ROOTS AND CONSTRUCTION

DEBRIS TO PREVENT SETTLING.

3. MAINTAIN 8' CLEARANCE FROM THE FRONT AND REAR DOORS AND 3' FROM THE SIDES.

4. CUT OFF ALL CONDUITS 6" ABOVE THE BOTTOM OF BOX AND CAP.

5. DO NOT FILL INTERIOR OF THE BOX WITH SOIL.

6. SOD MAY BE REQUIRED AROUND THE PAD TO PREVENT SOIL EROSION.

7. OTHER UTILITIES ARE NOT TO BE INSTALLED UNDER THE BOX PAD.

8. APPROXIMATE WEIGHT IS 2275 LBS.

9. SEE DWG. 28.06-07A AND 28.06-07B FOR COOPER 15KV VFI-5.

2. USE FIRE ANT CONTROL UNDER ENTIRE PAD INCLUDING PAD OPENINGS.

42"

R

0

3

2

1

APPR.REVISED BY CK'D

Page 13: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

NOTES:

24.05-09

DWG.

MOUNTING BOX FOR 15 KV, 12.5 KA,

VISTA AND NEXT GENERATION VISTA

10/4/10

DANNA GUINN ELKINS

SIDE VIEW

13/16" HOLE FOR LIFTING BOLT

6"

GROUND

12"

LINE

1/2" X 1/2"

CHAMFER

24"

R

74"

58"

37"

47" 63"

8"

BOTTOM EDGE

OF BOX

FOR CABINET

5/8" THREADED INSERT

OUTLINE OF

CABINET

PADSWGCVISTAF

PLAN VIEW

SEE DETAIL 'A'

DETAIL 'A'

8"

8-1/2"

6-1/16"

3-3/4" TYP.

2" TYP.

2" TYP.

1" TYP.

6" TYP.

OUTLINE OF CABINET

FOR CABINET

5/8" THREADED INSERT

5/8" THREADED INSERT

FOR SWITCHGEAR

13/16" HOLE

FOR LIFTING BOLT

CN 9220130615

6"

TERMINATION SIDE

OPERATION SIDE

0

3

2

1

APPR.REVISED BY CK'D

7. WEIGHT IS APPROXIMATELY 3500 LBS.

3. MAINTAIN 10' CLEARANCE FROM FRONT AND REAR DOORS AND 3' FROM SIDES.

6. SOD MAY BE REQUIRED AROUND PAD TO PREVENT SOIL EROSION.

5. DO NOT FILL INTERIOR OF BOX WITH SOIL.

4. CUT OFF ALL CONDUITS 6" ABOVE BOTTOM OF BOX AND CAP.

1. THE GROUND SHALL BE LEVELED AND THOROUGHLY COMPACTED BEFORE BOX IS INSTALLED.

INSTALL TIE DOWN PLATE

TO HOLD BOTH TANK

AND SHELL.

MAY NEED TO DRILL

AND INSTALL RED HEAD

2. USE FIRE ANT CONTROL UNDER ENTIRE PAD INCLUDING PAD OPENINGS.

Page 14: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

DWG.

24.05-11

5/24/12

DANNA BURLISON ELKINS

CABLE AND CONDUIT PLACEMENT

FOR TRAYER ATS VFI

PLAN VIEW

GALVANIZED COIL INSERT

(TYPICAL 2 LOCATIONS)

R

0

3

2

1

APPR.REVISED BY CK'D

SIDE VIEW

OPENING

1"

1"

7"

3-1/2"

87"

82"

6@6-5/8"=39-3/4"

3-1/2"

3@7-1/2"=22-1/2"

5@7=35"

3@7-1/2"=22-1/2"

3-1/2"

60"13-1/2"

32"

4"

2"

4"

13-1/2"

26"

4 - #4 BARS @ 24" LONG

(TYPICAL 4 LOCATIONS)

#4 BAR REINFORCING

TYPICAL

1 - EXTRA #4 BAR BETWEEN

EDGE OF PAD AND WINDOW

OPENING (TYPICAL EACH SIDE)

4"

2" 17" 11" 2"17"11"

4"

1. THE GROUND SHALL BE LEVELED AND THOROUGHLY COMPACTED BEFORE PAD IS INSTALLED.

NOTES:

4. SOD MAY BE REQUIRED AROUND PAD TO PREVENT SOIL EROSION.

3. MAINTAIN 10' CLEARANCE FROM FRONT AND REAR DOORS AND 3' FROM SIDES.

2. USE FIRE ANT CONTROL UNDER ENTIRE PAD INCLUDING PAD OPENINGS.

Page 15: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

3. NO PULLING EYES.

2. USE 1/0 PRIMARY - THREE-PHASE CONDUCTOR MAXIMUM.

NOTES:

4. NO BOTTOM.

5. FOUR (4) HOLES (2 ON EACH SIDE) FOR LIFTING BOX.

6. BELOW GRADE INSTALLATION REQUIRES ELECTRONIC POWER MARKER.

24.07-01

DWG.

HOLES FOR BOLTING

DIAMOND PLATE LIDS

13/16" HOLES

FOR LIFTING BOLTS

2 ON EACH SIDE

TOP VIEW

SIDE VIEW

SMALL PULL & SPLICE BOX

(30" X 48" X 24")

1. LIDS ARE DIAMOND PLATE ( CN 320189) OR CONCRETE (CN 320188).

24"

58"

40" 30"

5"

5"

58"

8. DO NOT FILL INTERIOR OF BOX.

48"

7. SEE DWG. 24.07-03 FOR LIDS.

R

0

3

2

1

APPR.REVISED BY CK'D

8/10/10DANNA GUINN ELKINS

CN 320185

APPROXIMATE WEIGHT - 1,780 LBS.

PBSPSMNOLID

Page 16: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

24.07-03

DWG.

4 HOLES

(2) LID LIFTING INSERTS

CONCRETE LID

(2) 1" LID LIFTING HOLESHOLES FOR BOLTING TO BOX

10/4/10

GUINNDANNA ELKINS

HOLES FOR BOLTING

FOR 3/4"

LIFTING EYE BOLTS

TWO ON EACH SIDE

LIDS FOR SMALL PULL & SPLICE BOX

58"

40"

58"

58"

40"

4"

40"

28"

CN 320188

(INCLUDES TWO PIECES)

R

0

3

2

1

APPR.REVISED BY CK'D

TO BOX

NOTES:

1. LID MUST BE SECURED TO BOX USING 1/2" X 1" STAINLESS STEEL BOLTS.

CU LID30X48CF

CU LID30X48SF

(INCLUDES TWO PIECES)

CN 320189

GALVANIZED LID

Page 17: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

DWG.

24.07-07

10/4/10DANNA GUINN ELKINS

LARGE PULL BOX, BOTTOM HALF

(6.5' X 4' X 2')

NOTES:

1. FOR ASSEMBLY, SEE DWG. 24.07-15.

PLAN VIEW

CN 320181

SIDE VIEW

12" 34" 12"

58"

88"

20-1/2"

20-1/2"

5" 48"

78"

1" THROUGH HOLE

FOR GROUND ROD

5" FROM SIDE WALL

7"

13"

24"

5"

6"

5"

11" DIAMETER ACCESS

FOR PUMP

DETAIL "A"

LIFTING EYE

R

SHIPLAP GROOVE

DETAIL 'B'

SEE DETAIL 'B'

3/4" PULLING EYE

3/4" PULLING EYE

SEE DETAIL "A"

2"

1/2"

2-1/2"

2"

0

3

2

1

APPR.REVISED BY CK'D

CU BOXSP6X4CBTMF

Page 18: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

DWG.

24.07-09

10/4/10

DANNA GUINN ELKINS

LARGE PULL BOX, TOP HALF

(6.5' X 4' X 3')

HOLE TO

3/4" PULLING EYES

1/2" THREADED

5"

36"

ACCOMMODATE

A STAINLESS

STEEL BOLT

NOTES:

1. FOR ASSEMBLY, SEE DWG. 24.07-15.

2"

5"

2-1/4"

2-1/2" X 1/4"

ANGLE

1/2" X 3/4"

FLAT BAR

WELDED TO ANGLE

PLAN VIEW

SIDE VIEW

12"

CN 320182

3/4" PULLING EYES

1/2"

R

7"34"7"

58"

48"

5"

88"

28-1/4"

28-1/4"

C

L

5"

6"

7"

DETAIL 'A'

SEE DETAIL 'A'

SHIPLAP GROOVE

2-1/2"

2"

2"

1/2"

10-3/4" (TYP.)

78"

25"

25"

0

3

2

1

APPR.REVISED BY CK'D

CU BOXSP6X4CTOPF

Page 19: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

DWG.

24.07-11

10/4/10

DANNA GUINN ELKINS

STEEL LIDS FOR LARGE PULL BOX

CN 320186

11"

1"

3" 11" 3"

1"

2 3/4"

52"

2 3/4"

MIDDLE

PLATE

(1 REQ'D)

1" LIFTING

HOLE

1" X 1 1/2"

SLOTTED HOLE

(2 REQ'D)

PLATE

END

3 1/2" 13 1/4" 9 3/4" 1"

3 1/2"

10 1/2" 8 1/2"

27"

13" 13"

1"

1/4"

46 1/2"

1/4"

R

0

3

2

1

APPR.REVISED BY CK'D

FOR BOLTING

LID TO BOX

1" X 1 1/2"

SLOTTED HOLE

FOR BOLTING

LID TO BOX

HOLE FOR

BOLTING

LID TO BOX

HOLE FOR

BOLTING

LID TO BOX

NOTES:

1. LID MUST BE SECURED TO BOX USING 1/2" X 1" STAINLESS STEEL BOLTS.

CU LID6X4SF

Page 20: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

DWG.

24.07-13

CONCRETE LIDS FOR LARGE PULL BOX

3'-8"

4'-10"LIFTING INSERTS

1'-10"

12"

TYPICAL BOTH

HALVES

1"

5"

CONCRETE COVER

(2 REQUIRED)

CN 320187

6"

R

0

3

2

1

APPR.REVISED BY CK'D

CU LID6X4CF

8/10/10

DANNA GUINN ELKINS

Page 21: SINGLE-PHASE TRANSFORMER PAD FOR 25-167 KVA...single-phase transformer pad for 25 - 167 kva plan view side view 3/4" lifting insert 5/8" insert notes: 1. the ground shall be leveled

PULLING EYE

LIFTING EYE

11" DIAMETER ACCESS

FOR PUMP

ENTRANCE FOR 6" PVC

FLARED DUCT

1. BOTTOM OF PULL BOX SHOULD BE LIFTED USING LIFTING EYES THAT ARE LOCATED ON THE FLOOR OF THE

BOTTOM SECTION.

NOTES:

2. WHEN SETTING TOP SECTION, USE PULLING EYES THAT ARE LOCATED ON THE END WALLS.

3. LISTED BELOW ARE OPTIONS REGARDING LID TYPES. THE 6.5 FT. X 4 FT. PULLBOX HAS THREE AVAILABLE LID

24.07-15

DWG.

LARGE PULL BOX ASSEMBLY

10/4/10DANNA GUINN ELKINS

88"

58"

34"

12"

13"

6"

24"

7"

36"

R

0

3

2

1

APPR.REVISED BY CK'D

4. NON-IMPACT TRAFFIC RATED IS FOR APPLICATIONS WHERE BOX AND LID WILL BE IN AREAS OF INCIDENTAL

OPTIONS.

CONCRETE FINISH AND CAN BE USED IN SIDEWALK APPLICATIONS. FOR USE WITH STANDARD TOP SECTION

3 - PIECE STEEL LID USED FOR NON-TRAFFIC RATED APPLICATION ( CN 320186). FOR USE WITH STANDARD

TOP SECTION (CN 320182) AND BOTTOM SECTION ( CN 320181).

3 - PIECE HEAVY DUTY NON-IMPACT TRAFFIC RATED STEEL LID ( CN 300406), WHICH MUST BE USED WITH

TOP SECTION (CN 320180) AND STANDARD BOTTOM SECTION ( CN 320181).

2 - PIECE HEAVY DUTY NON-IMPACT TRAFFIC RATED CONCRETE LID ( CN 320187). THIS LID HAS A BRUSHED

(CN 320182) AND BOTTOM SECTION ( CN 320181).

5. BELOW GRADE INSTALLATION REQUIRES ELECTRONIC POWER MARKER.

TRAFFIC ONLY (I.E. DRIVEWAYS, PARKING LOTS). IT IS NOT RATED FOR INSTALLATION IN ROADWAYS.

6. THE TOP AND BOTTOM SECTIONS SHALL BE INSTALLED FOR ALL INSTALLATIONS. THIS IS TO ENSURE THAT

THE INSTALLATION MEETS ALL TRAFFIC RATINGS, CONDUIT IS AT STANDARD DEPTH AND PULLING EYES ON

BOTTOM SECTION CAN BE USED FOR CABLE PULLING APPLICATIONS.

WHERE PHYSICAL CONSTRAINTS DO NOT ALLOW FOR THE ADDITIONAL SPACE OF THE BOTTOM SECTION.

EXCEPTION: TOP SECTIONS ONLY WITH LIDS CAN BE INSTALLED FOR NON-TRAFFIC RATED INSTALLATIONS

TOP HALF WEIGHT - 4100 LBS.

BOTTOM HALF WEIGHT - 5000 LBS.

SEE DWG. 24.07-09

SEE DWG. 24.07-07

TOP SECTION

BOTTOM SECTION