single packaged gas heating electric cooling … · to indoor coil. 95 d.b. entering air to outdoor...

10
© 2008 American Standard Heating & Air Conditioning NOTICE: The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. SPECIFICATIONS TAG: _________________________________ SINGLE PACKAGED GAS HEATING ELECTRIC COOLING 2YCC3024A1040/64A PRODUCT SPECIFICATIONS YCC3024A-SPEC-1E MODEL RATED Volts/PH/Hz Performance Cooling BTUHj Indoor Airflow (CFM) Power Input (KW) EER/SEER (BTU/Watt-Hr.) Sound Power Rating [dB(A)]7 Performance Heatingk Input BTUH (Natural Gas)l AFUE Temp. Rise — Min/Max (°F) Orifice Qty / Drill Size (Natural Gas) POWER CONN.—V/PH/HZ Min. Brch. Cir. Ampacity Fuse Size — Max. (amps) Fuse Size — Recmd. (amps) COMPRESSOR Volts/Ph/Hz R.L. Amps — L.R. Amps OUTDOOR COIL — TYPE Rows/F.P.I. Face Area (sq.ft.) Tube Size (in.) INDOOR COIL — TYPE Rows/F.P.I. Face Area (sq.ft.) Tube Size (in.) Refrigerant Control Drain Conn. Size (in.) OUTDOOR FAN — TYPE Dia. (in.) Drive/No. Speeds Motor — HP/R.P.M. Volts/Ph/Hz F.L. Amps/L.R. Amps INDOOR FAN — TYPE Dia x Width (in.) Drive/No. Speeds CFM @ 0.0 in. w.g.n Motor — HP/R.P.M. Volts/Ph/Hz F.L. Amps/L.R. Amps COMBUSTION FAN — TYPE Drive/No. Speeds Motor — HP/R.P.M. Volts/Ph/Hz FLA FILTER / FURNISHED Type Recommended Recmd. Face Area (sq. ft.)o REFRIGERANT Charge (lbs.)m GAS PIPE SIZE (in.) DIMENSIONS Crated (in.) WEIGHT Shipping (lbs.) / Net (lbs.) 2YCC3024A1040A 208-230/1/60 23000 725 2.162 11.0 / 13.0 74 40000 80.0 25 / 55 1 / #32 208-230/1/60 13.3 20 20 RECIPROCATING 208-230/1/60 9.0 / 59.5 SPINE-FIN 2 / 24 13.32 3/8 PLATE FIN 3 / 15 3.54 3/8 EXPANSION VALVE 3/4 FEMALE NPT PROPELLER 23 DIRECT / 1 1/12 / 810 208-230/1/60 0.54 / 0.95 CENTRIFUGAL 11 X 10 DIRECT / 2 SEE FAN PERF TABLE 1/4 / 825 200-230/1/60 1.5 / 2.85 CENTRIFUGAL DIRECT / 1 1/35 / 3480 208-230/1/60 0.53 NO THROWAWAY 2.7 R22 4.5 1/2 H X W X L 45.86 / 44.5 / 52.03 470 / 374 2YCC3024A1064A 208-230/1/60 23000 725 2.162 11.0 / 13.0 74 64000 80.0 35 / 65 2 / #37 208-230/1/60 13.3 20 20 RECIPROCATING 208-230/1/60 9.0 / 59.5 SPINE-FIN 2 / 24 13.32 3/8 PLATE FIN 3 / 15 3.54 3/8 EXPANSION VALVE 3/4 FEMALE NPT PROPELLER 23 DIRECT / 1 1/12 / 810 208-230/1/60 0.54 / 0.95 CENTRIFUGAL 11 X 10 DIRECT / 2 SEE FAN PERF TABLE 1/4 / 825 200-230/1/60 1.5 / 2.85 CENTRIFUGAL DIRECT / 1 1/35 / 3480 208-230/1/60 0.53 NO THROWAWAY 2.7 R22 4.5 1/2 H X W X L 45.86 / 44.5 / 52.03 481 / 385 1Rated in accordance with A.R.I. Standard 210/240. A.R.I. standard rating conditions are: 80 D.B. 67 W.B. entering air to indoor coil. 95 D.B. entering air to outdoor coil. 2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation. 3 Convertible to LPG. 4 This value is approximate. For more precise value, see Unit Nameplate. 5 Based on U.S. Government Standard Tests. 6 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recom- mendation with a clean resistance of 0.05" W.C. 0.05" W.C. 7 Sound Power values are not adjusted for ARI270-95 tonal corrections.

Upload: others

Post on 25-Mar-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SINGLE PACKAGED GAS HEATING ELECTRIC COOLING … · to indoor coil. 95 D.B. entering air to outdoor coil. 2All models are U L Listed. Ratings shown are for elevations up to 2000 ft

© 2008 American Standard Heating & Air ConditioningNOTICE: The manufacturer has a policy of continuous product and product data improvement and

reserves the right to change design and specifications without notice.

SPECIFICATIONSTAG: _________________________________

SINGLE PACKAGED GAS HEATINGELECTRIC COOLING 2YCC3024A1040/64A

PRODUCT SPECIFICATIONS

YCC3024A-SPEC-1E

MODELRATED Volts/PH/HzPerformance Cooling BTUH�Indoor Airflow (CFM)Power Input (KW)EER/SEER (BTU/Watt-Hr.)Sound Power Rating [dB(A)]7Performance Heating�Input BTUH (Natural Gas)�AFUETemp. Rise — Min/Max (°F)Orifice Qty / Drill Size (Natural Gas)POWER CONN.—V/PH/HZMin. Brch. Cir. AmpacityFuse Size — Max. (amps)Fuse Size — Recmd. (amps)COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)INDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.�Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsCOMBUSTION FAN — TYPEDrive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzFLAFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)�REFRIGERANTCharge (lbs.)�GAS PIPE SIZE (in.)DIMENSIONSCrated (in.)WEIGHTShipping (lbs.) / Net (lbs.)

2YCC3024A1040A208-230/1/60

23000725

2.16211.0 / 13.0

74

4000080.0

25 / 551 / #32

208-230/1/6013.32020

RECIPROCATING208-230/1/60

9.0 / 59.5SPINE-FIN

2 / 2413.32

3/8PLATE FIN

3 / 153.543/8

EXPANSION VALVE3/4 FEMALE NPT

PROPELLER23

DIRECT / 11/12 / 810

208-230/1/600.54 / 0.95

CENTRIFUGAL11 X 10

DIRECT / 2SEE FAN PERF TABLE

1/4 / 825200-230/1/60

1.5 / 2.85CENTRIFUGAL

DIRECT / 11/35 / 3480

208-230/1/600.53NO

THROWAWAY2.7R224.51/2

H X W X L45.86 / 44.5 / 52.03

470 / 374

2YCC3024A1064A208-230/1/60

23000725

2.16211.0 / 13.0

74

6400080.0

35 / 652 / #37

208-230/1/6013.32020

RECIPROCATING208-230/1/60

9.0 / 59.5SPINE-FIN

2 / 2413.32

3/8PLATE FIN

3 / 153.543/8

EXPANSION VALVE3/4 FEMALE NPT

PROPELLER23

DIRECT / 11/12 / 810

208-230/1/600.54 / 0.95

CENTRIFUGAL11 X 10

DIRECT / 2SEE FAN PERF TABLE

1/4 / 825200-230/1/60

1.5 / 2.85CENTRIFUGAL

DIRECT / 11/35 / 3480

208-230/1/600.53NO

THROWAWAY2.7R224.51/2

H X W X L45.86 / 44.5 / 52.03

481 / 385

11111Rated in accordance with A.R.I. Standard 210/240. A.R.I.standard rating conditions are: 80 D.B. 67 W.B. entering airto indoor coil. 95 D.B. entering air to outdoor coil.

22222 All models are U L Listed. Ratings shown are for elevationsup to 2000 ft. For higher elevations reduce ratings at a rateof 4% per 1000 ft. elevation.

33333 Convertible to LPG.44444 This value is approximate. For more precise value, see

Unit Nameplate.55555 Based on U.S. Government Standard Tests.66666 Filters must be installed in return air stream. Square

footages listed are based on 300 f.p.m. face velocity. Ifpermanent filters are used size per manufacturer's recom-mendation with a clean resistance of 0.05" W.C. 0.05" W.C.

77777 Sound Power values are not adjusted for ARI270-95 tonalcorrections.

Page 2: SINGLE PACKAGED GAS HEATING ELECTRIC COOLING … · to indoor coil. 95 D.B. entering air to outdoor coil. 2All models are U L Listed. Ratings shown are for elevations up to 2000 ft

2

Unit Clearance and Weight Information

Page 3: SINGLE PACKAGED GAS HEATING ELECTRIC COOLING … · to indoor coil. 95 D.B. entering air to outdoor coil. 2All models are U L Listed. Ratings shown are for elevations up to 2000 ft

3

Page 4: SINGLE PACKAGED GAS HEATING ELECTRIC COOLING … · to indoor coil. 95 D.B. entering air to outdoor coil. 2All models are U L Listed. Ratings shown are for elevations up to 2000 ft

4

Page 5: SINGLE PACKAGED GAS HEATING ELECTRIC COOLING … · to indoor coil. 95 D.B. entering air to outdoor coil. 2All models are U L Listed. Ratings shown are for elevations up to 2000 ft

5

Indoor Fan Performance 2YCC3024A1

Down Airflow

Horizontal Airflow

Unit Performance Data

Performance Data Cooling

2YCC3024A AT 800 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 75 78 80 KW

59 22.2 14.3 17.2 20 21.9 1.9185 63 23.2 13.1 15.8 18.4 20.1 1.92

67 25.0 11.3 13.6 15.9 17.3 1.9571 27.0 9.4 11.3 13.2 14.4 1.97

59 20.6 13.6 16.3 19.0 20.6 2.0795 63 21.5 12.5 15.0 17.5 19.1 2.09

67 23.2 10.8 12.9 15.1 16.5 2.1271 25.0 8.9 10.7 12.5 13.7 2.14

59 19.1 12.8 15.4 18 19.1 2.24105 63 19.9 11.8 14.1 16.5 18.0 2.25

67 21.4 10.1 12.2 14.2 15.5 2.2971 23.1 8.4 10.1 11.8 12.9 2.31

59 17.5 12.0 14.4 16.8 17.5 2.40115 63 18.2 11.0 13.2 15.4 16.9 2.41

67 19.6 9.5 11.4 13.3 14.6 2.4571 21.2 7.9 9.5 11.0 12.1 2.48

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)

AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITYLOW 700 0.98 0.97HIGH 900 1.02 1.03

VALUES AT ARI RATING CONDITIONS

TOTAL NET CAPACITY = 23000 BTUHAIRFLOW = 725 CFMCOMPRESSOR POWER = 1790 WATTSI.D. FAN POWER = 201 WATTSO.D. FAN POWER = 100 WATTSS.E.E.R. = 13.00 BTUH/WATTE.E.R = 11.00 BTUH/WATT

ALL TEMPERATURES IN DEGREES F.

2/4YC*3024A1HOR EXTERNAL STATIC PRESSURE (IN. WG)

MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

LOWWATTS 215 212 205 195 186 - - - - - -

CFM 831 796 743 677 602 - - - - - -

HIGHWATTS - - 358 345 327 302 277 266 - - -

CFM - - 1239 1165 1056 898 720 593 - - -

2/4YC*3024A1-DOWN EXTERNAL STATIC PRESSURE (IN. WG)

MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

LOWWATTS 215 208 201 193 183 - - - - - -

CFM 812 766 721 662 583 - - - - - -

HIGHWATTS 377 367 351 331 310 291 274 262 - - -

CFM 1331 1274 1193 1090 966 829 686 547 - - -

Page 6: SINGLE PACKAGED GAS HEATING ELECTRIC COOLING … · to indoor coil. 95 D.B. entering air to outdoor coil. 2All models are U L Listed. Ratings shown are for elevations up to 2000 ft

6

The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These draw-ings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer isnot responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting fromsuch unauthorized use.

BAYFLTR101, 201A, 1" - 2" Filter Rack(Mounts in Filter/Coil Section)

BAYACCDOR1A & BAYACCDOR2A Hinged Filter Access DoorReplaces Filter/Coil Access Panel

Filter

Page 7: SINGLE PACKAGED GAS HEATING ELECTRIC COOLING … · to indoor coil. 95 D.B. entering air to outdoor coil. 2All models are U L Listed. Ratings shown are for elevations up to 2000 ft

7

46 3/8

17 7/8

3

3 5/8

19 1/2

2 3/16

19 1/2

14

1 1/2

38 7/8

15

35 7/843 3/8

BAYCURB050A Full Perimeter Roof Mounting Curb for *****018-036A

The drawings on this page areprepared by the manufacturer in orderto provide detail regarding job layoutonly. These drawings are not intendedto be used as a basis to construct,build or modify the items depicted inthe drawings. The manufacturer is notresponsible for the unauthorized useof these drawings and expresslydisclaims any liability for damagesresulting from such unauthorized use.

Page 8: SINGLE PACKAGED GAS HEATING ELECTRIC COOLING … · to indoor coil. 95 D.B. entering air to outdoor coil. 2All models are U L Listed. Ratings shown are for elevations up to 2000 ft

8

BAYECON101,102A Down Discharge Economizer and Rain Hood(Mounts Over Horizontal Return Air Opening)

A

B

C D

E

BAYECON200,201A Horizontal Economizer and Rain Hood

ReturnDuctRoofcurb

Reliefdamper

Misteliminator

Economizerrain hood

HVAC Unit

Outside airdampers

Returnairdampers

Required filterkit, orderseparately

A

Economizer Unit ApplicationM odels A

BAYECON101A2/4YC,WC3018-036A

4TC*3018-036A4W/T/Y/DCY4024-060

20.125"

BAYECON102A2/4YC,WC3042-060A

4TC*3042-060A4W/T/Y/DCY4024-060

24.375"

Economizer A B C D E

BAYECON200AA 22" 20" 16 7/8" 15 11/16 11 11/16

BAYECON201AA 24" 22 21/32" 19" 17 11/16 14 11/16

Economizer

Gaskets (2)

Rain HoodDuct

The drawings on this pageare prepared by themanufacturer in order toprovide detail regardingjob layout only. Thesedrawings are not intendedto be used as a basis toconstruct, build or modifythe items depicted in thedrawings. The manufactureris not responsible for theunauthorized use of thesedrawings and expresslydisclaims any liability fordamages resulting fromsuch unauthorized use.

Mixed Air Sensor

Page 9: SINGLE PACKAGED GAS HEATING ELECTRIC COOLING … · to indoor coil. 95 D.B. entering air to outdoor coil. 2All models are U L Listed. Ratings shown are for elevations up to 2000 ft

9

A

B

CD

FULLYOPEN

2/31/3

FULLYCLOSED

BAYDMPR101,102A, 25% Motorized Outside Air Damper(Mounts Over Horizontal Return AIr Opening)

BAYOSAH001,002A, 25% Outside Air Damper(Replaces Filter/Coil Access Panel)

The drawings on this page are pre-pared by the manufacturer in order toprovide detail regarding job layout only.These drawings are not intended to beused as a basis to construct, build ormodify the items depicted in thedrawings. The manufacturer is notresponsible for the unauthorized use ofthese drawings and expressly dis-claims any liability for damagesresulting from such unauthorized use.

Manual FreshAir Model

Unit ApplicationModels

A B C D

BAYOSAH0012/4YC,WC3018-036A

4TC*3018-036A4W/T/Y/DCY4024-060A

22 7/16" 20 11/16" 12 3/8" 9 3/16"

BAYOSAH0022/4YC,WC3042-060A

4TC*3042-060A4W/T/Y/DCY4024-060

25 3/16" 20 11/16" 12 3/8" 9 3/16"

D

CB

A

E

Unit ApplicationModels

A B C D E

BAYDMPR101A2/4YC,WC3018-036A

4TC3018-036A4W/T/Y/DCY4024-0600

15 13/16" 11 13/16" 10 1/4" 11 1/2" 12 1/4"

BAYDMPR102A2/4YC,WC3042-060A

4TC3042-060A4W/T/Y/DCY4024-060

18 3/16" 15 1/8" 10 1/4" 11 1/2" 12 1/4"

Page 10: SINGLE PACKAGED GAS HEATING ELECTRIC COOLING … · to indoor coil. 95 D.B. entering air to outdoor coil. 2All models are U L Listed. Ratings shown are for elevations up to 2000 ft

American StandardHeating & Air Conditioning6200 Troup HighwayTyler, TX 75707

MechanicalSpecification Options

GeneralAll units shall be factory assembled, piped,internally wired and fully charged withrefrigerant. All units shall be designed tooperate at outdoor ambient temperaturesas high as 115°F. Cooling capacities shallbe rated in accordance with A.R.I.standards. The YC heating/cooling unitdesign is UL listed, specifically for outdoorapplications using natural gas or propane.All units shall be designed for outdoorrooftop or ground level installation. Unitcasing is constructed of heavy gauge,galvanized steel and painted with aweather-resistant powder paint.

Shipped for horizontal application,convertible to downflow.

CasingsAll panels shall be heavy gauge steel,gasketed and insulated. Foil-faced fiberinsulation shall be in the heat exchangersection. Foil-faced insulation shall be inthe evaporator section. Base pan shall beheavy gauge steel. WEATHERGUARD™exterior corrosion resistant screws shall beused for added resistance to rust andcorrosion.

ControlsRefrigeration cycle controls shall includecondenser fan, evaporator fan andcompressor contactors. Compressors shallbe equipped with a combination internalwinding thermostat/current overload.Internal high pressure relief shall also beprovided.

Refrigeration SystemCompressors —The Duration™ compressor featuresinternal over temperature and pressureprotector, total dipped hermetic motor.Other features include: roto lock suctionand discharge refrigeration connections,centrifugal oil pump, low vibration andnoise.

Evaporator Coil — Internally enhanced3/8-inch OD seamless copper tubingmechanically bonded to aluminum fins,factory pressure and leak tested at 250 to300 psig. All units have TXV to controlrefrigeration flow.

Condenser Coil —The Spine Fin™condenser coil shall becontinuously wrapped, corrosion resistantall aluminum with minimum brazed joints.This coil is 3/8 inch O.D. seamlessaluminum tubing glued to a continuousaluminum fin. Coils are lab tested towithstand 2,000 pounds of pressure persquare inch. The outdoor coil provideslow airflow resistance and efficient heattransfer. The coil is protected on all foursides by louvered panels.

Indoor Air Fan — Direct-drive, forward-curved, centrifugal wheel in a CompositeVortica® Blower housing. Motor shallhave thermal overload protection.Permanently lubricated motor bearings.Motor/blower assembly isolated from unitwith rubber mounts.

Condenser Fan — Direct-drive, drawthru propeller type. Weather-proofedpermanent split capacitor fan motor shallhave built-in thermal overload andpermanently lubricated motor bearings.

Low Ambient — Standard refrigerantsystem operation down to 55°F. Lowambient accessory required for operationto 0°F ambient condition.

Heating SystemGas-Fired Heating Section — Modelsshall provide completely assembled,wired and piped gas fired heatingsystems within unit. Design certified byUL, specifically for outdoor application.Threaded gas connection on the unit.

Electronic Ignition System — Mainburner is lit each time thermostat calls forheat. Flame sensor proves flame andkeeps the main burners on. Should a lossof flame occur, the main valve closes andthe spark recurs within 0.8 second. Whenthermostat is satisfied, main burner isextinguished.

Forced Combustion Blower — Insuresflame stability under varying windconditions. Gives higher combustionefficiency and location flexibility.

Heat Exchanger — stainless steel tubes.Free floating design.

Burners — stainless steel. Multi-portinshot.

Downflow Accessories(U.S. Domestic Models)Roof Curb — The roof curb shall bedesigned to mate with the unit andprovide support and complete weather-tight installation when properly installed.Curb shall ship knocked down for fieldassembly, and include wood nailer strips.

EconomizerModulating Economizer — Thisaccessory shall be field installed and becomposed of the following items: 0-100%fresh air damper, damper drive motorfixed dry bulb enthalpy control, and lowvoltage polarized plug for electricalconnections. Solid state enthalpy ordifferential enthalpy control is optional.Economizer operations shall becontrolled by the preset position of theenthalpy control. A barometic reliefdamper shall be standard with theeconomizer and provide a pressureoperated damper that shall be gravityclosing and prohibit entrance of outsideair on equipment “off” cycle.

Manual Fresh Air HoodManual outside air provides a fixedoutside air quantity from 0 to 25 percent.Includes hood and birdscreen.

Low Ambient ControlControl allows cycling of compressorunder low ambient cooling conditions.Required for cooling operation to 0°F.

Propane GasConversion Kit — For conversion fromnatural gas to LP gas.