SinamicS G120Multimedia Training Package

I_DT_G120_Booklet_RZ.indd 1 04.04.2012 13:11:25

Page 2: Sinamics g120 treinamento (en)

2

Required System Configuration CD-ROM

• Processorwithmin.2GHz(dualcorerecommended) • 1024MBRAM • Graphicscard(min.256MBmemoryrecommended) • Screenresolution:1280x1024px • OperatingSystems: Microsoft®Windows™XP(ServicePack2orlater) Microsoft®Windows™Vista Microsoft®Windows™7

I_DT_G120_Booklet_RZ.indd 2 04.04.2012 13:11:27

Page 3: Sinamics g120 treinamento (en)

3

ThisbookletcontainsthesameinformationastheattachedCD.Still,wehighlyrecommendtoworkthroughthelearn-ingprogrambeforeconsultingthebooklet.Themultimediatutorialisacomfortableandeasytounderstandintroduc-tion to the converter family SINAMICS G120.

04/2012 6FC5095-0AA85-0BA0

SinamicS G120Training Booklet

I_DT_G120_Booklet_RZ.indd 3 04.04.2012 13:11:28

Page 4: Sinamics g120 treinamento (en)

Materials and tools

Thecomponentslistedbelowarepresentedinthisbooklet.Totestyourknowledgeontheactualproduct,youhavethechoicebetweenthefollowingorderalternatives:

Training case

Product

• SINAMICSG120trainingcase*

Order no.

6ZB2480-0CJ00

Single components

Product

• SINAMICSG120PM240-2FSA0.55kW

• SINAMICSG120CU240E-2

• Motor(0.55kW)

• SINAMICSPCConnectionKit-2

• SINAMICSBOP-2

• IntelligentOperatorPanelIOP

• Screeningkit2

Order no.

6SL3210-1PE11-8AL0

6SL3244-0BB12-1BA1

1LA7096-4AA10

6SL3255-0AA00-2CA0

6SL3255-0AA00-4CA1

6SL3255-0AA00-4JA0

6SL3264-1EA00-0HA0

Optional components

Product

• IOP/BOP-2doormountingkit

Order no.

6SL3256-0AP00-0JA0

In addition, you will need the following equipment:

• PCwithUSBinterface • Switches–commerciallyavailable* • Potentiometer–commerciallyavailable* • VariousM4screwsandnuts(lengthdependsoninstallationlocation)withsuitablescrewdriver/

wrench–commerciallyavailable*

* The training case is a complete demo station including a motor, the power module of the converter, switches, lights and a 230 V power supply connection.

I_DT_G120_Booklet_RZ.indd 4 04.04.2012 13:11:28

Page 5: Sinamics g120 treinamento (en)

Safety instructions

Validity

Theseinstructionsapplytothefollowingconverter:

Product

SINAMICS G120

Prerequisites

YouareproficientinworkingwiththeMicrosoft®Windows™operatingsystem. Youareconversantwiththeprinciplesofelectronicsandelectricalengineering.

Warning

Dangerous currents and voltages! The equipment contains dangerous voltages and controls potentially dangerous rotating mechanical parts.Non-compliancewiththewarningsorfailuretofollowtheinstructionscontainedinthedocu-mentationcanresultinlossoflife,severepersonalinjuryorseriousdamagetoproperty.

Takeparticularnoticeofthegeneralandregionalinstallationandsafetyregulationsregardingworkondangerousvoltageinstallations(e.g.EN50178)aswellastherelevantregulationsregardingthecorrectuseoftoolsandpersonalprotectiveequipment(PPE).

Qualified Personnel

Thedevice/systemmayonlybesetupandusedinconjunctionwiththisdocumentation.Commission-ing and operation of a device/system may only be performed by qualified personnel. Within the con-textofthesafetynotesinthisdocumentation,qualifiedpersonsaredefinedaspersonswhoareauthorizedtocommission,groundandlabeldevices,systemsandcircuitsinaccordancewithestab-lished safety practices and standards.

Disclaimer of Liability

DependinguponthefirmwareandsoftwareversionoftheControlUnit,oftheOperatorPanelandoftheSTARTER,themasks,symbolsandmenusmaydiffer.Wehavereviewedthecontentsofthispubli-cationtoensureconsistencywiththehardwareandsoftwaredescribed.Sincevariancecannotbeprecludedentirely,wecannotguaranteefullconsistency.However,theinformationinthispublica-tionisreviewedregularlyandanynecessarycorrectionsareincludedinsubsequenteditions.

I_DT_G120_Booklet_RZ.indd 5 04.04.2012 13:11:28

Page 6: Sinamics g120 treinamento (en)

6

Welcome to the SinamicS G120 Tutorial for First Time Users. This tutorial will help acquaint you simply, quick-ly and comfortably with the frequency converter. We’ll take you step by step through installation, setting parameters and initial start-up. We recommend that you don’t skip any chapters.

1I_DT_G120_Booklet_RZ.indd 6 04.04.2012 13:11:28

Page 7: Sinamics g120 treinamento (en)

7

Converter family SINAMICS G120 08–21

1.1 Components PowerModule 12

ControlUnit 13

OperatorPanel2(BOP-2/IOP) 14

1.2Mountingandwiring PowerModule 15

ControlUnit 18

OperatorPanels(BOP-2/IOP) 20

Operator Panels BOP-2 and IOP 22‒41

2.1 Basic functions The BOP-2 display 24

Menu structure 25

2.2WorkingwithBOP-2 Parameter list 27

Operating pattern 27

Function buttons 29

2.3Quickcommissioning Resettingtheconverter 30

Setting the control mode 31

Selecting line frequency 31

Entering motor data 32

Specifying application parameters 33

Saving and restoring data 35

2.4 Intelligent Operator Panel The device 37

WorkingwithIOP 38

STARTER software and PC 42‒73

3.1 Mounting and preparation CreatingaSTARTERproject 46

STARTERuserinterface 49

Loading converter data 50

3.2Parameterization Configurationwizard 54

Safety Integrated 58

Start motor data identification 62

3.3 Application cases Setting setpoint specifications 65

Saving data 67

Restoringfactorysettings 70

Appendix Download overview 75

I_DT_G120_Booklet_RZ.indd 7 04.04.2012 13:11:28

Page 8: Sinamics g120 treinamento (en)

8

This chapter will introduce the low-voltage SinamicS G120 converter. You’ll learn about the main compo-nents, hear about its structure and get some practice-oriented insight about the assembly and wiring of the frequency converter.

1I_DT_G120_Booklet_RZ.indd 8 04.04.2012 13:11:28

Page 9: Sinamics g120 treinamento (en)

9

Converter family

SinamicS G120

I_DT_G120_Booklet_RZ.indd 9 04.04.2012 13:11:34

Page 10: Sinamics g120 treinamento (en)

10

1.1 components The SINAMICS G120 frequency converter is modular. It comprises of three basic components:

1 2ThePowerModulesupplies voltage to the motor

TheControlUnitcontrolsand monitorsthePowerModule

Converter family SINAMICS G120: Components

I_DT_G120_Booklet_RZ.indd 10 04.04.2012 13:11:35

Page 11: Sinamics g120 treinamento (en)

11

3 +TheBasicOperatorPanel(BOP-2)andtheIntelligentOperatorPanel(IOP)are used to operate and monitor the converter

TheoptionalPCConnectionKit-2canalsobeusedtosetparameters,operate and monitor the converter; thekitisrequiredinordertoestablishcommunicationbetweenaPCandtheControlUnit

EachControlUnitcanbefreelycombinedwitheachPowerModule.

NOTE

I_DT_G120_Booklet_RZ.indd 11 04.04.2012 13:11:37

Page 12: Sinamics g120 treinamento (en)

12

1

2

3

4

5

Power ModuleThedeviceisavailableinseveralsizes.Itspowerrangeisbetween0.37kWand250kW. ThepictureshowsthePM240-2framesizeA.

Pleasechecktheratingplate tomakesurethatthemodule also meets your requirement specifications.

NOTE

Ratingplate

Powerconnectors

Connectors/Brakingresistor

Motor connectors

PE terminals

1

2

2 5

5 4

4

3

3

Converter family SINAMICS G120: Components

I_DT_G120_Booklet_RZ.indd 12 04.04.2012 13:11:42

Page 13: Sinamics g120 treinamento (en)

13

1

2

33

1

6

42

5

8

8

8

7

4

5

6

7

8

Control UnitTherearevariousdesignsfortheControlUnits.Theydifferprimarilyintermsofthecontrolterminalassignmentsaswellasintermsofdifferentfieldbusinterfaces.ThistutorialwillusetheexampleoftheCU240E-2ControlUnit.Itwasdevelopedforstand-aloneoperation.

Anoverviewofthevariouscontrolunit versions and their differentia-tion can be found in the official SINAMICS G120 brochure at: http://www.siemens.com/ sinamics-g120/printmaterial

NOTE

Ratingplate

DIPswitchforanaloginputsand fieldbus address

Interface for the Operator Panel(BOP-2orIOP)

Status LEDs

Terminals for digital and analog inputs and outputs

USBinterfaceforSTARTER

InterfacetothePowerModule

Fastening clips

I_DT_G120_Booklet_RZ.indd 13 04.04.2012 13:11:43

Page 14: Sinamics g120 treinamento (en)

14

Basic Operator Panel 2 (BOP-2)The basic input and display device is used to operate and set parameters for the converter after being connectedtotheControlUnit.Itisoperatedbypressingthebuttonsandfeaturesasimplecommission-ingthankstothemenupromptingandthe2-linedisplay.

Intelligent Operator PanelThe Intelligent Operator Panel manages the same functions as the BOP-2 but adds several more options. Theintegratedapplicationwizard,fullgraphicaldiagnosticoverviewsandplaintextincreaseusabilitysubstantially.Itisavailableinvariousversionsandcanbeuseddrive-externallyforseriescommissioningand on-site diagnosis.

1

3

4

1

2

3

26

6

5 5

4

1

1

6 6

5 5

4 4

3 3

2 2

BOP-2 IOPSeven operating buttons

Display

Releasecatch

Doormountingscrewrecess

RS232connector

Product rating label

Graphical display

Navigationwheel

Five operating buttons

USBconnection

RS232connector

Product rating label

Converter family SINAMICS G120: Components

I_DT_G120_Booklet_RZ.indd 14 04.04.2012 13:11:49

Page 15: Sinamics g120 treinamento (en)

15

Mounting of the Power Module into the switch cabinetPleaserefertothedrillingpatternaccompanyingthePowerModuleforthecorrectdrillingcentersandclearancedistancesaboveandbelowthePowerModule.

1.2 mounting and wiringBeforestartingassembly,checktoensurethefollowingconditionshavebeenmet: • Allrequiredcomponents,toolsandsmallpartshavebeenprepared • Allrequiredcablesandlineshavebeenlaidinaccordancewithspecifications • Allminimumclearancesarebeingobserved

Normally the motor and converter areselectedinsuchawaythatthey match each other. This is also thecaseinourexample.However,the data from the rating plate of the motor are important for the initial start-up of the converter.

NOTE

The 5 Safety Regulations must be strictly observed

• Disconnect • Secureagainstunintentionalrestart • Verifythatitisfreeofvoltage • Groundandbypass • Coverandshieldanyadjacentliveparts

Exampleof drilling pattern

36.5 mm (1.44")

62.3mm (2.45")

5.3

5 m

m (0.2

1")

18

6 m

m (7.3

2")

I_DT_G120_Booklet_RZ.indd 15 04.04.2012 13:11:49

Page 16: Sinamics g120 treinamento (en)

16

Connecting the Power Module to the motorDependingontheoperatingenvironment,differentcablelengthlimitsarerequiredfortheconnectionbetweenthePowerModuleandmotor.Unshieldedcablesupto100minlengtharepossibleinindus-trialelectricalnetworks.

ThemotorandPowerModulearenowconnected.

Theelectricalwiringisnowcomplete.

Wiring the Power Module

• ConnectthephasesandtheearthconductortotheterminalsU2,V2,W2andPE

Wiring the motor

• Unscrewthecovertotheterminalboxonthemotor(theinsidecoverofSiemens’motors illustratesthepossiblewiringfortheStarconnectionandtheDeltaconnection) • Removethebridgerailsfromtheconnectingblockandloosenthescrews • Placethebridgerailsontheterminalblockandscrewthemintoplace(dependingonthe typeofconnectionsrequired–StarorDelta,inthisexampleaStarconnectionisshown) • InsertthecablesfromthePowerModulethroughtheopeningoftheterminalboxtothemotor • ConnectthePEconnectionfirst • Slidethephasesinaccordancetothephaseassignmentintheconnections • Replacetheterminalcoverandensureitissecuredwiththefourscrewstotherequiredtorque

Wiring the power supply

• ConnectthephasesandtheearthconductortothepluggableterminalclampsL1,L2,L3andPE

1

2

3

Converter family SINAMICS G120: Mounting and wiring

I_DT_G120_Booklet_RZ.indd 16 04.04.2012 13:11:49

Page 17: Sinamics g120 treinamento (en)

17

Motor lines represent interfering transmitters.Asaresult,youshould use shielded cable in order to meet the corresponding elec-tromagnetic compatibility condi-tions. The cable lengths that are actually possible depend upon the following: ‒ Operating environment ‒ Converter being used ‒Reactorsandfiltersused ‒ Shielded or unshielded cable

In order to meet Class A electro-magnetic compatibility require-ments,youneedafilterandashieldedcable(max.length:25meters). ThedepictedexampleshowsaStar connection. The rating plate provides information about the correctcircuitdata:e.g.230/400V∆/Y means that you are connec-tingthemotorinYwitha400Vnetwork.

NOTE

3

1

2

2

I_DT_G120_Booklet_RZ.indd 17 04.04.2012 13:11:54

Page 18: Sinamics g120 treinamento (en)

18

Attaching the Control UnitConnecttheControlUnitwiththefasteningclipsonthebottomofthePowerModuleandthenpress theupperedgeoftheControlUnitagainstthePowerModuleuntilthelockingdevicesnapsintoplace.Beforewiringthecontrolterminals,theterminalcoverhastobeopened.

Thewiringisnowcomplete.

Wiring the control terminals in the CU240E-2

The potentiometer: • Attachthepositivepoleofthesupplyvoltageto1 • Attachthenegativepoleto2 • Wiretheoutputofthepotentiometerarmto3 • Closethecircuitbyconnecting4withnegativepole2

On/Off,Reverse,andResetbuttons: • Wirethebutton’spowersupplyto9 • Attachtheassociateddigitalinputstoterminals5,6and7 • Toclosethecircuit,connect28and69to34

Indicator lamps: • Connect9with20and21toattachthepowersupplyfortheLEDs • WiretheFaultsLEDtodigitaloutput19andtheWarningLEDtodigitaloutput22 • Connectthenegativepoletoterminal28

Display for frequency output: • Connectthepositivepoleto12 • Connectthenegativepoleto13

1

2

3

4

General procedure for wiring with the cage clamp mechanism

• Slidethewireintotheterminalopening • Theinnerclampopensslightlyandsnapsthewiretightlyintoplace

Thewireisnowfirmlyattached.

• Toreleasethewirepressascrewdriverontothelever • Removethewire • Withdrawthescrewdriverfromtheterminal

Converter family SINAMICS G120: Mounting and wiring

I_DT_G120_Booklet_RZ.indd 18 04.04.2012 13:11:55

Page 19: Sinamics g120 treinamento (en)

19

4

1

3

2

I_DT_G120_Booklet_RZ.indd 19 04.04.2012 13:11:58

Page 20: Sinamics g120 treinamento (en)

20

Mounting the Operator Panels (BOP-2 or IOP)

• RemovethecoveroftheRS232connectionbyliftingitupandslidingittotheside • PlacethebottomedgeoftheIOP/BOP-2intothelowerrecessoftheControlUnithousing • PushtheIOP/BOP-2towardtheControlUnituntiltherelease-catchclicksintoplace

1

2

2

1

Converter family SINAMICS G120: Mounting and wiring

I_DT_G120_Booklet_RZ.indd 20 04.04.2012 13:12:02

Page 21: Sinamics g120 treinamento (en)

21

Mounting the IOP or BOP-2 in a cabinet doorTheoperatorpanelscansimplybemountedinacontrolcabinetdoorwithjustafewmanualoperationsusingtheoptionallyavailabledoormountingkit.DegreeofprotectionIP55/ULtype12isachievedwhenmountingtheminthecontrolcabinetdoor.

Door panel

Seal

Doormountingbracket

Screws

D-typeretainingscrews

Mounting the IOP IdenticalmountingwithBOP-2

43

1

2

5

1

2

3

4

5

Congratulations!Yourconverterisnowreadyforoperation. Afterassemblyiscompleted,theconverter’sparametersmustbesetup,i.e.,youmustgivethe converter the specific characteristics of the attached motor.

I_DT_G120_Booklet_RZ.indd 21 04.04.2012 13:12:03

Page 22: Sinamics g120 treinamento (en)

22

in this section, you will learn more about the usage of Operator Panels to control the converter locally on-site. You’ll learn how to use the Basic Operator Panel 2 (BOP-2) to set up parameters for the converter and the attached motor and how to operate the converter with the BOP-2. Then, you will learn how to use the intelligent Operator Panel (iOP) to your advantage.

2I_DT_G120_Booklet_RZ.indd 22 04.04.2012 13:12:03

Page 23: Sinamics g120 treinamento (en)

23

Basic Operator Panel (BOP-2) intelligent Operator Panel (iOP)

I_DT_G120_Booklet_RZ.indd 23 04.04.2012 13:12:11

Page 24: Sinamics g120 treinamento (en)

24

Menu bar indicates the selected menu function (seepage25)

Provides information about the selected functionality or displays the actual value

Displays the values

Operator Panels BOP-2 and IOP: Basic functions

Inthistutorial,weintroduceanapplicationthatisbasedon“V/fcontrolwithlinearcharacteristiccurve”. This control method is typically applied for conveyor belt applications. We recom-mendthatyouworkthroughtheexamplewehavepresentedhereinordertofamiliarizeyourselfwithsettingupparametersforaconverter.

NOTE

2.1 Basic functionsThe Operator Panel is the input and display instrument for controlling the converter. It is used in stand-aloneoperation,i.e.,locally,onthedevice,integratedinthecabinetdoororashandheldversionforseriessetup(IOP).

The BOP-2 display

TheBOP-2isusedtocommission,diagnose(troubleshoot)anddisplaythestatusoftheconverter.Upto2 status values can be simultaneously and continuously monitored. It features a simple navigation using atransparentandwell-structuredmenuandclearlyassignedoperatorkeys.

1 2

1

2

3

3

I_DT_G120_Booklet_RZ.indd 24 04.04.2012 13:12:12

Page 25: Sinamics g120 treinamento (en)

25

MONITORING

The actual status of the converter/motor system is dis-played

CONTROL

Setpoint,JogandReversemodecanbeactivated

DIAGNOSTICS

Faultsandalarmscanbeacknowledged,historyandstatus is displayed

PARAMETER

Parametervaluescanbeviewedandchanged

SETUP

Basic commissioning of the converter can be per-formed

EXTRAS

Additional functions such as saving and copying data sets into and from the BOP-2 can be performed

1

1

4

2

5

3

62

3

4

5

6

Menu structure

Whenmovingthemenubartothefollowingmenufunction,thefollowingapplies:

I_DT_G120_Booklet_RZ.indd 25 04.04.2012 13:12:12

Page 26: Sinamics g120 treinamento (en)

26 Operator Panels BOP-2 and IOP: Working with BOP-2

ESCkey–Takesyoubacktothe previous screen

Upkey–Changeselection

Downkey–Changeselection

OKkey–Confirmtheselection

OFFkey–Stopsthemotorinmanualmode

HAND/AUTOkey–SwitchesthecommandsourcebetweenHANDandAUTOmode

ON/RUNkey–StartstheMotorinmanual mode

2.2 Working with BOP-2TheBOP-2hasgotsevenbuttons.ForsetupandparameterizationonlytheUPandDOWN,OKandESCbuttonsarerelevant.TheON,OFFandHAND/AUTOkeysareneededforlocaloperation.

1

4 7

6

5

4

3

1

2

2

3

5 6 7

I_DT_G120_Booklet_RZ.indd 26 04.04.2012 13:12:12

Page 27: Sinamics g120 treinamento (en)

27

• PressUPtoaccessthenextparameter • Inthiscase,P3appears(Pmeansthatyoucanchangethevalueofthisparameter) • PressOKtoedittheparameter • UsetheUPandDOWNbuttonstoadjustthevalue • ConfirmthevaluebypressingOK

Operating pattern

• PressESCtoenterthemenuselection • UsetheUPandDOWNbuttonstomovethemenubartoPARAMSandpressOK • PressOKtoselecttheStandardLevel

Parameter listTobetterunderstandthefunctionalityofthebuttons,youshouldbeacquaintedwiththeoperating pattern: The Basic Operator Panel gives you access to a parameter list. Stored behind the parameters are parametervaluesthatcontroltheoperationofthemotor.However,notallthenumbersareassigned.

Thefirstparameternumberthatappearsisdisplayedontheleftsideofthescreen:r2(rstandsforreadonlyandmeansthatyoucanonlyreadthisvaluebutcannotchangeit).Ontherightside,theparame-tervalueoftheselectednumberisshown.

Exa

mp

le

Ifyouwanttochangeanyparam-eterusingtheparameterlist,youare requested to choose a filter level(StandardorExpert).TheStandard Level limits the avail-ableparameters,thuslimitingtheriskofdangerousparameters.TheExpertLevelgivesaccesstoall parameters.

NOTE

Exa

mp

le

ESC

ESC

OK

OK

OK

OK

I_DT_G120_Booklet_RZ.indd 27 04.04.2012 13:12:13

Page 28: Sinamics g120 treinamento (en)

28 Operator Panels BOP-2 and IOP: Working with BOP-2

Example for index parameters

• PressingOKtakesyouto[00] • UPtakesyouto[01],DOWNbackto[00] • Decideforanindexnumberofyourchoice • PressOKagaintoedittheindex • Thevaluestartsflashing • AdjustthevaluebypressingUPandDOWN • ConfirmbypressingOK

Someparametersstoremorethanonevalue.Inthiscase,pressingOKdoesnottakeyoudirectlytothevalue,buttoanindexthatisdisplayedinbrackets[00]abovetheactualvalue.

Exa

mp

le

OKOKOK

A complete list of all parameters can be found in the “Parameter Manual:ControlUnits–CU240E/B-2”asadownloadat:http://support.automation. siemens.com/WW/view/en/49946755 Ifyouwanttoadjustanyblink-ing/active value digit by digit (usingtheUPandDOWNbuttonmightjusttaketoolong),youcanalwayspresstheOKbuttonlongerthantwoseconds.Afterreleasingthebutton,youcanchange any single digit by using thebuttonsOK(movetonextdigit),ESC(movetopreviousdigit),UP(increasevalue),andDOWN(decreasevalue).

NOTE

I_DT_G120_Booklet_RZ.indd 28 04.04.2012 13:12:13

Page 29: Sinamics g120 treinamento (en)

29

Function buttons

Withthefunctionbuttons,youcanactuallyoperatethemotor.TheHAND/AUTObuttonchangesthecommandsourcebetweentheBOP-2(HAND)andfieldbus(AUTO).Ahandiconappearsinthescreento indicate HAND mode is active.

• InHANDmodetheONandOFFbuttonsareenabled • InAUTOmodetheONandOFFbuttonsaredisabled • IfHANDmodeisactive,pressingtheHAND/AUTObuttonwillswitchtheconvertertoAUTOmode • IfAUTOmodeisactive,pressingtheHAND/AUTObuttonwillswitchtheconvertertoHANDmode • ChangingHANDtoAUTOmodeispossiblewhilethemotorisstillrunning

Screen Icons

The BOP-2 displays a number of icons at the left-hand side of the display to indicate the actual state of the converter.

• Commandsourceauto/hand

• Converterstatusrunning

• JOG

• Fault/Alarmsactive

A detailed list of the Fault and Alarm messages can be found in the “Parameter Manual: Control Units–CU240E/B-2”asadown-load at: http://support. automation.siemens.com/WW/view/en/49946755

NOTE

JOG

I_DT_G120_Booklet_RZ.indd 29 04.04.2012 13:12:13

Page 30: Sinamics g120 treinamento (en)

30

Starting quick commissioning

• PressESCtoenterthemenuselection • UseUPandDOWNtomovethemenubartoSETUPandpressOK • Thescreenwillautomaticallydisplaythenextparameterinthecommissioningsequence

Resetting the converter

• PressOKwhiletheBOP-2showsRESET • PressUPorDOWNtochangethevaluetoYES • PressOKandwaituntiltheBUSYsigndisappears • Nowallvaluesareresettothefactorysetting

Operator Panels BOP-2 and IOP: Quick commissioning

Any step of the commissioning wizardcanbeskippedbypress-ing the DOWN button. Going backonestepcanbedonebypressingtheUPbutton.Bycon-firmingonestepwithOK,thescreenwillautomaticallydisplaythenextparameterinthecom-missioning sequence.

NOTE

2.3 Quick commissioningThefollowingdescriptionsshowhowtosetupthedriveusingthequickcommissioningwizard integrated in the BOP-2.

Quickcommissioningbeginsnow.Itwillhelpyousetallrelevantparametersstepbystep.Parametersthatarenotrelevantwillbeskippedautomatically.Thus,youadjustthefactorysettingsofyourcon-verter to the requirements of your motor.

OKOK

ESC OK

I_DT_G120_Booklet_RZ.indd 30 04.04.2012 13:12:13

Page 31: Sinamics g120 treinamento (en)

31

Setting the control mode (P1300)

Inourexampleitisassumedthatyourconverterandthemotorarenew.Asaresult,aseriesofpreparatorystepsarerequired,e.g.selectingthecontrolmode.Thisisindicatedbytheparameternumber1300.‘V/fcontrolwithlinearcharacteristiccurve’isdefinedbythefactorysetting.

• PressOKtomodifytheparametervalueCTRLMOD • Theupperrowshowsthecontrolmodeassociatedtotheactualparametervaluebelow • ChooseyourdesiredcontrolmodevaluebypressingUPorDOWN • Seehowthecontrolmodenameintheupperrowchangesaccordingly • PressOKifthedesiredcontrolmodeisdisplayed

Selecting line frequency (P100)

Thenextparametersequencesetsthelinefrequencyoftheregioninwhichthemotorisbeingused.Inourexample,thisisEurope.

• PressOKtomodifytheparametervalueEURUSA • Set0forEurope(50Hz)(1representstheUSlinefrequencyof60Hz) • ConfirmthevaluebypressingOK • Thescreenwillautomaticallydisplaythenextparameterinthecommissioningsequence

The applicable line frequency can be also found on your motor plate(seechapter“Enteringmotordata”).

NOTE

OKOK

OKOK

I_DT_G120_Booklet_RZ.indd 31 04.04.2012 13:12:13

Page 32: Sinamics g120 treinamento (en)

32

2.0 HP

3.55-3.552.05-2.05

84.5%84.5%86.5%

NOM.EFF

K

AV380 - 420660 - 725

CL

IP55 E0807/0496382_02 003

IMB3

UNIREX-N340°C Tamb Th.Cl. 155(F)25 kg

Design ATEFCMG1-12 NEMASF 1.15 CONT60Hz:

Intervall: 4000hrs

IEC/EN 60034 100L3~Mot. 1LE10011AC434AA0

6206-2ZC36206-2ZC3Bearing

DENE 11g

15g

D-91056 Erlangen

-20°C

Y400

460690

V970970

1175

rpm0.730.730.69

PF

3.15

3.52.05

A kWHz50

6050

1.5

1.51.5

Operator Panels BOP-2 and IOP: Quick commissioning

Ifyouwanttoadjustanyflash-ingvaluedigitbydigit(usingtheUPandDOWNbuttonmightjusttaketoolong)presstheOKbut-tonlongerthantwoseconds.Afterreleasingthebutton,youcan change each single digit by usingthebuttonsOK(movetonextdigit),ESC(movetoprevi-ousdigit),UP(increasevalue)andDOWN(decreasevalue).

NOTE

1 2 3 4 5

1

3

2

4

5

P304=MOTVOLT=Motorvoltage

P100=EURUSA=StandardIECorNEMA

P305=MOTCURR=Motorratedcurrent

P307=MOTPOW=Motorratedpower

P311=MOTRPM=Motorratedspeed

The line frequency has been set already inthebeginningofquickcommissioning(seepage31.)

Entering motor data

Inthenextstep,theconverterisadjustedtothemotor.Themotordatacanbefoundonthemotor’srating plate. Please set the values according to the plate.

• PressOKtoeditthemotorvoltagestoredunderP304 • Thepresetmotorvoltageof400voltsisdisplayed • LeavethevalueandconfirmbypressingOK

OKOKOK

I_DT_G120_Booklet_RZ.indd 32 04.04.2012 13:12:17

Page 33: Sinamics g120 treinamento (en)

33

Activating pre-defined settings (P15) e.g. for command and setpoint source

• PressOKtoactivatemacroparameterizationMAcPAr • Macro12(StdASP)isdisplayed,itdeterminesDI0forthecommandsourceandthe potentiometer for the setpoint source • LeavethevalueandconfirmbypressingOK

TheconvertercannowbeturnedonusingdigitalinputDI0. The setpoint source is specified as the potentiometer.

Motor data identificationAfterenteringthemotordata,thewizardsaskstoactivatethemotordataidentification.Thisisrecom-mendedforaliveverificationandoptimizationofthedatathatyouhaveentered.Themotordataiden-tificationinitiatesa“measurement”oftheconnectedmotor.Intheprocess,thedatapreviouslycalcu-lated in the converter are compared to the actual motor data and adapted to one another.

Specifying application parametersInthenextstep,pre-definedsettingsfortheconverter’sinterfacescanbeactivated.Thisisstoredinparameternumber15andindicatedbyMAcPArformacroparameterization.Forexample,theconverteroffers different pre-defined macros for setting the command and setpoint source.

Activating motor data identification (P1900)

• PressOKtoconfirmMOTID • Changethedisplayedvalueto1bypressingUP

Motor data identification does only start after the basic commissioning sequence has been completed andthemotorisswitchedonthefirsttime!

OK

OK OK

I_DT_G120_Booklet_RZ.indd 33 04.04.2012 13:12:17

Page 34: Sinamics g120 treinamento (en)

34 Operator Panels BOP-2 and IOP: Quick commissioning

Completing quick commissioning

• PressOKwhiletheBOP-2showsFINISH • SelectYESandpressOKagain

Thevaluesaredisplayedinseconds.Inbothcases,thetimesindicatedshouldnotbetooshort,becausethis might result in an alarm.

Theconverterisnowparameterizedoptimallytoyourapplicationandmotorspecifications.Nowmotordataidentificationshouldbeper-formedtofinalizethecommissioning.Thiscanbedonebyswitchingonthemotor.Atthemoment,commandsourceissettodigitalinputDI0.StartthemotorwithturningonDI0.

Minimum frequency, ramp up and ramp down time (P1080)

• SettheminimumfrequencyunderparameterMINRPM • PressOK(ParameterMINRPM) • ChangethevaluebypressingUPorDOWN • PressOKtoconfirm

• Settheramping-uptimeunderparameterRAMPUPforaccelerationtimetomaximum frequency(P1120) • Settheramping-downtimeunderparameterRAMPDWNfortimeuntilstandstill(P1121)

Changing the value digit by digit ispossiblebypressingtheOKbut-ton longer than 2 seconds. After releasingthebutton,eachsingledigit can be changed by using the buttonsOK(movetonextdigit),ESC(movetopreviousdigit),UP(increasevalue)andDOWN(decreasevalue). Refertothe“ParameterManual:ControlUnits–CU240E/B-2”foradescription of the control modes and their corresponding parame-ter settings at: http://support.automation.siemens.com/WW/view/en/49946755

NOTE

OK OK

OK OK

OK OK

OK OK

I_DT_G120_Booklet_RZ.indd 34 04.04.2012 13:12:17

Page 35: Sinamics g120 treinamento (en)

35

TheBasicOperatorPanel2canalsobeusedtomakeavarietyofotheradjustmentstoyourapplication.Pleasenotethatanoverviewoftheparameter numbers can be found in the Operating Instructions: Con-trolUnitsCU240E-2.

Motor data identification

• StartthemotormanuallybyusingdigitalinputDI0 • Themeasuringprocessissetinmotion • Whenfinished,themotorswitchesoff • BOP-2indicatesthatthemeasuredvaluesarenowbeingconvertedintodata

Saving parameter sets from converter to BOP-2

• NavigatewiththemenubartothefunctionEXTRAS • PressOK • PushtheDOWNbuttonuntilTOBOPappears • PressOK

Copying parameter sets from BOP-2 to converter

• NavigatetothemenuEXTRAS • PressOK • PushtheDOWNbuttonuntilFROMBOPappears • PressOK

Saving and restoring dataSavingdataindifferentlocationisimportant.TheEXTRASfunctionallowsloadingparameterdatafromthe converter memory to the BOP-2 and vice versa.

The BOP-2 can be mounted or removed at any time. The device is not necessary for ongoing operation.

NOTE

OKOK

OKOK

I_DT_G120_Booklet_RZ.indd 35 04.04.2012 13:12:17

Page 36: Sinamics g120 treinamento (en)

36 Operator Panels BOP-2 and IOP: Intelligent Operator Panel

2.4 intelligent Operator PanelWiththeIntelligentOperatorPanel,youcansettheinverterparameters,puttheinverterintooperation,monitortheongoingoperationofthemotor,andgetvaluableinformationaboutfaultsandalarms.Allthesefunctionscanbeaccessedwithoutexpertknowledge.Themainadvantagesareasfollows:

Fast commissioning without expert knowledge

• Simplecommissioningofstandardapplicationsusingapplication-specificassistants,no knowledgeofparameterstructurenecessary • Usercustomizedparameterlistswithreducedparametersets • Simplelocalcommissioningusingthehandheldversion • Fastmultiplecommissioningwithclonefunction • Commissioningwithoutdocumentationbyusingtheintegratedhelpfunction

Minimization of maintenance time

• Diagnosiswithcleartextdisplay,withoutdocumentationusableonsite • Simpleupdateoflanguages,applicationassistantsandfirmwareusingthe integratedUSBconnection • Integratedcleartexthelpfunctiontoreadandresolvefaultmessagesandreasonslocally

High usability, intuitive handling

• Direct,manualcontrolofthedrive–simpleswitchingfromlocaltoremoteoperation • Intuitivemenunavigationusingwheel-clickinterface • Graphicaldisplayfori.e.statusvaluesinvertical-barcharts(forexamplepressureorflowrate) • Statusdisplaywithfreelyselectableunits–displayofreal,physicalvalues

Flexible usage

• Availablefordirectcontrolunitmounting,fordoormountingorashandheldversion (dependingonfrequencyconvertertype) • Simpleandfastmechanicalandelectricaldoormounting • Handheldusableforalargevarietyoffrequencyconverters • 5integratedlanguages

I_DT_G120_Booklet_RZ.indd 36 04.04.2012 13:12:17

Page 37: Sinamics g120 treinamento (en)

37

1 2 3

The deviceThe IOP is a menu-driven device. Its functionality is structured by three options:

1

2

3

The display

Allnecessaryinformationisuser-friendlydisplayedinplaintextoricons.Thedisplayediconsareshownatthetopright-handedgeofthedisplay.Theyindicatevariousstatesoftheconverter.

• Commandsourceauto/hand

• Inverterstatusready/running

• Fault

• Alarmpending

• BatteryconditionFullyCharged/Discharged

[Wizards]Assistsyoutosetupstandardapplications

[Control]Allowsyoutochangesetpointvalue,turningdirectionactivatesthejogfunctioninreal-time

[Menu]Givesyouaccesstoallpossiblefunctionalities

I_DT_G120_Booklet_RZ.indd 37 04.04.2012 13:12:18

Page 38: Sinamics g120 treinamento (en)

38

Working with IOPTheIOPisoperatedmainlybyusingthepush-wheel.Thefiveadditionalbuttonsmakeitpossibletodisplaycertainvaluesortoswitchbetweenmanualandautomode.Thebuttonsarecalled:ONkey,OFFkey,ESCkey,INFOkeyandHAND/AUTOkey.

Turning changes the selection Pressing confirms the selection

Starts the motor in manual mode

Stops the motor in manual mode

Takesyoubacktothepreviousscreen

Displays additional information

SwitchesthecommandsourcebetweenHANDandAUTOmode

TheHAND/AUTOfunctionworksidentically to the one imple-mented in the BOP-2. After start-ingthemotorwiththeONbut-ton,youcanchangethesetpointspeed by navigating to CON-TROL/SETPOINTandturningthewheel(righttoincreasespeed,lefttodecreasespeed).

NOTE

1

1

2

23 6

4 5

3

4

5

6

Operator Panels BOP-2 and IOP: Intelligent Operator Panel

I_DT_G120_Booklet_RZ.indd 38 04.04.2012 13:12:18

Page 39: Sinamics g120 treinamento (en)

39

Onthetopofthescreen,youcan see numbers that indicate thepresentstepofthewizardthatyouarein.2/15forexamplemeans that you are in step 2 of 15.

NOTE

Example: Basic commissioning

• UsethewheeltohighlightthewordWIZARDS • ConfirmbypressingOK • NavigatetoBASICCOMMISSIONINGbyturningthewheel • ConfirmbypressingOK

The wizardsThereareseveralwizardswhichallowyoutosetupvariousfunctionsandcommissiontheconverter.Theynavigateyouinteractivelythroughtheparameterizationofstandardapplications.Thewizardsareaccessedfromthewizardmenu,atthebottom-leftofthestatusscreen.

Nowthewizardwillguideyoustepbystepthroughthebasiccommissioningprocessbypresentinganumberofscreenswhereyoucanchoosethenecessaryoptionsandvalues.Attheconclusionofthebasiccommissioningprocess,thedatacanbesavedtotheconvertersmemory,andcalculationofmotorand control data is started.

• AlwaysusethewheeltoselectanoptionandpressOKtoconfirm • PressESCtomovebackonestep • PressINFOtoreadcontext-sensitivehelpinformation

Wizards Basic CommissioningOK OKOK OK

I_DT_G120_Booklet_RZ.indd 39 04.04.2012 13:12:18

Page 40: Sinamics g120 treinamento (en)

40

Accessing diagnosticsIfyouwanttofindoutwhichinputandoutputdevicesareconnectedtotheconverter,simplynavigatetothediagnosticsmenuandselecttheI/OSTATUS.Thisoptiondisplaysalistofthedigitalandanaloginputsandoutputsoftheconverter.Inaddition,youcanmonitortheircurrentstatus.Thisisaninfor-mation screen and cannot be changed.

UsingthebuttonINFO,alwaysgives you more in-depth infor-mation on the presently high-lightedparameter,steporfeature.

NOTE

Reading the I/O status

• UsethewheeltohighlightthewordMENU • ConfirmbypressingOK • SelectDIAGNOSTICS • ConfirmbypressingOK • ChooseI/OSTATUS • ConfirmbypressingOK • ChooseSTATUSDIGITALINPUTS • ConfirmbypressingOK

YoucannowseeaclearlyarrangedoverviewofallconnectedI/Oincludingtheirstatus.

OK OK

OK OK

OK OK

OK OK

Diagnostics

I/O Status

Menu

Status Digital Inputs

Operator Panels BOP-2 and IOP: Intelligent Operator Panel

I_DT_G120_Booklet_RZ.indd 40 04.04.2012 13:12:18

Page 41: Sinamics g120 treinamento (en)

41

Ifyouwanttofindoutaboutpreviousfaultsandalarms,pleasenavigatebackonelevelandselect“History”.Thiswilldis-play a list of all previous faults and alarms including the time they occurred.

NOTE

Getting information on active faults

• UsethewheeltohighlightthewordMENU • ConfirmbypressingOK • ChooseDIAGNOSTICS • ConfirmbypressingOK • SelectACTIVEFAULTS/ALARMS

Now,allactivefaultmessagesthathavenotyetbeenacknowledgedaredisplayed. Togetfurtherinformation,youcanhighlighteachoneandpressINFO.

YounowknowhowtousetheOperatorPanelstosettheparametersonyourconverterandstartitup. A further possibility is setting up the parameters using your PC or a SIMATIC programming device. Thismethodisclearerandmoreconvenient,butrequiressomewhatmorepreparationtime.

OK OK

OK

OK OK

OK

Menu Diagnostics

Active Faults/Alarms

I_DT_G120_Booklet_RZ.indd 41 04.04.2012 13:12:18

Page 42: Sinamics g120 treinamento (en)

42

in the next step, you will learn how to connect your Pc or PG to the converter and how to set parameters with the STaRTER software. With STaRTER, you can also easily activate the Safety integrated functions of the drive.

3I_DT_G120_Booklet_RZ.indd 42 04.04.2012 13:12:18

Page 43: Sinamics g120 treinamento (en)

43

STaRTER software and Pc

I_DT_G120_Booklet_RZ.indd 43 04.04.2012 13:12:26

Page 44: Sinamics g120 treinamento (en)

44 STARTERsoftwareandPC: Mounting and preparation

3.1 mounting and preparationTheoptionalPCConnectionKit2isrequiredtosetuptheparametersusingaPC. Thekitconsistsoftwocomponents.

1 2Connecting cable STARTERsoftwareonDVD

I_DT_G120_Booklet_RZ.indd 44 04.04.2012 13:12:26

Page 45: Sinamics g120 treinamento (en)

45

Hardware preparation

• PlacetheSTARTERDVDintoyourDVDdrive • InstalltheSTARTERsoftwarebyfollowingthesetupwizard • ConnecttheUSBcabletotheControlUnit • ConnecttheotherendtotheUSBinterfaceofyourPC

TheSTARTERisalsoavailableasadownloadat:http://support.automation.siemens.com/WW/view/en/26233208

NOTE

YoumustinstalltheUSBdriverifyouareconnectingtheconverterandPCtogetherforthefirsttime.Windows7automaticallyinstallsthedriver;forolderWindowsversions,youmustconfirmtheauto-matic installation.

I_DT_G120_Booklet_RZ.indd 45 04.04.2012 13:12:27

Page 46: Sinamics g120 treinamento (en)

46

Creating a STARTER project

Afterinstallationiscomplete,switchontheconverter’spowersupplyandstarttheprogram.Theprojectwizardopensautomatically.Thewizardwillhelpyoucreateyourfirstproject.

Select “Find drive units online”

Givetheprojectanameandclick“Continue”

1

2

STARTERsoftwareandPC: Mounting and preparation

1 2

I_DT_G120_Booklet_RZ.indd 46 04.04.2012 13:12:27

Page 47: Sinamics g120 treinamento (en)

47

Checkthat“DEVICE”issetasAccesspoint.Ifnot,choose“Accesspoint...”andset“DEVICE”inthedialogbox“SetAccessPointforAccessibleNodes”.Checkthat“S7USB”issetasinterface.Ifnot,choose“PG/PC...”.

Openthedrop-downmenu“AccessPointoftheApplication”

Choosethecommand“DEVICE(STARTER–SCOUT)-->S7USB”

In“InterfaceParameterAssignmentUsed”select“S7USB”

ClosewithOK

3

4

5

6

6

7

3

45

7

I_DT_G120_Booklet_RZ.indd 47 04.04.2012 13:12:34

Page 48: Sinamics g120 treinamento (en)

48

The identified converter is displayed

Addtheconvertertoyourprojectwith“Insertdriveunits”

Closetheprojectwizardwith“Complete”10

10

8

9

STARTERsoftwareandPC: Mounting and preparation

TheconverterisnowintegratedintotheprojecttreeandtheparameterscanbesetupusingtheSTARTERsoftware.

8

9

I_DT_G120_Booklet_RZ.indd 48 04.04.2012 13:12:40

Page 49: Sinamics g120 treinamento (en)

49

STARTER user interface

Projecttree

Program menu

Toolbarwithspecialfeatures

Icon “Connect to selected target devices”

Connection mode

Workarea

1

1

4

2

2

5

5

6

3

34

6

I_DT_G120_Booklet_RZ.indd 49 04.04.2012 13:12:41

Page 50: Sinamics g120 treinamento (en)

50 STARTERsoftwareandPC: Mounting and preparation

Loading converter data

Beforeyoucanloadthecurrentconverter’sdataintoyourproject,anonlineconnectionbetweenthe PC and the converter has to be established.

Clicktheicon“Connecttoselectedtargetdevices”

Settheaccesspointto“DEVICE”andplaceacheckmarknexttoconvertername

Click“LoadHWconfigurationtoPG”

1

2

3

1

2

3

I_DT_G120_Booklet_RZ.indd 50 04.04.2012 13:12:46

Page 51: Sinamics g120 treinamento (en)

51

NowtheconverterdataisloadedintotheprojectandanonlineconnectionbetweenPCandconverter is established.

Thebluehighlighted“Offlinemode”changestotheyellowhighlighted“Onlinemode”

Theworkbenchareaopens

4

5

Workbench area

Theareaprovidesadditionalinformationsuchasalarms,thetargetsystemoutputandthediagnosticsoverview.Italsostoresadditionaloperatingfeatures.

4

5

I_DT_G120_Booklet_RZ.indd 51 04.04.2012 13:12:46

Page 52: Sinamics g120 treinamento (en)

52 STARTERsoftwareandPC: Parameterization

3.2 Parameterization Youcannowbegintoparameterizeyourconverter.

Double-clickontheconvertericonintheprojecttree

Clickon“LoadCPU/driveunittoPG”

1

2

1

2

2

I_DT_G120_Booklet_RZ.indd 52 04.04.2012 13:12:50

Page 53: Sinamics g120 treinamento (en)

53

Double-click“Configuration”

Click“Wizard...”intheworkareaandletthewizardguideyou

3

3

4

Werecommendparameterizingourexampleusingtheonlinemode.

NOTE

4

I_DT_G120_Booklet_RZ.indd 53 04.04.2012 13:12:52

Page 54: Sinamics g120 treinamento (en)

54

Configuration wizard

Theconfigurationwizardguidesyoustepbystepthroughthefollowingparameters:

• Controlstructure • Defaultsofthesetpointsourceandthecommandsource • Drivesetting • Motor • Motordata • Drivefunctions • Importantparameters • Calculationofthemotordata • Summary

Byclicking“Next”yougettothenextconfigurationstep.

STARTERsoftwareandPC: Parameterization

1 2

I_DT_G120_Booklet_RZ.indd 54 04.04.2012 13:12:54

Page 55: Sinamics g120 treinamento (en)

55

Start by setting the control structure

Define the command and setpoint source

Select the motor type

Input motor data corresponding to the rating plate

1

2

4

3

Fornon-Siemensmotors,pleaseuse the motor rating plate to input the motor data.

NOTE

3 4

I_DT_G120_Booklet_RZ.indd 55 04.04.2012 13:12:57

Page 56: Sinamics g120 treinamento (en)

56

Select “Identify motor data at standstill” for motor data identification

Entermaximumcurrent

Enterminimumandmaximumspeed

Enterramp-up,ramp-downtimeandOFF3ramp-downtimeemergencyshut-off

5

6

7

8

STARTERsoftwareandPC: Parameterization

5

6

7

8

I_DT_G120_Booklet_RZ.indd 56 04.04.2012 13:13:00

Page 57: Sinamics g120 treinamento (en)

57

Afterclicking“Next”,thecalculatingofthemotordatastarts.Thisconcludestheparameterizationwiththeconfigurationwizard.Youwillnowreceiveasummaryofallparametervaluesinput.Thesummarycanbeinsertedintoatextfilebypressingthe“Copytexttoclipboard”button.Finallyselect“CopyRAMtoROM”tostoretheparameterizationintheconvertersROMmemoryandclosethewindowbyclicking“Finish”.

I_DT_G120_Booklet_RZ.indd 57 04.04.2012 13:13:07

Page 58: Sinamics g120 treinamento (en)

58

Safety Integrated

Ifyourconverterisusedinasafetyrelatedenvironment,westronglyrecommendperformingSafetyIntegratedengineeringusingtheSTARTER.STARTERguidesyouclearlyandeasilythroughtheprocess.Thus,theriskofwrongparameterizationisreducedtoaminimum.

AllcontrolunitsCU240E-2comewiththeSafetyIntegratedfunctionSTO(SafeTorqueOff).STOcanbeusedwhenthemotorcandeceleratetoastandstillwithinashortperiodoftime.ActivatingtheSTOfunction,immediatelyensuresthatthemotorcannotsupplyanyfurthertorque-generatingenergy.

Advantages for the user:

• Nowearingpartsthankstoelectronicshutdown • Converterremainsconnectedtothesupply,italwayssupportsfulldiagnosticscapability • Passwordprotected,nomanipulationofthefunctionpossible

STARTERsoftwareandPC: Parameterization

TheCU240E-2_FandCU240E-2_DP-FControlUnitshaveseveralSafety functions integrated. Inthiscase,noencoderisneeded.Detailed information about SINAMICS Safety Integrated are available at: www.siemens.com/safety-integrated

NOTE

STO

t

v

I_DT_G120_Booklet_RZ.indd 58 04.04.2012 13:13:08

Page 59: Sinamics g120 treinamento (en)

59

Activating Safety Integrated

Browseto“SafetyIntegrated”intheprojecttree

Select “Change settings”

Choose”STOviaterminal”fromthedrop-downmenu

1

1

23

2

3

Didyouknowthatextended SINAMICS Safety Integrated functionscanbeusedwithoutthe need of an encoder at the motor?Thisworldwideuniquefeature saves installation and engineeringtime,reducessys-tem costs and saves space. For further instructions consult the Safety functional manual SINAMICS G120 and SINAMICS G120C using the Siemens Prod-uctInformationSystem(Prodis)at: http://support.automation.siemens.com/WW/view/en/50736819

NOTE

3

I_DT_G120_Booklet_RZ.indd 59 04.04.2012 13:13:10

Page 60: Sinamics g120 treinamento (en)

60

Ifyourconverterisconnectedtoacontroller,settheoutputsignalto“STOactive”inthecorrespondingdrop-downmenu

Clickon“extendedsettings”forfurtheradjustments

FollowtheSTARTERinstructions

5

4

6

STARTERsoftwareandPC: Parameterization

56

4

I_DT_G120_Booklet_RZ.indd 60 04.04.2012 13:13:12

Page 61: Sinamics g120 treinamento (en)

61

NowyourfirstSafetychannelisset.Forthesecondchanneljustcopytheparameters.Clicking“Activatesettings”concludesthesafetyengineering.Intheworkbenchareaclickon“Alarms”andpressthe“Acknowledge”buttontoactivatetheactuallysafetyfunctions.

I_DT_G120_Booklet_RZ.indd 61 04.04.2012 13:13:15

Page 62: Sinamics g120 treinamento (en)

62

Start motor data identification

Openthe“Commissioning”entryintheprojecttree

Double-click“Controlpanel”intheprojecttree

Clickon“Assumecontrolpriority!”intheworkbencharea

Asetupwindowforcommandtransferopens,acceptthedisplayedvaluesandsafetyinstructions

The pending motor data identifi-cation is indicated by the mes-sage “A7991” in the alarm tab. The message tells you that motor dataidentificationwillbeper-formedafterswitchingthemotor on.

NOTESTARTERsoftwareandPC: Parameterization

1

2

3

4

1

3

4

4

2

I_DT_G120_Booklet_RZ.indd 62 04.04.2012 13:13:18

Page 63: Sinamics g120 treinamento (en)

63

Placeacheckmarknextto“Enables”intheworkbencharea

NowtheSTARTERsoftwarehascontrolauthorityfortheattachedmotor.

Clickthegreenbuttontostartthemotor

5

6

56

I_DT_G120_Booklet_RZ.indd 63 04.04.2012 13:13:27

Page 64: Sinamics g120 treinamento (en)

64

Motor data identification is processed. Parameter setup has been successfully completed whenAlarm7991hasdisappeared.

STARTERsoftwareandPC: Parameterization

I_DT_G120_Booklet_RZ.indd 64 04.04.2012 13:13:29

Page 65: Sinamics g120 treinamento (en)

65

3.3 application cases BeforereturningcontrolauthorityfromtheSTARTERsoftwaretotheterminal,youshouldtrycontrollingthe motor from the PC.

Setting setpoint specifications

Input1.500rpminthe“setpointspecification”box

Clickthegreenbuttontostartthemotor

Seehowthemotorrunswith1.500rpm

1

2

3

1 3

2

I_DT_G120_Booklet_RZ.indd 65 04.04.2012 13:13:42

Page 66: Sinamics g120 treinamento (en)

66

Adjustthespeedwiththeslider

Clicktheredbuttontostopthemotor

Concludetheprocessbyclicking“Giveupcontrolpriority!”

AllfunctionsfromthedisplayedcontrolareaintheSTARTERwillbedeactivated.Thecontrolauthorityhas been returned to the terminal.

4

5

6

STARTERsoftwareandPC: Application cases

4

56

I_DT_G120_Booklet_RZ.indd 66 04.04.2012 13:13:54

Page 67: Sinamics g120 treinamento (en)

67

Saving data

Apoweroutagemaycausethelossoftheparametersettings.Asaresult,STARTERoffers various possibilities for protecting your parameter settings.

Double-clickthe“Drivenavigator”intheprojecttree

Select“Commissioning”intheworkarea

1

2

1

2

I_DT_G120_Booklet_RZ.indd 67 04.04.2012 13:13:57

Page 68: Sinamics g120 treinamento (en)

68

Select“Savedataindrive(RAMtoROM)”tostoretheparametersettingsintheconverter’sEEPROMmemory

STARTERsoftwareandPC: Application cases

3

3

I_DT_G120_Booklet_RZ.indd 68 04.04.2012 13:14:06

Page 69: Sinamics g120 treinamento (en)

69

Becauseyouhaveworkedinonlinemode,nodatawhatsoeverhavebeenstoredinyourproject.

Click“Savedatatoproject”tosavetheparametersettinginyourproject

Nowyoucoulddisconnecttheonlineconnectiontotheconverterbyclickingthe “Disconnectfromtargetsystem”icon.Inourexample,pleasecontinuetoremainonlinetorestorethe converter to its factory settings.

4

4

I_DT_G120_Booklet_RZ.indd 69 04.04.2012 13:14:08

Page 70: Sinamics g120 treinamento (en)

70 STARTERsoftwareandPC: Application cases

Restoring factory settings

Resettingyourconvertertofactorysettingsmightbehelpfulifyouhaveexperiencedanyproblemsduringparameterization.

Double-clickthe“Drivenavigator”

Select “Commissioning”

1

2

1

2

I_DT_G120_Booklet_RZ.indd 70 04.04.2012 13:14:10

Page 71: Sinamics g120 treinamento (en)

71

Click“Factorysettings”

Thesecurityquerythatisnowdisplayedletsyouknowthatallsettingsyouhavemadewillbereset.Usingthecheckboxquery,youwillhavetheopportunitytosaveyoursettingstotheconverter’sROMmemory beforehand.

3

3

I_DT_G120_Booklet_RZ.indd 71 04.04.2012 13:14:12

Page 72: Sinamics g120 treinamento (en)

72 STARTERsoftwareandPC: Application cases

Click“OK”toresetallconvertersettingstothefactorysetting4

4

I_DT_G120_Booklet_RZ.indd 72 04.04.2012 13:14:20

Page 73: Sinamics g120 treinamento (en)

73

Afterresetclick“Disconnectfromtargetsystem”

YounowknowhowtouseSTARTERtoquicklyandclearlyinsertyourconverterintoaproject,setupitsparameters,andputitintooperation.Pleasemakesurethatyoualwaysremembertosavetheparame-terdatatotheconverterandinthesoftwarebeforeexitingaproject.

5

5

I_DT_G120_Booklet_RZ.indd 73 04.04.2012 13:14:28

Page 74: Sinamics g120 treinamento (en)

74

congratulations! You have mastered the SinamicS G120 Training Booklet. Thank you for your time and efforts. We hope that this tutorial has addressed all the questions you had and was useful to you. more detailed information can be found online.

I_DT_G120_Booklet_RZ.indd 74 04.04.2012 13:14:30

Page 75: Sinamics g120 treinamento (en)

75

Download overview

Overviewofthevariouscontrolunitversions

http://www.siemens.com/sinamics-g120/printmaterial SINAMICS G120 brochure

Safety Integrated Function Manual

http://support.automation.siemens.com/WW/view/en/50736819

STARTERsoftware

http://support.automation.siemens.com/WW/view/en/26233208

Additional information on parameters

http://support.automation.siemens.com/WW/view/en/49946755 “ParameterManual:ControlUnits–CU240B/E-2”

Detailed information about SINAMICS G120

http://support.automation.siemens.com/WW/view/en/50815575 “OperatingInstructions:SINAMICSG120InverterwithCU240B-2andCU240E-ControlUnits”