DISCLAIMER: THIS REPORT HAS BEEN PREPARED FOR THE BENEFIT OF FIJI INSTITUTION OF ENGINEERS &MINISTRY OF FINANCE TO ESTABLISH THE EXTENT OF DAMAGES BASED ON A HIGH LEVEL PRELIMINARY ASSESSMENT. IN NO CIRCUMSTANCES IS THE REPORT TO BE USED FOR SCOPING OR ESTABLISHMENT OF DETAILED COSTS FOR DAMAGES. NO RESPONSIBILITY SHALL BE TAKEN FOR ANY INCORRECT OR INCOMPLETE INFORMATION DUE TO THE SHORT TIME IN CARRYING OUT THE INITIAL ASSESSMENT AS PART OF VOLUNTARY PROBONO SERVICE OFFERED BY SHRI SINGH & ASSOCIATES LIMITED DETAILED ASSESSMENT SHOULD BE CARRIED OUT FOR DETAILED COST AND SCOPE FOR REPAIR AND REINSTATEMENT WORKS. Shri Singh & Associates Limited Consulting Building, Civil & Structural Engineers CYCLONE WINSTON PRELIMINARY ASSESSMENT SCHOOLS, HEALTH FACILITIES & PUBLIC BUILDINGS FOR THE FIJI INSTITUTION OF ENGINEERS & DEPARTMENT OF NATIONAL PLANNING (MINISTRY OF FINANCE) NAME OF FACILITY: St John’s College TYPE: Secondary School LOCATION: Cawaci, Ovalau DATE OF ASSESSMENT: 19 th March 2016 DATE OF REPORT: 01 st April 2016 JOB NO: 9213.1 GOVERNMENT FACILITY NO: 154

Upload: others

Post on 21-Feb-2021

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

DISCLAIMER: THIS REPORT HAS BEEN PREPARED FOR THE BENEFIT OF FIJI INSTITUTION OF ENGINEERS &MINISTRY OF FINANCE TO ESTABLISH THE EXTENT OF DAMAGES BASED ON A HIGH LEVEL PRELIMINARY ASSESSMENT. IN NO CIRCUMSTANCES IS THE REPORT TO BE USED FOR SCOPING OR ESTABLISHMENT OF DETAILED COSTS FOR DAMAGES. NO RESPONSIBILITY SHALL BE TAKEN FOR ANY INCORRECT OR INCOMPLETE INFORMATION DUE TO THE SHORT TIME IN CARRYING OUT THE INITIAL ASSESSMENT AS PART OF VOLUNTARY PRO‐BONO SERVICE OFFERED BY SHRI SINGH & ASSOCIATES LIMITED DETAILED ASSESSMENT SHOULD BE CARRIED OUT FOR DETAILED COST AND SCOPE FOR REPAIR AND REINSTATEMENT WORKS.    

Shri Singh & Associates Limited Consulting Building, Civil & Structural Engineers

CYCLONE WINSTON PRELIMINARY ASSESSMENT SCHOOLS, HEALTH FACILITIES & PUBLIC BUILDINGS

FOR

THE FIJI INSTITUTION OF ENGINEERS & DEPARTMENT OF NATIONAL PLANNING (MINISTRY OF FINANCE)

NAME OF FACILITY: St John’s College TYPE: Secondary School LOCATION: Cawaci, Ovalau DATE OF ASSESSMENT: 19th March 2016 DATE OF REPORT: 01st April 2016 JOB NO: 9213.1 GOVERNMENT FACILITY NO: 154

 

Page 2: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

GENERAL DAMAGESCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES 

Shri Singh & Associates Limited

GENERAL INFORMATION

Building Name: St Johns College

Location:

No. of Buildings:

Ariel Plan Available: NO

Government facility no.:

1 FENCING / GATES / DRIVEWAY / RETAINING WALLS ETC (INCLUDE TYPE / LENGTH ETC)

Approximately 600 linear meter chainlink fence 2m high on 100 dia pine posts. About 5m noted to be damaged.                                                                              

Cawaci Village, Ovalau 

26

154

2 WATER TANKS/METERS/PLUMBING

2‐ water tanks noted on site placed on natural ground

                                                                                                                                                                                                                                                                                                                                

3 POWER LINES / METERS / WIRING

4 OTHER ITEMS 

Broken FEA power lines noted on site. Major damage to electrical works noted since plenty of the buildings severly damaged. Detailed review of all electrical works are required 

prior to any occupancy of the buildings.

1‐ UNICEF tent noted on site used as classroom.

TOTAL COST ESTIMATE: INTERMEDIATE LONG TERM

DESCRIPTION FEE FEE

Site Works 50,000              50,000              

Building 1 50,000              200,000           

Building 2 50,000              300,000           

Building 3 60,000              300,000           

Building 4 50,000              100,000           

Building 5 300,000            350,000           

Building 6 20,000              50,000              

Building 7 50,000              120,000           

Building 8 50,000              150,000           

Building 9 60,000              60,000              

Building 10 100,000            100,000           

Building 11 100,000            120,000         g , ,

Building 12 100,000            100,000           

Building 13 80,000              80,000              

Building 14 50,000              50,000              

Building 15 50,000              50,000              

Building 16 30,000              50,000              

Building 17 20,000              30,000              

Building 18 20,000              30,000              

Building 19 60,000              60,000              

Building 20 15,000              15,000              

Building 21 10 000 20 000Building 21 10,000              20,000            

Building 22 10,000              10,000              

Building 23 60,000              60,000              

Building 24 15,000              15,000              

Building 25 15,000              20,000              

Building 26 100,000            500,000           

TOTAL: 1,575,000$      2,990,000$     

TOTAL COST AFTER LOCATION MULTIPLIER (1.25): 1,968,750$      3,737,500$     

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

Page 3: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

14

4 Ackland StreetVatuwaqa Ind. Sub-DvsnP.O. Box 12798 Suva FijiPhoneFaxE-Mail

SHRI SINGH & ASSOCIATES LTD

Consulting Building & Civil Engineers

: (679) 3386 532: (679) 3370 481: shrisingh @ is.com.fj

1~

EXISTING SITE PLAN NTS

BUILDING NAME :ST JOHNS COLLEGE

LOCATION :CAWACI, OVALAU

NO. OF BUILDING : 26

KEY :

1 - GIRLS HOSTEL

2 - GIRLS HOSTEL

3 - SCHOOL BLOCK

4 - STAFF QUARTERS

5 - SCHOOL BLOCK

6 - SCHOOL BLOCK

7 - SCHOOL BLOCK

8 - SCHOOL BLOCK

AC

CE

SS

RO

AD

3

4

12

5

1

11 - SCHOOL BLOCK

12 - SCHOOL BLOCK

13 - SCHOOL BLOCK

14 - BOYS HOSTEL

15 - BOYS HOSTEL

16 - BOYS HOSTEL

17 - BOYS HOSTEL

18 - BOYS HOSTEL

9 - SCHOOL BLOCK 19 - BOYS HOSTEL10 - SCHOOL BLOCK

2

6

7

8

9

10

17

15

16

20

26

11

13

18 19 21 22 23 24 25

20 - BOYS HOSTEL

21 - BOYS HOSTEL

22 - BOYS HOSTEL

23 - BOYS HOSTEL

24 - BOYS HOSTEL

25 - BOYS HOSTEL

26 - CHURCH

Page 4: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 1 Utility Building (FEA, Services, etc) Building No. : 1 Divisional Hospital Building Approx Age: Approx. 40 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 30l x 8w x 3.2h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 4 43 Poor

Foundations 1 Good2 Average 4 63 Poor

Walls 1 Good2 Average 4 33 Poor

Rafters 1 Good2 Average 0 N/A3 Poor

Purlins 1 Good2 Average 0 N/A3 Poor

Roof 1 Good2 Average 4 1,2,53 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 1,2,33 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 43 Poor

Terraces/Verandah 1 Good2 Average 4 1,23 Poor

Tiles/Floor Covering 1 Good2 Average N/A N/A3 Poor

Gutters 1 Good2 Average 4 1,2,33 Poor

Downpipes 1 Good2 Average 4 1,2,33 Poor

Fascia Boards 1 Good2 Average 4 1,2,33 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

N/A

Severe damages noted. Demolish and rebuild of structure recommended. Estimated damage to repair back to pre cyclone condition: $50,000

Severe damage noted 60% blown out

N/A

Timber doors and louvered and solid board windows

N/A

Timber lining Ceiling

Concrete floor and roof unknown

N/A

CGI roof cladding nail fixed

Unknown

Unknown

Timber fascia boards

N/A

10% damage noted

Severe damage noted 100% blown out

N/A

Severe damage noted 100% blown out

Severe damage noted 100% blown out

Not safe to occupy, demolish and rebuild recomended

Typical piping system

No visible damage

20% detoriation noted

50% blown out- temporary fixed

Detailed review required

Detailed review required

Timber No visible damage

Timber purlins

Severe damages noted. Demolish and rebuild of structure recommended for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around: $200,000

Standard switches & fluorescent tube lights

15% damage noted

Build Quality

Shri Singh & Associates Limited

minor detoriation noted

severe cracks notedConcrete

Timber flooring

Timber Walls

Page 5: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 2 Utility Building (FEA, Services, etc) Building No. : 2 Divisional Hospital Building Approx Age: Approx. 40 years (established 1897) Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 28l x 16w x 3.2h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 4 N/A3 Poor

Foundations 1 Good2 Average 4 N/A3 Poor

Walls 1 Good2 Average 4 N/A3 Poor

Rafters 1 Good2 Average 4 N/A3 Poor

Purlins 1 Good2 Average 4 N/A3 Poor

Roof 1 Good2 Average 4 7,8,93 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 7,8,9,103 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 N/A3 Poor

Terraces/Verandah 1 Good2 Average 4 73 Poor

Tiles/Floor Covering 1 Good2 Average N/A N/A3 Poor

Gutters 1 Good2 Average 4 7,8,9,103 Poor

Downpipes 1 Good2 Average 4 7,8,9,103 Poor

Fascia Boards 1 Good2 Average 4 7,8,9,103 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

Severe damages noted. Demolish and rebuild of structure recommended for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around: $300,000

Standard switches & fluorescent tube lights

15% damage noted

Build Quality

Shri Singh & Associates Limited

minor detoriation noted

severe cracks notedConcrete

Timber flooring

Timber Walls

Not safe to occupy, demolish and rebuild recomended

Typical piping system

detoriation noted

20% detoriation noted

90% blown out- temporary fixed

Detailed review required

Detailed review required

Timber detoriation noted

Timber purlins

CGI roof cladding nail fixed

Unknown

Unknown

Timber fascia boards

N/A

10% damage noted

Severe damage noted 100% blown out

N/A

Severe damage noted 100% blown out

Severe damage noted 100% blown out

N/A

Severe damages noted. Demolish and rebuild of structure recommended. Estimated damage to repair back to pre cyclone condition: $50,000

Severe damage noted 60% blown out

N/A

Timber doors and louvered and solid board windows

N/A

Timber lining Ceiling

Concrete floor and roof unknown

N/A

Page 6: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 3 Utility Building (FEA, Services, etc) Building No. : 3 Divisional Hospital Building Approx Age: Approx. 35 years Sub-Divisional Hospital No. of Storeys: 2 Health CentreDimension(m): 35l x 28w x 6h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 4 N/A3 Poor

Purlins 1 Good2 Average 4 N/A3 Poor

Roof 1 Good2 Average 4 11,12,133 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 11,12,13,143 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 N/A3 Poor

Terraces/Verandah 1 Good2 Average N/A N/A3 Poor

Tiles/Floor Covering 1 Good2 Average N/A N/A3 Poor

Gutters 1 Good2 Average 4 11,12,13,143 Poor

Downpipes 1 Good2 Average 4 11,12,13,143 Poor

Fascia Boards 1 Good2 Average 4 11,12,13,143 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

N/A

All roof framing member are to be fixed in accordance with the Fiji Building Code Standard. Roofing iron to be fixed with roofing screws throughout the entire roof on every 2nd crest. All hydraulics and electrical works to be reviewed in detail. New guttering, flashing, downpipes, ceilings and shutters are to be installed. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition: $60,000

Severe damage noted 60% blown out

N/A

Timber doors and louvered windows

N/A

Masonite ceiling

N/A

N/A

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

60% damage noted

N/A

N/A

Severe damage noted 60% blown out

Severe damage noted 60% blown out

40% safe to occupy, major rebuliding subject to intermediate solution required for full use

Typical piping system

Severe damage noted- temporary fixed

No visible damage

60% blown out- temporary fixed

Detailed review required

Detailed review required

Timber Severe damage noted- temporary fixed

Timber purlins

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around: $300,000

Standard switches & fluorescent tube lights

20% damage noted

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damageConcrete

Concrete floor and roof unknown

Masonry walls

Page 7: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 4 Utility Building (FEA, Services, etc) Building No. : 4 Divisional Hospital Building Approx Age: Approx. 40 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 21l x 19w x 3h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 4 15,163 Poor

Purlins 1 Good2 Average 4 15,163 Poor

Roof 1 Good2 Average 4 15,163 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 15,163 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 N/A3 Poor

Terraces/Verandah 1 Good2 Average N/A N/A3 Poor

Tiles/Floor Covering 1 Good2 Average N/A N/A3 Poor

Gutters 1 Good2 Average 4 15,163 Poor

Downpipes 1 Good2 Average 4 15,163 Poor

Fascia Boards 1 Good2 Average 4 15,163 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around: $100,000

Standard switches & fluorescent tube lights

40% damage noted

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damageConcrete

Concrete floor

Masonry walls

Safe to occupy subject to major rebuilding as per intermediate solution.

Typical piping system

Severe damage 40% as noted

No visible damage

45% blown out

Detailed review required

Detailed review required

Timber Severe damage 40% as noted

Timber purlins

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

40% damage noted

N/A

N/A

Severe damage noted 60% blown out

Severe damage noted 60% blown out

N/A

New roof framing to be designed. All hydraulics and electrical works to be reviewed in detail. New guttering, flashing, downpipes, ceilings and shutters are to be installed. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition: $50,000

Severe damage noted 60% blown out

N/A

Timber doors and louvered windows

N/A

Masonite ceiling

N/A

N/A

Page 8: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 5 Utility Building (FEA, Services, etc) Building No. : 5 Divisional Hospital Building Approx Age: Approx. 50 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 75l x 12w x3.2h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 4 193 Poor

Rafters 1 Good2 Average 4 17,183 Poor

Purlins 1 Good2 Average 4 17,183 Poor

Roof 1 Good2 Average 4 17,18,3 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 17,183 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 N/A3 Poor

Terraces/Verandah 1 Good2 Average 4 17,183 Poor

Tiles/Floor Covering 1 Good2 Average N/A 203 Poor

Gutters 1 Good2 Average 4 17,183 Poor

Downpipes 1 Good2 Average 4 17,183 Poor

Fascia Boards 1 Good2 Average 4 17,183 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around:$350,000

Standard switches & fluorescent tube lights

100% damage noted

Build Quality

Shri Singh & Associates Limited

minor cracks on walls noted

No visible damageConcrete

Concrete floor

Masonry walls

Safe to occupy subject to major rebuilding as per intermediate solution.

Typical piping system

Severe damage 70% as noted

No visible damage

70% blown out

Detailed review required

Detailed review required

Timber Severe damage 70% as noted

Timber purlins

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

80% damage noted

80% blown out

N/A

Severe damage noted 100% blown out

Severe damage noted 100% blown out

N/A

New roof framing to be designed. All hydraulics and electrical works to be reviewed in detail. New guttering, flashing, downpipes, ceilings and shutters are to be installed. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition: $300,000

Severe damage noted 100% blown out

N/A

Timber doors and louvered windows

N/A

Masonite ceiling

concrete floor, CGI roog cladding on timber framing supported on 50 dia galv. posts

N/A

Page 9: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 6 Utility Building (FEA, Services, etc) Building No. : 6 Divisional Hospital Building Approx Age: Approx. 35 years Sub-Divisional Hospital No. of Storeys: 2 Health CentreDimension(m): 36l x 11w x6.4h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 0 N/A3 Poor

Purlins 1 Good2 Average 0 N/A3 Poor

Roof 1 Good2 Average 0 N/A3 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 N/A3 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 N/A3 Poor

Terraces/Verandah 1 Good2 Average 4 223 Poor

Tiles/Floor Covering 1 Good2 Average N/A N/A3 Poor

Gutters 1 Good2 Average 4 21,223 Poor

Downpipes 1 Good2 Average 4 21,223 Poor

Fascia Boards 1 Good2 Average 4 21,223 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

N/A

All roof framing member are to be fixed in accordance with the Fiji Building Code Standard. Roofing iron to be fixed with roofing screws throughout the entire roof on every 2nd crest. All hydraulics and electrical works to be reviewed in detail. New guttering, flashing, downpipes, ceilings, louvere blades and shutters are to be installed. All rusted steel members to be replaced. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition: $20,000

Severe damage noted 40% blown out

N/A

Timber doors and louvered windows

N/A

Masonite ceiling

concrete floor, CGI roof cladding on timber framing supported on 100 dia galv. posts

N/A

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

20% damage noted

severe rusting of galv. posts noted

N/A

Severe damage noted 100% blown out

Severe damage noted 100% blown out

Safe to occupy subject to major rebuilding as per intermediate solution.

Typical piping system

No visible damage

No visible damage

No visible damage

Detailed review required

Detailed review required

Steel No visible damage

Timber purlins

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around: $50,000

Standard switches & fluorescent tube lights

30% damage noted

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damageConcrete

Concrete floor

Masonry walls

Page 10: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 7 Utility Building (FEA, Services, etc) Building No. : 7 Divisional Hospital Building Approx Age: Approx. 50 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 30l x 12w x3.2h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 4 N/A3 Poor

Rafters 1 Good2 Average 4 253 Poor

Purlins 1 Good2 Average 4 253 Poor

Roof 1 Good2 Average 4 N/A3 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 24,25,273 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 N/A3 Poor

Terraces/Verandah 1 Good2 Average 4 24,253 Poor

Tiles/Floor Covering 1 Good2 Average 0 N/A3 Poor

Gutters 1 Good2 Average 4 25,273 Poor

Downpipes 1 Good2 Average 4 25,273 Poor

Fascia Boards 1 Good2 Average 4 25,273 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

N/A

New roof framing to be designed. All hydraulics and electrical works to be reviewed in detail. New guttering, flashing, downpipes, ceilings and shutters are to be installed.New coluns to be constructed for the terrace roof. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition: $50,000

Severe damage noted 100% blown out

N/A

Timber doors and louvered windows

N/A

Gib board ceiling

concrete floor, CGI roog cladding on timber framing supported on Concrete columns

Ceremic tiles

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

60% damage noted

Major damages to conrete columns noted

No visible damage

Severe damage noted 100% blown out

Severe damage noted 100% blown out

Not safe to occupy, major repair as intermediate solution required

Typical piping system

Severe damage 60% as noted- temporary fixed

No visible damage

60% blown out- temporary fixed

Detailed review required

Detailed review required

Timber Severe damage 60% as noted- temporary fixed

Timber purlins

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around: $120,000

Standard switches & fluorescent tube lights

40% damage noted

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damageConcrete

Concrete floor

Masonry walls

Page 11: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 8 Utility Building (FEA, Services, etc) Building No. : 8 Divisional Hospital Building Approx Age: Approx. 35 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 25l x 11w x3.2h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 0 N/A3 Poor

Purlins 1 Good2 Average 0 N/A3 Poor

Roof 1 Good2 Average 4 283 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 28,29,303 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 N/A3 Poor

Terraces/Verandah 1 Good2 Average 4 N/A3 Poor

Tiles/Floor Covering 1 Good2 Average 0 N/A3 Poor

Gutters 1 Good2 Average 4 28,303 Poor

Downpipes 1 Good2 Average 4 28,303 Poor

Fascia Boards 1 Good2 Average 4 28,29,303 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around: $150,000

Standard switches & fluorescent tube lights

60% damage noted

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damageConcrete

Concrete floor

Masonry walls

Not safe to occupy, major repair as intermediate solution required

Typical piping system

No visible damage

No visible damage

10% damage noted

Detailed review required

Detailed review required

Timber No visible damage

Timber purlins

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

30% damage noted

Major damages to conrete columns noted. Minor cracks on concrete floor notedNo visible damage

Severe damage noted 100% blown out

Severe damage noted 100% blown out

N/A

All roof framing member are to be fixed in accordance with the Fiji Building Code Standard. Roofing iron to be fixed with roofing screws throughout the entire roof on every 2nd crest. All hydraulics and electrical works to be reviewed in detail. New guttering, flashing, downpipes, ceilings, louvere blades, roofing sheets and shutters are to be installed. All damaged concrete columns to be reviewed in detail. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition: $50,000

Severe damage noted 10% blown out

N/A

Timber doors and louvered windows

N/A

Masonite board ceiling

concrete floor, CGI roog cladding on timber framing supported on Concrete columns

Ceremic tiles

Page 12: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 9 Utility Building (FEA, Services, etc) Building No. : 9 Divisional Hospital Building Approx Age: Approx. 40 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 10L x 8W x height unknown Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 4 313 Poor

Foundations 1 Good2 Average 4 N/A 3 Poor

Walls 1 Good2 Average 4 N/A 3 Poor

Rafters 1 Good2 Average 4 N/A 3 Poor

Purlins 1 Good2 Average 4 N/A 3 Poor

Roof 1 Good2 Average 4 N/A 3 Poor

Electrical 1 Good2 Average 4 N/A 3 Poor

Hydraulics 1 Good2 Average 4 N/A 3 Poor

Windows/Doors 1 Good2 Average 4 N/A 3 Poor

Shutters 1 Good2 Average 4 N/A 3 Poor

Ceilings 1 Good2 Average 4 N/A 3 Poor

Terraces/Verandah 1 Good2 Average 4 N/A 3 Poor

Tiles/Floor Covering 1 Good2 Average 4 N/A 3 Poor

Gutters 1 Good2 Average 4 N/A 3 Poor

Downpipes 1 Good2 Average 4 N/A 3 Poor

Fascia Boards 1 Good2 Average 4 N/A 3 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A 3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

Redesign and rebuilding required since whole strucutre was blown out. Estimated damage to repair back to pre cyclone condition: $60,000

Not safe to occupy re-building of the whole structure required

Redesign and rebuilding required since whole strucutre was blown out. Estimated cost for long term solution would be around $60,000

Build Quality

N/A N/A

Shri Singh & Associates Limited

Concrete

Timber Flooring

Unknown - since structure totally blown out

REDESIGN AND REBUILDING REQUIRED SINCE WHOLE STRUCTURE

IS BLOWN AWAY

Page 13: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 10 Utility Building (FEA, Services, etc) Building No. : 10 Divisional Hospital Building Approx Age: Approx. 50 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 21l x 8w x3.2h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 343 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 4 32,333 Poor

Purlins 1 Good2 Average 4 32,333 Poor

Roof 1 Good2 Average 4 32,33,343 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 32,333 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 343 Poor

Terraces/Verandah 1 Good2 Average 4 323 Poor

Tiles/Floor Covering 1 Good2 Average N/A N/A3 Poor

Gutters 1 Good2 Average 4 32,333 Poor

Downpipes 1 Good2 Average 4 32,333 Poor

Fascia Boards 1 Good2 Average 4 32,33,343 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

N/A

New roof design recomended fro the whole structure. New guttering, flashing, downpipes, ceilings, louvere blades,and shutters are to be installed. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition:$100,000

Severe damage noted 100% blown out

N/A

Timber doors and louvered windows

N/A

Masonite board ceiling

Unknown

N/A

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

100% damage noted

100% damage noted

N/A

Severe damage noted 100% blown out

Severe damage noted 100% blown out

Not safe to occupy, major repair as intermediate solution required

Typical piping system

100% damage noted

No visible damage

100% damage noted

Detailed review required

Detailed review required

Timber 100% damage noted

Timber purlins

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around: $100,000

Standard switches & fluorescent tube lights

80% damage noted

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damageConcrete

Concrete floor

Masonry walls

Page 14: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 11 Utility Building (FEA, Services, etc) Building No. : 11 Divisional Hospital Building Approx Age: Approx. 50 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 21l x 10w x3.2h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 4 353 Poor

Purlins 1 Good2 Average 4 353 Poor

Roof 1 Good2 Average 4 N/A3 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 35,363 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 373 Poor

Terraces/Verandah 1 Good2 Average 0 35,383 Poor

Tiles/Floor Covering 1 Good2 Average N/A N/A3 Poor

Gutters 1 Good2 Average 4 35,363 Poor

Downpipes 1 Good2 Average 4 35,363 Poor

Fascia Boards 1 Good2 Average 4 35,363 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around:$120,000

Standard switches & fluorescent tube lights

Damage in form of damaged louvere blades 100% noted

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damageConcrete

Concrete floor

Masonry walls

Not safe to occupy, major repair as intermediate solution required

Typical piping system

60% damage noted

No visible damage

60% damage noted- temporary fixed

Detailed review required

Detailed review required

Timber 60% damage noted

Timber purlins

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

80% damage noted

No visible damage

N/A

Severe damage noted 60% blown out

Severe damage noted 60% blown out

N/A

New roof design recomended fro the whole structure. New guttering, flashing, downpipes, ceilings, louvere blades,and shutters are to be installed. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition:$100,000

Severe damage noted 40% blown out

N/A

Timber doors and louvered windows

N/A

Masonite board ceiling

concrete floor, CGI roof cladding on timber framing supported on 50 dia galv. Posts

N/A

Page 15: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 12 Utility Building (FEA, Services, etc) Building No. : 12 Divisional Hospital Building Approx Age: Approx. 60 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 12L x 8W x height unknown Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 4 393 Poor

Foundations 1 Good2 Average 4 N/A 3 Poor

Walls 1 Good2 Average 4 N/A 3 Poor

Rafters 1 Good2 Average 4 N/A 3 Poor

Purlins 1 Good2 Average 4 N/A 3 Poor

Roof 1 Good2 Average 4 N/A 3 Poor

Electrical 1 Good2 Average 4 N/A 3 Poor

Hydraulics 1 Good2 Average 4 N/A 3 Poor

Windows/Doors 1 Good2 Average 4 N/A 3 Poor

Shutters 1 Good2 Average 4 N/A 3 Poor

Ceilings 1 Good2 Average 4 N/A 3 Poor

Terraces/Verandah 1 Good2 Average 4 N/A 3 Poor

Tiles/Floor Covering 1 Good2 Average 4 N/A 3 Poor

Gutters 1 Good2 Average 4 N/A 3 Poor

Downpipes 1 Good2 Average 4 N/A 3 Poor

Fascia Boards 1 Good2 Average 4 N/A 3 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A 3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

Redesign and rebuilding required since whole strucutre was blown out. Estimated cost for long term solution would be around $100,000

Build Quality

N/A N/A

Shri Singh & Associates Limited

Concrete

Timber Flooring

WHOLE STRUCTURE HAS TILTED, SEVERE DETORIATION TO TIMBER MEMBERS NOTED

REDESIGN AND REBUILDING REQUIRED SINCE WHOLE

STRUCTURE HAS TILTED, SEVERE DETORIATION TO TIMBER MEMBERS

NOTED

Redesign and rebuilding required since whole strucutre was blown out. Estimated damage to repair back to pre cyclone condition: $100,000

Not safe to occupy re-building of the whole structure required

Page 16: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 13 Utility Building (FEA, Services, etc) Building No. : 13 Divisional Hospital Building Approx Age: Approx. 50 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 11L x 7W x height unknown Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 4 403 Poor

Foundations 1 Good2 Average 4 N/A 3 Poor

Walls 1 Good2 Average 4 N/A 3 Poor

Rafters 1 Good2 Average 4 N/A 3 Poor

Purlins 1 Good2 Average 4 N/A 3 Poor

Roof 1 Good2 Average 4 N/A 3 Poor

Electrical 1 Good2 Average 4 N/A 3 Poor

Hydraulics 1 Good2 Average 4 N/A 3 Poor

Windows/Doors 1 Good2 Average 4 N/A 3 Poor

Shutters 1 Good2 Average 4 N/A 3 Poor

Ceilings 1 Good2 Average 4 N/A 3 Poor

Terraces/Verandah 1 Good2 Average 4 N/A 3 Poor

Tiles/Floor Covering 1 Good2 Average 4 N/A 3 Poor

Gutters 1 Good2 Average 4 N/A 3 Poor

Downpipes 1 Good2 Average 4 N/A 3 Poor

Fascia Boards 1 Good2 Average 4 N/A 3 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A 3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

Redesign and rebuilding required since whole strucutre was blown out. Estimated cost for long term solution would be around $80,000

Build Quality

N/A N/A

Shri Singh & Associates Limited

Concrete

Timber Flooring

Unknown - since structure totally blown out

REDESIGN AND REBUILDING REQUIRED SINCE WHOLE STRUCTURE

IS BLOWN AWAY

Redesign and rebuilding required since whole strucutre was blown out. Estimated damage to repair back to pre cyclone condition: $80,000

Not safe to occupy re-building of the whole structure required

Page 17: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 14 Utility Building (FEA, Services, etc) Building No. : 14 Divisional Hospital Building Approx Age: Approx. 25 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 23l x 14w x3.2h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 4 N/A3 Poor

Purlins 1 Good2 Average 4 N/A3 Poor

Roof 1 Good2 Average 4 41,433 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 41,423 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 443 Poor

Terraces/Verandah 1 Good2 Average N/A N/A3 Poor

Tiles/Floor Covering 1 Good2 Average 0 N/A3 Poor

Gutters 1 Good2 Average 4 41,423 Poor

Downpipes 1 Good2 Average 4 41,423 Poor

Fascia Boards 1 Good2 Average 4 41,42,433 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

N/A

All roof framing member are to be fixed in accordance with the Fiji Building Code Standard. Roofing iron to be fixed with roofing screws throughout the entire roof on every 2nd crest. All hydraulics and electrical works to be reviewed in detail. New guttering, flashing, downpipes, ceilings, roofing sheets and shutters are to be installed. All damaged louvere blades and timber members are to be replaced. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition:$50,000

Severe damage noted 60% blown out

N/A

Timber doors and louvered windows

N/A

Ply board ceiling

N/A

Ceremic tiles

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

40% damage noted

N/A

No visible damage

Severe damage noted 100% blown out

Severe damage noted 100% blown out

Safe to occupy, subject to major repair as intermediate solution required

Typical piping system

5% damage noted

No visible damage

10% damage noted

Detailed review required

Detailed review required

Timber 5% damage noted

Timber purlins

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around:$50,000

Standard switches & fluorescent tube lights

10% damage noted

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damageConcrete

Concrete floor

Masonry walls

Page 18: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 15 Utility Building (FEA, Services, etc) Building No. : 15 Divisional Hospital Building Approx Age: Approx. 30 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 29l x 7w x3.8h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 4 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 0 N/A3 Poor

Purlins 1 Good2 Average 0 N/A3 Poor

Roof 1 Good2 Average 4 463 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 45,46,473 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 N/A3 Poor

Terraces/Verandah 1 Good2 Average 4 N/A3 Poor

Tiles/Floor Covering 1 Good2 Average N/A N/A3 Poor

Gutters 1 Good2 Average 4 473 Poor

Downpipes 1 Good2 Average 4 473 Poor

Fascia Boards 1 Good2 Average 4 46,473 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

N/A

All roof framing member are to be fixed in accordance with the Fiji Building Code Standard. Roofing iron to be fixed with roofing screws throughout the entire roof on every 2nd crest. All hydraulics and electrical works to be reviewed in detail. New guttering, flashing, downpipes, ceilings, roofing sheets and shutters are to be installed. All damaged louvere blades and timber members are to be replaced. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition: $50,000

Severe damage noted 20% blown out

N/A

Timber doors and louvered windows

N/A

Ply board ceiling

Timber floor and roofing unknown

N/A

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

30% damage noted

100% damage noted

N/A

Severe damage noted 20% blown out

Severe damage noted 20% blown out

Safe to occupy, subject to minor repair as intermediate solution required

Typical piping system

No visible damage

No visible damage

10% damage noted

Detailed review required

Detailed review required

Timber No visible damage

Timber purlins

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around: $50,000

Standard switches & fluorescent tube lights

10% damage noted

Build Quality

Shri Singh & Associates Limited

No visible damage

cracks notedConcrete

Timber flooring

Timber walls

Page 19: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 16 Utility Building (FEA, Services, etc) Building No. : 16 Divisional Hospital Building Approx Age: Approx. 25 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 29l x 9w x3.2h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 4 N/A3 Poor

Purlins 1 Good2 Average 4 N/A3 Poor

Roof 1 Good2 Average 4 483 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 48,493 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 N/A3 Poor

Terraces/Verandah 1 Good2 Average N/A N/A3 Poor

Tiles/Floor Covering 1 Good2 Average 0 N/A3 Poor

Gutters 1 Good2 Average 4 48,493 Poor

Downpipes 1 Good2 Average 4 48,493 Poor

Fascia Boards 1 Good2 Average 4 48,493 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

N/A

All roof framing member are to be fixed in accordance with the Fiji Building Code Standard. Roofing iron to be fixed with roofing screws throughout the entire roof on every 2nd crest. All hydraulics and electrical works to be reviewed in detail. New guttering, flashing, downpipes, ceilings, roofing sheets and shutters are to be installed. All damaged louvere blades and timber members are to be replaced. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition:$30,000

Severe damage noted 10% blown out

N/A

Timber doors and louvered windows

N/A

Ply board ceiling

N/A

Ceremic tiles

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

30% damage noted

N/A

No visible damage

Severe damage noted 50% blown out

Severe damage noted 50% blown out

Safe to occupy, subject to minor repair as intermediate solution required

Typical piping system

5% damage noted

No visible damage

10% damage noted

Detailed review required

Detailed review required

Timber 5% damage noted

Timber purlins

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around: $50,000

Standard switches & fluorescent tube lights

5% damage noted

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damageConcrete

Concrete floor

Masonry walls

Page 20: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 17 Utility Building (FEA, Services, etc) Building No. : 17 Divisional Hospital Building Approx Age: Approx. 25 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 29l x 9w x3.2h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 0 N/A3 Poor

Purlins 1 Good2 Average 0 N/A3 Poor

Roof 1 Good2 Average 0 N/A3 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 0 N/A3 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 0 N/A3 Poor

Terraces/Verandah 1 Good2 Average N/A N/A3 Poor

Tiles/Floor Covering 1 Good2 Average 0 N/A3 Poor

Gutters 1 Good2 Average 0 N/A3 Poor

Downpipes 1 Good2 Average 4 503 Poor

Fascia Boards 1 Good2 Average 0 N/A3 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

N/A

All roof framing member are to be fixed in accordance with the Fiji Building Code Standard. Roofing iron to be fixed with roofing screws throughout the entire roof on every 2nd crest. All hydraulics and electrical works to be reviewed in detail. New downpipes and shutters are to be installed. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition: $20,000

No visible damage

N/A

Timber doors and louvered windows

N/A

Ply board ceiling

N/A

Ceremic tiles

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

No visible damage

N/A

No visible damage

No visible damage

Severe damage noted 50% blown out

Safe to occupy, subject to minor repair as intermediate solution required

Typical piping system

No visible damage

No visible damage

No visible damage

Detailed review required

Detailed review required

Timber No visible damage

Timber purlins

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around: $30,000

Standard switches & fluorescent tube lights

No visible damage

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damageConcrete

Concrete floor

Masonry walls

Page 21: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 18 Utility Building (FEA, Services, etc) Building No. : 18 Divisional Hospital Building Approx Age: Approx. 30 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 14l x 9w x3.2h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 4 N/A3 Poor

Purlins 1 Good2 Average 4 N/A3 Poor

Roof 1 Good2 Average 4 51,523 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 0 51,523 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 0 N/A3 Poor

Terraces/Verandah 1 Good2 Average N/A N/A3 Poor

Tiles/Floor Covering 1 Good2 Average 0 N/A3 Poor

Gutters 1 Good2 Average 4 51,523 Poor

Downpipes 1 Good2 Average 4 51,523 Poor

Fascia Boards 1 Good2 Average 4 51,523 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

N/A

All roof framing member are to be fixed in accordance with the Fiji Building Code Standard. Roofing iron to be fixed with roofing screws throughout the entire roof on every 2nd crest. All hydraulics and electrical works to be reviewed in detail. New guttering, flashing, downpipes, ceilings, roofing sheets and shutters are to be installed. All damaged timber members are to be replaced. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition:$20,000

Severe damage noted 10% blown out

N/A

Timber doors and louvered windows

N/A

Ply board ceiling

N/A

Ceremic tiles

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

No visible damage

N/A

No visible damage

Severe damage noted 50% blown out

Severe damage noted 50% blown out

Safe to occupy, subject to major repair as intermediate solution required

Typical piping system

5% damage noted

No visible damage

15% damage noted

Detailed review required

Detailed review required

Timber 5% damage noted

Timber purlins

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around: $30,000

Standard switches & fluorescent tube lights

No visible damage

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damageConcrete

Concrete floor

Masonry walls

Page 22: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 19 Utility Building (FEA, Services, etc) Building No. : 19 Divisional Hospital Building Approx Age: Approx. 40 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 11L x 6W x Unknown Nursing Station uUsability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 543 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 4 N/A3 Poor

Rafters 1 Good2 Average 4 N/A3 Poor

Purlins 1 Good2 Average 4 N/A3 Poor

Roof 1 Good2 Average 4 N/A3 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 N/A

3 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 N/A3 Poor

Terraces/Verandah 1 Good2 Average 4 N/A3 Poor

Tiles/Floor Covering 1 Good2 Average 0 N/A3 Poor

Gutters 1 Good2 Average 4 N/A3 Poor

Downpipes 1 Good2 Average 4 N/A3 Poor

Fascia Boards 1 Good2 Average 4 N/A3 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

Severe damages noted. Demolish and rebuild is recommended. Existing floor slab can be used. Estimated cost: $60,000

Typically standard switches & fluorecent tubelights

Damages in form of broken louvered blades & damaged window frames frames 100% noted

Build Quality

Shri Singh & Associates Limited

100% damage noted

No visible damage Concrete

Reinforced concrete slab on ground

Timber walls

Typical piping system

Severe damage noted 100% blown out

No visible damage

Severe damage noted 100% blown out

Detailed review required

Detailed review required

Timber rafters Severe damage noted 100% blown out

Timber purlins

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipes

timber facia boards

N/A

Roof sturcture totally blown out

Roof sturcture totally blown out

No visible damage

All gutter & downpipes blown out 100% damage noted

All gutter & downpipes blown out 100% damage noted

Not Safe to occupy, demolish rebuild required. Same concrete floor can be used.

Standard desk and chairs

Severe damages noted. Demolish and rebuild is recommended. Existing floor slab can be used. Estimated cost: $60,000

Severe damage noted 100% blown out.

No visible damage

Timber doors and louvered windows

No provisions for shutters

Unknown

Unknown

Ceremic tiles

Page 23: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 20 Utility Building (FEA, Services, etc) Building No. : 20 Divisional Hospital Building Approx Age: Approx. 35 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 6L x 4W x Unknown Nursing Station uUsability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 4 55,563 Poor

Purlins 1 Good2 Average 4 55,563 Poor

Roof 1 Good2 Average 4 N/A3 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 55,56

3 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 N/A3 Poor

Terraces/Verandah 1 Good2 Average N/A N/A3 Poor

Tiles/Floor Covering 1 Good2 Average N/A N/A3 Poor

Gutters 1 Good2 Average 4 55,563 Poor

Downpipes 1 Good2 Average 4 55,563 Poor

Fascia Boards 1 Good2 Average 4 55,563 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

Not Safe to occupy, new roof framing is required

N/A

Redesign of roof structure required. New windows and doors to be installed. Estimated cost: $15,000

Severe damage noted 100% blown out.

N/A

Timber doors and louvered windows

No provisions for shutters

Unknown

N/A

N/A

Typical PVC guttering

Typical PVC downpipes

timber facia boards

N/A

Roof sturcture totally blown out

N/A

N/A

All gutter & downpipes blown out 100% damage noted

All gutter & downpipes blown out 100% damage noted

Typical piping system

Severe damage noted 100% blown out

No visible damage

Severe damage noted 100% blown out

Detailed review required

Detailed review required

Timber rafters Severe damage noted 100% blown out

Timber purlins

CGI roof cladding nail fixed

Redesign of roof structure required. New windows and doors to be installed. Estimated cost: $15,000

Typically standard switches & fluorecent tubelights

Damages in form of broken louvered blades & damaged window frames frames 100% noted

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damage Concrete

Reinforced concrete slab on ground

Concrete walls

Page 24: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 21 Utility Building (FEA, Services, etc) Building No. : 21 Divisional Hospital Building Approx Age: Approx. 30 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 16l x 9w x3.2h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 0 N/A3 Poor

Purlins 1 Good2 Average 0 N/A3 Poor

Roof 1 Good2 Average 4 N/A3 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 0 59,603 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 0 N/A3 Poor

Terraces/Verandah 1 Good2 Average N/A N/A3 Poor

Tiles/Floor Covering 1 Good2 Average 0 N/A3 Poor

Gutters 1 Good2 Average 4 59,603 Poor

Downpipes 1 Good2 Average 4 59,603 Poor

Fascia Boards 1 Good2 Average 4 59,603 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

N/A

All roof framing member are to be fixed in accordance with the Fiji Building Code Standard. Roofing iron to be fixed with roofing screws throughout the entire roof on every 2nd crest. All hydraulics and electrical works to be reviewed in detail. New guttering, flashing, downpipes, ceilings, roofing sheets and shutters are to be installed. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition:$10,000

Severe damage noted 10% blown out

N/A

Timber doors and louvered windows

N/A

Ply board ceiling

N/A

Ceremic tiles

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

No visible damage

N/A

No visible damage

Severe damage noted 10% blown out

Severe damage noted 10% blown out

Safe to occupy, subject to major repair as intermediate solution required

Typical piping system

No visible damage

No visible damage

5% damage noted

Detailed review required

Detailed review required

Timber No visible damage

Timber purlins

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around:$20,000

Standard switches & fluorescent tube lights

No visible damage

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damageConcrete

Concrete floor

Masonry walls

Page 25: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 22 Utility Building (FEA, Services, etc) Building No. : 22 Divisional Hospital Building Approx Age: Approx. 30 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 15l x 9w x3.2h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 0 N/A3 Poor

Purlins 1 Good2 Average 0 N/A3 Poor

Roof 1 Good2 Average 0 N/A3 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A 57,583 Poor

Windows/Doors 1 Good2 Average 0 N/A3 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 0 N/A3 Poor

Terraces/Verandah 1 Good2 Average N/A N/A3 Poor

Tiles/Floor Covering 1 Good2 Average 0 N/A3 Poor

Gutters 1 Good2 Average 0 583 Poor

Downpipes 1 Good2 Average 0 583 Poor

Fascia Boards 1 Good2 Average 0 57,583 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around: $10,000

Standard switches & fluorescent tube lights

No visible damage

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damageConcrete

Concrete floor

Masonry walls

Safe to occupy, subject to minor repair as intermediate solution required

Typical piping system

No visible damage

No visible damage

No visible damage

Detailed review required

Detailed review required

Timber No visible damage

Timber purlins

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

No visible damage

N/A

No visible damage

No visible damage

No visible damage

N/A

All roof framing member are to be fixed in accordance with the Fiji Building Code Standard. Roofing iron to be fixed with roofing screws throughout the entire roof on every 2nd crest. All hydraulics and electrical works to be reviewed in detail. New downpipes and shutters are to be installed. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition: $10,000

No visible damage

N/A

Timber doors and louvered windows

N/A

Ply board ceiling

N/A

Ceremic tiles

Page 26: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 23 Utility Building (FEA, Services, etc) Building No. : 23 Divisional Hospital Building Approx Age: Approx. 40 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 10L x 8W x height unknown Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 4 613 Poor

Foundations 1 Good2 Average 4 N/A 3 Poor

Walls 1 Good2 Average 4 N/A 3 Poor

Rafters 1 Good2 Average 4 N/A 3 Poor

Purlins 1 Good2 Average 4 N/A 3 Poor

Roof 1 Good2 Average 4 N/A 3 Poor

Electrical 1 Good2 Average 4 N/A 3 Poor

Hydraulics 1 Good2 Average 4 N/A 3 Poor

Windows/Doors 1 Good2 Average 4 N/A 3 Poor

Shutters 1 Good2 Average 4 N/A 3 Poor

Ceilings 1 Good2 Average 4 N/A 3 Poor

Terraces/Verandah 1 Good2 Average 4 N/A 3 Poor

Tiles/Floor Covering 1 Good2 Average 4 N/A 3 Poor

Gutters 1 Good2 Average 4 N/A 3 Poor

Downpipes 1 Good2 Average 4 N/A 3 Poor

Fascia Boards 1 Good2 Average 4 N/A 3 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A 3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

Redesign and rebuilding required since whole strucutre was blown out. Estimated cost for long term solution would be around $60,000

Build Quality

N/A N/A

Shri Singh & Associates Limited

Concrete

Timber Flooring

Unknown - since structure totally blown out

REDESIGN AND REBUILDING REQUIRED SINCE WHOLE STRUCTURE

IS BLOWN AWAY

Redesign and rebuilding required since whole strucutre was blown out. Estimated damage to repair back to pre cyclone condition: $60,000

Not safe to occupy re-building of the whole structure required

Page 27: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 24 Utility Building (FEA, Services, etc) Building No. : 24 Divisional Hospital Building Approx Age: Approx. 35 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 6L x 4W x Unknown Nursing Station uUsability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 4 643 Poor

Purlins 1 Good2 Average 4 643 Poor

Roof 1 Good2 Average 4 643 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 64

3 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 4 643 Poor

Terraces/Verandah 1 Good2 Average N/A N/A3 Poor

Tiles/Floor Covering 1 Good2 Average N/A N/A3 Poor

Gutters 1 Good2 Average 4 643 Poor

Downpipes 1 Good2 Average 4 643 Poor

Fascia Boards 1 Good2 Average 4 643 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

Not Safe to occupy, new roof framing is required

N/A

Redesign of roof structure required. New windows and doors to be installed. Estimated cost: $15,000

Severe damage noted 100% blown out.

N/A

Timber doors and louvered windows

No provisions for shutters

Unknown

N/A

N/A

Typical PVC guttering

Typical PVC downpipes

timber facia boards

N/A

Roof sturcture totally blown out

N/A

N/A

All gutter & downpipes blown out 100% damage noted

All gutter & downpipes blown out 100% damage noted

Typical piping system

Severe damage noted 100% blown out

No visible damage

Severe damage noted 100% blown out

Detailed review required

Detailed review required

Timber rafters Severe damage noted 100% blown out

Timber purlins

CGI roof cladding nail fixed

Redesign of roof structure required. New windows and doors to be installed. Estimated cost: $15,000

Typically standard switches & fluorecent tubelights

Damages in form of broken louvered blades & damaged window frames frames 100% noted

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damage Concrete

Reinforced concrete slab on ground

Concrete walls

Page 28: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: School Block 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 25 Utility Building (FEA, Services, etc) Building No. : 25 Divisional Hospital Building Approx Age: Approx. 30 years Sub-Divisional Hospital No. of Storeys: 1 Health CentreDimension(m): 15l x 9w x3.2h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 0 N/A3 Poor

Rafters 1 Good2 Average 0 N/A3 Poor

Purlins 1 Good2 Average 0 N/A3 Poor

Roof 1 Good2 Average 0 N/A3 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 0 62,633 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average 0 N/A3 Poor

Terraces/Verandah 1 Good2 Average N/A N/A3 Poor

Tiles/Floor Covering 1 Good2 Average 0 N/A3 Poor

Gutters 1 Good2 Average 0 62,633 Poor

Downpipes 1 Good2 Average 0 62,633 Poor

Fascia Boards 1 Good2 Average 0 N/A3 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones. Estimated cost for long term solution would be around: $20,000

Standard switches & fluorescent tube lights

No visible damage

Build Quality

Shri Singh & Associates Limited

No visible damage

No visible damageConcrete

Concrete floor

Masonry walls

Safe to occupy, subject to minor repair as intermediate solution required

Typical piping system

No visible damage

No visible damage

No visible damage

Detailed review required

Detailed review required

Timber No visible damage

Timber purlins

CGI roof cladding nail fixed

Typical PVC guttering

Typical PVC downpipe

Timber fascia boards

N/A

No visible damage

N/A

No visible damage

10% Blown Away

10% Blown Away

N/A

All roof framing member are to be fixed in accordance with the Fiji Building Code Standard. Roofing iron to be fixed with roofing screws throughout the entire roof on every 2nd crest. All hydraulics and electrical works to be reviewed in detail. New downpipes and shutters are to be installed. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition: $15,000

No visible damage

N/A

Timber doors and louvered windows

N/A

Ply board ceiling

N/A

Ceremic tiles

Page 29: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

Consulting Building, Civil & Structural Engineers

RAPID ASSESSMENT TEMPLATE: CYCLONE WINSTON DAMAGED BUILDINGSSCHOOLS, PUBLIC BUILDINGS & HEALTH FACILITIES

Extent of Damage Rating Description0 No Damage

GENERAL INFORMATION 1 Minor/Cosmetic/WaterBuilding Name: St. Johns College 2 Some DamageType: Chapel 3 Extensive but RepairableLocation: Cawaci Village, Ovalau 4 IrreparableNo. of Buildings: 26 Types of BuildingsAriel Plan Available: NO School Block

Staff QuartersREPORT Toilet Block Page No. : 26 Utility Building (FEA, Services, etc) Building No. : 26 Divisional Hospital Building Approx Age: Approx. 64 years Sub-Divisional Hospital No. of Storeys: 3 Health CentreDimension(m): 32l x 27w x10h Nursing Station Usability: Public Building or Facility

EVALUATIONType of Construction Description Damage Extent of

Photo No.

Floor 1 Good2 Average 0 N/A3 Poor

Foundations 1 Good2 Average 0 N/A3 Poor

Walls 1 Good2 Average 4 65,66,673 Poor

Rafters 1 Good2 Average 4 65,673 Poor

Purlins 1 Good2 Average 4 65,673 Poor

Roof 1 Good2 Average 4 65,673 Poor

Electrical 1 Good2 Average N/A N/A3 Poor

Hydraulics 1 Good2 Average N/A N/A3 Poor

Windows/Doors 1 Good2 Average 4 65,66,673 Poor

Shutters 1 Good2 Average N/A N/A3 Poor

Ceilings 1 Good2 Average N/A N/A3 Poor

Terraces/Verandah 1 Good2 Average N/A N/A3 Poor

Tiles/Floor Covering 1 Good2 Average 0 N/A3 Poor

Gutters 1 Good2 Average 0 N/A3 Poor

Downpipes 1 Good2 Average 0 N/A3 Poor

Fascia Boards 1 Good2 Average N/A N/A3 Poor

Furniture/Desks etc. 1 Good2 Average N/A N/A3 Poor

Possible Intermediate Solution

Possible Long Term Solution

Damage Assessment ($)Basis of Calculation

FEES ESTIMATE:Design/Documentation:Tender/Approval:Inspection/End Construction:

Disclaimer: This assessment is being done on a pro-bono basis as assistance for the Government of Fiji. All care is taken but no liability. This is a preliminary assessment therefore further review and assessment will be required on these preliminary findings.

N/A

All roof framing member are to be fixed in accordance with the Fiji Building Code Standard. Roofing iron to be fixed with roofing screws throughout the entire roof on every 2nd crest. All hydraulics and electrical works to be reviewed in detail. New downpipes and shutters are to be installed. Detailed review of the structure required. Estimated damage to repair back to pre cyclone condition: $100,000

N/A

N/A

Timber doors and fixed glass windows

N/A

N/A

N/A

Ceremic tiles

CGI roof cladding nail fixed

Unknown

Unknown

N/A

N/A

N/A

N/A

No visible damage

No visible damage

No visible damage

Safe to occupy, subject to minor repair as intermediate solution required

Typical piping system

20% damage noted

No visible damage

40% damage noted

Detailed review required

Detailed review required

Timber 20% damage noted

Timber purlins

Detailed investigations recommended for the whole structure for more tolerance towards category 4 cyclones and earthquakes. Estimated cost for long term solution would be around: $500,000

Standard switches & fluorescent tube lights

60% damages noted

Build Quality

Shri Singh & Associates Limited

Minor damages to concrete walls noted

No visible damageConcrete

Concrete floor

Masonry walls

Page 30: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

1  

Cyclone Winston Damage Assessment – Saint Johns College 

Girls Hostel 

Photos – Building 1 

 

Photo 1: Front View – Walkway Roof Blown Away, Main Roof Damages, No Guttering & Downpipes 

 

Photo 2: Side View – Walkway Roof Blown Away, Minor Damages To main Building Roof 

 

 

Page 31: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

2  

Cyclone Winston Damage Assessment – Saint Johns College 

 

Photo 3: Rear View  

 

Photo 4: Internal View Showing T&G Ceiling Damage  

 

 

 

Page 32: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

3  

Cyclone Winston Damage Assessment – Saint Johns College 

 

Photo 5: Part of Side View – Showing Roof Damage  

 

Photo 6: View of Pier 

 

 

 

 

Page 33: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

4  

Cyclone Winston Damage Assessment – Saint Johns College 

Girls Hostel 

Photos – Building 2 

 

Photo 7: Front View 

 

Photo 8: Side View 

 

 

Page 34: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

5  

Cyclone Winston Damage Assessment – Saint Johns College 

 

Photo 9: Rear View 

 

Photo 10: Rear View 

 

 

 

 

Page 35: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

6  

Cyclone Winston Damage Assessment – Saint Johns College 

Girls Hostel 

Photos – Building 3 

 

Photo 11: Front View – Missing Guttering & Downpipes 

 

Photo 12: Rear View – Missing Guttering & Downpipes 

 

  

Page 36: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

7  

Cyclone Winston Damage Assessment – Saint Johns College 

 

Photo 13: Rear View ‐ Showing No Guttering & Downpipes 

 

Photo 14: Side View  

 

 

 

 

Page 37: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

8  

Cyclone Winston Damage Assessment – Saint Johns College 

Girls Hostel 

Photos – Building 4 

 

Photo 15: Side View – Showing Damaged Roof 

 

Photo 16: Rear View – Showing Damaged Roof 

 

 

Page 38: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

9  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 5 

 

Photo 17: Front View ‐ Showing Damaged Roof 

 

Photo 18: Rear View – Showing Damaged Roof 

 

Page 39: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

10  

Cyclone Winston Damage Assessment – Saint Johns College 

 

Photo 19: Showing Cracks on wall 

 

Photo 20: Internal View – Showing Damaged Truss & Ceramic Tiles 

 

 

 

 

Page 40: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

11  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 6 

 

Photo 21: Front View – Showing Missing Fascia 

   

Photo 22: Side View – Showing Damaged Roof 

 

Page 41: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

12  

Cyclone Winston Damage Assessment – Saint Johns College 

 

Photo 23: Rear View  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 42: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

13  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 7 

 

Photo 24: Front View – Showing Roof Damage 

 

Photo 25: Side View – Showing Roof Damage 

 

Page 43: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

14  

Cyclone Winston Damage Assessment – Saint Johns College 

 

Photo 26: Rear view – Showing Damaged Door 

 

Photo 27: Side View  

 

 

 

Page 44: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

15  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 8 

 

Photo 28: Front View – Showing Damaged Fascia, Missing Guttering & Downpipes 

 

Photo 29: Side View 

 

Page 45: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

16  

Cyclone Winston Damage Assessment – Levuka Public secondary School 

 

Photo 30: Rear View  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 46: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

17  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 9 

 

Photo 31: Overall Front View  

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 47: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

18  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 10 

 

Photo 32: Front View – Showing Roof Damage 

 

Photo 33: Rear View – Showing Roof Damage  

   

Page 48: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

19  

Cyclone Winston Damage Assessment – Saint Johns College 

 

Photo 34: Partial Internal View 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 49: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

20  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 11 

 

Photo 35: Front View – Showing Roof Damage 

 

Photo 36: Rear View – Showing Damaged Guttering, Downpipes & Windows 

 

Page 50: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

21  

Cyclone Winston Damage Assessment – Saint Johns College 

 

Photo 37: Internal View – Showing Damaged Ceiling 

 

Photo 38: View Through Walkway 

 

 

 

Page 51: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

22  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 12 

 

Photo 39: front View  

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 52: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

23  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 13 

 

Photo 40: Overall View  

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 53: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

24  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 14 

 

Photo 41: Front View – Showing Roof Damage 

 

Photo 42: Rear View 

 

Page 54: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

25  

Cyclone Winston Damage Assessment – Levuka Public secondary School 

 

Photo 43: Side View – showing Roof Damage  

 

Photo 44: Internal View Showing Damaged Ceiling  

 

 

 

 

Page 55: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

26  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 15 

 

Photo 45: Front View – Showing Roof Damage 

 

Photo 46: Side View  

 

Page 56: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

27  

Cyclone Winston Damage Assessment – Saint Johns College 

 

Photo 47: Rear View – Missing Guttering & Downpipes 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 57: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

28  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 16 

 

Photo 48: Front View 

 

Photo 49: Side View‐ Showing Missing Guttering & Downpipes 

 

Page 58: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

29  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 17 

 

Photo 50: Front & Side View 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 59: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

30  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 18 

 

Photo 51: Front View – Showing Roof Damage 

 

Photo 52: Side View – Showing Roof Damage 

 

Page 60: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

31  

Cyclone Winston Damage Assessment – Saint Johns College 

 

Photo 53: Ceiling Damage 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 61: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

32  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 19 

 

Photo 54: Overall View of Building 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 62: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

33  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 20 

 

Photo 55: Rear View – Roof Blown Away 

 

Photo 56: Front View – Roof Blown Away 

 

Page 63: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

34  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 21 

 

Photo 57: Front View  

 

Photo 58: Side View  

 

 

 

 

Page 64: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

35  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 22 

 

Photo 59: Front View 

  

Photo 60: Side View – Showing Minor Roof Damage, Missing Guttering & Downpipes 

 

 

 

 

 

Page 65: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

36  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 23 

 

Photo 61: Rear View 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 66: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

37  

 

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 24 

 

Photo 62: Front View 

 

Photo 63: Side View – Showing Missing Guttering & Downpipes 

 

 

 

 

Page 67: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

38  

 

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 25 

 

Photo 64: Overall View Showing Major Structural Damage 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 68: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

39  

Cyclone Winston Damage Assessment – Saint Johns College 

School Blocks 

Photos – Building 26 

 

Photo 65: Front View 

 

Photo 66: Side View 

 

 

 

 

 

Page 69: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

40  

Cyclone Winston Damage Assessment – Saint Johns College 

 

Photo 67: Side View 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 70: Shri Singh & Associates Limited...14 4 Ackland Street Vatuwaqa Ind. Sub-Dvsn P.O. Box 12798 Suva Fiji Phone Fax E-Mail SHRI SINGH & ASSOCIATES LTD Consulting Building & Civil Engineers:

41  

Cyclone Winston Damage Assessment – Saint Johns College 

Photos: General site 

 

Photo 68: Damaged Chain Link Fence with Pine Post