SHORT CIRCUIT TESTS
&
Hengelo, Netherlands
SHORT CIRCUIT TESTSConfiguration of tests:
Tested according to standard EN 50638 (2003)
Tray used:
CF105/450 (3 meters)
Span 1500
Coupled with fast coupler EDRN at 1/5th of the span
Cables:
Three 38mm outside diameter single core power cables in a trefoil formation.
They represent the most common form of cabling used and potentially the most difficult cables to test (the smaller the diameter the higher the strain on the cleats).
Cleats
Ellis Patents cleats. See details of rigs for cleat model.
SHORT CIRCUIT TESTSRig 1:
Cleat: ALPHA (aluminium)
Spacing of cleats: 600mm
Peak current: 70 kA (72.4 kA actual)
Represents a force of 13 152N on the cleats
SHORT CIRCUIT TESTSRig 2:
Cleat: VULCAN (stainless steel)
Spacing of cleats: 600mm
Peak current: 100 kA (104 kA actual)
Represents a force of 26 842N on the cleats
SHORT CIRCUIT TESTSThe lab:
3 cables are short circuited Close inspection before/after
High speed camera link up
SHORT CIRCUIT TESTS before test 50ms after short circuit
Rig 1
Rig 2
SHORT CIRCUIT TESTSMOVIE:
Movie can be viewed on youtube.com!!!
SHORT CIRCUIT TESTSRESULTS
Rig 1: 70 kA
Class 1: Water spray:
Class 2: according to EIC draft
Rig 2: 100 kA
Class 1: Water spray:
Class 2: according to EIC draft
Class 2 test is equivalent to Class 1 test after the rig has already been tested once.
9
SHORT CIRCUIT TESTS
SHORT CIRCUIT TESTS
Conclusion:
First time ever a short circuit test conducted on wire cable tray.
Confirming Cablofil as a power cable management solution.