Series Residual MCCB
Series Electronic MCCB
Series MCCB
Catalogue
Product features Application Conforming standards Operating condition Classification Types and meaning Release pattern and internal accessories code Table for quick selection of UEM5 series MCCB Main technical parameter Protection characteristics Use and Maintenance Characteristics of the residual current circuit breakers Standard of wiring Characteristic curve and Temperature compensation curve Externality and installation dimensions Internal accessories External accessories
Product feature
The casing like base and cover, which is made of the USA IDI company’s thermosetting material, has
high quality in strength and insulation, so as to ensure the breakers’ performance reliably. Advanced design of operation mechanism, rapid breaking and slight tripping force. Adopting the
“Double-way breaking system”, not only reducing the circuit breaker’s cubage, but greatly improving the short circuit breaking capacity as well.
The contact system adopts the principle of electromagnetic repulsion. Once there is fault current, the electromagnetic repulsion can separate the moving and stationary contacts rapidly, and increases the spacing, so as to achieve current limiting and improve the breaking capacity.
The circuit breakers of the same rated current frame and different breaking capacity share the absolutely identical dimensions of externality and installation, which can extremely improve the interchangeability.
The design of cassette-type accessories (including shunt release, under-voltage release, auxiliary contact and alarm contact) insures the flexibility of control function. The user can install them without opening the cover, and need not any adjustment. Since adopting design of the insulation box, the operation security has been improved.
The shunt release is applicable for a wide range of rated working voltage, and both of AC220V and AC380V, which not only makes wiring convenient, but also effectively prevents the shunt release from damage caused by mistaken voltage.
The UEM5L series residual MCCB have reliable low-voltage protection, which have insured the residual current protection to work normally even with the line voltage low to 50V. For one product, not only the residual operating current can be adjusted, but operating time’s non-delay and delay can be adjustable as well, furthermore, can open or close the residual current protection based on customers’ requirements, which have improved the operation flexibility.
The rated insulation voltage up to 800V, rated impulse withstands voltage up to 8000V, which can meet the application requirement of switch cabinet.
New and unique design (Several national patent right)
Appearance patent
◇Full series with patented appearance
Application of new material
◇The application of new polymer material
which can produce the gas for automatic arc
blowing.
Mechanism design paten
◇The self-locking mechanism after
dissembling movable contact.
◇New cover reversal mechanism
◇Double-way repulsion contact system
And etc.
(1) Application of new material (2) Double-way repulsion contact system
(3) New arc extinguish mechanism (4) Electro-Dynamic repulsion force for movable
contact and self-lock mechanism
(5) Reliable wiring nut (6) Reliable cover reversal mechanism
Polymer material to produce gas
Polymer material to produce gas
◇Rapid cut arc ◇Shorten arc burning
time ◇Increase the
electrical life ◇Increase the short
circuit breaking capacity
Adopts the principle of electromagnetic repulsion, design the fixed and movable contact as rolling type, greatly improved the short circuit breaking capacity.
◇ Rapid extinguish arc
◇ Improve the ultimate short circuit breaking capacity
◇ Movable contact repulsion mechanism: Rapid interrupt loop under short circuit, improve the short circuit breaking capacity
◇ Self-lock mechanism: effective avoid the contact re-burning under short-circuit, to improve the products reliability.
◇New wiring nut, avoid the customer cannot use.
◇Easy and quick to operate and replace.
◇Reversal cover mechanism
◇Rapid and reliable installation
◇Easy to operate and maintain
(7) Shunt-less current flow technology (8) New appearance design
Double insulation
Use double insulation to complete isolate the main circuit and control circuit, the shell of all accessories are completely isolated from main circuit, which eliminate the risk of electric shock, and protect the operator’s safety during operation and equipment inspection. In addition, the thickness and insulation distance of the insulation material in the internal electrified parts ensure the enough insulation strength, which is far exceeding the IEC standard.
Reliable operation
Circuit breaker operating handle instruct the position of movable contact to ensure safe and reliable indication (I = Closed; O = Open; -- = tripping off). Circuit breaker operating mechanism is trip-free, no related with the pressure and operating speed on handle. The release tripping will automatically disconnect the movable contact; if need to Close again, the operating handle need to be reset (via putting the handle from the middle position to the minimum limit of Open position).
Selectivity
Complete tripper series allow selecting the optional equipment protection base on the current, time, power or residual current, so as to isolate the fault zone, maximum guarantee the power supply continuity.
Convenient inspection
Once circuit breaker does not work properly, can directly check the status of internal parts and electrified parts, remove the circuit breaker cover, then can check the arc extinguishing chamber, movable contact and fixed contact, as the parts is fewer, the maintenance time can be greatly reduced, the maintenance safety has also been better ensured.。
◇Mechanical life reach up to 10000 cycles;
◇Stable and reliable line loop resistance
◇ Laser printing ◇ The printing will not
fall off under the different environment and temperature.
Application
UEM5 Series Molded Case Circuit Breakers (circuit breakers for short below) are applicable to the electrical network under the condition of AC50Hz, rated working current 10A - 800A, rated insulation voltage 800V and rated working voltage 400V or below. They have overload, short-circuit and under-voltage protection performances, among which the UEM5L series residual current circuit breakers can be used to protect human body and equipment from electric shock and residual current, as well as to prevent from fire danger due to earth-fault current which is caused by equipment insulation damage. Normally, the circuit breakers also take the role of infrequent turn-on or turn-off and infrequent motor starting-up.
The circuit breakers can be equipped with the accessories such as under-voltage release, shunt release, auxiliary contact, alarm contact, motor-driven operation mechanism, turning operation handle, etc.
This series of circuit breakers have a disconnecting function and the corresponding symbol is shown as “ ”
Conforming standards
IEC 60947-2 (GB14048.2) Low voltage switchgear and control gear: Low voltage breaker
GB14048.4 Low voltage switchgear and control gear: Electro-mechanical contactor and motor
starter
GB14048.5 Low voltage switchgear and control gear Part 1 of control circuit device and switching element: Mechanical and electric control circuit device
GB6829 Residual current operated protective devices’ general standard.
Operating condition
Ambient air temperature a) Upper limit: +40℃; b) Lower limit: -5℃; c) The average value within a 24-hour period must not exceed +35℃.
Altitude
The installation place’s altitude must not exceed 2000m.
Relative humidity
Relative humidity must not exceed 50% at the maximum ambient temperature of +40℃, but can be higher at a lower temperature; the average maximum relative humidity should be 90% at the average lowest temperature of +25℃ in the most humid month, considering the dews on product surface due to temperature change as well.
Pollution degree The pollution degree is 3, and that of the internal accessories is 2.
Installation category Ⅲ for the main circuit of the breakers, and Ⅱ for the auxiliary and control circuits.
Installation conditions The circuit breakers can be installed either vertically or horizontally. Wire connection usually follows line side on top, load side on bottom, and the magnetic intensity of installed location should not be more than 5 times that of earth magnetic field at any direction.
Classification
According to the applications a) for power distribution protection b) for motor protection
According to the number of the poles a) 3 poles b) 4 poles
According to the operation patterns a)direct operation b)motor-driven(P) c)turning handle(Z)
According to the wiring methods a) Front fix b) Back fix c) Plug in
According to the residual current operating time a) non-delay; b) delay. Type and meaning
Accessories code
Poles
Operation Pattern
Deriuative code
Moulded case circuit breaker
XIAMEN HONGMEI ELECTRONIC Co.,Ltd.
Design code
UE M 5
Rated frame current
Application code
Rated current
Breaking capacity grade
N-pole mode code
Installation pattern code
Release pattern and accessories code co Handle
● Alarm contact ■ Shunt release
Left Right ○ Auxiliary contact □ Under-voltage release
UEM5-63L UEM5-100L,M,H,R UEM5-225L,M, H,R
UEM5L-100L,M,HUEM5L-225L,M,H
UEM5-63L UEM5-100M UEM5-225M UEM5L-100M UEM5L-225M
UEM5-400L,M,H,R UEM5-800L,M,H,R
UEM5L-400L,M,H,RUEM5L-800L,M,H,R
UEM5-400M UEM5-800M UEM5L-400M UEM5L-800M
Type Pole Acce. Acce. code name
3 3 4 3 3 4
200,300 No accessories —— —— —— —— —— ——
208,308 Alarm contact
●
●
●
●
●
●
220,320 Auxiliary
contact
〇
〇
〇
〇
〇
〇
210,310 Shunt release
■
——
■
■
■
■
230,330 Low-voltage
release
□
——
□
□
□
□
228,328
Alarm contact
Auxiliary
contact
● 〇
● 〇
● 〇
● 〇
● 〇
● 〇
218,318 Alarm contact
Shunt release
● ■
——
● ■
● ■
——
● ■
238,338
Alarm contact
Under-voltage
release
● □
——
● □
● □
——
● □
248,348
Alarm contact
Auxiliary
contact
● ■ 〇
——
● ■ 〇
● ■ 〇
——
● ■ 〇
278,378
Alarm contact
Auxiliary
contact
Shunt release
● □ 〇
——
● □ 〇
● □ 〇
——
● □ 〇
240,340
Auxiliary
contact
Shunt release
〇 ■
——
〇 ■
■ 〇
——
■ 〇
270,370
Auxiliary
contact
Under-voltage
release
〇 □
——
〇 □
〇 □
——
〇 □
Note: 1. When an auxiliary contact is installed at the right side for 4p breakers, the N-pole mode only can be B or C. 2. When the UEM5L series three poles residual circuit breaker needs to install a shunt release, it needs to use special
structure
Quick selection table of UEM5 series MCCB
Derivative Code No code: Thermal & magnetic compound over-current release, without residual current protection. L: Thermal & magnetic compound over-current release, with residual current protection. Z1: intelligent over-current release, without residual current protection.
Rated current
UEM5 L 100 L P / 80 3 300 2 A H
Number of poles 3: three poles 4: four poles
Homer MCCB
The N-pole of the four-pole products has four types: A, B, C and D. Type A: N-pole without over-current release, it has been connected all along, and does not act with other three poles. Type B: N-pole without over-current release, it could act with other three poles. Type C: N-pole fixed with over-current release, it could act with other three poles. Type D: N-pole fixed with over-current release, it has been connected all along, and does not act with other three poles.
Short circuit breakers capacity L: Standard M: Relatively high breaking H: High breaking R: Conditional current
Code for release pattern and internal accessories 200- electromagnetic protection 300- compound protection Refer to the release pattern and internal accessories codes in detail
Operation Pattern No code: handle operation P: motor-driven Z: turning handle
Application code No code: power distribution protection 2: motor protection
Rated Frame Current 63 100 225 250 400 800
Installation pattern code No code: Front fix H: Back fix R: Plug in
Main technical parameter
With a modular design, we can organically combine Thermal & magnetic, electronic and residual current operated protection, to form UEM5 molded case circuit breaker, UEM5L residual current circuit breaker, UEM5Z1 electronic molded case circuit breaker.
UEM5-63 series MCCB
Rated frame current (A)
63
Type UEM5-63 Rated current In(A) 10, 16, 20, 25, 32, 40, 50, 63 Pole number 3 4 Rated insulation voltage Ui(V) AC800 Rated working voltage Ue(V) AC400 Rated ultimate short-circuit breaking capacity Icu (kA) 35
Rated service short-circuit breaking capacity Ics(kA)
AC400V
20
Rated impulse withstand voltage Uimp (V) 8000 Arc-over distance (mm) ≤50 Use category A Pollution grade 3
a 90 120 b 155 c 62
Dimension(mm) d 90 Front fix ● ● Back fix ● ●
Wiring pattern
Plug in ● ● Shunt release ● ● Under-voltage release ● ● Auxiliary contact ● ● Alarm contact ● ● Motor-driven ● ● Turning handle ● ●
Accessories
Back fix accessories ● ● Protection function Over load, short circuit over-current release device Thermal & magnetic Weight(kg) 1.3 2.2
■ UEM5-100 series MCCB
Rated frame current (A)
100
Type UEM5-100L UEM5-100M Rated current In(A) 16, 20, 25, 32, 40,
50, 63, 80, 100 16, 20, 25, 32, 40,
50, 63, 80, 100 Pole number 3 4 3 4 Rated insulation voltage Ui(V) AC800 AC800 Rated working voltage Ue(V) AC400 AC400 Rated ultimate short-circuit breaking capacity Icu (kA)
35 50
Rated service short-circuit breakincapacity Ics(kA)
AC400V
25 35
Rated impulse withstand voltage Uimp (V) 8000 8000 Arc over distance (mm) ≤50 ≤50 Use category A A Pollution grade 3 3
a 90 120 90 120 b 155 155 c 62 78
Dimension (mm) d 90 106 Front fix ● ● ● Back fix ● ● ●
Wiring pattern
Plug in ● ● ● Shunt release ● ● ● Under-voltage release ● ● ● Auxiliary contact ● ● ● Alarm contact ● ● ● Motor-driven ● ● ● Turning handle ● ● ●
Accessories
Back fix accessories ● ● ● Protection function Overload, short circuit, residual
current Overload, short circuit,
residual current over-current release device Thermal & magnetic Thermal & magnetic Weight(kg) 1.3 2.2 1.6 2.5
■ UEM5-100 series MCCB
Rated frame current (A)
100
Type UEM5-100H UEM5-100R
Rated current In(A) 16,20,25,32,40, 50,63,80,100
16,20,25,32,40,50,63,80,100
Pole number 3 4 3 4
Rated insulation voltage Ui(V) AC800 AC800
Rated working voltage Ue(V) AC400 AC400
Rated ultimate short-circuit breaking capacity Icu (kA)
70 85
Rated service short-circuit breaking capacity Ics(kA)
AC400V
50 65
Rated impulse withstand voltage Uimp (V) 8000 8000
Arc over distance (mm) ≤50 ≤50
Use category A A
Pollution grade 3 3
a 90 120 90 120
b 155 155
c 78 78 Dimension (mm)d 106 106
Front fix ● ● ● ● Back fix ● ● ● ●
Wiring pattern
Plug in ● ● ● ● Shunt release ● ● ● ● Under-voltage release ● ● ● ● Auxiliary contact ● ● ● ● Alarm contact ● ● ● ● Motor-driven ● ● ● ● Turning handle ● ● ● ●
Accessories
Back fix accessories ● ● ● ● Protection function Overload, short circuit,
residual current Overload, short circuit,
residual current over-current release device Thermal & magnetic Thermal & magnetic Weight(kg) 1.6 2.5 1.6 2.5
■ UEM5-225/250 series MCCB
Rated frame current(A)
225/250
Type UEM5-225/250L UEM5-225/250M Rated current In(A) 100,125,140,
160,180,200,225,250 100,125,140,
160,180,200,225,250 Pole number 3 3 4 Rated insulation voltage Ui(V) AC800 AC800 Rated working voltage Ue(V) AC400 AC400 Rated ultimate short-circuit breaking capacity Icu (kA)
35 50
Rated service short-circuit breaking capacity Ics(kA)
AC400V
25 35
Rated impulse withstand voltage Uimp (V) 8000 8000 Arc over distance (mm) ≤50 ≤50 Use category A A Pollution grade 3 3
a 105 105 140 b 165 165 c 62 85
Dimension (mm) d 90 118
Front fix ● ● ● Back fix ● ● ●
Wiring pattern
Plug in ● ● — Shunt release ● ● ● Under-voltage release ● ● ● Auxiliary contact ● ● ● Alarm contact ● ● ● Motor-driven ● ● ● Turning handle ● ● ●
Accessories
Back fix accessories ● ● ● Protection function Overload, short circuit Overload, short circuit over-current release device Thermal & magnetic Thermal & magnetic Weight(kg) 1.5 2.0 2.9
UEM5-225/250 series MCCB
Rated frame current(A)
225/250
Type UEM5-225/250H UEM5-225/250R Rated current In(A) 100,125,140,
160,180,200,225,250 100,125,140,
160,180,200,225,250 Pole number 3 4 3 4 Rated insulation voltage Ui(V) AC800 AC800 Rated working voltage Ue(V) AC400 AC400 Rated ultimate short-circuit breaking capacity Icu (kA)
70 85
Rated service short-circuit breaking capacity Ics(kA)
AC400V
50 65
Rated impulse withstand voltage Uimp (V) 8000 8000 Arc over distance (mm) ≤50 ≤50 Use category A A Pollution grade 3 3
a 105 140 105 140 b 165 165
c 85 85 Dimension (mm) d 118 118
Front fix ● ● ● ● Back fix ● ● ● ●
Wiring pattern
Plug in ● ● ● ● Shunt release ● ● ● ● Under-voltage release ● ● ● ● Auxiliary contact ● ● ● ● Alarm contact ● ● ● ● Motor-driven ● ● ● ● Turning handle ● ● ● ●
Accessories
Back fix accessories ● ● ● ● Protection function Overload, short circuit Overload, short circuit over-current release device Thermal & magnetic Thermal & magnetic Weight(kg) 2.0 2.9 2.0 2.9
■ UEM5-400 series MCCB
Rated frame current(A)
400
Type UEM5-400L UEM5-400M Rated current In(A) 225,250,315,350,400 225,250,315,350,400 Pole number 3 4 3 4Rated insulation voltage Ui(V) AC800 AC800 Rated working voltage Ue(V) AC400 AC400 Rated ultimate short-circuit breaking capacity Icu (kA)
50 65
Rated service short-circuit breaking capacity Ics(kA)
AC400V
35 50
Rated impulse withstand voltage Uimp (V) 8000 8000 Arc over distance (mm) ≤50 ≤50 Use category A A Pollution grade 3 3
a 140 184 140 184 b 257 257 c 99 99
Dimension (mm) d 155 155 Front fix ● ● ●Back fix ● ● ●Wiring pattern Plug in ● ● ●Shunt release ● ● ●Under-voltage release ● ● ●Auxiliary contact ● ● ●Alarm contact ● ● ●Motor-driven ● ● ●Turning handle ● ● ●
Accessories
Back fix accessories ● ● ●Protection function Overload, short circuit Overload, short
circuit over-current release device Thermal & magnetic Thermal & magnetic Weight(kg) 6.2 8 6.2 8
■ UEM5-400 series MCCB
Rated frame current(A)
400
Type UEM5-400H UEM5-400R Rated current In(A) 225,250,315,350,400 225,250,315,350,400 Pole number 3 4 3 4 Rated insulation voltage Ui(V) AC800 AC800 Rated working voltage Ue(V) AC400 AC400 Rated ultimate short-circuit breaking capacity Icu (kA)
85 100
Rated service short-circuit breaking capacity Ics(kA)
AC400V
65 75
Rated impulse withstand voltage Uimp (V) 8000 8000 Arc over distance (mm) ≤50 ≤50 Use category A A Pollution grade 3 3
a 140 184 140 184 b 257 257 c 99 99
Dimension (mm) d 155 155 Front fix ● ● ● ● Back fix ● ● ● ● Wiring pattern Plug in ● ● ● ● Shunt release ● ● ● ● Under-voltage release ● ● ● ● Auxiliary contact ● ● ● ● Alarm contact ● ● ● ● Motor-driven ● ● ● ● Turning handle ● ● ● ●
Accessories
Back fix accessories ● ● ● ● Protection function Overload, short
circuit Overload, short
circuit over-current release device Thermal & magnetic Thermal & magnetic Weight(kg) 6.2 8 6.2 8
UEM5-800 series MCCB
Rated frame current(A)
800
Type UEM5-800L UEM5-800M Rated current In(A) 400,500,630,700,800 400,500,630,700,800 Pole number 3 4 3 4 Rated insulation voltage Ui(V) AC800 AC800 Rated working voltage Ue(V) AC400 AC400 Rated ultimate short-circuit breaking capacity Icu (kA)
50 65
Rated service short-circuit breaking capacity Ics(kA)
AC400V
35 50
Rated impulse withstand voltage Uimp (V) 8000 8000 Arc over distance (mm) ≤50 ≤50 Use category A A Pollution grade 3 3
a 210 280 210 280 b 275 275 c 103 103
Dimension (mm) d 160 160
Front fix ● ● ● Back fix ● ● ●
Wiring pattern
Plug in ● ● ● Shunt release ● ● ● Under-voltage release ● ● ● Auxiliary contact ● ● ● Alarm contact ● ● ● Motor-driven ● ● ● Turning handle ● ● ●
Accessories
Back fix accessories ● ● ● Protection function Overload, short circuit Overload, short circuit over-current release device Thermal & magnetic Thermal & magnetic Weight(kg) 9.7 12.8 9.7 12.8
UEM5-800 series MCCB
壳架等级(A)
800
Type UEM5-800H UEM5-800R Rated current In(A) 400,500,630,700,800 400,500,630,700,800 Pole number 3 4 3 4 Rated insulation voltage Ui(V) AC800 AC800 Rated working voltage Ue(V) AC400 AC400 Rated ultimate short-circuit breaking capacity Icu (kA)
85 100
Rated service short-circuit breaking capacity Ics(kA)
AC400V
65 75
Rated impulse withstand voltage Uimp (V) 8000 8000 Arc over distance (mm) ≤50 ≤50 Use category A A Pollution grade 3 3
a 210 280 210 280 b 275 275 c 103 103
Dimension (mm) d 160 160 Front fix ● ● ● ● Back fix ● ● ● ● Wiring
pattern Plug in ● ● ● ●
Shunt release ● ● ● ●
Under-voltage release ● ● ● ●
Auxiliary contact ● ● ● ●
Alarm contact ● ● ● ●
Motor-driven ● ● ● ●
Turning handle ● ● ● ●
Accessories
Back fix accessories ● ● ● ● Protection function Overload, short circuit Overload, short circuit over-current release device Thermal & magnetic Thermal & magnetic Weight(kg) 9.7 12.8 9.7 12.8
UEM5L-100 residual MCCB
Rated frame current (A) 100
Type UEM5L-100M UEM5L-100H UEM5L-100R
Rated current In(A) 16,20,25,32,40,50,63,80,100
16,20,25,32,40,50,63,80,100
16,20,25,32,40,50,63,80,100
Pole number 3 4 3 4 3 4 Rated residual operating current I△n(mA)
30/100/300 adjustable
30/100/300 adjustable
30/100/300 adjustable Non-delay
5I△n max disconnect time(s) 0.04 0.04 0.04 Rated residual operating current
I△n(mA) 30/100/300 adjustable
30/100/300 adjustable
30/100/300 adjustable
2I△n max disconnect time(s) 0.5,0.8 0.5,0.8 0.5,0.8 Time delay
2I△n max. non-driven time △t(s) 0.1,0.3 0.1,0.3 0.1,0.3
Residual current indication Button Button Button Rated insulation voltage Ui(V) AC800 AC800 AC800 Rated working voltage Ue(V) AC400 AC400 AC400
Ultimate breaking capacity Icu(kA) 50 70 85 Service breaking capacity Ics(kA)
AC400V 35 50 65 Rated impulse withstand voltage Uimp (V) 8000 8000 8000
Arc over distance (mm) ≤50 ≤50 ≤50 Use category A A A
Insulation grade 3 3 3 a 90 90 120 90 120 b 155 155 155
c 78 78 78 Dimension (mm)
d 106 106 106
Front fix ● ● ● ● ● ● Back fix ● ● ● ● ● ●
Wiring pattern
Plug in ● ● ● ● ● ● Shunt release ● ● ● ● ● ● Under-voltage release ● ● ● ● ● ● Auxiliary contact ● ● ● ● ● ● Alarm contact ● ● ● ● ● ● Motor-driven ● ● ● ● ● ● Turning handle ● ● ● ● ● ●
Accessories
Back fix accessories ● ● ● ● ● ●
Protection function Overload, short circuit, residual
current
Overload, short circuit, residual
current
Overload, short circuit, residual
current over-current release device Thermal & magnetic Thermal & magnetic Thermal & magnetic
Action characteristic AC AC AC
UEM5L-225 residual MCCB
Rated frame current (A) 225
Type UEM5L-225M UEM5L-225H UEM5L-225R
Rated current In(A) 100,125,140,160, 180,200,225
100,125,140,160, 180,200,225
100,125,140,160, 180,200,225
Pole number 3 4 3 4 3 4 Rated residual operating current I△n(mA)
30/100/300 adjustable
30/100/300 adjustable
30/100/300 adjustable Non-delay
5I△n max disconnect time(s) 0.04 0.04 0.04 Rated residual operating current
I△n(mA) 30/100/300 adjustable
30/100/300 adjustable
30/100/300 adjustable
2I△n max disconnect time(s) 0.5,0.8 0.5,0.8 0.5,0.8 Time delay 2I△n max. non-driven time △t
(s) 0.1,0.3 0.1,0.3 0.1,0.3
Residual current indication Button Button Button Rated insulation voltage Ui(V) AC800 AC800 AC800 Rated working volatage Ue(V) AC400 AC400 AC400
Ultimate breaking capacity Icu(kA) 50 70 85 Service breaking capacity Ics(kA)
AC400V 35 50 65 Rated impulse withstand voltage Uimp (V) 8000 8000 8000
Arc over distance (mm) ≤50 ≤50 ≤50 Use category A A A
Insulation grade 3 3 3 a 105 140 105 140 105 140 b 165 165 165 c 85 85 85
Dimension (mm) d 118 118 118 Front fix ● ● ● ● ● ● Back fix ● ● ● ● ● ●
Wiring pattern
Plug in ● ● ● ● ● ● Shunt release ● ● ● ● ● ●
Under-voltage release ● ● ● ● ● ● Auxiliary contact ● ● ● ● ● ●
Alarm contact ● ● ● ● ● ● Motor-driven ● ● ● ● ● ●
Turning handle ● ● ● ● ● ●
Accessories
Back fix accessories ● ● ● ● ● ●
Protection function Overload, short circuit, residual
current
Overload, short circuit, residual
current
Overload, short circuit, residual
current over-current release device Thermal & magnetic Thermal & magnetic Thermal & magnetic
Action characteristic AC AC AC
UEM5L-400 residual MCCB
Rated frame current (A) 400
Type UEM5L-400M UEM5L-400H UEM5L-400R
Rated current In(A) 225,250,315,350,400 225,250,315,350,400
225,250,315,350,400
Pole number 3 4 3 4 3 4 Rated residual operating current I△n(mA)
100/300/500 adjustable
100/300/500 adjustable
100/300/500 adjustable Non-delay
5I△n max disconnect time(s) 0.04 0.04 0.04 Rated residual operating current
I△n(mA) 100/300/500
adjustable 100/300/500
adjustable 100/300/500
adjustable 2I△n max disconnect time(s) 0.7, 1.5, 2 0.7, 1.5, 2 0.7, 1.5, 2
Time delay
2I△n max. non-driven time △t(s) 0.2, 0.5, 1 0.2, 0.5, 1 0.2, 0.5, 1
Residual current indication Button Button Button Rated insulation voltage Ui(V) AC800 AC800 AC800 Rated working volatage Ue(V) AC400 AC400 AC400
Ultimate breaking capacity Icu(kA) 65 85 100 Service breaking capacity Ics(kA)
AC400V 50 65 75
Rated impulse withstand voltage Uimp (V) 8000 8000 8000 Arc over distance (mm) ≤50 ≤50 ≤50
Use category A A A Insulation grade 3 3 3
a 140 184 140 184 140 184 b 257 257 257
c 99 99 99 Dimension (mm) d 155 155 155
Front fix ● ● ● ● ● ● Back fix ● ● ● ● ● ●
Wiring pattern
Plug in ● ● ● ● ● ● Shunt release ● ● ● ● ● ●
Under-voltage release ● ● ● ● ● ● Auxiliary contact ● ● ● ● ● ●
Alarm contact ● ● ● ● ● ● Motor-driven ● ● ● ● ● ●
Turning handle ● ● ● ● ● ●
Accessories
Back fix accessories ● ● ● ● ● ●
Protection function Overload, short circuit, residual
current
Overload, short circuit, residual
current
Overload, short circuit, residual
current over-current release device Thermal & magnetic Thermal & magnetic Thermal & magnetic
Action characteristic AC AC AC
UEM5L-800 residual MCCB
Rated frame current (A) 800
Type UEM5L-800M UEM5L-800H UEM5L-800R Rated current In(A) 400,500,630,700,800 400,500,630,700,800 400,500,630,700,800
Pole number 3 4 3 4 3 4 Rated residual operating current I△n(mA)
300/500/1000 adjustable
300/500/1000 adjustable
300/500/1000 adjustable Non-dela
5I△n max disconnect time(s) 0.04 0.04 0.04 Rated residual operating current
I△n(mA) 300/500/1000
adjustable 300/500/1000
adjustable 300/500/1000
adjustable 2I△n max disconnect time(s) 0.7, 1.5, 2 0.7, 1.5, 2 0.7, 1.5, 2
Time delay 2I△n max. non-driven time △t
(s) 0.2, 0.5, 1 0.2, 0.5, 1 0.2, 0.5, 1
Residual current indication Button Button Button Rated insulation voltage Ui(V) AC800 AC800 AC800 Rated working volatage Ue(V) AC400 AC400 AC400
Ultimate breaking capacity Icu(kA) 65 85 100 Service breaking capacity Ics(kA)
AC400V 50 65 75
Rated impulse withstand voltage Uimp (V) 8000 8000 8000 Arc over distance (mm) ≤50 ≤50 ≤50
Use category A A A Insulation grade 3 3 3
a 210 280 210 280 210 280 b 275 275 275
c 103 103 103 Dimension (mm) d 160 160 160
Front fix ● ● ● ● ● ● Back fix ● ● ● ● ● ●
Wiring pattern
Plug in *(700A) — *(700A) — *(700A) — Shunt release ● ● ● ● ● ●
Under-voltage release ● ● ● ● ● ● Auxiliary contact ● ● ● ● ● ●
Alarm contact ● ● ● ● ● ● Motor-driven ● ● ● ● ● ●
Turning handle ● ● ● ● ● ●
Accessories
Back fix accessories ● ● ● ● ● ●
Protection function Overload, short circuit, residual current
Overload, short circuit, residual
current
Overload, short circuit, residual
current over-current release device Thermal & magnetic Thermal & magnetic Thermal & magnetic
Action characteristic AC AC AC
UEM5Z1 electronic MCCB
Rated frame current (A)
100 225 400 800
Type M H R M H R M H R M H R
Rated current In(A) 16-32, adjustable 40-100 adjustable
100-225 adjustable
200-400 adjustable 400-800 adjustable
Pole number 3 3 3 / 4 3 / 4
Rated insulation voltage Ui(V) AC800 AC800 AC800 AC800
Rated working voltage Ue(V) AC400 AC400 AC400 AC400
Rated impulse withstand voltage Uimp (V) 8000 8000 8000 8000
Arc over distance (mm) ≤50 ≤50 ≤50 ≤50
Use category A A B B
Insulation grade 3 3 3 3
Ultimate breaking capacity Icu(kA) 50 70 85 50 70 85 65 85 100 65 85 100
Service breaking capacity Ics(kA)
AC400V 35 50 65 35 50 65 50 65 75 50 65 75
Rated service short-circuit breaking capacity Ics(kA)
- - 5 10
a 90 105 140 / 184 210 / 280
b 155 165 257 275
c 80 91 97 101
Dimension(mm)
d 106 118 155 158
Front fix ● ● ● ●
Back fix ● ● ● ● Wiring Plug in ● ● ● ●
Shunt release ● ● ● ●
Under-voltage release ● ● ● ●
Auxiliary contact ● ● ● ●
Alarm contact ● ● ● ●
Motor-driven ● ● ● ●
Turning handle ● ● ● ●
Accessories Back fix accessories ● ● ● ●
Protection function Over load, short
circuit delay, short circuit
instantaneous
Over load, short circuit delay, short circuit
instantaneous
Over load, short circuit delay, short circuit
instantaneous
Over load, short circuit delay, short
circuit instantaneous
Over-current release device Electronic & adjustable
Electronic & adjustable
Electronic & adjustable
Electronic & adjustable
Weight(kg) 1.6/2.5 2.0/2.9 5.7/7.5 9.5 / 12.5
Protection characteristic
Inverse time-delay over-current protection characteristics of UEM5 and UEM5L series circuit breakers a) For power distribution UEM5 and UEM5L series circuit breakers protection characteristics for power distribution(basic temperature+40℃)
Conventional time Test current Setting current In≤63A In>63A
Initial state
conventional non-tripping current
1.05 ≥1h ≥2h Cold state
conventional tripping 1.30 <1h <2h Hot state Returnable
Returnable current 3.0 5s 8s
Cold state
b) For motor protection UEM5 and UEM5L series circuit breakers protection characteristics for motor protection(basic temperature+40℃)
Conventional time Test current Setting current In≤225A In>255A
Initial state
conventional non-tripping current
1.0 ≥2h Cold state
1.2 ≤2h Hot state 1.5 ≤4min ≤8min Hot state
conventional tripping current
7.2 4s<T≤10s 6s<T≤20s Cold state
The breaking characteristics of over-current releases on the condition of short-circuit The breaking characteristics of UEM5 and UEM5L series circuit breakers’ over-current releases on the condition of short-circuit. 1) For power distribution protection circuit breakers, the short circuit protection setting current is 10In; 2) For motor protection circuit breakers, the short circuit protection setting current is 12In; The setting current described upside has precision of ±20%.
Operation performance of circuit breaker
Number of Rated frame current (A)
Number of operation cycles per hour energized Un-energized Total number
63 120 8000 20000 28000
100 120 8000 20000 28000
225 120 8000 20000 28000
400 60 7500 10000 17500
800 60 7500 10000 17500
Use and maintenance The circuit breaker’s protection characteristics of long time delay and instantaneous short circuit have
been set by the manufacturer, and it could not be adjusted arbitrarily. The rated residual working current
and residual current working time can be adjusted by the users according to actual needs.
When the main circuit is energized, the circuit breaker should be off if the “test” button is pushed down.
This test can only prove that the residual current protection function is in normal state, but cannot show
the concrete residual operating current value and time.
For the circuit breaker equipped with under-voltage release, the under-voltage release should be energized
in advance before the circuit breaker is switched on. Otherwise, the circuit breaker would be damaged!
The voltage withstand test and the insulation resistance test can be only made between polarity and ground,
but not between polarities, because of the electronic elements in the products.
The power side and the load side are showed on the outside of the residual current circuit breakers, and the
wires must be fixed according to regulations. The circuit breakers usually cannot be fed inversely.
No. “1, 3, 5” stands for the line side, “2, 4, 6” stands for the load side, “N” stands for the neutral.
The residual current protection function should be tested regularly (for example, one time per month) by
pushing down the test button. It is not permitted to directly connect the line with the neutral to do action
tests
Wiring standard
Table for Cross-sectional area of wiring cable and corresponding rated current
Rated current (A)
10 16
20
25
3240
50
63
80
100125
140
160
180
200
225
250 315
350
400
Cross-sectional area of
wire(mm2)
1.5 2.5 4 6 10 16 25 35 50 70 95 120 185 240
Cable Copper bar Rated Current(A) Number Area of wire
(mm2) Number Dimension(mm×mm)
500 2 150 2 30x5630 2 185 2 40x5
700 2 240 2 50x5
Characteristic of MCCB with residual current The work principle of residual current operated circuit breakers:
When the protected circuit (which is wired behind the residual current operated circuit breakers) occurs residual current or electric shock, as long as the value of residual current or electric shock current reaches the residual current operation value, the zero sequence current transformer’s secondary winding will send a voltage signal, which is examined by IC circuit, magnified and output, and enable the residual current release work to rapidly break the fault circuit off (according the setting requirement, the time-delay residual current operated circuit breakers breaks the fault circuit off after a certain delay time), so as to protect from residual current or electric shock.
Warning: the residual current operated circuit breakers cannot protect from electric shock danger
when human body touches both phase lines.
■ UEM5L series residual MCCB protection action time: 2I△n Limiting non-
operating time
Residual current I△n 2I△n 5I△n 10I△n
Non-delay — Max. disconnect
time(s)
0.3 0.15 0.04 0.04
0.1s 0.6 0.5 0.4 —
0.2s 0.8 0.7 0.5 —
0.3s 1 0.8 0.6 —
0.5s 2 1.5 1 —
Delay
1.0s
Max. disconnect time (s)
2.5 2 1.8 —
Note: If special residual operating current is needed, please note while making orders or note in the design diagram.
■General setting value of UEM5L series residual MCCB:
I△n Max. disconnect time Type Rated residual current setting value Non-delay Delay
UEM5L-100 100mA 0.3s —
UEM5L-225 100mA 0.3s —
UEM5L-400 300mA — 2s
UEM5L-800 500mA — 2.5s
Notices for operation of the residual current operated circuit breakers
The acting characteristic of residual current should be selected according to the standard of residual current protection installation and application, GB13955-92.
a) For protection for outlet loop at the end of circuit and hand-hold mobile electric apparatus, select the no time-delay circuit breakers of I△n 30mA.
b) The rated residual operating current (I△n) of integration power distribution protection circuit breaker which is not for end protection, is usually selected according to one thousandth of the circuit working current. For breaking time, the time-delay type should be selected first.
c) For three-phase and four-line load circuit, select the four-pole circuit breaker.
Notices for wiring::
a) The circuit breaker is applicable for TT, TN-C-S and TN-S system of neutral earthed conductor. In
these conditions, it is strictly prohibited to connect PEN line or PE line to the N pole on the circuit
breaker’s load side, so as to prevent from unwanted operation or refuse operation.
b) In TN-C system, it should be considered to select residual current operating circuit breakers with N
pole constantly switched on. The PEN line can not break off, so the PE line of load cover should be
connected on the incoming end of the residual current operating circuit breakers, so as to prevent from
refuse operation as residual current can not be detected. For protect N line from over load, the residual
current operating circuit breakers with over current release on the N pole can be considered.
c) In IT system, usually it is suitable to install the RCCB. It is because that the system neutral point is
not earthed, and the residual current operating circuit breakers fail to operate with small fault residual
current. But in some location, failure insulation of circuit or too long routing can enlarge the
distributed capacitance in the networks. In this situation, the residual current operating circuit
breakers should be installed.
d) The neighbor outlet ends of circuitries with residual current protection should be connected with zero
lines in each, but cannot share one line.
For the UEM5L series residual current operating circuit breakers, no matter three-pole or four-pole,
the electronic circuits of the residual current release are both power-supplied by A,B and C 3 phases
(380V).
The imbalance in load will not affect the normal operation of the residual current operating circuit
breakers.
The test button can be pushed down to examine whether the circuit breaker works, but it is not
specially used for breaking operation. So do not push it frequently to prevent the test resistance from
being burnt.
If a newly installed circuit breaker is “unwanted tripping”, please examine whether the outlet end of
circuit breaker has been earthed repeatedly or connected wrongly.
For the other notes, please refer to the part of “Use and Maintenance”.
Intelligent electronic module specification
Protection category(1;2;3;4;5) 1:LI: Overload long delay + short circuit instantaneous protection; 2:LSI: Overload long delay + short circuit time delay + short circuit instantaneous protection; 3:LSIP: Overload long delay +short circuit short delay + short circuit instantaneous + pre-alarm protection; 4:LSIG: Overload long delay + short circuit short delay + short circuit instantaneous + ground fault
protection; 5:LCD: Intelligent LCD control,
Specification (1)Protection catagary 1 LI :
■ Two sect current protection (two adjustable values) Overload long time delay protection; Short circuit instantaneous protection;
■ The protection range: Long time delay protection: Ir =(0.4~1.0)In Short circuit instantaneous protection Ii =(3~12)In + OFF
■ Nameplate
■ Protection curve
(2)Protection catagary 2 LSI: ■ Three sect current protection (three adjustable values)
Overload (long time delay) protection (adjustable current, fixed time) Short circuit short time delay protection (adjustable current, fixed time) Short circuit instantaneous protection (adjustable current)
■ The protection range: Overload (long time delay) protection:Ir =(0.4~1.0)In Short circuit short time delay protection:Isd =(2~12)Ir Short circuit instantaneous protection:Ii =(3~12)In+OFF
■ Nameplate
(3)Protection catagary 3 LSIP:
■ Three sects current protection (6 adjustable values) Overload (long time delay) protection (adjustable current and time) Short circuit short time delay protection (adjustable current and time) Short circuit instantaneous protection (adjustable current) Pre-alarm protection (adjustable current)
■ The protection range: Overload (long time delay) protection:Ir =(0.4~1.0)In Overload long delay time protection:Tr= 12S、60S、80S、100S +OFF Short circuit short time delay protection:Isd = (2~10)Ir Short circuit short delay time protection:Tsd= 0.06S、0.1S、0.2S、0.3S Short circuit instantaneous protection:Ii = (3~12)In+OFF Pre-alarm protection:Ip=(0.7~1.0)Ir
■ Nameplate
■ Protection curve
(4)Protection catagary 4 LSIG: ■ Three sects current protection+ground fault protction(6 adjustable values) Notice: Four sects protection.
Overload (long time delay) protection (adjustable current and time) Short circuit short time delay protection (adjustable current and time) Short circuit instantaneous protection (adjustable current) Ground fault protction (adjustable current)
■ The protection range: Overload (long time delay) protection:Ir =(0.4~1.0)In Overload long delay time protection:Tr= 12S、60S、80S、100S+ OFF Short circuit short time delay protection:Isd =(2~10)Ir Short circuit short delay time protection:Tsd= 0.06S、0.1S、0.2S、0.3S Short circuit instantaneous protection:Ii =(3~12)In + OFF Ground fault protction:Ig=(0.2~1.0)In + OFF
■ Nameplate
■ Protection curve:
(5)Protection catagary 5 LCD:
1. Protection function Overload pre-alarm Overload long time delay Short circuit short time delay Short circuit instantaneous Unbalance protection N shunt protection Ground fault protection
2. Auxiliary function Test function(Software/hard ware) Thermal memory function Protection parameter by button setting Fault memory function LCD indication function Pin for paramter inspection or setting Chinese and English operation interface
3. Controller structure and operation
Controller use the button setting, easy operation. The protection setting of current and time for controller should be operated by professional
personnel, save the setting by OK button.
1. External power DC12V interface; 2. LCD; 3. Up button; 4. Down button; 5. Exit; 6. Ok
4. Extension new function
Control pannel
Communication function
Fault memory and check
Motor shunt break inspection and
protection
LCD current indication parameter
setting
UVT & OVT function
Long time delay thermal memory protection
Short time delay thermal memory protection
Intelligent electronic module extension new function
Fire alarm function
Temperature protection function
Dual passive contact output
5. Extension new function
(1)Communication function Controller with RS485 communication interface, support MODBUS-RTU bus protocol, through the
communication protocol conversion module for easy access protocol networks and other distribution automation network, with "remote control, remote transfer, remote telecommunications and telemetry" function, which can realize the long-distance circuit breaker remote operation function and achieve the long-distance power dispatch purpose.
(2)Overload thermal memory function (external power) The thermal memory function of controller can be selected by user; the factory default setting is OFF. The energy of controller thermal memory can be released within 30 minutes.
(3)Short circuit (short time delay) thermal memory function (external power)
Controller (short time delay) short-circuit current protection thermal memory function can be selected by user, the factory default setting is OFF, controller (short time delay) short circuit thermal memory energy can be released within 15 minutes. Note: The thermal memory function requires external power supply (DC12V/2W).ku
(4)External residual current protection function--3P added selectable function. When the detected residual current> Ig, the circuit breaker trip.
(5)Temperature protection function When the ambient temperature over 105 ℃, the circuit breaker trip.
(6)Dual passive contact output Controller has four optical signal output, DO1 and DO2 optical signal can be programmed to function as output, DO3 is "sub-gate signal", DO4 is "switch on signal."
(7)Fault memory function (LCD type)
Controller can memorize the latest 100 times of fault types, such as: a, fault trip time; b, the fault shunt and the maximum fault current records; c, long time delay action value; d, long time delay action time;
Characteristic curve and temperature compensation curve
■ UEM5-100C,L,M,H; UEM5L-100L,M,H
■ UEM5-225C,L,M,H; UEM5L-225L,M,H
■ UEM5-400C,L,M,H; UEM5L-400L,M,H
■ UEM5-800C,L,M,H; UEM5L-800L,M,H
Externality and installation dimension
Back fix
Front fix
Plug in
Plug in
Front fix
Back fix
Front fix
Back fix
Plug in
Front fix
Back fix
Plug in
Front fix
Back fix
Plug in
Front fix
Back fix
Plug in
Front fix
Back fix
Plug in
Internal accessories
Under-voltage release The under-voltage release is used for under-voltage protection of circuit and power
equipment. Rated working voltage: AC50Hz, 220V or 380V. With the working voltage of 35%-70% of the rated voltage, the under-voltage release can
make the circuit breaker trip reliably. With the working voltage less than 35% of the rated voltage, the under-voltage release can
prevent the circuit breaker from being switched on. With the working voltage of 85%-110% of the rated voltage, the under-voltage release can
ensure the circuit breaker to work normally. (Note: only after the under-voltage release is energized with the rated working voltage, the
circuit breaker can be switched on. Otherwise, the circuit breaker would be damaged.)
Appearance Wiring
Shunt release The shunt release is used for long distance control of circuit breaker switched off. Rated working voltage: AC50Hz, 220V or 380V; DC 24V or 110V. The shunt release should make the breaker trip reliably when the operation voltage is 70%-
110% of the rated control voltage.
Appearance Wiring
Auxiliary contact and alarm contact The auxiliary contact is used for auto control of circuit breaker’s control loop. For example
the signal of circuit breaker switched on and off. The alarm contact is used for alarm of “free release”, which is caused by over-load and short
circuit of circuit breaker’s load current, and under-voltage fault of circuit and equipment. Rated working voltage: AC50Hz, 220V or 380V; DC 220V.
Input
Input
Auxiliary contact wiring diagram
Breaker position Auxiliary contact Wiring of one group One group:
Rated frame current≤225A
Position “On” Two groups:
Position “Off”
Rated frame currentt≥400A
One group:
Rated frame current≤225A
Two groups:
Rated frame currentt≥400A
Switch off Switch on
Alarm contact wiring
Breaker position Alarm contact Wiring
Position “on” or “off”
Position “free release”
Technical parameter of auxiliary contact and alarm contact
Rated current Ie(A)Type Frame current Conventional thermal current Ith(A) AC380V DC220V
≤225A 3 0.30 0.15 Auxiliary contact ≥400A 3 0.40 0.15
Alarm contact 63A~800A 3 0.30 0.15
External accessories
Motor-driven operation mechanism
Mounted in the circuit breakers, the motor-driven operation mechanism is used for long-distance control of circuit breakers’ close and open. There are three types: DC1, DC2 and DC3. DC1--adopting motor-driven, and applicable to circuit breakers with rated frame current 400A to 800A. DC2--adopting electromagnet-driven, and applicable to circuit breakers with rated frame current 250A or below. DC3- adopting advanced switch power technology and mini type permanent magnetic motor-driven, low working current, and applicable to both AC and DC circuit and circuit breakers with rated frame current 63A-800A.
Dimension (mm) Type P/N Fitting
breaker Rated control voltage (A)
Action current (A) A B H H
DC2-63/UEM5 UEM5-63 ≤5 76 120 85 146DC2-100/UEM5 UEM5-100 ≤7 91 145 85 146
DC2
DC2-225/UEM5 UEM5-225/250
AC220V/AC380V
≤8.5 105 156 89 150DC3-63/UEM5 UEM5-63 ≤0.5 90 132 89 150DC3-100/UEM5 UEM5-100 ≤0.5 90 152 90 151
DC3
C3DC3-225/UEM5 UEM5-225/250 ≤0.5 90 146 92 153DC3-400/UEM5 UEM5-400 ≤2 130 219 151 248DC1/DC3
DC3-630/UEM5 UEM5-800
DC220V (ApplicableDC3) AC220V/AC380V
≤2 130 268 153 250
DC1 外观图 DC1 电操机构外形及接线图
DC2 appearance DC2 externality and wiring
DC3 appearance DC3 externality and wiring
Turning handle operation mechanism The operation mechanism is mounted on the circuit breaker’s cover and applicable to the circuit breaker installed on electric control cubicle. It can make the circuit breaker close, open and re-cramp by turning the handle and has a guide location function to prevent the handle from fracture caused by misoperation or violent operation. Turning handle operation mechanism can divide to: SC1—centre operation mechanism SC2—eccentricity operation mechanism Two types of handle are available for the same mechanism: F-square handle; Y-round handle.
Dimension (mm) Type Fitting breaker A B C D H
SC1-(Y,F)-63/UEM5 UEM5-63 25 111 — — 44.5 SC1-(Y,F)-100/UEM5 UEM5-100 30 132 — — 44.5 SC1-(Y,F)-225/UEM5 UEM5-225/250 35 126 — — 45 SC1-(Y,F)-400/UEM5 UEM5-400 128 195 — — 76 SC1-(Y,F)-630/UEM5 UEM5-800 198 242 — — 76 SC2-(Y,F)-63/UEM5 UEM5-63 25 111 0 35 15
SC2-(Y,F)-100/UEM5 UEM5-100 30 132 11 35 15 SC2-(Y,F)-225/UEM5 UEM5-225/250 35 126 11 35 15 SC2-(Y,F)-400/UEM5 UEM5-400 128 187 15 60 30 SC2-(Y,F)-630/UEM5 UEM5-800 198 242 15 60 30
SC1 appearance SC1 externality
SC2 appearance SC2 externality
Externality of type ”F” square handle and the aperture dimension on the panel sheet (unit: mm)
Externality of type ”Y” round handle and the aperture dimension on the panel sheet (unit: mm)
Note: 1). The short handles are used for breakers with rated frame current 225A or below, and the long
handles are used for breakers with rated frame current 400A or above. 2). The breakers with rated frame current 225A or below should be equipped with 8 x 8 square axes.
The breakers with rated frame current 400A or above should be equipped with 10 x 10 square axes .both square axes are 150mm long.