selv constant current control gear, 1-channel zitares qcs€¦ · zitares qcs selv constant current...

4
ZITARES QCS SELV constant current control gear, 1-channel Errors reserved. We reserve the right to modify in the interest of progress. 1/4 2015.12.10 www.BAGelectronics.com ECG versions Model Order number Output current Total power output QCS150-25QI-11/220-240 10134612 1 x 500 mA 14 ... 25 W QCS170-35QI-11/220-240 10134613 1 x 700 mA 23 ... 35 W QCS190-40QI-11/220-240 10134614 1 x 900 mA 27 ... 40 W QCS1105-40QI-11/220-240 10134615 1 x 1050 mA 32 ... 42 W Performance features • Non-dimmable 1-channel ECG for constant current operation of LED modules • SELV output voltage ≤ 60 VDC for simplified luminaire construction • Very high efficiency of up to 88 % at maximum output load • ECG extensively protected against abnormal operating conditions at the output, e.g. short-circuit, open circuit or overload • Certified as thermally protected ECG • Conformance with international regulations, regarding safety and operation, electromagnetic compatibility and immunity to interference • Nominal service lifetime: 30,000 h with failure rate ≤ 10 % and operation at t c = t c,max • Nominal service lifetime: 50,000 h with failure rate ≤ 10 % and operation at t c = t c,max - 10 K Applications Industry Office & Commercial Shop Markings

Upload: others

Post on 17-Aug-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SELV constant current control gear, 1-channel ZITARES QCS€¦ · ZITARES QCS SELV constant current control gear, 1-channel 2015.12.10 2/4 Errors reserved. We reserve the right to

ZITARES QCSSELV constant current control gear, 1-channel

Errors reserved.

We reserve the right to modify in the interest of progress. 1/42015.12.10

www.BAGelectronics.com

ECG versionsModel Order number Output current Total power outputQCS150-25QI-11/220-240 10134612 1 x 500 mA 14 ... 25 WQCS170-35QI-11/220-240 10134613 1 x 700 mA 23 ... 35 WQCS190-40QI-11/220-240 10134614 1 x 900 mA 27 ... 40 WQCS1105-40QI-11/220-240 10134615 1 x 1050 mA 32 ... 42 W

Performance features

• Non-dimmable 1-channel ECG for constant currentoperation of LED modules

• SELV output voltage ≤ 60 VDC for simplified luminaireconstruction

• Very high efficiency of up to 88 % at maximum outputload

• ECG extensively protected against abnormal operatingconditions at the output, e.g. short-circuit, open circuit oroverload

• Certified as thermally protected ECG• Conformance with international regulations, regarding

safety and operation, electromagnetic compatibility andimmunity to interference

• Nominal service lifetime: 30,000 h with failure rate ≤ 10 %and operation at tc = tc,max

• Nominal service lifetime: 50,000 h with failure rate ≤ 10 %and operation at tc = tc,max - 10 K

Applications

Industry Office &Commercial

Shop

Markings

Page 2: SELV constant current control gear, 1-channel ZITARES QCS€¦ · ZITARES QCS SELV constant current control gear, 1-channel 2015.12.10 2/4 Errors reserved. We reserve the right to

ZITARES QCSSELV constant current control gear, 1-channel

2015.12.10

www.BAGelectronics.com 2/4Errors reserved.

We reserve the right to modify in the interest of progress.

General technical data

Mains voltage supplyRated voltage range 220 ... 240 [V]Voltage range continuous AC 198 ... 264 [V]Rated frequency 50 ... 60 [Hz]Protection against voltage peaksVoltage peaks L - N 1 kVStarting timeStarting time max. 1 sTotal harmonic disortionTotal harmonic distortion (max.) 20 %, at 100 % loadOutput dataOutput current tolerance +/- 10 %Max. ripple output current (high frequency) +/- 1 %Max. ripple output current (low frequency) +/- 25 %Max. wire length to LED-module 2 mGalvanic separation to mains input yes, test voltage 3.75 kVProtection functions output sideOverload operation yes, limitation of the output voltageOpen-circuit operation yes; output voltage max. 60 VDC (SELV)TerminalsType 90° push-in terminal with keyWire cross section 0,5 ... 1,5 mm²Wire stripping length 7,5 ... 8,5 mmThermally protected deviceMax. case temperature (acc to EN 61347-2-13/C5e) 110 ° CDegree of protectionProtection rating IP 20

Page 3: SELV constant current control gear, 1-channel ZITARES QCS€¦ · ZITARES QCS SELV constant current control gear, 1-channel 2015.12.10 2/4 Errors reserved. We reserve the right to

ZITARES QCSSELV constant current control gear, 1-channel

Errors reserved.

We reserve the right to modify in the interest of progress. 3/42015.12.10

www.BAGelectronics.com

Operation temperatureModel Ambient (ta) Case (tc,max)QCS150-25QI... -20 ... 50 °C 75 °CQCS170-35QI... -20 ... 50 °C 75 °CQCS190-40QI... -20 ... 50 °C 75 °CQCS1105-40QI... -20 ... 50 °C 75 °C

LifetimeLifetimeOperation at tc = tc max 30,000 h, failure rate ≤ 10 %Operation at tc = tc max -10 K 50,000 h, failure rate ≤ 10 %

Circuit breaker/starting currentNumber of ECGs on single-pole power circuit breakers(CB)

Model typ.lpeak/Δt

CB-Typ

10 A 16 A 20 A 25 A

B 22 35 43 54QCS150-25QI... 13 A / 400 µsC 37 58 72 90B 17 27 34 43QCS170-35QI... 14 A / 400 µsC 28 45 57 71B 16 25 32 40QCS190-40QI... 14 A / 400 µsC 26 43 55 68B 16 25 32 40QCS1105-40QI... 14 A / 400 µsC 26 43 55 68

• All specifications with Umains= 230 VAC, mains impedance = 1Ω

• With multi-pole power circuit breakers the max. number isreduced by 20 %.

• With power circuit breakers from different manufacturers themax. number may deviate; observe manufacturer specifications.

• For lighting groups the use of C circuit-breakers is generallyrecommended.

Typical sequence of current-time curves with switch-on

I[A]Ipeak

½ x Ipeak

∆t t

Operating dataModel Input current Input power Power factor ECG efficiency Output current

(default)Output voltage Total power

outputA W % mA VDC W

QCS150-25QI... 0,13 30 0,95 88 % 1 x 500 28 ... 50 14 ... 25QCS170-35QI... 0,18 41 0,95 88 % 1 x 700 32 ... 50 23 ... 35QCS190-40QI... 0,21 48 0,95 88 % 1 x 900 30 ... 45 27 ... 40QCS1105-40QI... 0,21 49 0,95 88 % 1 x 1050 30 ... 40 32 ... 42

- All specifications with 230 VAC nominal operation and 100 % load

ECG connection diagrams output

+CH1

LN

Page 4: SELV constant current control gear, 1-channel ZITARES QCS€¦ · ZITARES QCS SELV constant current control gear, 1-channel 2015.12.10 2/4 Errors reserved. We reserve the right to

ZITARES QCSSELV constant current control gear, 1-channel

2015.12.10

www.BAGelectronics.com 4/4Errors reserved.

We reserve the right to modify in the interest of progress.

ECG dimensions

Model X XM Y YM Z

mm mm mm mm mmQCS150-25QI... 135 93,5 67 57,5 30QCS170-35QI... 135 93,5 67 57,5 30QCS190-40QI... 135 93,5 67 57,5 30QCS1105-40QI... 135 93,5 67 57,5 30

X

XM

Y YM

Z

Logistical data

Model Order number EAN (onepiece)

Weight ECG PU DimensionsPU

Weight PU

kg St. mm kgQCS150-25QI-11/220-240 10134612 4046189035750 0,127 60 422 x 352 x 147 8,10QCS170-35QI-11/220-240 10134613 4046189035767 0,144 60 422 x 352 x 147 9,10QCS190-40QI-11/220-240 10134614 4046189035774 0,154 60 422 x 352 x 147 9,70QCS1105-40QI-11/220-240 10134615 4046189035781 0,154 60 422 x 352 x 147 9,70

Conformity to standards

EN 61347-1 Lamp controlgear - Part 1: General and safety requirementsEN 61347-2-13 Lamp controlgear - Part 2-13: Particular requirements for d.c. or a.c. supplied electronic control gear for LED

modulesEN 62384 D.C. or A.C. supplied electronic control gear for LED modules - Performance requirementsEN 55015 Limits and methods of measurement of radio disturbance characteristics of electrical lighting and similar equipmentEN 61547 Equipment for general lighting purposes - EMC immunity requirementsIEC 60068-2-6 Environmental testing: Tests – Test Fc: Vibration (sinusoidal)IEC 60068-2-27 Environmental testing: Tests – Test Ea and guidance: ShockIEC 60068-2-29 Basic environmental testing procedures - Part 2: Tests; test Eb and guidance: Bump

BAG electronics GmbHKleinbahnstraße 27 • 59759 Arnsberg/Germany · [email protected] • Telefon +49 2932 9000-9800 • Fax +49 2932 9000-9796