American Standard
Selectronic 605XRCTRemote Control
Operation Manual
2013 firmware_2013-0903
OPERATION: The remote programmer has 4 keys:
“Enter” or validate
“Cancel”
“Scroll UP”
“Scroll Down”The ‘Down’ Key is also used to turn “ON” the remote programmer. After not being used for 2 minutes, the programmer automatically turns itself off.
Mini-USB Port
Transmission Area
2
When using the programmer, the sensor will begin blinking for approximately 5 seconds after the “enter” key is pressed and the display shows “TRANSMISSION OK”. While it is blinking move your finger to within 1 inch of the sensor (nearly covering it). When the light stops blinking and stays on steady, remove your finger and, with the palm of your hand facing the sensor, move your hand to the distance to be set. When the sensor starts to blink again, move you hand away from the detection area. The flashing will stop and the sensor will now be programmed with the new range setting.
The Programmer will now display BACKUP FUNCTION. You can program the next sensor(s) with the same modes and functions by pointing the programmer at the sensor and pressing the “enter” key. The programmer will remember the programmed settings (other than the manually set range/distance) for approximately 3.5 minutes before turning off.
NOTE: See “Product Settings & Specifications Chart”
Adjusting The Range (Detection Distance)
*** ONLY DONE AFTER SELECTING ALL OTHER MODE SETTINGS ***
3
ON
MENU 1
CLEANING
MENU 2
DISINFECTION
Press to activate the menus
Press to turn on the programmer
DISINFECTION
DURATION :1 min
Press up or down to adjust time
Align the programmer with the sensor and press to transmit the signal to sensor to activate the DISINFECTION cycle for the selected period of time
MENU 3
DIAGNOSTIC
Align the programmer with the sensor and press to transmit the signal to sensor to activate the DIAGNOSTIC feature. NOTE: Use the up and down arrow keys to scroll through the current settings
Press to go to MENU 2
Press to go to MENU 3
Press to go to MENU 4
To MENU 4
Start
Cleaning
Disinfection
Diagnostics
TIP: Cleaning – Use this mode to disable the sensor for 1 minute. This is sometimes used by the cleaning crew to keep the faucet “off” while cleaning the fitting and or fixture.
TIP: Disinfection – This is typically used in healthcare facilities that conduct periodic high temperature or high anti-bacterial chemical purging of the water lines. The maintenance person should activate this mode and stay present to avoid any users from exposure to the purged water. This ‘mode’ can be activated while in any function (handwash faucet, urinal flush valve, etc..). The duration (run time) can be programmed from 1 minute to 120 minutes in 1 minute intervals.
TIP: Diagnostics – Use this mode to determine the settings of the faucet or flush valve. NOTE: this feature will only work with products made 2008 or newer.
CELEC V 0.7
AMSTDThis display identifies the software version
Press to start the cleaning mode
4
MENU 4
PARAMETER
SENSOR
2013 VERSION
SENSOR
2008 VERSION
From MENU 3
MENU 5
PARTIAL COUNT
MENU 6
TOTAL COUNT
NOTE: Not all features available with this version
From this menu, scroll down to the specific mode you want to program:
Parameter
Language
Backlight
• Hand-Wash
• Metering
• On/OFF
• Urinal
• LF Urinal + PF **(NOT USED)**
• Flushometer
• Kitchen **(NOT USED)**
• DB Toilet
TIP: Sensor Version • Select 2013 Version for all
Selectronic products manufactured starting in July 2013.
• Select 2008 Version for all Selectronic products manufactured from 2008 to June 2013.
• Call for Assistance for products manufactured from 2003 through 2007.
• NOTE: Versions 2008 & 2013 will have a label on the sensor terminal to identify the version
SENSOR
2003 VERSION
NOTE: Not all features available with this version
Align the programmer with the sensor and press to transmit the signal to sensor to activate the PARTIAL COUNT feature. (This is the number of activations since the last time the count was checked)
Align the programmer with the sensor and press to transmit the signal to sensor to activate the TOTAL COUNT feature. (This is the number of activations since the sensor was manufactured, and cannot be reset)
To MENU 7
Go To Page 7
Go To Page 14
Call for Assistance
5
MENU 7
LANGUAGE
MENU 7.1
Francais
Press up or down to select language – French, English, Spanish, Italian, or German
MENU 8
BACKLIGHT
BACKLIGHT
Press up or down to select display backlight intensity
Press to set selected language
Press to set selected display intensity for easy reading in different lighting conditions.
From MENU 6
6
After selecting “SENSOR 2013 VERSION,” scroll down to the specific mode you want to program:
• Hand-Wash
• Metering
• On/OFF
• Urinal
• LF Urinal + PF **(NOT USED)**
• Flushometer
• Kitchen **(NOT USED)**
• DB Toilet
FOR SENSOR 2013 VERSION
7
MENU 4.1
HAND-WASHER
COMF. Timeout
= 1 Sec
To MENU 4.2
Hand-Wash -- Faucet
From MENU 4
NOTE: This is the standard ‘instant on / instant off’ faucet mode.
TIP: The 'COMF. Timeout' (Comfort Timeout) is how long the water will run after the users' hands are removed from the detection zone. This prevents the water from quickly turning On & Off as the users' hands move in & out of the detection zone. Recommended setting: 1.5 sec (adjustable from 0 to 10 sec in 0.5 sec increments).
TIP: The 'Auto. RINSE' (Auto Purge) allows the faucet to automatically turn ON after a set period time of non use, to prevent the water from becoming stagnant or to maintain the trap seal. This time period can be set to activate from OFF to 72 hrs (of non-use) in 1 hr. increments. Then set the duration of run time from 1 sec. to 240 sec. Default Setting: ‘OFF’
TIP: The 'SAFETY Timeout' is sometimes referred to as the ‘vandal timer’. This feature automatically turns the faucet off after a set period of time to prevent a person from intentionally blocking the eye (with chewing gum, tape, etc.) to keep the faucet running and have the sink overflow. Default Setting: 55 sec(adjustable from 5 to 120 sec in 5 sec increments)
Setting the sensor to the Hand-Wash faucet mode: • Set the 'COMF. Timeout'• Set the 'SAFETY Timeout'• Set 'Auto-RINSE' frequency (if the frequency is set to 0,
‘auto-rinsing' (auto-purging) is Off)• Set 'Auto-RINSE' duration (run time)
FOR SENSOR 2013 VERSION
Auto. RINSE
= OFF
Press up or down to turn ONthe Auto Rinse feature and adjust frequency
Align the programmer with the sensor and press to transmit the program to the sensor
Auto. RINSE
= 72 h
Auto. RINSE
= 15 s
SENSOR DIST.
= 16 cm
Press up or down to select distance:16 cm (6.3”) is the Default
See TIP
SAFETY Timeout
= 55 s
See TIP
See TIP
Press up or down to adjust the rinse duration
Units ConverterCentimeters
(cm)Inches
(in)
5 2
16 6.3
25 9.8
40 15.75
60 23.6
80 31.5
8
MENU 4.2
METERING
From MENU 4.1
To MENU 4.3
Metering -- FaucetSetting the sensor to the Metering faucet mode: • Set the 'COMF. Timeout' (run time)• Set 'Auto. Rinse' frequency (if the frequency is set to 0,
‘auto-rinsing' (auto-purging) is Off)• Set 'Auto. Rinse' duration (run time)• Set 'SENSOR DIST.' (range)
TIP: In this Metering Mode, the 'COMF. Timeout' (Comfort Timeout) is the RUN TIME - how long the water will run once activated by the user. Run Times (sec.): 3.25, 7.5, 10, 15, 30, 60, 120, or 240
TIP: The 'Auto. RINSE' (Auto Purge) allows the faucet to automatically turn ON, after a set period time of non use, to prevent the water from becoming stagnant or to maintain the trap seal . This time period can be set to activate from OFF to 72 hrs (of non-use) in 1 hr. increments. Then set the duration of run time from 1 sec. to 240 sec. Default Setting: ‘OFF’
Auto. RINSE
= OFF
SENSOR DIST.
SHORT RANGE
Align the programmer with the sensor and press to transmit the program to the sensor
Press up or down to select between Short and Long Range –SHORT is the Default
Auto. RINSE
= 72 h
Auto. RINSE
=15s
SENSOR DIST.
= 16 cm
COMF. Timeout
= 15 Sec
Press up or down to adjust the run time
Press up or down to select distance – 16 cm (6.3”) is the Default
Press up or down to turn ONthe Auto Rinse feature and adjust frequency
Press up or down to adjust the rinse duration
FOR SENSOR 2013 VERSION
9
Units ConverterCentimeters
(cm)Inches
(in)
5 2
16 6.3
25 9.8
40 15.75
60 23.6
80 31.5
MENU 4.3
ON/OFF
From MENU 4.2
COMF. Timeout
= 15 Sec
Press up or down to adjust the run time
Auto. RINSE
= OFF
SENSOR DIST.
SHORT RANGE
Align the programmer with the sensor and press to transmit the program to the sensor
To MENU 4.4
Metering with On/Off -- Faucet
TIP: The 'Auto. RINSE' (Auto Purge) allows the faucet to automatically turn ON, after a set period time of not being used, to prevent the water from becoming stagnant or to maintain the trap seal . This time period can be set to activate from OFF to 72 hrs (of non-use) in 1 hr. increments. You can set the duration of run time from 1 sec. to 240 sec. Default Setting: ‘OFF’
Setting the sensor to the Metering faucet mode: • Set the 'COMF. Timeout' (run time), • Set 'Auto. Rinse' frequency (if the frequency is set to 0,
‘auto-rinsing' (auto-purging) is Off)• Set 'Auto. Rinse' duration (run time)• Set 'SENSOR DIST.' (range)
NOTE: This is actually the ‘Metering’ mode, but with the added feature of being able to start and stop the water flow before the metering time runs out.
TIP: In this ‘Metering with On/Off’ Mode, the 'COMF. Timeout' is the RUN TIME - how long the water will run once activated by the user, The detection distance is set very short, so the user must start & stop the water by moving hands close to the sensor. This is suited for gooseneck type fittings where the movement of the user may be outside the normal detection zone. Run Times (sec.): 3.25, 7.5, 10, 15, 30, 60, 120, or 240
Auto. RINSE
= 72 h
Auto. RINSE
= 15 s
SENSOR DIST.
= 5 cm
Units ConverterCentimeters
(cm)Inches
(in)
5 2
16 6.3
25 9.8
40 15.75
60 23.6
80 31.5
Press up or down to select between Short and Long Range –SHORT is the Default
Press up or down to select distance – 5 cm (2.0”) is the Default
Press up or down to turn ONthe Auto Rinse feature and adjust frequency
Press up or down to adjust the rinse duration
FOR SENSOR 2013 VERSION
10
MENU 4.4
URINAL
From MENU 4.3
DETEC. INTERVAL
= 5 Sec
Press up or down to adjust the required user detection arming time
RINSE START INT
= 3
Press up or down to adjust how long the valve waits after the user leaves the detection zone to begin the flush
Align the programmer with the sensor and press to transmit the program to the sensor
To MENU 4.5
Auto. RINSE
= OFF
Auto. RINSE
= 72 h
RINSE
= 3 s
**This Function Not Normally Used. See page 21 for information on use of this function.
Urinal -- Urinal Flush ValveTIP: The 'DETEC. INTERVAL' (Detection Interval) is how long a user must be in the detection zone to arm the flush valve. This eliminates false flushing due to people walking past the urinals. Default setting is 5 sec.
TIP: The 'RINSE START INT' (rinse start interval) is how long after the user leaves the detection zone before the valve flushes. Default setting is 3 sec.
TIP: The 'Auto. RINSE' (Sanitary Flush) allows the flush valve to automaticallyflush, after a set period time of not being used, to maintain the trap seal . The Frequency can be set from OFF to 72 hrs (of non-use) in 1 hr.. increments. The Duration of flush time can set from 1 sec. to 240 sec.
Frequency Default Setting: ’ OFF’ (unless prolonged non-use is expected)
NOTE: 'Auto. RINSE' Duration must never deliver more water than the fixture can drain before overflowing!
Recommended 'Duration is 2 sec. (when used)
TIP: The 'RINSE' is the flush time (flush duration). See Flush Valve Settings Chart on page 20
HEAVY FLUSH
COUNT : OFF
Auto. RINSE
= 2 s
SENSOR DIST.
= 40 cm
Press up or down to select distance –40 cm (15.75”) is the Default
Units ConverterCentimeters
(cm)Inches
(in)
5 2
16 6.3
25 9.8
40 15.75
60 23.6
80 31.5
Press up or down to turn ONthe Auto Rinse feature and adjust frequency
Press up or down to adjust the rinse duration
FOR SENSOR 2013 VERSION
11
MENU 4.6
FLUSHOMETER
From MENU 4.4
To MENU 4.7
MENU 4.5
LF URINAL + PF
Flushometer – Toilet Flush Valve
MENU 4.7
KITCHENNOT USED
TIP: The 'DETEC. INTERVAL' (Detection Interval) is how long a user must be in the detection zone to arm the flush valve. (Default setting is 5 sec.)
TIP: The 'RINSE START INT' (rinse start interval) is how long after the user leaves the detection zone before the valve flushes. Default setting is 3 sec.
TIP: The 'RINSE' is the flush time (flush duration). See Flush Valve Settings Chart on page 20
DETEC. INTERVAL
= 5 Sec
RINSE START INT
= 3
Align the programmer with the sensor and press to transmit the program to the sensor
Auto. RINSE
= OFF
Auto. RINSE
= 72 h
RINSE
= 3 s
**This Function Not Normally Used. See page 21 for information on use of this function.
HEAVY FLUSH
COUNT : OFF
Auto. RINSE
= 2 s
SENSOR DIST.
= 40 cm
NOT USED
Press up or down to select distance –60 cm (23.6”) is Recommended
Units ConverterCentimeters
(cm)Inches
(in)
5 2
16 6.3
25 9.8
40 15.75
60 23.6
80 31.5
Press up or down to turn ONthe Auto Rinse feature and adjust frequency
Press up or down to adjust the rinse duration
Press up or down to adjust the required user detection arming time
Press up or down to adjust how long the valve waits after the user leaves the detection zone to begin the flush
TIP: The 'Auto. RINSE' (Sanitary Flush) allows the flush valve to automaticallyflush, after a set period time of not being used, to maintain the trap seal . The Frequency can be set from OFF to 72 hrs (of non-use) in 1 hr.. increments. The Duration of flush time can set from 1 sec. to 240 sec.
Frequency Default Setting: ’ OFF’ (unless prolonged non-use is expected)
NOTE: 'Auto. RINSE' Duration must never deliver more water than the fixture can drain before overflowing!
Recommended 'Duration is 2 sec. (when used)
FOR SENSOR 2013 VERSION
12
MENU 4.8
DB Toilet
From MENU 4.4
DETEC. INTERVAL
= 3 Sec
Press up or down to adjust the user detection arming time
RINSE START INT
= 3
RINSE
= 3 s
Press up or down to adjust Flush Time
Dual Flush – Toilet Flush Valve
SHORT RINSING
= 1.5 Sec
TIP: The 'DETEC. INTERVAL' (Detection Interval) is how long a user must be in the detection zone to arm the flush valve. (Default setting is 5 sec.)
Press up or down to adjust how long the valve waits after the user leaves the detection zone to begin the flush
TIP: The 'SHORT RINSING' is the flush time (flush duration) used when the user stays in the detection zone for less than 60 sec. This should be the setting for the lowest of the 2 flush volumes listed for this model flush valve. See Flush Valve Settings Chart on page 20
TIP: The 'RINSE' is the long flush time (flush duration) if the user stays in the detection zone for 60 sec. or longer. See the Flush Valve Settings Chart on page 20
Align the programmer with the sensor and press to transmit the program to the sensor
Auto. RINSE
= OFF
Auto. RINSE
= 72 h
Auto. RINSE
= 2 s
SENSOR DIST.
= 40 cm
**This Function Not Normally Used. See page 21 for information on use of this function.
HEAVY FLUSH
COUNT : OFF
Units ConverterCentimeters
(cm)Inches
(in)
5 2
16 6.3
25 9.8
40 15.75
60 23.6
80 31.5
Press up or down to select distance –60 cm (23.6”) is Recommended
Press up or down to turn ONthe Auto Rinse feature and adjust frequency
Press up or down to adjust the rinse duration
TIP: The 'Auto. RINSE' (Sanitary Flush) allows the flush valve to automatically flush, after a set period time of not being used, to maintain the trap seal . The Frequency can be set from OFF to 72 hrs (of non-use) in 1 hr.. increments. The Duration of flush time can set from 1 sec. to 240 sec.
Frequency Default Setting: ’ OFF’ (unless prolonged non-use is expected)
NOTE: 'Auto. RINSE' Duration must never deliver more water than the fixture can drain before overflowing!
Recommended 'Duration is 2 sec. (when used)
TIP: The 'RINSE START INT' (rinse start interval) is how long after the user leaves the detection zone before the valve flushes. Default setting is 3 sec.
13
FOR SENSOR 2013 VERSION
After selecting “SENSOR 2008 VERSION,” scroll down to the specific mode you want to program:
• Hand-Wash
• Metering
• On/OFF
• Urinal
• LF Urinal + PF **(NOT USED)**
• Flushometer
• Kitchen **(NOT USED)**
• DB Toilet
FOR SENSOR 2008 VERSION
14
MENU 4.1
HAND-WASHER
COMF. Timeout
= 1 Sec
To MENU 4.2
Hand-Wash -- Faucet
From MENU 4
NOTE: This is the standard ‘instant on / instant off’ faucet mode.
Setting the sensor to the Hand-wash faucet mode: • Set the ‘COMF. Timeout’• Set the 'SAFETY Timeout'• Set 'Auto. RINSE' frequency (if the frequency is set to 0,
‘auto-rinsing' (auto-purging) is Off)• Set the 'Auto. RINSE' duration (run time)
Auto. RINSE
= OFF
Align the programmer with the sensor and press to transmit the program to the sensor
Auto. RINSE
= 72 h
Auto. RINSE
= 15 s
See TIP
SAFETY Timeout
= 55 s
See TIP
See TIP
Press up or down to turn ONthe Auto Rinse feature and adjust frequency
Press up or down to adjust the rinse duration
TIP: The 'COMF. Timeout' (Comfort Timeout) is how long the water will run after the users' hands are removed from the detection zone. This prevents the water from quickly turning On & Off as the users' hands move in & out of the detection zone. Recommended setting: 1.5 sec (adjustable from 0 to 10 sec in 0.5 sec increments).
TIP: The 'Auto. RINSE' (Auto Purge) allows the faucet to automatically turn ON after a set period time of non use, to prevent the water from becoming stagnant or to maintain the trap seal. This time period can be set to activate from OFF to 72 hrs (of non-use) in 1 hr. increments. Then set the duration of run time from 1 sec. to 240 sec. Default Setting: ‘OFF’
TIP: The 'SAFETY Timeout' is sometimes referred to as the ‘vandal timer’. This feature automatically turns the faucet off after a set period of time to prevent a person from intentionally blocking the eye (with chewing gum, tape, etc.) to keep the faucet running and have the sink overflow. Default Setting: 55 sec(adjustable from 5 to 120 sec in 5 sec increments)
FOR SENSOR 2008 VERSION
15
MENU 4.2
METERING
From MENU 4.1
To MENU 4.3
Metering -- Faucet
Auto. RINSE
= OFF
Align the programmer with the sensor and press to transmit the program to the sensor
Auto. RINSE
= 72 h
Auto. RINSE
= 15 s
COMF. Timeout
= 15 Sec
Press up or down to adjust the run time
Press up or down to turn ONthe Auto Rinse feature and adjust frequency
Press up or down to adjust the rinse duration
Setting the sensor to the Metering faucet mode: • Set the 'COMF. Timeout' (run time)• Set 'Auto. Rinse' frequency (if the frequency is set to 0,
‘auto-rinsing' (auto-purging) is Off)• Set 'Auto. Rinse' duration (run time)• Set 'SENSOR DIST.' (range)
TIP: In this Metering Mode, the 'COMF. Timeout' (Comfort Timeout) is the RUN TIME - how long the water will run once activated by the user. Run Times (sec.): 3.25, 7.5, 10, 15, 30, 60, 120, or 240
TIP: The 'Auto. RINSE' (Auto Purge) allows the faucet to automatically turn ON after a set period time of non use, to prevent the water from becoming stagnant or to maintain the trap seal. This time period can be set to activate from OFF to 72 hrs (of non-use) in 1 hr. increments. Then set the duration of run time from 1 sec. to 240 sec. Default Setting: ‘OFF’
FOR SENSOR 2008 VERSION
16
MENU 4.3
ON/OFF
From MENU 4.2
COMF. Timeout
= 15 Sec
Press up or down to adjust the run time
Auto. RINSE
= OFF
Align the programmer with the sensor and press to transmit the program to the sensor
To MENU 4.4
Auto. RINSE
= 72 h
Auto. RINSE
= 15 s
Press up or down to turn ON the Auto Rinse feature and adjust frequency
Press up or down to adjust the rinse duration
Setting the sensor to the Metering faucet mode: • Set the 'COMF. Timeout' (run time), • Set 'Auto. Rinse' frequency (if the frequency is set to 0,
‘auto-rinsing' (auto-purging) is Off)• Set 'Auto. Rinse' duration (run time)• Set 'SENSOR DIST.' (range)
NOTE: This is actually the ‘Metering’ mode, but with the added feature of being able to start and stop the water flow before the metering time runs out.
TIP: In this ‘Metering with On/Off’ Mode, the 'COMF. Timeout' is the RUN TIME - how long the water will run once activated by the user, The detection distance is set very short, so the user must start & stop the water by moving hands close to the sensor. This is suited for gooseneck type fittings where the movement of the user may be outside the normal detection zone. Run Times (sec.): 3.25, 7.5, 10, 15, 30, 60, 120, or 240
TIP: The 'Auto. RINSE' (Auto Purge) allows the faucet to automatically turn ON after a set period time of non use, to prevent the water from becoming stagnant or to maintain the trap seal. This time period can be set to activate from OFF to 72 hrs (of non-use) in 1 hr. increments. Then set the duration of run time from 1 sec. to 240 sec. Default Setting: ‘OFF’
Metering with On/Off -- FaucetFOR SENSOR 2008 VERSION
17
MENU 4.4
URINAL
From MENU 4.3
DETEC. INTERVAL
= 5 Sec
Press up or down to adjust the required user detection arming time
RINSE START INT
= 3
Press up or down to adjust how long the valve waits after the user leaves the detection zone to begin the flush
Align the programmer with the sensor and press to transmit the program to the sensor
To MENU 4.5
Auto. RINSE
= OFF
Auto. RINSE
= 72 h
RINSE
= 3 s
Urinal -- Urinal Flush Valve
Auto. RINSE
= 2 s
Press up or down to turn ONthe Auto Rinse feature and adjust frequency
Press up or down to adjust the rinse duration
TIP: The 'DETEC. INTERVAL' (Detection Interval) is how long a user must be in the detection zone to arm the flush valve. This eliminates false flushing due to people walking past the urinals. Default setting is 5 sec.
TIP: The 'RINSE START INT' (rinse start interval) is how long after the user leaves the detection zone before the valve flushes. Default setting is 3 sec.
TIP: The 'Auto. RINSE' (Sanitary Flush) allows the flush valve to automaticallyflush, after a set period time of not being used, to maintain the trap seal . The Frequency can be set from OFF to 72 hrs (of non-use) in 1 hr.. increments. The Duration of flush time can set from 1 sec. to 240 sec.
Frequency Default Setting: ’OFF’ (unless prolonged non-use is expected)
NOTE: 'Auto. RINSE' Duration must never deliver more water than the fixture can drain before overflowing!
Recommended 'Duration is 2 sec. (when used)
TIP: The 'RINSE' is the flush time (flush duration). See Flush Valve Settings Chart on page 20
FOR SENSOR 2008 VERSION
18
MENU 4.6
FLUSHOMETER
From MENU 4.4
To MENU 4.8
MENU 4.5
LF URINAL + PF
Flushometer – Toilet Flush Valve
MENU 4.7
KITCHENNOT USED
DETEC. INTERVAL
= 5 Sec
Press up or down to adjust the required user detection arming time
RINSE START INT
= 3
Press up or down to adjust how long the valve waits after the user leaves the detection zone to begin the flush
Align the programmer with the sensor and press to transmit the program to the sensor
Auto. RINSE
= OFF
Auto. RINSE
= 72 h
RINSE
= 3 s
Auto. RINSE
= 2 s
NOT USED
Press up or down to turn ONthe Auto Rinse feature and adjust frequency
Press up or down to adjust the rinse duration
TIP: The 'DETEC. INTERVAL' (Detection Interval) is how long a user must be in the detection zone to arm the flush valve. (Default setting is 5 sec.)
TIP: The 'RINSE START INT' (rinse start interval) is how long after the user leaves the detection zone before the valve flushes. Default setting is 3 sec.
TIP: The 'RINSE' is the flush time (flush duration). See Flush Valve Settings Chart on page 20
TIP: The 'Auto. RINSE' (Sanitary Flush) allows the flush valve to automaticallyflush, after a set period time of not being used, to maintain the trap seal . The Frequency can be set from OFF to 72 hrs (of non-use) in 1 hr.. increments. The Duration of flush time can set from 1 sec. to 240 sec.
Frequency Default Setting: ’ OFF’ (unless prolonged non-use is expected)
NOTE: 'Auto. RINSE' Duration must never deliver more water than the fixture can drain before overflowing!
Recommended 'Duration is 2 sec. (when used)
FOR SENSOR 2008 VERSION
19
MENU 4.8
DB Toilet
From MENU 4.4
DETEC. INTERVAL
= 5 Sec
Press up or down to adjust the user detection arming time.
RINSE START INT
= 3
RINSE
= 3 s
Press up or down to adjust Flush Time –see TIP
Dual Flush – Toilet Flush Valve
SHORT RINSING
= 1.5 Sec
Press up or down to adjust how long the valve waits after the user leaves the detection zone to begin the flush
TIP: The 'RINSE' is the long flush time (flush duration) if the user stays in the detection zone for 60 sec. or longer. See the Flush Valve Settings Chart on page 20
FOR SENSOR 2008 VERSION
Align the programmer with the sensor and press to transmit the program to the sensor
Auto. RINSE
= OFF
Auto. RINSE
= 72 h
Auto. RINSE
= 2 s
Press up or down to turn ONthe Auto Rinse feature and adjust frequency
Press up or down to adjust the rinse duration
TIP: The 'DETEC. INTERVAL' (Detection Interval) is how long a user must be in the detection zone to arm the flush valve. (Default setting is 5 sec.)
TIP: The 'Auto. RINSE' (Sanitary Flush) allows the flush valve to automatically flush, after a set period time of not being used, to maintain the trap seal . The Frequency can be set from OFF to 72 hrs (of non-use) in 1 hr.. increments. The Duration of flush time can set from 1 sec. to 240 sec.
Frequency Default Setting: ’ OFF’ (unless prolonged non-use is expected)
NOTE: 'Auto. RINSE' Duration must never deliver more water than the fixture can drain before overflowing!
Recommended 'Duration is 2 sec. (when used)
TIP: The 'RINSE START INT' (rinse start interval) is how long after the user leaves the detection zone before the valve flushes. Default setting is 3 sec.
TIP: The 'SHORT RINSING' is the flush time (flush duration) used when the user stays in the detection zone for less than 60 sec. This should be the setting for the lowest of the 2 flush volumes listed for this model flush valve. See Flush Valve Settings Chart on page 20
20
URINAL FLUSH VALVE SETTINGS
Model (GPF)
Detect Interval
Rinse Start (Flush Start)
Rinse (Flush-time)
Auto Rinse (Sanitary Flush)
Auto Rinse (run-time)
Innsbrook 5 3 8 OFF or 72h 2
1.0 5 3 6 OFF or 72h 2
0.5 5 3 3 OFF or 72h 1
0.25 5 3 1.5 OFF or 72h 1
0.125 5 3 1 OFF or 72h 1
TOILET FLUSH VALVE SETTINGS
Model (GPF)
Detect Interval
Rinse Start (Flush Start)
Rinse (Flush-time)
Auto Rinse (Sanitary Flush)
Auto Rinse (run-time)
1.6 5 3 3.5 OFF or 72h 2
1.28 5 3 3 OFF or 72h 2
1.1 5 3 2.5 OFF or 72h 2
DUAL-FLUSH VALVE SETTINGSModel (GPF)
Short Rinsing(Short Flush)
Detect Interval
Rinse Start (Flush Start)
Rinse (Flush-time)
Auto Rinse (Sanitary Flush)
Auto Rinse (run-time)
1.6 / 1.1 2.5 5 3 3.5 OFF or 72h 2
1.28 / 1.1 2.5 5 3 3.0 OFF or 72h 2
Flush Valve Settings
Units ConverterCentimeters
(cm)Inches
(in)
5 2
16 6.3
25 9.8
40 15.75
60 23.6
80 31.5
21
PERIODIC HEAVY FLUSH FEATUREPeriodic Heavy Flush - A slug of water (higher than the standard flush volume) is sent through the drain line after a pre-programmed number of flushes, or specified time period of non-use, to help prevent drain line clogging. The volume and frequency of the slug of water are easily programmable. Flush valves with the Periodic Heavy Flush Feature can be located upstream of ultra-high efficiency fixtures or in areas of potential drain line carry issues. See pages 22 & 23 for water conservation chart and application examples.
The PHF feature can be activated for the Urinal, Flushometer, and Dual Flush functions with the
Sensor 2013 Version.
HEAVY FLUSH
COUNT : OFF
Press up or down to turn on the Heavy Flush feature and set the activation count
HEAVY FLUSH
COUNT = 20
Press up or down to adjust the Heavy Flush run time
HEAVY FLUSH
DURATION : 5 s
From RINSE MENU
Align the programmer with the sensor and press to transmit the program to the sensor
Auto. RINSE
= OFF
Auto. RINSE
= 72 h
Auto. RINSE
= 2 s
Press up or down to turn ON the Auto Rinse (Heavy Flush) feature based on time of non-use and adjust time activation frequency
Press up or down to adjust the heavy flush duration
TIP: The 'HEAVY FLUSH COUNT' feature allows the flush valve to automatically flush a heavy flush after a set number of flush activations, to maintain the drain line. The activation count can be set from OFF to 100 in increments of 10 activations. You can set the duration of flush time from 1 sec. to 240 sec. – never set for more than the fixture can drain before overflowing!
Default setting: 'OFF'
TIP: The 'Auto. RINSE' (HEAVY FLUSH) allows the flush valve to automatically flush after a set period time of not being used, to maintain the drain line. This time period can be set to activate from OFF to 72 hrs (of non-use) in 1 hr. increments. You can set the duration of the heavy flush time from 1 sec. to 240 sec. –never more than the fixture can drain before overflowing!
Default setting: 'OFF'
22
Water Savings Afforded by PHFD Flush Valves Versus Standard 1.6 GPF Flushing Systems
# ToiletsFlush
VolumeFlushes Per Day
Total Gallons
Savings (gal.)
% Savings vs. 1.6
1.6 GPF Standard Toilets 14 1.6 10 224.0 0 0
1.28 GPF HET Toilets 14 1.28 10 179.2 44.8 20%
1.1 GPF UHET Toilet Systems 14 1.1 10 154.0- 1 Heavy Flush after timed-out period of 'non-use'. 3 1.6 3 14.4
168.4 55.6 25%
1.1 GPF UHET Toilet Systems 14 1.1 8 123.2- 1 Heavy Flush every 5 Flushes 14 1.6 2 44.8
168.0 56.0 25%
1.1 GPF UHET Toilet Systems 11 1.1 10 121.03 1.1 7 23.1
- 3 Heavy Flushes/day for 3 flush valves based on count usage 3 1.6 3 14.4158.5 65.5 29%
23
HET Fixture & Flush Valve (Typ)
Branch Drain/Waste Line (Typ)
Possible application for drain line purge flush from seldom used end of branch line Flush Valve. Flush cycle is based on period of non-use.
Possible application for branch drain line purge flush from end Flush Valve. Flush cycle is based on period of non-use.
Possible application for drain line purge flush from frequently used Flush Valve. Flush cycle is based on number of uses.
Using PHFD To Address Drain Line Carry-out With UHET & HET Fixtures
Drain Line SagPossible application for a
drain line purge flush to overcome potential clogging due to drain line sag and low flow fixtures