Page 1: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

Selective Arc-Flash Protection

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

Page 2: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

Selective Arc-Flash Protection• Arc flash is a short circuit via ionized gas (air)• Safety hazard to personnel• Damage to equipment• Interruptions to processes

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

Page 3: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

How to mitigate the impact?The incident energy depends on• Distance• Voltage• Current • Arcing time

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

Page 4: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

Time is the critical factor

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

Incident energy with different arcing timesU = 480V, I = 65kA, gap = 32mm, distance = 610mm

0,00

5,00

10,00

15,00

20,00

25,00

30,00

35,00

450 ms 150 ms 57 ms 2 ms

Ener

gy /

cal/c

m^2

According to IEEE Std 1584™-2002

Page 5: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

Time is the critical factor

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

Short-circuit test, 50kA

Arcing time 450ms Arcing time 47ms

Page 6: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

In the beginning – there is light

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

Page 7: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

In the beginning – there is light

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

In the beginning there is so much light that the camera is blinded.

Page 8: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

Detection of the light

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

Optical sensors• Point sensors

• Fibre sensors

Page 9: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

Detection principlesDetection of arc light is the fastest way to detect arc.

Light & Current &I > (I0>)

L > Trip

TripL >Light only

Detection principles

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

The detection of light is often confirmed by the detection of instantaneous overcurrent.

Page 10: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

Dedicated arc-flash protection

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

• Optical sensors• Current measurement (CT’s of

the normal protection system)• Light I/O units• (Current I/O units )• Communication• Arc Master• Self-supervision

Page 11: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

Detection and protection

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

• Detect the arc light • Detect the instantaneous

overcurrent (phase or earth-fault current)

• Initiate the trip of the appropriate circuit breaker within a few milliseconds

• Indicate the activated sensor

trip

Over current 1ms

Page 12: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

Arc-Flash protection integrated into protection relays

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

• Numerical relays equipped with arc-flash option

• Low-cost alternative

Page 13: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

Selective arc-flash protection

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

Page 14: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

Stand-alone arc-flash protection

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

Page 15: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

Ultra-fast protection

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

Arcing time = detection & trip initiation time + CB time= 1..15ms + 50..80ms

Source: Testing and Certification of Medium Voltage Control Centers to Arc Resistant Standards, 2005 John A. Kay, CET

Pressure versus current at arc initialization

Incident energy with different arcing timesU = 480V, I = 65kA, gap = 32mm, distance = 610mm

0,00

5,00

10,00

15,00

20,00

25,00

30,00

35,00

450 ms 150 ms 57 ms 2 ms

Ener

gy /

cal/c

m^2

CB time7ms 60ms

Page 16: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

Arc Eliminator

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

• Makes a controlled bolted fault• Faulty zone potential free within 5ms

Page 17: Selective Arc-Flash Protection - CIRED · Selective Arc-Flash Protection • Arc flash is a short circuit via ionized gas (air) • Safety hazard to personnel • Damage to equipment

Prague, 8-11 June 2009

Summary

Lauri Kumpulainen – Finland Session 1 Paper ID 0660

• Detection of light - the fastest method• Selectivity by means of point sensors • Self-supervision of all the components

and cables

• Recognized by IEC standard 62271-200• Thousands of installed units• Easy retrofit