    Selecting Current Transformers

    Presented to:

    80th Southeastern Meter School &Conference

    By

    William H. (Bill) Hardy, Ph.D.TEC Powermetrix

  • 8/14/2019 Selecting CTs

    2/13

    2

    TEC POWERMETRIX

    Current Transformers (CTs)

  • 8/14/2019 Selecting CTs

    3/13

    3

    TEC POWERMETRIX

    CT Accuracy Class/Burden

    Most CTs used in NorthAmerica are 0.3 (0.3

    percent) Class devices.

    When an accuracy classis specified the maximum

    burden for which the

    device meets the class

    accuracy is also

    specified.

  • 8/14/2019 Selecting CTs

    4/13

    4

    TEC POWERMETRIX

    CT Class 0.3

    Metering error shall be lessthan 0.3% when the CT isused at FULL RATED LOADand with rated burden.

    Metering error shall be lessthan 0.6% when the CT isused between 10% and 100%

    of full rated load. Error is a combination ofamplitude and phase error.

  • 8/14/2019 Selecting CTs

    5/13

    5

    TEC POWERMETRIX

    CT Accuracy Burden - Load

  • 8/14/2019 Selecting CTs

    6/13

    6

    TEC POWERMETRIX

    Slide Courtesy Kent Jones, GE

    0.3% ACCURACY

    ACCURACYC

    LAS

    S

    RATING

    SECONDARY

    FACTOR

    CURRENT

    20

    4.0

    15

    3.02.0

    10

    1.0

    5.02.51.00.5

    .25

    0.1

    5%10%

    50% 100% 200 300 400

    0.60

    0.30

    0.15

    0.15

    0.30

    0.60

    0.6% ACCURACY REGION

    NO ACCURACY GUARANTEEDIN FRONT OF THIS LINE

    0.3% @BX.X RF 4.0

    X CT TEST POINT

    C20 METER TEST POINT

    X X

    ACTUAL

    IEEE C57.13 ACCURACY

    MAXIMUM CONTINUOUSAMPS (RF=4.0)

    X

  • 8/14/2019 Selecting CTs

    7/13

    7

    TEC POWERMETRIX

    0.15% ACCURACY

    ACCURACYC

    LAS

    S

    RATING

    SECONDARY

    FACTOR

    CURRENT

    20

    4.0

    15

    3.02.0

    10

    1.0

    5.02.51.00.5

    .25

    0.1

    5%10%

    50% 100% 200 300 400

    0.60

    0.30

    0.15

    0.15

    0.30

    0.60 0.3% ACCURACY REGION

    NO ACCURACY GUARANTEEDIN FRONT OF THIS LINE

    0.15 @E0.04, 0.15 @E0.20, 0.15 @BX.X RF 4.0

    X CT TEST POINT

    C20 METER TEST POINT

    X X

    ACTUAL

    PROPOSED IEEE C57.13.6 ACCURACY

    CURRENT (RF=4.0)MAXIMUM CONTINUOUS

    Slide Courtesy Kent Jones, GE

  • 8/14/2019 Selecting CTs

    8/13

    8

    TEC POWERMETRIX

    Slide Courtesy Kent Jones, GE

    ACC

    URACYC

    LASS

    RATING

    SECONDARY

    FACTOR

    CURRENT

    20

    4.0

    15

    3.02.0

    10

    1.0

    5.02.51.00.5

    .25

    0.1

    5%

    10%

    50% 100% 200 300 400

    0.60

    0.30

    0.15

    0.15

    0.30

    0.60

    0.15% ACCURACY REGION

    NO ACCURACY GUARANTEEDIN FRONT OF THIS LINE

    0.15S @E0.04, 0.15S @E0.20, 0.15S @BX.X RF 4.0

    X CT TEST POINT

    C20 METER TEST POINT

    X X

    ACTUAL

    PROPOSED IEEE C57.13.6 ACCURACY

    CURRENT (RF=4.0)MAXIMUM CONTINUOUS

    X

  • 8/14/2019 Selecting CTs

    9/13

    9

    TEC POWERMETRIX

    Errors with Instrument TransformersCT - Burden

    Many CTs are onlyrated at B0.1 andB0.2

    #16 wire is 4.5 m/ft

    #14 wire is 2.8 m/ft

    #12 wire is 1.8 m/ft

    #10 wire is 1.1 m/ft

    #8 wire is 0.7 m/ft 50 ft of #12 wire is nearly

    100 m

  • 8/14/2019 Selecting CTs

    10/13

    10

    TEC POWERMETRIX

    CT TransformersField Verification Full Ratio Measurement

    Measure

    Here

    Measure

    Here

  • 8/14/2019 Selecting CTs

    11/13

    11

    TEC POWERMETRIX

    CT Accuracy Burden - Load

  • 8/14/2019 Selecting CTs

    12/13

    12

    TEC POWERMETRIX

    CT Rating FactorThe MOST Misunderstood Spec

    Rating Factor has absolutely nothing to dowith burden.

    If a CT has a rating factor of 4 it meansthat at 30C it can be used up to 4X its

    label current and maintain its accuracyClass.

  • 8/14/2019 Selecting CTs

    13/13

    13

    TEC POWERMETRIX

    CT Rating Factor Rating Factor is a strong

    function of temperature. If a CT has a rating factorof 4 it means that at 30Cit can be used up to 4X its

    label current and maintainits accuracy Class.

    Operating temperatureaffects Rating Factor

    significantly. A CT with RF=4 at 30C is

    only RF=3 at 55C