11-1 © 2007 Schneider Electric All Rights Reserved 11 SWITCHBOARDS AND SWITCHGEAR Download Section 11 PDF Table of Contents Section 11 Switchboards and Switchgear Transparent Ready ® Equipment Switchboards and switchgear with Powerlogic ® circuit monitors and Web-enabled ethernet communication devices are a part of Schneider Electric’s Transparent Ready power equipment family. When specified as Transparent Ready, the power equipment is provided with a factory- configured “plug and play” communications system that allows the authorized user access to equipment status and monitoring information using only a standard Web browser. Ask your nearest Schneider Electric sales office for details about Transparent Ready power distribution equipment. QED-S Switchboard see page 11-2 HVL/cc and Metalclad Switchgear see pages11-8 and 11-15 Unit Substation see page 11-16 Model III Package Unit Substation see page 11-16 Power-Style ® Switchboards Power-Style ® QED-S Switchboard (UL Listed) 11-2 Power-Style ® QED-2 Switchboard (UL Listed) 11-2 Power-Style ® QED-6 Switchboard (UL Listed) 11-3 Power-Style ® Commercial Multi-Metering Switchboards 11-3 Speed-D ® Switchboards Speed-D ® SB/SF Switchboards (UL Listed) 11-4, 11-5 Switchgear Power-Zone ® 4 Low Voltage Switchgear with Masterpact® Circuit Breakers 11-6 Micrologic ® Trip Units 11-6 MiniBreak™ Compact Height Switches— 5.5 kV—200 Amperes 11-7 HVL/cc Metal-Enclosed Load Interrupter Switchgear—Full Range 11-8 HVL/cc Switchgear—Quick Ship Program—5–15 kV, 600 Amperes 11-9, 11-10 HVL Metal-Enclosed Load Interrupter Switchgear—Full Range 11-11 HVL Switchgear—Quick Ship Program— 5 kV–15 kV, 600 Ampere Features 11-11 HVL Switches for Power-Dry™, Power-Cast®, and Uni-Cast® Transformer Connections 11-12, 11-13 Square D ® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL 11-14 Masterclad ® Medium Voltage Metalclad™ Switchgear (UL Listed) 11-15 Arc Terminator™ Arc Extinguishing System 11-15 Unit Substations Unit Substations 11-16 Power-Zone ® Model III Package Unit Substations 11-16 MV Controllers and Substation Circuit Breakers Motorpact™ Medium Voltage Motor Controllers (UL Listed) 11-18 Powersub ® Vacuum Substation Circuit Breaker Type FVR (Not UL Listed) 11-18 New! New! Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Upload: others

Post on 26-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

11-1© 2007 Schneider ElectricAll Rights Reserved

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Download Section 11 PDF Table of Contents

Section 11Switchboards and Switchgear

Transparent Ready® EquipmentSwitchboards and switchgear with Powerlogic® circuit monitors and Web-enabled ethernet communication devices are a part of Schneider Electric’s Transparent Ready power equipment family.When specified as Transparent Ready, the power equipment is provided with a factory- configured “plug and play” communications system that allows the authorized user access to equipment status and monitoring information using only a standard Web browser. Ask your nearest Schneider Electric sales office for details about Transparent Ready power distribution equipment.

QED-S Switchboardsee page 11-2

HVL/cc and Metalclad Switchgearsee pages11-8 and 11-15

Unit Substationsee page 11-16

Model III Package Unit Substation see page 11-16

Power-Style® Switchboards

Power-Style® QED-S Switchboard (UL Listed) 11-2

Power-Style® QED-2 Switchboard (UL Listed) 11-2

Power-Style® QED-6 Switchboard (UL Listed) 11-3

Power-Style® Commercial Multi-Metering Switchboards 11-3

Speed-D® Switchboards

Speed-D® SB/SF Switchboards (UL Listed) 11-4, 11-5

Switchgear

Power-Zone® 4 Low Voltage Switchgear with Masterpact® Circuit Breakers

11-6

Micrologic® Trip Units 11-6

MiniBreak™ Compact Height Switches— 5.5 kV—200 Amperes 11-7

HVL/cc Metal-Enclosed Load Interrupter Switchgear—Full Range 11-8

HVL/cc Switchgear—Quick Ship Program—5–15 kV, 600 Amperes

11-9, 11-10

HVL Metal-Enclosed Load Interrupter Switchgear—Full Range 11-11

HVL Switchgear—Quick Ship Program— 5 kV–15 kV, 600 Ampere Features

11-11

HVL Switches for Power-Dry™, Power-Cast®, and Uni-Cast® Transformer Connections

11-12, 11-13

Square D® DIN/E Fuse Selection Tables—HVL 11-14

Fuse Selection Tables Boric Acid Fuses—HVL 11-14

Masterclad® Medium Voltage Metalclad™ Switchgear (UL Listed) 11-15

Arc Terminator™ Arc Extinguishing System 11-15

Unit Substations

Unit Substations 11-16

Power-Zone® Model III Package Unit Substations 11-16

MV Controllers and Substation Circuit Breakers

Motorpact™ Medium Voltage Motor Controllers (UL Listed) 11-18

Powersub® Vacuum Substation Circuit Breaker Type FVR (Not UL Listed)

11-18

New!

New!

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 2: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

11-2 © 2007 Schneider ElectricAll Rights Reserved

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Power-Style® Switchboards

QED-S and QED-2 (UL Listed)Classes 2741, 2742 / Refer to Catalog 2742CT9501 or Brochure 2700BR0202

Power-Style® QED-S Switchboard (UL Listed)• Front accessible load connections• Front and rear alignment standard• Switchboard fed by cable• Switchboard ratings through 4000 amperes, 200 kA• Thermal-magnetic, electronic, and Micrologic® fixed-mounted circuit breaker mains

and feeders• Stored energy fixed-mounted mains• Fixed-mounted fusible switch mains and feeders• Group-mounted circuit breaker and fusible switch mains and feeders• Main devices in six sub-division or single main configurations• Main and branch devices in single section configuration• Multiple individual devices in single section configurations• Main lugs in separate section in lineup or behind devices• Thermal-magnetic circuit breakers with standard, high, extra-high, or current-limiting

capability• Electronic circuit breakers with standard, high, or extra-high capability• Exclusive Micrologic microprocessor trip circuit breakers, 80% or 100% rated• Selected utilities and Powerlogic® customer metering• Selected options on circuit breakers and fusible switches• Internally mounted Surgelogic® Transient Voltage Surge Suppression (TVSS) optional

Power-Style® QED-2 Switchboard (UL Listed)• Front accessible load connections• Front and rear alignment standard• Switchboard fed by cable, busway, transformer, or QED switchboard• Switchboard ratings through 5000 amperes, 200 kA; higher amperages available• Thermal-magnetic, electronic, and Micrologic, or stored energy fixed- and drawout-

mounted, circuit breaker mains and feeders• Fixed-mounted fusible switch mains and feeders• Group-mounted circuit breaker and fusible switch mains and feeders• Main devices in six sub-division or single main configurations• Main and branch devices in single section configuration• Multiple individual devices in single section configurations• Main lugs in separate section in lineup or behind devices• Group-mounted mains and branches• Thermal-magnetic circuit breakers with standard, high, extra-high or current-limiting

capability• Electronic circuit breakers with standard, high, or extra-high capability• Exclusive Micrologic microprocessor trip circuit breakers, 80% or 100% rated• All utilities• Powerlogic customer metering, including custom communications capability and

interwiring• Transparent Ready® Equipment communications• Zone selective interlocking on Micrologic circuit breakers, and group mounted 100/250

ampere thermal-magnetic circuit breakers with add-on ground-fault and bolted pressure fusible switches

• All options available on circuit breakers and fusible switches• Custom engineering including main-tie-mains, multiple sets of thru-bus, reduced

heights, and engineered houses• Internally mounted Surgelogic TVSS option

QED-S switchboard(class 2741)

QED-2 switchboard(class 2742)

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 3: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

© 2007 Schneider ElectricAll Rights Reserved

11-3

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Power-Style® Switchboards

QED-6 (UL Listed); Commercial Multi-MeteringClasses 2746, 2755, 2756 / Refer to Catalog 2746CT0101

Power-Style® QED-6 Switchboard (UL Listed)

Masterpact® NW and NT, and PowerPact ® H, J, and D Circuit BreakersThe QED-6 switchboard is designed to provide excellent distribution, protection, and power quality management in commercial electrical equipment. The circuit protective components of the switchboard are the Masterpact NW and NT circuit breakers in 800–5000 ampere frame sizes, as well as the PowerPact H, J, and D circuit breakers in 15–600 ampere frame sizes. These circuit breakers deliver maximum system uptime, system selectivity, ease of maintenance, and reliable circuit protection.QED-6 switchboard features include: Masterpact NW UL 489 Listed circuit breakers for main and feeder devices, Masterpact NT UL 489 Listed circuit breakers for feeder devices, PowerPact H, J, and D UL 489 Listed circuit breakers for feeder devices, and a wide range of designs and options. Highly flexible drawout/plug-in circuit breakers can meet a wide variety of power distribution requirements. Choices include plug-in or drawout construction in PowerPact H, J, and D circuit breakers, and prepared drawout or plug-in spaces that are equipped with all specified control functions. This capability allows quick additions for load upgrades.• QED-6 switchboards are designed, listed, and built to

UL 891; Masterpact and PowerPact circuit breakers are designed, listed, and built to UL 489

• Circuit breakers are individually mounted, rear connected; Masterpact NW and NT circuit breakers are drawout; PowerPact H, J, and D breakers are plug-in as standard, drawout as an option

• Family of field installable and upgradeable Micrologic® trip units with optional Powerlogic® data communications features

• QED-6 switchboards can offer optional Transparent Ready® Web-enabled communications capability

• Switchboard ratings up to 150 kA short-circuit current rating for services 1600–5000 amperes

• Up to (12) 250 ampere PowerPact H and J circuit breakers in a single 30-inch wide section

• Up to (8) 600 ampere frame PowerPact D or (8) 1200 ampere frame Masterpact NT circuit breakers in a single 30-inch wide section

• Flexible branch circuit breaker locations: Masterpact NW and NT and PowerPact H, J, and D circuit breakers can be mixed in a single 30-inch wide section (15–2000 amperes)

• Compartmentalization: separate compartments for circuit breakers, bussing, and load cabling

• Available in 54-inch, 60-inch, and 72-inch deep construction

• Available in NEMA 3R outdoor walk-in enclosures• Masterpact and PowerPact circuit breakers are field

maintainable

QED-6 switchboards are reliable power protection equipment when working with telecommunication facilities, e-business servers, or mainframes that perform critical business transactions. These types of facilities cannot afford downtime.QED-6 rear-connected switchboards are designed as standalone switchboards or as an integral part of the low voltage equipment lineup in a user’s power unit substation.

Specify QED-6 SwitchboardsWhen drawout construction is required for quick circuit breaker changeout; system requirements call for circuit breakers to close within five cycles; stored energy circuit breakers are required; front access to control wires is desired; ease of installation, maintenance, and upgrade of circuit breaker compartmentalization is required; system integrity and segregation of circuit breaker compartments from bus and cable compartments is required; equipment isolation is required.

Benefits/Values of Circuit Breaker PerformanceMasterpact NW and NT circuit breakers are designed to provide maximum protection and reliable operation with a long service life. They exceed all UL 489 endurance testing requirements and are certified to a minimum of 10,000 operations through the 3000 ampere frame.

System CoordinationShort-time ratings are high, giving users excellent system coordination and selectivity with downstream breakers.

High Short-Circuit Current Ratings (SCCR)Up to 150 k AIR at 480 volts and 200 k AIR at 240 volts, which allows customers to design systems with high fault current and paralleling schemes.

Arc Flash Limiting Feeder BreakersHigh speed operation of Masterpact NW and NT circuit breakers (150 k AIR) help reduce arc flash incident energy (cal/cm2) on downstream equipment.

Ease of Installation and MaintenanceThru-the-door construction, an easy to operate drawout mechanism, and front access to all control wiring make this equipment easy to install, maintain, and upgrade. Load connections in the cable compartment are easily accessible in the rear of the switchboard.

Ability to UpgradeUL Listed, field-installable accessories include: motor operators, shunt trips, under voltage devices, trip units, and communication modules for trip units. Manually operated circuit breakers are field convertible to electrical operation.

Open Communication SystemThe Masterpact NW and NT circuit breakers’ Micrologic trip units use Modbus® RTU protocol. This is a widely accepted protocol, which allows QED-6 to be integrated into new or many existing communication systems including Transparent Ready Web-enabled communications.

AdaptableDrawout and bolt-in circuit breakers, front access control wiring, and expandable lineups are quickly adaptable to changing load and control requirements.

ExpandableMasterpact NW and NT circuit breakers have many control termination points, giving the equipment extensive flexibility and expandability for sophisticated control schemes.

Power-Style® Commercial Multi-Metering Switchboards• UL Listed• Lever bypass and EUSERC non lever bypass• Hot sequence metering—EUSERC, NEMA, LOCAL• Front and rear alignment standard• Switchboard ratings through 4000 amperes, 100 kA• Meter sections in either three- or six-socket section

configuration• Tenant mains either circuit breaker or fusible• 60–200 amperes without lever bypass with self-contained

meter sockets, 5- or 7-jaw, ring type and test block where required

• 60–200 amperes lever bypass with self-contained meter sockets, 7-jaw, ringless

• Factory-installed devices with completely wired from meter socket to disconnect

• Provisions for adding future tenants available, as well as future sections

• Sections in either NEMA 1 or NEMA 3R construction• For use on 120/240, 120/208, and 277/480 volt systems

Rating (A) (Frame) Circuit Breakers

150–250 PowerPact H, J 400–600 PowerPact D800–1200 Masterpact NT800–5000 Masterpact NW

QED-6 switchboard (class 2746)

Commercial multi-metering switchboard

(classes 2755, 2756)

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 4: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

11-4 © 2007 Schneider ElectricAll Rights Reserved

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Speed-D® SwitchboardsClass 2710 / Refer to Pricing List 2710PL9602

Speed-D® SB/SF Switchboards (UL Listed)• UL Listed• Hot sequence utility compartment per EUSERC requirements• Two types:

— Utility–Service disconnect–distribution— Utility–Up to six service disconnects

• Single service disconnect, either circuit breaker or fusible rated 400, 600, or 800 amperes with either type of distribution interiors, NQOD up to 240 Vac, I-Line® through 480 Vac

• Six service disconnects, group-mounted fusible, QMB/QMJ, 30–400 amperes; utility compartment—400, 600, and 800 amperes

• Meter doors can be 15 inches with one meter socket and test block or 30 inches high with two meter sockets and test block

• Meter sockets can be 6-, 8-, 13- or 15-jaw meter sockets with test block, based on application

• Accessories include:— Underground pull sections with and without lug landing— Loadside wireway— Bus links for donut type current transformers— Double padlock hasp attachments— Plug-on distribution panel— Subfeed circuit breakers

• Full height add-on I-Line distribution section• Stand-alone I-Line distribution section

ApplicationSuitable for use as service entrance equipment on ac systems. Sections contain metering compartment, barriers, main disconnects, distribution panel, neutral bus, and grounding provisions.

MeteringC/T compartment with two 15-inch blank meter doors. (Order doors with meter socket from Table E on 11-5.) Incoming cable lugs are for top feed with one twin conductor 2 AWG–600 kcmil lug per phase and neutral, suitable for aluminum or copper cables. Optional single conductor lug is available. Refer to Table F on page 11-5.

MainsMain circuit breaker types are either LH or MH. Main fusible device is supplied with Class T fuses. Multiple main devices use plug-on fusible switches.

BranchesNQOD distribution bus is rated 400 amperes and provides mounting space for QO®/QOB Type (150 amperes maximum) circuit breakers. Panel provides space for mounting 42 single pole circuit breakers. One or two individually mounted 225 amperes maximum circuit breakers can be added with bus connectors. (Order subfeed circuit breakers from Table G on page 11-5.)I-Line® distribution bus is rated 400, 600, or 800 amperes and will accept 27-inches of I-Line circuit breakers on the left side maximum frame size of “J” or “K”. The right side will accept either a QO plug-on distribution panel (240 volts only) or LA or LH I-Line circuit breaker.

EnclosureTotally enclosed front accessible with ANSI 49 gray baked enamel finish. Dimensions are 90 in. (H) x 36 in. (W) x 14 in. (D) for indoor and 90 in. (H) x 36 in. (W) x 24.5 in. (D) for outdoor enclosures.

EUSERC Utility Metering, Main Disconnects and Distribution Panel (UL Listed)

a Can be used on 3Ø3W Delta voltage systems (i.e. 240 V Delta or 480 V Delta).b QMB/QMJ fusible switches, maximum 400 amperes, SCCR based on Class J, R, or T

fuses. QMB plug-in circuit breaker rating is equal to the lowest rating of the circuit breaker.c Multiple mains—provisions for mounting 30 inches of fusible devices. No more than six

main devices permitted per NEC.

New!

New!

EUSERC UCT, Single main circuit breaker with

I-Line distribution panelEUSERC UCT,

Fusible multiple mains

Table A: Single Main Circuit Breaker with Distribution

Sys

tem

Service Voltage M

ains

R

atin

gs(A

)

Dis

trib

utio

n In

teri

or

SC

CR

240

V

Max

.S

CC

R48

0 V

Circuit Breaker

Indoor Outdoor

Catalog No. $ Price Catalog

No. $ Price

1Ø3W 120/240400

NQOD 65 — SB124QS 4398.00 SB124QR 6263.00I-Line 65 — SB124IS 4453.00 SB124IR 6513.00None 65 — SB124WS 3852.00 SB124WR 5913.00

600 I-Line 65 — SB126IS 4947.00 SB126IR 7421.00None 65 — SB126WS 4346.00 SB126WR 6821.00

3Ø4Wa208Y/120 400 NQOD 65 — SB324QS 4994.00 SB324QR 7445.00240/120

3Ø4Wa208Y/120 400 None 65 — SB324WS 4618.00 SB324WR 7069.00240/120

3Ø4Wa208Y/120

400 I-Line 65 35 SB344IS 5703.00 SB344IR 8123.00240/120480Y/277

3Ø4Wa208Y/120

400 None 65 35 SB344WS 5102.00 SB344WR 7522.00240/120480Y/277

3Ø4Wa208Y/120

600 I-Line 65 50 SB346IS 7174.00 SB346IR 9420.00240/120480Y/277

3Ø4Wa208Y/120

600 None 65 65 SB346WS 6573.00 SB346WR 8819.00240/120480Y/277

3Ø4Wa208Y/120

800 I-Line 65 50 SB348IS 13046.00 SB348IR 14692.00240/120480Y/277

3Ø4Wa208Y/120

800 None 65 65 SB348WS 12446.00 SB348WR 14091.00240/120480Y/277

Table B: Single Main Fusible Disconnect with Distribution

1Ø3W 120/240400

NQOD 65 — SF124QS 3876.00 SF124QR 6077.00I-Line 100 — SF124IS 4623.00 SF124IR 6488.00None 200 — SF124WS 4023.00 SF124WR 5887.00

600 I-Line 100 — SF126IS 4948.00 SF126IR 7390.00None 200 — SF126WS 4347.00 SF126WR 6789.00

3Ø4Wa208Y/120 400 NQOD 65 — SF324QS 4984.00 SF324QR 7438.00240/120

3Ø4Wa208Y/120 400 None 200 — SF324WS 4608.00 SF324WR 7062.00240/120

3Ø4Wa208Y/120

400 I-Line 100 65 SF344IS 5709.00 SF344IR 8126.00240/120480Y/277

3Ø4Wa208Y/120

400 None 200 200 SF344WS 5108.00 SF344WR 7525.00240/120480Y/277

3Ø4Wa208Y/120

600 I-Line 100 65 SF346IS 7174.00 SF346IR 9591.00240/120480Y/277

3Ø4Wa208Y/120

600 None 200 200 SF346WS 6573.00 SF346WR 8990.00240/120480Y/277

3Ø4Wa208Y/120

800 I-Line 100 65 SF348IS 16934.00 SF348IR 19188.00240/120480Y/277

3Ø4Wa208Y/120

800 None 200 200 SF348WS 16334.00 SF348WR 18587.00240/120480Y/277

Table C: Multiple Mains (Fusible)c

System Service Voltage

Mains Rating

(A)

240 V or

480 V Max.b

Multiple Mains (6) Fusible

Indoor Outdoor

Catalog No. $ Price Catalog

No. $ Price

1Ø3W 120/240 400 200 SF124FS 3710.00 SF124FR 5652.001Ø3W 120/240 600 200 SF126FS 3956.00 SF126FR 5977.00

3Ø4Wa208Y/120

400 200 SF344FS 4683.00 SF344FR 6700.00240/120408Y/277

3Ø4Wa208Y/120

600 200 SF346FS 4879.00 SF346FR 6822.00240/120480Y/277

3Ø4Wa208Y/120

800 200 SF348FS 5522.00 SF348FR 7466.00240/120480Y/277

PE1A Discount Schedule

Modified10/8/08

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 5: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

© 2007 Schneider ElectricAll Rights Reserved

11-5

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Speed-D® Switchboards Merchandised, Service SelectionClass 2710 / Refer to Pricing List 2710PL9602

a 6-jaw meter socket can also be used on 4- and 5-jaw applications.b Door with provisions for mounting meter socket.

Note: To order structure with meter door factory-installed, add door catalog number as suffix to structure (e.g. SF344IS-15D13MS).

c All EUSERC Utilities (except Arizona Public Service and Salt River Project) require a lug landing kit SA8LL.d To be used on 120/240 V, 3Ø4W delta applications.

e Cannot use subfeed circuit breaker kit with multiple mains service section switchboards.f Two pole circuit breaker catalog numbers are completed by adding required phase connection letters as suffix (e.g. SASFB100LAC).

Ordering Information

1. Service section: Order service section from either Table A on page 11-4 (single main circuit breaker with distribution), Table B on page 11-4 (single main fusible with distribution), or Table C on page 11-4 (multiple mains fusible), as determined by mains rating, voltage, and system.

2. Meter doors: Order meter door from Table E (meter door selection) as determined by the height and utility metering requirements.

3. Accessories and subfeeds: Order as required from Table F (accessories) and/or Table G (subfeed circuit breakers).

4. Circuit breakers and switches: Order devices from pages listed below as determined by voltage, trip rating, AIR, and mounting space.

Multiple Mains and Branch Devices• QO, QOB, QO-VH, QOB-VH: pages 7-10 and 9-10• I-Line: pages 9-23–9-27• QMB Switches: page 9-34

Table D: I-Line® Distribution Section

System Service Voltage

Mains Ratings

(A)

DistributionInterior

SCCR 240 V Max.

SCCR 480 V Max.

Distribution TypeIndoor Outdoor

Catalog No. $ Price Catalog

No. $ Price

3Ø4W208Y/120240/120

480Y/277800 I-Line 65 k 65 k

Add-on distribution section, must be connected to an SB UCT and main section without distribution panel, such as SB348WS. An I-Line plug-on subfeed lug kit must be ordered to terminate the distribution section.

SBAD800 6840.00 SBAD800R 8870.00

3Ø4W208Y/120240/120

480Y/277800 I-Line 125 k 100 k

Stand-alone distribution section not connected to an SB section. A back-fed main circuit breaker or I-Line plug-on subfeed lug kit must be ordered toterminate the distribution section. (Non-ULSE)

SBSAD800 7080.00 SBSAD800R 9180.00

New!

Table E: Meter Door Selection

MeterSocketJaws

15-inch High Door With One MeterSocket and Test Block

30-inch High Door With Two MeterSockets and Test Blocks

Catalog No. $ Price Catalog No. $ Price

6a SBA15D6MS 615.00 — 0.008 SBA15D8MS 656.00 — 0.0013 SBA15D13MS 820.00 SBA30D13MS 1395.0015 SBA15D15MS 905.00 SBA30D15MS 1478.00

Blank SBA15DBC 330.00 — 0.00b SBA15DMS 411.00 — 0.00

Table F: AccessoriesDescription Catalog No. $ Price

Indoor underground pull section (w/o lug landing)—26-in. (W)Order separate SA8LL lug kit below if required. SA26PS 1478.00

Outdoor (3R) underground pull section (w/o lug landing)—26 in. (W) x 24.5 in. (D)Order separate SA8LL lug landing kit below when required. SA26PSR 3039.00

Lug landing kit—800 amperes max. For terminating utility service cables in indoor or outdoor underground pull sections. SA8LLc 502.00Single barrel lug kit —Kit provides single barrel lugs and pad in lieu of twin barrel lug provided with service section. Mechanical lugs provided are sized to fit 1-3/0–750 kcmil cable. Two lugs per phase are supplied. SA7PL 263.00

Loadside wireway—11.5 in. (W) x 14 in. (D)—indoor only SA10LW 701.00Bus link kit—800 amperes max.—Order one kit per phase for 400, 600, and 800 A. SA10BL 164.00Double padlock hasp attachment—For mounting two padlocks on door handle of rainproof enclosure. Padlocks not included. SS2PL 75.00

Plug-On Distribution Panel—mounts on right side of I-Line interior. Cannot be used with LA/LH branch circuit breaker. Panel rated 225 A for 240 V applications. For QO® type plug-on circuit breakers only.

System Phase PoleSpaces

1Ø AC12

SS212AC 1559.003Ø ABC SS312 1971.003Ø AB SS212ABd 1559.00

Table G: Subfeed Circuit Breakers e

Description Rating (A)

2-Polef

$ Price

3-Pole

$ PriceCatalog No. Catalog No.

Left Right Left Right

Subfeed Circuit Breaker Kit—Price includes circuit breaker, connectors and mounting hardware. The complete kit, mounting hardware, circuit breaker and connectors will be shipped direct from plant. Delivery is stock to three days.

100 SASFB100L( ) SASFB100R( ) 765.00 SASFB100L SASFB100R 1370.00110 SASFB110L( ) SASFB110R( ) 765.00 SASFB110L SASFB110R 1370.00125 SASFB125L( ) SASFB100R( ) 765.00 SASFB125L SASFB125R 1370.00150 SASFB150L( ) SASFB150R( ) 765.00 SASFB150L SASFB150R 1370.00175 SASFB175L( ) SASFB175R( ) 765.00 SASFB175L SASFB175R 1370.00200 SASFB200L( ) SASFB200R( ) 765.00 SASFB200L SASFB200R 1370.00225 SASFB225L( ) SASFB225R( ) 765.00 SASFB225L SASFB225R 1370.00

PE1A Discount Schedule

Modified10/8/08

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 6: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

11-6 © 2007 Schneider ElectricAll Rights Reserved

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Switchgear Low Voltage Metal-Enclosed DrawoutClass 6037 / Refer to Catalog 6037CT9901

Power-Zone® 4 Low Voltage Switchgear with Masterpact® Circuit BreakersThe Square D® Power-Zone® 4 low voltage metal-enclosed drawout switchgear is designed to provide superior electrical distribution, protection, and power quality management. The prime components of the switchgear are the Masterpact® NW and NT ANSI rated circuit breaker. Power-Zone 4 switchgear is designed to maximize the functionality of the Masterpact circuit breakers, which, in turn, deliver maximum uptime, system selectivity, ease of maintenance, and reliable circuit protection. All of these features are packed into the smallest footprint available for low voltage drawout switchgear.• Power-Zone 4 is designed and built to ANSI®

C37.20.1 and is Listed to UL® 1558• Masterpact NW and NT drawout low voltage power

circuit breakers are designed and built to ANSI C37.13 and C37.16. Listed to UL 1066

• Short-circuit current rating up to 200 kA without fuses• High short-time withstand ratings up to 100 kA for 30

cycles, minimum• Arc flash limiting Masterpact NW feeder breakers

available in 800, 1600, and 2000 ampere ratings• Family of field installable and upgradeable

Micrologic® trip units with optional Powerlogic® data communications features

• Power-Zone 4 switchgear can offer optional Transparent Ready® Web-enabled data communications capability

• Smallest equipment footprint available in this product class

• Front access to control and communications wire connections

• Bolted copper bus provided as standard (up to 5000 amperes maximum)

• Large rear cable compartment pull area allowing maximum room for power cables

• Bus provision for future equipment expansion• System designed for maximum uptime with low

maintenance• Modular circuit breaker designed for easy addition of

control accessories• Available in NEMA 3R outdoor walk-in enclosuresMasterpact NW circuit breakers are available in various levels of interrupting ratings from 42–200 kA at 480 volts and 130 kA at 600 volts.The Masterpact NT circuit breaker is available in an 800 ampere frame size and 42 kA at 480 volts interrupting rating. Up to 8 Masterpact NT circuit breakers can be mounted in a 30-inch wide section. (Not available for 600 volts.)Circuit breakers of like frame sizes and interrupting ratings are interchangeable.

Micrologic® Trip UnitsA modern family of field-installable trip units is available with Masterpact NW and NT circuit breakers. The circuit breaker overcurrent protection consists of a microprocessor-based tripping device that requires no external power source. The complete tripping system has three main components: the air-core sensors, the trip device (with rating plug), and the trip actuator. The microprocessor-based trip unit uses true RMS current level sensing.The Powerlogic® system is used in conjunction with Micrologic Type A, Type P, and Type H trip units for the Masterpact NW and NT circuit breakers. Modbus® industry standard data communications allow the Powerlogic system to replace discrete meters, multiple transducers, analog wires, and analog-to-digital conversion equipment. Extensive information can be transmitted over a single communications cable to a Powerlogic system display, a personal computer, programmable logic controller, or other host system.Basic circuit information, such as amperes, can be monitored using Micrologic Type A trip unit. Circuit breaker remote operation is available using the Micrologic Type P and Type H trip units with Powerlogic functionality. In addition to its metering capabilities, the Micrologic trip unit system is available with optional status inputs and relay outputs for monitoring discrete contacts and remote control of devices by way of the data communications channel.Micrologic trip unit metering functions include:• Amperes and volts• Frequency• Power • Power demand• Energy• Energy demand• Power factor• Power quality measurements• Communications• Fault waveform capture• Waveform capture• Data logging• Programmable contacts• Current unbalance• Over/under voltage• Over/under frequency• Voltage unbalance• Phase loss• Phase sequence• Reverse power• Long time imaging• Contact wear indicator• Temperature indication• Masterpact circuit breaker maintenance information

Rating (A)Catalog No.

Masterpact® NW

800

NW08N1NW08H1NW08H2NW08H3NW08L1

NW08L1F

1600

NW16N1NW16H1NW16H2NW16H3NW16L1

NW16L1F

2000

NW20H1NW20H2NW20H3NW20L1

NW20L1F

3200

NW32H1NW32H2NW32H3NW32L1

4000NW40H2NW40H3NW40L1

5000NW50H2NW50H3NW50L1

Masterpact NT

800 NT08N1

Power-Zone 4 low voltage switchgear

(class 6037)

New!

New!

New!

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 7: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

© 2007 Schneider ElectricAll Rights Reserved

11-7

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Switchgear Medium Voltage Metal-Enclosed—MiniBreak™Class 6042 / Refer to Brochure 6042BR9401

MiniBreak™ Compact Height Switches— 5.5 kV—200 AmperesThe Square D® MiniBreak compact height switch enclosure is only 66-inches high and contains a single 3-pole load interrupter switch, rated 5.5 kV and 200 amperes. Enclosures are free-standing and suitable for both indoor (NEMA 1) and outdoor (NEMA 3R) applications. These switches are available unfused or with provisions for Square D® current-limiting fuses rated from 10E amperes to 200E amperes. Factory-installed accessories include an auxiliary switch, strip heaters, and provisions for a “lock open” only key interlock. The door is mechanically interlocked with the switch operating handle. Set screw cable lugs for #14 solid—2/0 stranded aluminum or copper cable are provided for two line and one load connections. Fuses are not furnished with this equipment. For fuse information and pricing see table below. The Fused switches and many of the fuses listed below are available from stock.

Note: 1200 horsepower maximum.

Ordering Information

1. Select switch catalog number based on fused or unfused.

2. Select catalog numbers for modifications from Factory Modifications table.

3. If fused, select 5 kV, 200 amperes maximum current-limiting fuse from table below.

4. Price switch and fuses separately. Switches are furnished with provisions only for fuses.

5. Weight 450 lbs (204 kg).

a Arresters are line side connected.

Pricing ExamplePrice one (1), 5 kV, 200 ampere switch with 65E current-limiting fuses. Provide one auxiliary switch with 1-N.O. and 1-N.C. contact and with provision for installing a “lock open” key interlock on the switch operating mechanism.

RatingsMax. design voltage (kV) 5.5BIL (kV) 60Frequency (Hz) 60Continuous amperes 200Interrupting amperes 200Momentary (amperes asymmetrical) 20,000Fault close (amperes asymmetrical) 20,000Capacitor switching (kVAR) NoneShort time, 2 seconds (amperes symmetrical) 12,500Low frequency withstand (kV) 19Fuse integrated (symmetrical) 63,000

5 kV—200 Ampere Switch

Type SwitchCatalog No. $ Price

Unfused HVMB305200U 10274.00Fused HVMB305200 11844.00

Current-Limiting Fuses Non-Disconnect Type (Extended travel blown fuse indicator)(Contact your nearest Square D/Schneider Electric sales office for Current Stock Quantities) Price Includes 1 Set of 3 Packed in 1 Box

Continuous Current

Fuse Mounting ClipCatalog Number $ Price

Size Centers

5 kV Fuse

10E

D 12”

5GS010

954.0015E 5GS01520E 5GS02025E 5GS02530E

D 12”

5GS030

1980.00

40E 5GS04050E 5GS05065E 5GS06580E 5GS080100E 5GS100125E

D 12”

5GS125

3326.00150E 5GS150175E 5GS175200E 5GS200

MiniBreak™ switch enclosure with door

(class 6042)

MiniBreak switch enclosure with fuses

(class 6042)

Listed metal-enclosed interrupter switchgear

Factory ModificationsCatalog No. Description $ Price

HVMX1 Auxiliary switch, 1-N.O. and 1-N.C. contacts 152.00

HVMK1 Provisions for lock open only key interlock (does not include the key cylinder—order separately) 341.00

HVMH1 Strip heater 100 W @ 120 V 1150.00HVMH2 Strip heater with thermostat 100 W @ 120 V 1772.00

HVMSA3 Distribution class surge arrester (set of three arresters) 3 kV, 2.55 MCOVa 1618.00

HVMSA6 Distribution class surge arrester (set of three arresters) 6 kV, 5.10 MCOVa 1926.00

Order: Catalog No. $ Price

Switch with enclosure HVMB305200 11844.00Auxiliary switch HVMX1 152.00Key interlock adapter HVMK1 340.00Fuses (set of three, from page 11-14) 5GS065 1980.00

Total Price 14316.00

25.15639

25.20640

15.35390

47.521207

47.521207

29.00737

25.20640

66.001677

25.15639

23.78604

18.38467

2.7069

2.2056

20.75527

2.2056

Front viewSection view

(unfused)

Section view (fused)

Top viewselected area recommended (bottom conduit

entrance)

PE5A Discount Schedule

Modified10/8/08

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 8: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

11-8 © 2007 Schneider ElectricAll Rights Reserved

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Switchgear Medium Voltage Metal-Enclosed —HVL/cc™Class 6045 / Refer to Product Data 6040PD9601 or Handout 6040HO9501

HVL/cc Metal-Enclosed Load Interrupter Switchgear—Full RangeThe Square D® HVL/cc metal-enclosed load interrupter switchgear provides switching, metering, and interrupting capabilities for medium voltage electrical power distribution systems and is designed and tested per applicable ANSI/IEEE and NEMA standards.

Made up of modular units, the HVL/cc is easy to expand. Two main bus positions allow future extensions and connections to existing equipment.

HVL/cc switchgear is available in either single or multiple bay units. The design is compact, with front accessibility.

The HVL/cc switch can be equipped with either an over-toggle mechanism (OTM), which is standard, or an optional stored energy mechanism (SEM). An option with both mechanisms is the Fuselogic™ system. The Fuselogic system offers fuse tripping (with SEM) to provide protection against single phasing loads when a fuse has blown. It also has a mechanical interlock to prevent inadvertent switching until fuses have been installed or blown fuses have been replaced.

The HVL/cc enclosure is designed for front access only and can be positioned against walls, in small rooms or in pre-fabricated buildings. The small footprint can result in considerable cost savings from the reduction of building or room sizes.

Switch Standard Features• Switch Positions: Closed, open, and internally grounded

(optional) (connects switch contacts to ground)• Enclosure: Epoxy• Medium: Sulphur hexalfluoride• Maintenance: Maintenance free sealed for life• Pressure:

— 5.8 PSI (≤ 17.5 kV)— 22 PSI (25.8–38 kV)

• View ports to show switch blade position

Options• Internal ground switch: Has full fault making capability• Fuselogic™ system• Infrared viewing windows• Class I, Division 2• Fast auto transfers• Duplex configurations• Protective relaying• Powerlogic® metering• 20-inch or 29.5-inch wide enclosures

Fuselogic™Fuselogic is a protection system that provides the ultimate in medium voltage fuse protection. This patented system utilizes the Square D® current-limiting fuses with mechanical sensors that function without any auxiliary power requirements. Several combinations of Fuselogic functions can be combined to provide simple blown fuse indication contacts with mechanical lockout to anti-single phasing protection. Anti-single phasing requires the optional stored energy mechanism (SEM). Fuselogic is available on both HVL/cc and HVL switches.

Switchgear Standard Features• Compartments: Switch, bus, fuse/cable, mechanism,

and optional low voltage/control• 11 gauge steel enclosure• Epoxy insulators• Fuse/cable access panel interlocked with switch• Front access only• Animated mechanism mimic bus• Padlocking open or closed provision• Top or bottom cable entry• UL/CUL Listed• Live line indicators on all incoming switch bays and

outgoing feeder circuits• Cable lugs included for one cable per phase• Tin plated copper bus for lineups

HVL/cc Load Interrupter Switches— Full Range 600/1200 Ampere RatingsSwitch (kV)—maximum design 5.5 17.5 17.5 25.8 38

BIL (kV) 60 95 110 125 150Frequency (Hz) 50/60 50/60 50/60 50/60 50/60Withstand (kV) 19 36 36 50 80Continuous current (A) 600/1200 600/1200 600/1200 600 600Interrupting current (A) 600/1200 600/1200 600/1200 600 600Fault close (kA asymmetrical) 40 40 40 32 32

Momentary current (kA asymmetrical) 40 40 40 32 32

Short time current (kA symmetrical) 25 25 25 25 25

Electrical endurance (number of operations at 80% P.F.)

100/600 A 100/600 A 100/600 A100 10026/1200 A 26/1200 A 26/1200 A

Mechanical endurance (number of operations) 1000 1000 1000 1000 1000

37.25946

Optional low voltage compartment

Mechanism compartment

Fuse/cable access panel

Front

Switch with enclosure

Main bus compartment

Fuse cable compartment

Right side view

14.75375

90.002286

37.25946

W

Plan view

Front view

Open Position

ToGround

Bus

Closed Position

ToGround

Bus

Grounded Position

ToGround

Bus

Switch contact positions

Surge ArrestersSystem L-L Voltage kV Arrester MCOV-kV

Nominal MaximumEffectivelyGrounded

Neutral Circuits

Impedance Groundedand Ungrounded

Circuits

2.44.164.86.912.0

2.544.45.087.2612.7

—2.55——

7.65

2.555.15.17.6512.70

12.4713.213.8

13.213.9714.52

7.658.48.4

12.70——

Listed metal-enclosed interrupter switchgear

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 9: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

© 2007 Schneider ElectricAll Rights Reserved

11-9

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Switchgear Medium Voltage Metal-Enclosed —HVL/cc™Class 6045 / Refer to Catalog 6045CT9801

HVL/cc Switchgear—Quick Ship Program—5–15 kV, 600 AmperesThe HVL/cc quick ship program provides basic fused and unfused load interrupter switch configurations for stand-alone or transformer primary applications. The Quick Ship program offers faster delivery, but with fewer options.

Three-pole, 600 ampere individual HVL/cc switches are available in free-standing indoor (NEMA 1) enclosures. These switches are available unfused or with provisions for Square D® current-limiting DIN/E fuses. Factory optional accessories include auxiliary bays, main bus, auxiliary switches, extra cable terminating lugs, and distribution class surge arresters. The fuse access panel is mechanically interlocked with the switch mechanism. Key interlocks are not an available option with Digest-listed HVL/cc switches. (1) Set screw type lugs for (2) #2–350 kcmil copper or aluminum cables are provided for line and load connections. Fuses are not furnished with this equipment. For fuse information and pricing refer to page 11-10.

Provisions for Future ExpansionAll “single” HVL/cc switches have provisions for future expansion on either side. Order main bus kits for copper 600 ampere bus. Include sketch for factory-assembled parts or lineups.

600 Ampere Single Switch UnfusedManual over-toggle mechanism, no grounding switchIncludes (1) set screw lug for (2) #2–350 kcmil Cu or Al conductor per phaseApplication A = Top entry (incoming—cable or main bus), bottom exit (load—cable or main bus)Application B = Bottom entry (incoming—cable or main bus), top exit (load—cable or main bus)

600 Ampere Single Switch Fused(Provisions only for Square D current-limiting DIN/E fuses—order fuses separately)Manual over-toggle mechanism, no grounding switchIncludes (1) set screw lug for (2) #2–350 kcmil Cu or Al conductor per phaseApplication A = Top entry (incoming—cable or main bus), bottom exit (load—cable or main bus)Application B = Bottom entry (incoming—cable or main bus), top exit (load—cable or main bus)

600 Ampere Incoming Line Auxiliary BayFor bottom incoming cable to application A (bottom cable exit) switch(es)Order 600 ampere tin plated Cu main bus to adjacent section from bus tableIncludes (1) set screw lug for (2) #2–350 kcmil Cu or Al conductor per phase

For top incoming cable to application B (top cable exit) switch(es)Order 600 ampere tin plated Cu main bus to adjacent section from main bus kits tableIncludes (1) set screw lug for (2) #2–350 kcmil Cu or Al conductor per phase

600 Ampere Tin Plated Copper Main Bus Kits

RatingsHVL/cc Switch with manually operated type OTM mechanism in cubicle enclosure (does not include internal ground switch). Ratings are based on an X/R ratio of 1.6.

a 50,000 for 630 A fuse.

Factory Modifications

Distribution Class Surge Arresters (One Set of Three) Switch Load Side Connected or Incoming Line Bay)

Catalog No.

kV Rating

Fuse Range Application

Width$ Price

in mm

HVLCCA14305N 4.76 — A 14.75 375 17500.00HVLCCA20305N 4.76 — A 20.00 508 18024.00HVLCCA14315N 15 — A 14.75 375 19244.00HVLCCA20315N 15 — A 20.00 508 19770.00HVLCCB14305N 4.76 — B 14.75 375 17500.00HVLCCB20305N 4.76 — B 20.00 508 18024.00HVLCCB14315N 15 — B 14.75 375 19244.00HVLCCB20315N 15 — B 20.00 508 19770.00

Catalog No.

kV Rating

Fuse Range Application

Width$ Price

in mm

HVLCCA14305D 4.76 10–450E A 14.75 375 19392.00HVLCCA20305D 4.76 10–600E A 20.00 508 19916.00HVLCCA14315D 15 10–200E A 14.75 375 19858.00HVLCCA20315D 15 10–360E A 20.00 508 20382.00HVLCCB14305D 4.76 10–450E B 14.75 375 19392.00HVLCCB20305D 4.76 10–600E B 20.00 508 19916.00HVLCCB14315D 15 10–200E B 14.75 375 19858.00HVLCCB20315D 15 10–360E B 20.00 508 20382.00

90.002286

14.75375

37.25946

M

M450E

NOTE: Cable entry and exit must be opposite to maintain the minimum sections shown.

5 kV Indoor N1 top cable in/bottom cable out

switch in Position A

90.002286

14.75375

37.25946

M

M450E

Mechanical interlock between switch and fuse access panel.

5 kV Indoor N1 top cable in/bottom cable out

switch in position B

NOTE: Mechanical interlock is standard on switches.

Catalog No.

kV Rating

Fuse Range Application

Width$ Price

in mm

HVLCCA14A 4.76/15 — A 14.75 375 1968.00HVLCCA20A 4.76/15 — A 20.00 508 2492.00

Catalog No.

kV Rating

Fuse Range Application

Width$ Price

in mm

HVLCCB14A 4.76/15 — B 14.75 375 1968.00HVLCCB20A 4.76/15 — B 20.00 508 2492.00

Catalog No.

Lef

t (Fr

om)

App

licat

ion Width

Rig

ht (T

o)A

pplic

atio

n Width

$ Pricein mm in mm

HVLCCMBA14A14 A 14.75 375 A 14.75 375 882.00HVLCCMBA14A20 A 14.75 375 A 20.00 508 946.00HVLCCMBA20A14 A 20.00 508 A 14.75 375 946.00HVLCCMBA20A20 A 20.00 508 A 20.00 508 1008.00HVLCCMBA14B14 A 14.75 375 B 14.75 375 2258.00HVLCCMBA14B20 A 14.75 375 B 20.00 508 2362.00HVLCCMBA20B14 A 20.00 508 B 14.75 375 2362.00HVLCCMBA20B20 A 20.00 508 B 20.00 508 2436.00HVLCCMBB14B14 B 14.75 375 B 14.75 375 882.00HVLCCMBB14B20 B 14.75 375 B 20.00 508 946.00HVLCCMBB20B14 B 20.00 508 B 14.75 375 946.00HVLCCMBB20B20 B 20.00 508 B 20.00 508 1008.00HVLCCMBB14A14 B 14.75 375 A 14.75 375 2258.00HVLCCMBB14A20 B 14.75 375 A 20.00 508 2362.00HVLCCMBB20A14 B 20.00 508 A 14.75 375 2362.00HVLCCMBB20A20 B 20.00 508 A 20.00 508 2436.00

Switch (kV)—maximum design 5.5 17.5BIL (kV) 60 95Frequency (Hertz) 50/60 50/60Withstand (kV) 19 36Continuous current (amperes) 600 600Interrupting current (amperes) 600 600Fault close (amperes asymmetrical) 40,000 40,000Integrated switch and fuse rating (amperes 65,000 65,000Momentary current (amperes asymmetrical) 40,000 40,000Short time current, 2 seconds (amperes symmetrical) 25,000 25,000Operations at Full Load 100 100Mechanical Endurance (number of operations) 1000 1000

Catalog No. Description $ Price

HVLCC-X3 Auxiliary switch 2 N.O.–2 N.C. contact 762.00

Catalog No. kV Rating

Section WidthMinimum Required $ Price

in mm

HVLCCDSA3 3 kV, 2.55 kV MCOV 14.75 375 1618.00HVLCCDSA6 6 kV, 5.10 kV MCOV 14.75 375 1926.00HVLCCDSA9 9 kV, 7.65 kV MCOV 14.75 375 2248.00HVLCCDSA10 10 kV, 8.40 kV MCOV 14.75 375 2446.00HVLCCDSA12 12 kV, 10.20 kV MCOV 14.75 375 2836.00HVLCCDSA15 15 kV, 12.70 kV MVOV 20.00 508 3424.00HVLCCDSA18 18 kV, 15.3 kV MCOV 20.00 508 3948.00

Listed metal-enclosed interrupter switchgear

PE5A Discount Schedule

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 10: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

11-10 © 2007 Schneider ElectricAll Rights Reserved

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Switchgear Medium Voltage Metal-Enclosed—HVL/cc™Class 6045 / Refer to Catalog 6045CT9801

600 Ampere “Single” HVL/cc Switch with PROVISIONS ONLY for Square D® Current-Limiting Non-Disconnect Type Fuses for Cable Connection to Power-Dry™, Power-Cast® and Uni-Cast® Transformers (FLC = 300 Ampere MAXIMUM) RH—Transformer on right, LH—Transformer on LeftApplication A = Top Entry (Incoming Cables)Application B = Bottom Entry (Incoming Cables)

Note: Switches with transformer connections are painted ANSI 49. Standalone switches are painted ANSI 61. Transformer connections in HVL/cc switches are based on Square D® standard transformer connections. If these switches are used to connect to other manufacturers' transformers, then connections must match Square D connections. (Cable connections are furnished with the transformer.)

General Purpose E-Rated Current-Limiting Fuses:Type DIN/E for HVL/cc SwitchesIntegrated rating for 600 ampere HVL/cc switches with Square D® DIN/E fuses listed below is 65 kA rms symmetrical amperes. (50 kA rms for 630 ampere fuse.)Current-limiting fuses increase the integrated short-circuit current rating because of their energy-limiting capabilities.To increase the short-circuit current rating of the entire lineup of switchgear, current-limiting fuses must be used in the entrance sections.

a Each (1) set of fuses contains three fuses. (E.g., (2) sets of fuses yield a total of six fuses.)

600 Ampere “Duplex” HVL/cc Switch with PROVISIONS ONLY for Square D Current-Limiting Non-Disconnect Type Fuses for Cable Connection to Power-Dry, Power-Cast and Uni-Cast Transformers (FLC = 300 Ampere MAXIMUM) RH—Transformer on Right, LH—Transformer on Left Includes Mechanical Interlock to Prevent Paralleling of SourcesApplication A = Top Entry (Incoming Cables)Application B = Bottom Entry (Incoming Cables)

Ordering Information

1. Select switch catalog number based on fused or unfused and cable entry locations (top or bottom) from table on page 11-9.

2. Select incoming line auxiliary bay from table on page 11-9, if required.

3. Select main bus from table on page 11-9, if required.4. Select catalog numbers for factory modifications from

table on page 11-9, if required.5. If fused, select DIN/E fuses.

Pricing ExampleOrder indoor 600 A, 5 kV, HVL/cc switch with bottom incoming and bottom outgoing cables (1) #2 AWG per phase, (1) set 200E fuses, and (1) set 6 kV surge arresters.

Catalog No.

kVRating

Fuse Range

App

licat

ion Width

RH / LH $ Price

in mm

HVLCCA14405DGR 4.76 10–450E A 14.75 375 RH 20134.00HVLCCA20405DGR 4.76 10–450E A 20.00 508 RH 20660.00HVLCCA14405DGL 4.76 10–450E A 14.75 375 LH 20134.00HVLCCA20405DGL 4.76 10–450E A 20.00 508 LH 20660.00HVLCCA14415DGR 15 10–200E A 14.75 375 RH 20614.00HVLCCA20415DGR 15 10–200E A 20.00 508 RH 21138.00HVLCCA14415DGL 15 10–200E A 14.75 375 LH 20614.00HVLCCA20415DGL 15 10–200E A 20.00 508 LH 21138.00HVLCCB14405DGR 4.76 10–450E B 14.75 375 RH 20134.00HVLCCB20405DGR 4.76 10–450E B 20.00 508 RH 20660.00HVLCCB14405DGL 4.76 10–450E B 14.75 375 LH 20134.00HVLCCB20405DGL 4.76 10–450E B 20.00 508 LH 20660.00HVLCCB14415DGR 15 10–200E B 14.75 375 RH 20614.00HVLCCB20415DGR 15 10–200E B 20.00 508 RH 21138.00HVLCCB14415DGL 15 10–200E B 14.75 375 LH 20614.00HVLCCB20415DGL 15 10–200E B 20.00 508 LH 21138.00

CatalogNo.

kV Rating

FuseRating

Set of Fuses a

Fuse Size

Section Width Required $ Price

in mm

55DE010 5.5 10E 1 Actual 14.75 375 954.0055DE015 5.5 15E 1 Actual 14.75 375 954.0055DE020 5.5 20E 1 Actual 14.75 375 954.0055DE025 5.5 25E 1 Actual 14.75 375 954.0055DE030 5.5 30E 1 Actual 14.75 375 1980.0055DE040 5.5 40E 1 Actual 14.75 375 1980.0055DE050 5.5 50E 1 Actual 14.75 375 1980.0055DE065 5.5 65E 1 Actual 14.75 375 1980.0055DE080 5.5 80E 1 Actual 14.75 375 1980.0055DE100 5.5 100E 1 Actual 14.75 375 3326.0055DE125 5.5 125E 1 Actual 14.75 375 3326.0055DE150 5.5 150E 1 Actual 14.75 375 3326.0055DE175 5.5 175E 1 Actual 14.75 375 3326.0055DE200 5.5 200E 1 Actual 14.75 375 3326.0055DE250 5.5 250E 1 Actual 14.75 375 5742.0055DE300 5.5 300E 1 Actual 14.75 375 5742.0055DE350 5.5 350E 1 Actual 14.75 375 5742.0055DE400 5.5 400E 1 Actual 14.75 375 6430.0055DE450 5.5 450E 1 Actual 14.75 375 6430.0055DE540 5.5 540A 2 300 20.00 508 11088.0055DE600 5.5 630A 2 350 20.00 508 11088.00175DE010 15.5 10E 1 Actual 14.75 375 3214.00175DE015 15.5 15E 1 Actual 14.75 375 3214.00175DE020 15.5 20E 1 Actual 14.75 375 3214.00175DE025 15.5 25E 1 Actual 14.75 375 3214.00175DE030 15.5 30E 1 Actual 14.75 375 3290.00175DE040 15.5 40E 1 Actual 14.75 375 3290.00175DE050 15.5 50E 1 Actual 14.75 375 3290.00175DE065 15.5 65E 1 Actual 14.75 375 4446.00175DE080 15.5 80E 1 Actual 14.75 375 4446.00175DE100 15.5 100E 1 Actual 14.75 375 4446.00175DE125 15.5 125E 1 Actual 14.75 375 6878.00175DE150 15.5 150E 1 Actual 14.75 375 6878.00155DE175 15.5 175E 1 Actual 14.75 375 6878.00155DE200 15.5 200E 1 Actual 14.75 375 6878.00155DE225 15.5 225A 2 125 20.00 508 13336.00155DE270 15.5 270A 2 150 20.00 508 13336.00155DE315 15.5 315A 2 175 20.00 508 13336.00155DE360 15.5 360A 2 200 20.00 508 13336.00

90.002286

14.75375

14.75375

37.25946

M

M

200E

600 ampere tin plated copper bus

Listed metal-enclosed interrupter switchgear

Catalog No.

kVRating

Fuse Range

Width

RH / LH $ Price

App

licat

ion

in mm

HVLCCA14505DGR 4.76 10–450E A 14.75 375 RH 54174.00HVLCCA20505DGR 4.76 10–450E A 20.00 508 RH 56068.00HVLCCA14505DGL 4.76 10–450E A 14.75 375 LH 54174.00HVLCCA20505DGL 4.76 10–450E A 20.00 508 LH 56068.00HVLCCA14515DGR 15 10–200E A 14.75 375 RH 57428.00HVLCCA20515DGR 15 10–200E A 20.00 508 RH 59322.00HVLCCA14515DGL 15 10–200E A 14.75 375 LH 57428.00HVLCCA20515DGL 15 10–200E A 20.00 508 LH 59322.00HVLCCB14505DGR 4.76 10–450E B 14.75 375 RH 54174.00HVLCCB20505DGR 4.76 10–450E B 20.00 508 RH 56068.00HVLCCB14505DGL 4.76 10–450E B 14.75 375 LH 54174.00HVLCCB20505DGL 4.76 10–450E B 20.00 508 LH 56068.00HVLCCB14515DGR 15 10–200E B 14.75 375 RH 57428.00HVLCCB20515DGR 15 10–200E B 20.00 508 RH 59322.00HVLCCB14515DGL 15 10–200E B 14.75 375 LH 57428.00HVLCCB20515DGL 15 10–200E B 20.00 508 LH 59322.00

Order: Catalog. No. $ Price

Switch w/fuse provisions andbottom exit load cables HVLCCA14305D 19392.00

600 incoming line auxiliary bay(Application A—bottom entry) HVLCCA14A 1968.00

Main Bus(Application A—14 in. to Application A–14 in.) HVLCCMBA14A14 882.00

6 kV LAs HVLCCDSA6 1926.00Set 200E fuses 55DE200 3326.00

Total Price 13747.00

PE5A Discount Schedule

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 11: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

© 2007 Schneider ElectricAll Rights Reserved

11-11

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

HVL Metal-Enclosed Load Interrupter Switchgear—Full RangeHVL™ 5–38 kV Load Interrupter is the most popular ANSI-rated switchgear in its class in America. Among medium voltage interrupter switchgear, both the switch and the enclosure stand as industry benchmarks in the areas of design, manufacturing, and performance. Load interrupter switchgear must perform a number of critical functions in a unit substation - protecting equipment and disconnecting faulted lines and transformers. Designed and tested to the latest applicable standards, HVL has been engineered to provide superior protection for your distribution system.

HVL switchgear is available for Various applications and configurations, including:• Individual service entrance bays• Multiple-bay lineups incorporating HVL load

interrupters and optional Visi/Vac® circuit interrupters• Substation primariesSquare D® metal-enclosed switchgear has become an industry standard for its better systemperformance, lower maintenance cost, easier system expansion, and reduced system expense.A full range of ratings and options are available but not listed in this publication. Contact your nearest Schneider Electric sales office or your local Schneider Electric distributor.

Standard Features• 11 gauge steel enclosure• Direct drive mechanism• Permanently attached operating handle• Visible isolation viewing window• Mechanical interlocked fuse access door• Provision for padlock and key interlock• Highly flexible design• ANSI 61 paint

Options• Outdoor construction• Square D® DIN-style current-limiting fuses• Boric acid fuses• Silver or tin plated copper bus• 600, 1200 or 2000 ampere main bus• Heat shrink insulated bus• Motor operator• Shunt trip• Fuselogic™ tripping system• Automatic load transfer schemes• Roof bushings• Key interlocks• Surge arresters• Utility metering bays• Line selector switch• Duplex switch• Transformer connections• Infrared windows for thermal scanning of connections

Fuselogic™Fuselogic is a protection system that provides the ultimate in medium voltage fuse protection. This patented system utilizes the Square D® current-limiting fuses with mechanical sensors that function without any auxiliary power requirements. Several combinations of Fuselogic functions can be combined to provide simple blown fuse indication contacts with mechanical lockout to anti-single phasing protection. Anti-single phasing requires the optional stored energy mechanism (SEM). Fuselogic is available on both HVL/cc™ and HVL switches.

HVL Switchgear—Quick Ship Program— 5 kV–15 kV, 600 Ampere FeaturesThe HVL quick ship program provides basic fused and unfused load interrupter switch configurations for stand-alone or transformer primary applications. The Quick Ship program offers faster delivery, but with fewer options.Three-pole, 600 ampere individual HVL switches are available in free-standing indoor (NEMA 1) or outdoor (NEMA 3R) enclosures. The switches used in these enclosures are UL Recognized and are listed under Category WIQG2 in File E140591(M). These switches are available unfused or with provisions for 3-inch diameter Square D® current-limiting fuses or for boric acid fuses. Factory optional accessories include auxiliary switches, extra cable terminating lugs and distribution class surge arresters. The door is mechanically interlocked with the switch operating handle and provisions for key interlocks are standard. Set screw type lugs for one #2 solid—600 kcmil copper or aluminum cables are provided for line and load connections. Other standard features include a bolted enclosure with a viewing window, ground pad, and space heater (NEMA 3R only). Control power for heater must be from external source. Fuses are not furnished with this equipment. For fuse information and pricing, refer to page 11-14. Switches are listed on pages 11-11–11-12, and many of the fuses listed on page 11-14 are available from stock.

RatingsMaximum design voltage (kV) 4.76 15 17 25.8 29 38

BIL (kV) 60 95 95 125 125 150Frequency (Hz) 50/60 50/60 50/60 50/60 50/60 50/60Continuous amperes 600/1200 600/1200 600 600/1200 600/1200 600

Interrupting amperes 600/1200 600/1200 600 600 400 400

Momentary (kA asymmetrical)

40/61/80 40/61/80 61 40/61 40/61 40

Fault close (kA asymmetrical) 40/61 40/61 40 40 40 20

Capacitor switching (kVAR) 2400 2400 – – – –

Short time rating2 seconds(kA symmetrical)

25/38/50 25/38/50 25 25 25 25

Low frequency withstand (kV) 19 36 36 60 60 60

Listed metal-enclosed interrupter switchgear

600 Ampere “Single” Switch UnfusedCatalog No.

kV Rating Fuse Range Enclosure Type $ Price

HVL305NG 4.76 — NEMA 1 17500.00HVL305NW 4.76 — NEMA 3R 21524.00HVL315NG 15 — NEMA 1 19244.00HVL315NW 15 — NEMA 3R 23478.00

600 Ampere “Single” Switch with PROVISIONS ONLY for Square D Current-Limiting Non-Disconnect Type Fuses

HVL305DEG 4.76 10–450E NEMA 1 19392.00HVL315DEW 4.76 10–450E NEMA 3R 21636.00HVL315DEG1 15 10–100E NEMA 1 19858.00HVL315DEG2 15 125–200E NEMA 1 19858.00HVL315DEW1 15 10–100E NEMA 3R 23978.00HVL315DEW2 15 125-200E NEMA 3R 23978.00

600 Ampere “Single” Switch with PROVISIONS ONLY for S&C Boric Acid Non-Disconnect Type Fuses

HVL305BG 4.76 10E–400E NEMA 1 24936.00HVL305BW 4.76 10E–400E NEMA 3R 28606.00HVL315BG 15 10E–400E NEMA 1 26650.00HVL315BW 15 10E–400E NEMA 3R 30688.00HVL317BG 17 10E–400E NEMA 1 29610.00HVL317BW 17 10E–400E NEMA 3R 34098.00

H

D W

2.0051

2.0051

6.36162

35.74908

1.1329

4.00102

Conduit

38.00965

D D1

34 x 6864 x 152

34 x 6864 x 152

ControlConduit Area

2 x 451 x 102

.875 Mounting Hole(4 Places for .75 Anchor Bolts)

Side view Front view

Recommended powercable conduit area

New!

Switchgear Medium Voltage Metal-Enclosed—HVLClass 6040 / Refer to Catalog 6040CT9201 or Handout 6040HO9501

PE5A Discount Schedule

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 12: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

11-12 © 2007 Schneider ElectricAll Rights Reserved

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Switchgear Medium Voltage Metal-Enclosed—HVLClass 6040 / Refer to Catalog 6040CT9201 or Brochure 6040BR9401

Provisions for Future ExpansionAll “single” Digest switches have provisions for future expansion on either side. Order kits HVMB for top crossover copper 600 ampere bus and HVLC for line connections to the top bus. (Refer to the Factory Modifications table on page 11-13.) Include sketch for factory-assembled parts or lineups.

HVL Switches for Power-Dry™, Power-Cast®, and Uni-Cast® Transformer ConnectionsHVL switches can be configured for close coupling cable connections to listed dry type transformers for primary main switches of unit substations. These are listed in the tables below with current-limiting or boric acid fuses. Both single and duplex switch mains are included in this selection. Transformers are listed on page 14-20 and may not be suitable for close coupling. For transformer availability and specific configurations, contact your local Schneider Electric sales office. All connections in this digest are based on Square D® standard transformer connections. If these switches are used to connect to other manufacturers’ transformers, then connections must coordinate with Square D connections. (Cable connections are furnished with the transformer.)

a Includes fuse holder only. See table on page 11-14 for fuse refills.Note: Switches with transformer connections are painted ANSI 49.

Standalone switches are painted ANSI 61.

RatingsMax. Design Voltage (kV) 4.76 15.0BIL (kV) 60 95Frequency (Hz) 50/60 50/60Continuous amperes 600 600Interrupting amperes 600 600Momentary (amperes asymmetrical) 40,000 40,000Fault close (amperes asymmetrical) 40,000 40,000Capacitor switching (kVAR) 2,400 2,400Short-time rating, 2 seconds(amperes symmetrical) 25,000 25,000

Low frequency withstand (kV) 19 36

Distribution Class Surge ArrestersSystem L-L Voltage kV Arrester MCOV-kV

Nominal MaximumEffectivelyGrounded

Neutral Circuits

Impedance Groundedand Ungrounded

Circuits

2.44.164.86.9

12.0

2.544.45.087.2612.7

—2.55——7.65

2.555.15.17.65

12.7012.4713.213.8

13.213.9714.52

7.658.48.4

12.70——

Enclosure Type

TypeW D H Weight

in mm in mm in mm lbs kg

Indoor 38.00 965 54.50 1384 90.00 2286 1200 545Outdoor 38.00 965 60.00 1524 97.50 2477 1400 636

600 Ampere “Single” Switch with PROVISIONS ONLY for Square D Current-Limiting Non-Disconnect Type Fuses for Cable Connection to Power-Dry, Power-Cast and Uni-Cast Transformers (FLC = 300 Ampere MAXIMUM) RH—Transformer on Right, LH—Transformer on Left

Catalog No. kV

Rating Fuse Range Enclosure Type RH / LH $ Price

HVL405DEGR 4.76 10–450E NEMA 1 RH 20134.00HVL405DEGL 4.76 10–450E NEMA 1 LH 20134.00

HVL405DEWRH 4.76 10–450E NEMA 3R RH 25322.00HVL405DEWLH 4.76 10–450E NEMA 3R LH 25322.00HVL415DEGR1 15 10–100E NEMA 1 RH 20614.00HVL415DEGR2 15 125–200E NEMA 1 RH 20614.00HVL415DEGL1 15 10–100E NEMA 1 LH 20614.00HVL415DEGL2 15 125–200E NEMA 1 LH 20614.00

HVL415DEWR1H 15 10–100E NEMA 3R RH 28070.00HVL415DEWR2H 15 125-200E NEMA 3R RH 28070.00HVL415DEWL1H 15 10–100E NEMA 3R LH 28070.00HVL415DEWL2H 15 125-200E NEMA 3R LH 28070.00

600 A “Duplex” Switch with PROVISIONS ONLY for SQUARE D Current-Limiting Non-Disconnect Type Fuses for Cable Connection to Power-Dry, Power-Cast and Uni-Cast Transformers (FLC = 300 Ampere MAXIMUM) RH—Transformer on Right, LH—Transformer on Left

HVL505DEGR 4.76 10–450E NEMA 1 RH 42028.00HVL505DEGL 4.76 10–450E NEMA 1 LH 42028.00

HVL505DEWRH 4.76 10–450E NEMA 3R RH 49484.00HVL505DEWLH 4.76 10–450E NEMA 3R LH 49484.00HVL515DEGR1 15 10–100E NEMA 1 RH 43084.00HVL515DEGR2 15 125–200E NEMA 1 RH 43084.00HVL515DEGL1 15 10–100E NEMA 1 LH 43084.00HVL515DEGL2 15 125–200E NEMA 1 LH 43084.00

HVL515DEWR1H 15 10–100E NEMA 3R RH 54904.00HVL515DEWR2H 15 125–200E NEMA 3R RH 54904.00HVL515DEWL1H 15 10–100E NEMA 3R LH 54904.00HVL515DEWL2H 15 125-200E NEMA 3R LH 54904.00

600 Ampere “Single” Switch with PROVISIONS ONLY for S&C Boric Acid Non-Disconnect Type Fuses for Cable Connection to Power-Dry, Power-Cast and Uni-Cast Transformers a (FLC = 300 Ampere MAXIMUM) RH—Transformer on Right, LH—Transformer on Left

HVL405BGR 4.76 10E–400E NEMA 1 RH 25666.00HVL405BGL 4.76 10E–400E NEMA 1 LH 25666.00

HVL405BWRH 4.76 10E–400E NEMA 3R RH 30674.00HVL405BWLH 4.76 10E–400E NEMA 3R LH 30674.00HVL415BGR 15 10E–400E NEMA 1 RH 27390.00HVL415BGL 15 10E–400E NEMA 1 LH 27390.00

HVL415BWRH 15 10E–400E NEMA 3R RH 32476.00HVL415BWLH 15 10E–400E NEMA 3R LH 32476.00

600 Ampere “Duplex” Switch with PROVISIONS ONLY for S&C Boric Acid Non-Disconnect Type Fuses for Cable Connection to Power-Dry, Power-Cast and Uni-Cast Transformers a (FLC = 300 Ampere MAXIMUM) RH—Transformer on Right, LH—Transformer on Left

HVL505BGR 4.76 10E–400E NEMA 1 RH 47470.00HVL505BGL 4.76 10E–400E NEMA 1 LH 47470.00

HVL505BWRH 4.76 10E–400E NEMA 3R RH 57742.00HVL505BWLH 4.76 10E–400E NEMA 3R LH 57742.00HVL515BGR 15 10E–400E NEMA 1 RH 49540.00HVL515BGL 15 10E–400E NEMA 1 LH 49540.00

HVL515BWRH 15 10E–400E NEMA 3R RH 60514.00HVL515BWLH 15 10E–400E NEMA 3R LH 60514.00

New!

PE5A Discount Schedule

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 13: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

© 2007 Schneider ElectricAll Rights Reserved

11-13

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Switchgear Medium Voltage Metal-Enclosed—HVLClass 6040 / Refer to Catalog 6040CT9201

Fuse SelectionThe rule of thumb method for selecting fuses for transformer protection is 1.33 times the self-cooled full load current of the transformer or the next higher fuse rating. Selection of the fuse is the customer’s responsibility and should be based on transformer and system characteristics.• Maximum Fuse Size:

Maximum fuse size should be determined by comparing the fuse total clearing curve to the transformer damage curve. Contact Schneider Electric for transformer overload and short-circuit withstand capability.

• Minimum Fuse Size:Minimum fuse size shall carry the transformer magnetizing inrush current of 12 times full load amperes for 0.1 second.

a Load side connected

Standard Features• Switches for transformer primaries are cable

connected only.• Key interlocks must be ordered and coordinated by

customer.• Standard color is ANSI 61 for stand alone units; • ANSI 49 for switches connecting to transformers.• If switches are purchased to coordinate with Square D®

transformers, composite drawings and shipment coordination will not be available.

• Switches are not designed for any special dimensions for retrofit purposes. For dimensions other than shown, contact your nearest Schneider Electric sales office or your local Schneider Electric distributor.

Ordering Information

1. Select switch catalog number based on fused or unfused and enclosure type.

2. Select catalog numbers for factory modifications from the table above.

3. If fused, select fuse from table on page 11-14.4. Price switch and fuses separately. Switches are

furnished with provisions only for current-limiting fuse or boric acid fuse.

Pricing ExamplePrice one (1) indoor (NEMA 1), 15 kV, 600 ampere switch with 80E SM-5S boric acid fuses and 10 kV distribution class surge arresters for a 7.62/13.2 kV grounded wye system.

Factory ModificationsCatalog

No. Description $ Price

HVMB Main Bus Kit, 600 ampere copper 2288.00

HVLC

Line side connector kit (main bus) 600 ampereswith 2–1/0=500 MCM lugs (top only) 1282.00

Provisions for key interlocks (does not include key cylinders—order separately 0.00

HVLX3 Auxiliary switch 2 N.O.—2 N.C. contact 762.00HVLC2 Set screw type lugs 1/0—500 kcmil (qty. 3) 196.00

Distribution Class Surge Arresters a

HVDSA3 3 kV, 2.55 MCOV 1618.00HVDSA6 6 kV, 5.10 MCOV 1926.00HVDSA9 9 kV, 7.65 MCOV 2248.00HVDSA10 10 kV, 8.40 MCOV 2446.00HVDSA12 12 kV, 10.20 MCOV 2836.00HVDSA15 15 kV, 12.70 MCOV 3424.00

Order: Catalog No. $ Price

Switch with indoor enclosure HVL315BG 26650.00Surge arrester, 10 kV HVDSA10 2446.00Boric acid fuse (set of three, from page 11-14 15SM5080 1508.00

Total Price 30634.00

PE5A Discount Schedule

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 14: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

11-14 © 2007 Schneider ElectricAll Rights Reserved

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Switchgear Medium Voltage Metal-Enclosed—HVLClass 6040 / Refer to Catalog 6040CT9201

Square D® DIN/E Fuse Selection Tables—HVL

a Square D® DIN/E fuses are shown in this table. For fuses produced by other manufacturers, contact your nearest Schneider Electric sales office or your local Schneider Electric distributor.

b All fuses are single barrel arrangement with ferrule diameters per the chart.

c Current-limiting fuses will increase the integrated short-circuit ratings beyond the non-fusible units. Contact your nearest Schneider Electric sales office or your local Schneider Electric distributor.

d Caution—These fuses will not work for the MiniBreak. See page 11-7 for the appropriate MiniBreak fuses.

Fuse Selection Tables Boric Acid Fusesg—HVL

e S&C Boric Acid FusesType SM-5S fuses are manufactured by the S&C Electric Company. SM-5S has a 25.0 kA symmetrical short-circuit rating from 2.4 kV to 17.0 kV. For 16.5 kV ratings, only S&C boric acid fuses can be used.

f Cutler-Hammer - Westinghouse FusesType RBA-400 fuses are manufactured by Cutler-Hammer - EATON Corporation. RBA-400 has a 37.5 kA symmetrical ampere short-circuit rating from 2.4 kV to 4.8 kV and 29.4 kA symmetrical from 12 kV to 13.8 kV.

g Caution—These fuses will not work for the MiniBreak. See page 11-7 for the appropriate MiniBreak fuses.

DIN/E Current-Limiting Fuses Non-Disconnecting Typeacd (Extended travel blown fuse indicator)(Contact your nearest Schneider Electric sales office for current stock quantities.) Price Includes One Set of Three Packed in One Box

ContinuousCurrent

Fuse Mounting Clip b Catalog No.

$ PriceCenters (in)

Diameter (mm)

5 kV Fuse

10E 17.4 51 55DE010

954.0015E 17.4 51 55DE01520E 17.4 51 55DE02025E 17.4 51 55DE02530E 17.4 51 55DE030

1980.00

40E 17.4 51 55DE04050E 17.4 51 55DE05065E 17.4 51 55DE06580E 17.4 51 55DE080

100E 17.4 51 55DE100125E 17.4 76 55DE125

3326.00150E 17.4 76 55DE150175E 17.4 76 55DE175200E 17.4 76 55DE200250E 17.4 76 55DE250

5742.00300E 17.4 76 55DE300350E 17.4 76 55DE350400E 17.4 76 55DE400 6430.00450E 17.4 76 55DE450

15 kV Fuse

10E 17.4 51 175DE010

3214.0015E 17.4 51 175DE01520E 17.4 51 175DE02025E 17.4 51 175DE02530E 17.4 51 175DE030

3290.0040E 17.4 76 175DE04050E 17.4 76 175DE05065E 17.4 76 175DE065

4446.0080E 17.4 76 175DE080100E 17.4 88 175DE100125E 21.14 88 175DE125

6878.00150E 21.14 88 175DE150175E 21.14 88 175DE175200E 21.14 88 175DE200

New!

(Contact your nearest Schneider Electric sales office for current stock quantities.) Price Includes One Set of Three Packed in One Box

Con

tinuo

us

Cur

rent

FuseTypee

Catalog No. $ Price Fuse Type

fCatalog

No. $ Price

5 kV Fuse Refill

10E SM-5S 5SM5010

1472.00

RBA400 405WBAF010

1692.00

15E SM-5S 5SM5015 RBA400 405WBAF01520E SM-5S 5SM5020 RBA400 405WBAF02025E SM-5S 5SM5025 RBA400 405WBAF02530E SM-5S 5SM5030 RBA400 405WBAF03040E SM-5S 5SM5040 RBA400 405WBAF04050E SM-5S 5SM5050 RBA400 405WBAF05065E SM-5S 5SM5065 RBA400 405WBAF06580E SM-5S 5SM5080 RBA400 405WBAF080

100E SM-5S 5SM5100 RBA400 405WBAF100125E SM-5S 5SM5125 RBA400 405WBAF125150E SM-5S 5SM5150 RBA400 405WBAF150175E SM-5S 5SM5175 — —200E SM-5S 5SM5200

1528.00

RBA400 405WBAF200

1758.00250E SM-5S 5SM5250 RBA400 405WBAF250300E SM-5S 5SM5300 RBA400 405WBAF300400E SM-5S 5SM5400 RBA400 405WBAF400

15 kV Fuse Refill

10E SM-5S 15SM5010

1508.00

RBA400 415WBAF010

1732.00

15E SM-5S 15SM5015 RBA400 415WBAF01520E SM-5S 15SM5020 RBA400 415WBAF02025E SM-5S 15SM5025 RBA400 415WBAF02530E SM-5S 15SM5030 RBA400 415WBAF03040E SM-5S 15SM5040 RBA400 415WBAF04050E SM-5S 15SM5050 RBA400 415WBAF05065E SM-5S 15SM5065 RBA400 415WBAF06580E SM-5S 15SM5080 RBA400 415WBAF080

100E SM-5S 15SM5100 RBA400 415WBAF100125E SM-5S 15SM5125 RBA400 415WBAF125150E SM-5S 15SM5150 RBA400 415WBAF150175E SM-5S 15SM5175 — —200E SM-5S 15SM5200

1554.00

RBA400 415WBAF200

1788.00250E SM-5S 15SM5250 RBA400 415WBAF250300E SM-5S 15SM5300 RBA400 415WBAF300400E SM-5S 15SM5400 RBA400 415WBAF400

PE5A Discount Schedule

Modified10/8/08

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 15: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

© 2007 Schneider ElectricAll Rights Reserved

11-15

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Switchgear Masterclad® Metalclad™ (UL Listed); Arc Terminator™Class 6055 / Refer to Catalog 6055CT9901 or Brochure 6055BR9402

Masterclad® Medium Voltage Metalclad™ Switchgear (UL Listed)

The Reliability of a Quality DesignThe quality of Square D® Masterclad medium voltage Metalclad switchgear stems from a design and manufacturing process that focuses on long-term switchgear performance with the highest degree of reliability.Based on specific customer application needs, Schneider Electric engineers and technicians select the appropriate standard sections and bus configurations, with the ability to customize where needed. After the specified circuit breakers, instrument and control power transformers, relays, meters and other components are selected and approved. All are factory-assembled, wired, and tested as a complete assembly.

Type VR Vacuum Circuit BreakerThe VR breaker is a horizontal drawout type designed to provide long life, reduced maintenance, and ease of handling. The Type RI advanced design motor-charged stored energy mechanism is a model of reliability with simplicity-with an operating life exceeding ANSI requirements. The VR circuit breaker is UL labeled and includes a permanently mounted manual charging handle.

Switchgear Construction

• Floor mounted breaker racking mechanism • Standard epoxy supports or optional porcelain supports • Aluminum or copper main bus • Indoor NEMA 1 • Outdoor NEMA 3R • Walk-in • Non walk-in

Arc Terminator™ Arc Extinguishing System

Active system detects and controls the effects of internal arcing faults. It complies with ANSI C37.20.7 requirements for arc resistant switchgear for Type 1, Type 2, and Type 2A.

Benefits

• Prevents pressure buildup• Reduces release of toxic materials• Eliminates need for reinforced switchgear• Elimnates special requirements for buildings or plenums• Minimizes equipment damage• Reduces operating downtime

RatingsNominal voltage (kV) 4.16 7.2 13.8 24.9Maximum voltage (kV) 4.76 8.25 15.0 27.0BIL (kV) 60 95 95 125Frequency (Hz) 50/60 50/60 50/60 50/60Continuous amperes (A) 1200–3000 1200–3000 1200–3000 1200–2000MVA (reference only) 250–350 500 500–750–1000 1250–2000Short-time rating (kA) 3 seconds 36 49 41 23 36 48 25 40Close and latch rating (kA) (peak) 97 132 111 62 97 130 68 108

Two-high Masterclad 5–27 kV Metalclad switchgear

Vacuum VR circuit breaker for Masterclad switchgear

Two-high Masterclad 5–27 kV Metalclad switchgear

Arc-Terminator™ arc extinguising system

Listed metalclad switchgear

New!

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 16: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

11-16 © 2007 Schneider ElectricAll Rights Reserved

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Unit Substations Power-Zone® Model IIIClasses 6010, 6020 / Refer to Handout 6010HO0101 or Brochure 6020BR9401

Unit Substations

Power-Zone® Model III Package Unit Substations

GeneralModel III Power-Zone package unit substations combine a primary switch, dry-type transformer and I-Line® distribution section into a single compact unit. All components are engineered, manufactured and tested by Schneider Electric. The substation is available with UL listing.

The Model III is only 37.25-inches deep and 90-inches high, which allows passing the entire substation through standard size doorways and narrow hallways.

Ventilation is toward the front, at the top of the transformer section, so the unit can be installed against a wall or in a corner without altering or derating.

Model IIIs are ideal for renovations and high rise applications requiring increased customer electrical demand as well as new construction requiring multiple zones and a small footprint.

75–1000 kVA at 480 Volts; 75–500 kVA at 240 VoltsAvailable with primary voltages of 2400–13800 volts. Forced air cooling (AA/FA) provides an additional 33%. Features 220°C insulation and 150°, 115° or 80°C temperature rise. Largest 80° or 115°C rise unit available is 750 kVA.

The secondary circuit breaker distribution section may be equipped with an individually mounted secondary main breaker or an I-Line® distribution panelboard. Branch circuit breakers from 15 amperes FY to PowerPact RLC 1200 ampere may be installed. PowerPact ® molded case circuit breakers M, P, and R frame are available with electronic trip units.

Additional options include CM 3000 and CM 4000 series circuit monitors, PM-800 series power meters, surge arresters, and I-Line plug-on unit with Surgelogic® Transient Voltage Surge Suppression (TVSS).

Incoming Line SectionMost Model IIIs are supplied with a Square D® fused HVL/cc 600 ampere load interrupter switch. The HVL/cc offers the smallest footprint in the industry and is an exclusive sealed interruption type compartmentalized switch. Where switching and overcurrent protection are provided elsewhere, a full-height air-filled terminal chamber can be provided in place of the switch.

Complete Close Coupled Unit Substations AvailableProduct Type Class Nos. Product Section No.

Primary Section

Medium voltage load interrupter switchgear 6040, 6045

11-1Metalclad switchgear 6055Low voltage Power-Style® QED switchboard 2741-2744Air terminal chamber 7421-23, 7310, 7240, 7320

Transformer Section

Open, ventilated dry—Power-Dry™ 7421-23

14-1Open, ventilated dry/cast resin combination—Uni-Cast® 7320Open, ventilated cast resin—Power-Cast® 7310Mineral oil or high fire point fluid—liquid 7240

Secondary Section

Medium voltage load interrupter switchgear 6040

11-1

Metalclad switchgear 6055Medium voltage motor control center 8198Low voltage Power-Style QED switchboard 2741-2744Air terminal chamber 7421,23, 7310, 7240, 7320Low voltage drawout switchgear 6037Low voltage Model 6 motor control centers 8998 17-1

Primary Switch Ratings, Type HVL/ccNominal Voltage 4.16 13.8BIL 60 95Continuous amperes 600 600Interrupting amperes 600 600Fault close (kA asymmetrical) 40 40Momentary current (kA asymmetrical 10 cycles) 40 40Duty-cycle-fault-close (number of operations) 4 4Grounding switch fault close (kA asymmetrical) 40 40Short-time rating (kA asymmetrical 2 seconds) 25 25Dielectric withstand (kV 1 minute) 19 36Electrical endurance (close-open) 100 100Mechanical endurance (close-open) 1000 1000

Unit substation

Model III shown with HVL/cc load interrupter switch

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 17: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

© 2007 Schneider ElectricAll Rights Reserved

11-17

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

Unit Substations Power-Zone® Model III; Distribution SectionClass 6010 / Refer to Catalog 6020CT9401

Transformer SectionSpecial barrel wound dry-type transformers employing resin encapsulated VPI (Vacuum Pressure Impregnation) techniques are used to achieve the low-loss, compact design necessary for the space-saving package substation concept. Class H, 220°C insulation is used throughout. Temperature rise is 150°C as standard, although 80°C or 115°C low temperature premium transformers are available through 750 kVA. Aluminum windings are standard with copper as an option. Four full capacity 2-1/2 percent taps are provided-two above nominal voltage and two below.

Fan cooling is optional. When selected, it increases the capacity rating of the transformer an additional 33 percent. The Model 98 digital controller is employed. This system provides precision control through the use of three high accuracy thermocouple type sensors—one in each phase of the windings.

The controller has a membrane front panel for displaying the temperature of all three phases with individual readings. The hottest phase is automatically displayed. The Model 98 features simple three-button operation with fan, alarm and trip function settings and is Powerlogic® compatible.

Distribution Section

I-Line® Mounted Molded Case Circuit Breakers

Molded case circuit breakers are group mounted in an I-Line panelboard section offering the inherent ease of installation for which the plug-on I-Line circuit breaker has become known. All circuit breakers are quick-make, quick-break, thermal magnetic, permanent trip type and are factory-calibrated and sealed for accurate overcurrent response and maximum short-circuit strength. PowerPact® P and R circuit breakers are available with solid-state Micrologic® trip units. Current limiting high interrupting capacity FI, KI and LI circuit breakers are also available. Circuit breakers may be safely back-fed for use as main circuit breakers. All circuit breakers are UL listed and carry integrated equipment rating when used exclusively with other Square D® circuit breakers in intended assemblies.I-Line panel is available in 1200 amperes. Maximum mounting space is 108 inches. Tin-plated copper bus is standard.

HCR-U 1200 ampere I-Line panelboards can be used for up to 600 Vac. They are Underwriters Laboratories® (UL®) Listed under File E33139.

Contact your nearest Schneider Electric sales office for pricing assistance.

Transformer Basic Insulation LevelsKV Class Primary Voltages BIL 600 Hz Test

1.2 < 600 V Secondary 10 4 kV2.5 2400 20 10 kV5.0 4160, 4800 30 12 kV7.2 6900, 7200 30 12 kV8.7 8320 45 19 kV15.0 12, 12.47, 13.2, 13.8 60 31 kV

Substation Dimensions and Approximate Weights

kVA Temperature Rise° C Dimension "A" Estimated Weight

75 80, 115, 150 48 3600112.5 80, 115, 150 48 3600150 80, 115, 150 48 3600225 80, 115, 150 48 4500300 80, 115, 150 48 4500500 150 48 6000500 80, 115 60 6200750 80, 115, 150 60 67001000 150 60 7500

14.75375 A

79.852028

5.45138

1.5640

2.0051

22.00559

10.46266

31.40798

5.00127

5.50140

8.25210

2.0051

6.00152

85.062161

LiftingJacks

Ventilation Grillunder Removable Cover

HVL/cc™ SwitchTop Feed

RemovableCover

I-LINE PanelboardNameplate

1.125Conduit

Knockouts

Top conduit entrance

Front view

36.00914

2.0051

28.25718

13.50343

8.00203

8.00203

14.75375

4.00102

6.00152

.6316

A

.55 Mounting Holes (4)

RGC, RJC, RLC

1 2 TotalBreaker

MountingSpaceEachSide

PG, PJ, PLPGC, PJC, PLC

QB, QDQG, QJ

FI, KI, JDJG, JJ, JL

Q4, LA, LH

LC, LI, LXLXI, LE

QB, QDQG, QJ

FA,FH,FYHD,HGHJ, HL

1200 A Max. Main Lugs or1200 A Max. Main Breaker

MG, MJ

S N

FA,FH,FYHD,HGHJ, HL

FI, KI, JDJG, JJ, JL

HCR-UBottom conduit entrance

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 18: Section 11 - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/45174-11.pdf · Square D® DIN/E Fuse Selection Tables—HVL 11-14 Fuse Selection Tables Boric Acid Fuses—HVL

www.us.schneider-electric.comFOR CURRENT INFORMATION

11-18 © 2007 Schneider ElectricAll Rights Reserved

11S

WIT

CH

BO

AR

DS

AN

D

SW

ITC

HG

EA

R

MV Controllers and Substation Circuit Breakers

Motorpact™; Powersub® Vacuum Substation Circuit BreakersClasses 8198, 6065 / Refer to Documents 8198CT0201, 8198HO0201, 6065HO9601

Motorpact™ Medium Voltage Motor Controllers (UL Listed)Square D® Motorpact medium voltage motor controllers are designed and manufactured to tackle the toughest power and process control challenges. Our motor controllers feature industry-first innovations that provide unmatched performance, high reliability, low maintenance and exclusive technologies. Motorpact medium voltage motor controllers are designed to provide the most efficient means to control and protect a wide range of applications and may be configured for motor starting, transformer feeders, capacitor feeders or future spaces.

Motorpact controllers are designed to meet or exceed the standards for NEMA ICS3 Part 2, UL Standard 347, and IEC 60470. UL and cULus labels are standard.Starting application for squirrel cage induction motors:• Full voltage non-reversing• Full voltage reversing• Reduced voltage non-reversing

— Auto transformers— Solid state soft start

Enclosures are available in Type 1, 1A, and 3R and feature the smallest footprint in the industry at 14.75 inches wide. Enclosures that are 20-inches and 29.5-inches wide are also available for FVNR.Optional arc resistant Type 2 enclosures are also available.Units are designed as one-high construction for ease of use with a optimum height for the operator controls and isolation switch disconnect handle.Full front and or front and rear accessibility are provided. A full height cable pulling area is standard.Controller voltage ratings range from 2.3–7.2 kV vacuum contactors feature a drawout design and have ratings of 200, 400, 450, and 720 amperes.Options include live line indicators, blown fuse tripping, solid state protective relays, power factor correction capacitors, surge arresters, surge capacitors and a cable grounding switch.

Powersub® Vacuum Substation Circuit Breaker Type FVR (Not UL Listed)

By combining the latest developments in circuit breaker technology with world-renowned quality, Powersub vacuum substation circuit breakers are the most advanced medium voltage circuit breakers available. The Type FVR Powersub circuit breakers include arc-resistant construction and are built to comply with ANSI standards.

Features and Ratings

• Voltage—15–38 kV• 110–200 kV BIL• Ampere Ratings—600, 800, 1200, 2000, 3000, 3500 and 4000• Interrupting amperes—12.5–40 kA (rms symmetrical)• Arc resistant enclosure construction, 2000 amperes and below, based on EEMAC and

IEC test standards• No fans required for 3000 ampere ratings• Interrupting time of three (3) cycles• Hermetically sealed vacuum interrupters

The arc-resistant design takes safety to the next level. In the event of an arc, the arc-resistant construction provides increased safety for personnel working in proximity of the breaker by venting resultant arc by-products and ionized gases upward and away from exterior panels that otherwise may not remain intact and in place. The Powersub circuit breakers also provide superior protection as a result of their high speed operation. You can expect long life from the product as the vacuum interrupter contacts are protected from corroding elements and contamination.

Listed Controllers