Sec. Distr. AutomationRodrigo Braga, Technical Sales Consultant
September 20-21, 2017VAR Partner Day
. AutomationRodrigo Braga, Technical Sales Consultant
21, 2017 I Berlin
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 2
Secondary Distribution AutomationTable of Content
• Scope of a
• SAIDI performance
• Implementation
• Fault and outage management
• Project reference
• Product overview
Rodrigo Braga / Technical Sales Consultant
application 3
performance worldwide 4
Implementation 5
Fault and outage management 8
reference Netze BW 12
Product overview 15
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 3
Secondary Distribution AutomationScope of application
Distribution automation
HVMV
NOP
UHV transmission
UHVHV
LVMV
Rodrigo Braga / Technical Sales Consultant
Distribution automation
ransmission Generation andtransmission (HV)
Distribution (MV)• Distribution substation
Distribution and feederautomation• Transformer station• Pole top-mountedDual characteristics:• Generation• Consumption
Distribution (LV)Dual characteristics:• Generation• Consumption
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 4
Secondary Distribution AutomationTop 5 Cities with best SAIDI performance: 4.59mins/customer
San Francisco115.40
New York City14.35
London49.60
Paris75.00
SAIDI
Rodrigo Braga / Technical Sales Consultant
Top 5 Cities with best SAIDI performance: 4.59mins/customer
Source: KEMA Grid Price and Performance Benchmarking Report 2014
*
*
Amsterdam23.20
Milan36.50
Singapore0.74
Hong Kong2.30
Tokyo5.00
Osaka7.00
Frankfurt7.90
* Highly automated grids
*
*
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 5
Secondary Distribution AutomationImplementation
Rodrigo Braga / Technical Sales Consultant
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 6
Secondary Distribution Automation“The 3 Levels of Intelligence”
§ Signalingtelecommunication of topologicalstates
§ Signalingtelecommunication of topologicalstates§ Measurement
Measurement in real time of line§ Basic Protection
Protection for cable and overheadlines§ Telecontrol
Motorization of the commandelements
Monitoring Control
Rodrigo Braga / Technical Sales Consultant
§ Signalingtelecommunication of topologicalstates§ Measurement
Measurement in real time of line§ Basic Protection
Protection for cable and overheadlines§ Telecontrol
Motorization of the commandelements§ Intelligent Applications
Local automatisms functionalityand Self Healing automation;Volt/VAR control; Load Balancing,Load Management, ATS, …
telecommunication of topological
MeasurementMeasurement in real time of lineBasic ProtectionProtection for cable and overhead
Motorization of the command
Automation
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 7
Secondary Distribution AutomationGrid intelligence in all levels of automation
Rodrigo Braga / Technical Sales Consultant
Grid intelligence in all levels of automation
Distributed solutionIntelligent secondary substationsor pole top installations
Semi-distributed solutionAutomation systems atthe primary substation andfeeder level
Central solutionImplemented in thecontrol center
HolisticCustomized distributionautomation solutionsto fit individual needs
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 8
Secondary Distribution AutomationFault and outage management
Rodrigo Braga / Technical Sales Consultant
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 9
Fault and outage management –Remote monitoring and control of secondary substations
Cable grid 20 kV
Field level
Control center
NOP
Rodrigo Braga / Technical Sales Consultant
secondary substations
Modem
Faultindicator
Faultindicator
Fault
RTU
Modem
Faultindicator
Faultindicator
Fault
RTU
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 10
Fault and outage management –Automated switching for isolation and service
Regional controller
Rodrigo Braga / Technical Sales Consultant
service restoration (cable)
Time zero
Semi-distributed
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 11
Fault and outage management –Automated switching for isolation and service
Regional controller IEC 60870IEC 60870
Fault locationFault isolationService restoration
Rodrigo Braga / Technical Sales Consultant
service restoration (cable)
Less than1 minute
IEC 60870-5-101IEC 60870-5-104
Semi-distributed
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 12
Fault and outage management –Automated switching for isolation and service
NOP
Rodrigo Braga / Technical Sales Consultant
service restoration (OHL)
Time zero
Distributed
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 13
Fault and outage management –Automated switching for isolation and service
IEC 61850-GOOSE
NOP
Rodrigo Braga / Technical Sales Consultant
service restoration (OHL)
Less than 300 ms
Fault locationFault isolationService restoration
Distributed
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 14
Secondary Distribution AutomationArea voltage control and self-healing grid
Rodrigo Braga / Technical Sales Consultant
healing grid – Netze BW, Germany
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 15
Intelligence replaces copper – NiederstettenMaking power grids ready for the future
Solution• Grid monitoring and fault management with intelligent
measuring technology and long-range control for activevoltage stability
• Distributed intelligence with a self-healing functionality –self-healing grid
• Installation of two medium-voltage in-phase regulators,including power quality measurement on the primary andsecondary side, for long-range voltage control
Benefits• Distributed grid intelligence makes operation highly energy-
and cost-efficient• Reduction of outage times• Improvement of voltage stability, including voltage
optimization
Challenge• Distribution grid with long feeders and long outage times• Integration of distributed renewable generation• Problems with voltage stability
Rodrigo Braga / Technical Sales Consultant
Niederstetten, Germany
Project partner: Netze BW - Distribution grid operatorCountry: Germany
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 16
Intelligence replaces copper – NiederstettenOne implementation for different use cases
Customer environment:• Two electrical circuits with 84 distribution substations (19 customer
stations) separated by two normal open points• Up to 18 km-long segments with a large share of overhead lines
(45% cable grid)
Usecases:• Automated switching for isolation and service restoration• Optimization of Volt/ Var Conditions
Implementation:• Control: 1x regional controller based on SICAM• Automation: 9 intelligent distribution substations equipped with
SICAM A8000 and SICAM FCM, 5 SICAM MMUs, 2 Line voltageregulators (MV), including power quality measurement, 2 power qualityanalyzers
Features:Regional controller includes• Self-healing for outage management
• Fault detection• Fault isolation• Reconfiguration
• Area voltage control• Voltage measurement• Control of line voltage regulator
Rodrigo Braga / Technical Sales Consultant
Niederstetten, Germanycases
Regional Controller
NOP
NOP
SLR
SLR
regulators (MV), including power quality measurement, 2 power quality
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 17
Secondary Distribution AutomationProduct overview
Rodrigo Braga / Technical Sales Consultant
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 18
Secondary Distribution AutomationIntelligent Mini Substation
Rodrigo Braga / Technical Sales Consultant
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 19
Intelligent Mini Substation -Intelligent Components
Low-Power Current Transformersaccording IEC60044
Low-Poweraccording IEC600443,25V/√3 @ Ur max. 24kV
Smart Grid RTUSICAM CMICfor Distribution
MCUElectronic switchcontroller in 8DJH
Monitor for Medium Voltage DistributionSystems, SICAM FCM(Feeder Condition Monitor)
Rodrigo Braga / Technical Sales Consultant
Power Current Transformersaccording IEC60044-8, 225mV @ 300A
Power Voltage Transformeraccording IEC60044-7,3,25V/√3 @ Ur max. 24kV
Smart Grid RTUSICAM CMICfor Distribution Automation
MCU - Motor Control UnitElectronic switchcontroller in 8DJH
Monitor for Medium Voltage DistributionSystems, SICAM FCM(Feeder Condition Monitor)
• FITformer® REG• Transformer with LV load
regulation and SICAM CMICas Transformer controllerrange in three steps
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 21
• >100 values can be measured• Graphic display with background illumination• 2 binary output modules• Tolerances: ±0,5 %
• Serial communication: Profibus, Modbus, IEC 60870• Harmonics up to the 21st• Easy configuration with SICAM P Manager• Additional IO-modules (optional)
SICAM P50
SICAM 850
• Serial communication: Modbus, IEC 60870-5-103• Ethernet communication: IEC 61850 and Modbus• Harmonics up to the 40st• Easy configuration via web server and soft keys• 0,2S acc. to IEC 62053-21
Power Quality & MeasurementSICAM P50 & SICAM 850
Rodrigo Braga / Technical Sales Consultant
, IEC 60870-5-103
103Modbus TCP, NTP
Easy configuration via web server and soft keys
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 22
Flexible Feeder Protection & AutomationSIPROTEC 7SC80
Basic functions:• One device for:
• Recloser controller• Switch controller• Capacitor bank controller
• Overcurrent protection• Peer-to-peer communication: IEC 61850• Environmental conditions: –50°C to +85°C• Compliant with high EMC standard
Enhanced Functions:• Jump detector = simplified line differential protection• Self-healing automation – FLISR (fault location isolation service
restoration)• Load balancing by moving the normally open point• Automatic Volt/VAR control/voltage conservation• NERC/CIP security requirements
Simplified engineering:• with graphic tools: FASE and test tool FAST• Web-based HMI with complete remote control
Rodrigo Braga / Technical Sales Consultant
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 23
Secondary Distribution AutomationContact Page
Rodrigo BragaTechnical Sales ConsultantEnergy Management DivisionDigital GridSecondary Distribution AutomationEM DG SDA
Siemens AG
Humboldtstr. 5990459 Nürnberg, Deutschland
E-Mail:[email protected]/ingenuityforlife
Rodrigo Braga / Technical Sales Consultant
Rodrigo BragaTechnical Sales Consultant
Management Division
Distribution AutomationEM DG SDA
Siemens AG
Humboldtstr. 5990459 Nürnberg, Deutschland
[email protected]/ingenuityforlife
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 24
Standard§ Size: 380x600x210§ Weight of Housing: 15,6 kg§ Rows: 3 DIN Rails§ Version A: Cable Bushing / Version B: Connector per field§ BI/BO: up to 128 possible with 8 expansion modules
Secondary Distribution Automation InteroperabilityDistribution Automation Box
Large§ Size: 600x760x210§ Weight of Housing: 32,1 kg§ Rows: 4 DIN Rails§ Customizable§ BI/BO: up to 2.048 I/O -- CP8050 , multiple lines and expansion modules
Compact§ Size: 380x380x210§ Weight of Housing: 9.8 kg§ Rows: 2 DIN Rails§ BI/BO: up to 116 (6 modules)
Rodrigo Braga / Technical Sales Consultant
Secondary Distribution Automation Interoperability
CP8050 , multiple lines and expansion modules
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 25
Secondary Distribution AutomationCost benefit analysis (CBA)
Outage KPI Improvement (SAIFI* & SAIDI
0,00,10,20,30,40,50,60,70,80,91,0
0% 20% 40% 60% 80% 100%
Without FLISR - SAIFI
Without FLISR - SAIDI
With FLISR - SAIFI
With FLISR - SAIDI
Potential to improve key outage KPIs by 80-90% with anautomation degree between 10% to 20%
Source: DISTRIBUTION AUTOMATION SOLUTIONS – IMPACT ON SYSTEM AVAILABILITY IN DISTRIBUTION NETWORKS by O. Schroedel, 2011, Paper
* Disturbance+ Disturance Rodrigo Braga / Technical Sales Consultant
(SAIFI* & SAIDI+)
100%
• Research has shown that there is asignificant improvement of SAIDI and SAIFIonly with 15% to 20% of the grid automated.
• The cost of the automation system representsonly a small percentage of a new lineinstallation or a grid structure change fromoverhead lines to underground cables.
IMPACT ON SYSTEM AVAILABILITY IN DISTRIBUTION NETWORKS by O. Schroedel, 2011, Paper 1117, CIRED
Disturbance FrequencyDisturance Duration
Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 26
Secondary Distribution AutomationCustomer Support
ü SDA HQ Lab for testing and engineering
ü Training on SW tools (e.g. FASE, DIGSI, etc.)
ü Support closer to customer through regional
organization with worldwide presence
Rodrigo Braga / Technical Sales Consultant
SDA HQ Lab for testing and engineering
Training on SW tools (e.g. FASE, DIGSI, etc.)
Support closer to customer through regional
organization with worldwide presence