schedule of work i/c. installation of 7x16 kva, sub-stations for electrification of 7(seven) nos. of...
TRANSCRIPT
-
Ch to: Deposit work with the TTAADC.
Sl No
Description of Items Qty. Unit Rate/Unit () Amount ()
A. Erection of the following items.
1
Erection of 9.0 mtr. Long Steel Tubular Poles(Designation 410: SP-54) conforming to ISS:2713 (P-I & II)-1980 with base plate direct inearth including excavation, refilling andramming etc. as required (1/6th length of thepole to be embedded in earth) and groutingwith CC of ratio 1:2:4 (1 cement : 2 river sand: 4 jhama brick aggregate of 20 mm. nominalsize) ilc supply of cement, sand and brickaggregate complete with excavation, refillingof earth, ramming alongwith centering andshuttering as required (@ 0.273 Cum perSteel Tubular Pole as per TSECLspecification ) etc. and applying paints withready mixed primer (two or more coats) andaluminium paint of approved quality to givean even shade etc. as required as perdirection of the Engineer-in-Charge.
431 No
2
Erection of 8 mtr. long Steel Tubular Poles(Designation 410: SP-54) conforming to ISS:2713 (P-I & II)-1980 with base plate direct inearth including excavation, refilling andramming etc. as required (1/6th length of thepole to be embedded in earth) and groutingwith CC of ratio 1:2:4 (1 cement : 2 river sand: 4 jhama brick aggregate of 20 mm. nominalsize) ilc supply of cement, sand and brickaggregate complete with excavation, refillingof earth, ramming alongwith centering andshuttering as required (@ 0.273 Cum perSteel Tubular Pole as per TSECLspecification ) etc. and applying paints withready mixed primer (two or more coats) andaluminium paint of approved quality to givean even shade etc. as required as perdirection of the Engineer-in-Charge.
381 No
Name of work: Extension of HT line with ACSR Conductor and LT line with 25 mm2 Aerial BunchedCable i/c. installation of 7x16 KVA, Sub-Stations for electrification of 7(seven) nos. of un-electrifiedhabitations having population below 100 at Ataram para habitation of Kakracherra VC, Jugendrapara habitation of Haludia VC, Hadukalak para habitation of Kakracherra V.C., Bangaisi parahabitation of Haludia VC, Rabi para habitation of Kakracherra VC, Biswamani para habitation ofNunacherra VC and Samprai Bahadur para habitation of Nunacherra VC located under thejurisdiction of Nunacherra Census Village of Mungiakami R.D. Block covered by ESD-Mungiakami.(Revised Estimate)
SCHEDULE OF WORK
Signature of Bidder/Condractor Page No 1 of 6
-
3
Erection of painted Stay Set complete directin earth with 16 mm. dia. 1.8 mtr. longpainted stay rod, anchor plate of size 300 X300 X 8 mm. thick, turn buckle of length 356mm. with 300 mm. long threaded adjustable16 mm. dia. MS rod , thimble, guy insulatoras per IS specification, hot dip (heavy duty)galvanized stay stranded wire of size 7/2.5mm. fastened with stay clamps as required. (including supply of MS clamp & Nuts & Boltsas reqd) and Grouting of stay set with CC ofratio 1 :2:4 (1 cement: 2 river sand: 4 jhamabrick aggregate of 20 mm. nominal size) ilcsupply of cement, sand and brick aggregatecomplete with excavation, refilling of earth,ramming alongwith centering and shutteringas required ( @ 0.119 Cum per stay set asper TSECL Specification)
650 Set
4
Erection of 2.8 mtr. long made of 75 X 40 X40 X 6 mm. MS Channel for Sub-StationGOS, DOF bracket as per direction of theEngineer-in-Charge.
28 No
5Erection of .3 mtr. long S/P top bracket madeof 75 X 40 X 40 X 6 mm. MS Channel as perdirection of the Engineer-in-Charge.
127 No
6Erection of 1.2 mtr. long S/P bottom bracketmade of 75 X 40 X 40 X 6 mm. MS Channelas per direction of the Engineer-in-Charge.
127 No
7Erection of 2.2 mtr. long D/P bracket made of75 X 40 X 40 X 6 mm. MS Channel as perdirection of the Engineer-in-Charge.
136 No
8
Erection of 2.8 mtr long made of100x50x50x6 mm. MS Channel fortransformer base as per direction of theEngineer-in-Charge.
21 Nos
9
Erection of 0.8 mtr long made of100x50x50x6 mm. MS Channel fortransformer base as per direction of theEngineer-in-Charge.
14 Nos
10
Erection of 2.8 mtr long made of 65x65x6mm. MS Angle for cross arm for GOShandle bracket as per direction of theEngineer-in-Charge.
7 No
11Erection of 3.2 mtr. long Sub-Station guardbracket by 65x65x6 mm MS Angle as perdirection of the Engineer-in-Charge.
7 Nos
12Erection of 1.5 mtr. long single pole guardbracket by 65x65x6 mm MS Angle as perdirection of the Engineer-in-Charge.
127 Nos
13Erection of 2.5 mtr. long double pole guardbracket by 65x65x6 mm MS Angle as perdirection of the Engineer-in-Charge.
136 Nos
Signature of Bidder/Condractor Page No 2 of 6
-
14
Erection of Polimerik Disc Insulator Ball andSocket type for 11 KV system (EMS-45 KN)conforming to ISS:731/1971 in angle anddead end locations including tension fittingsof EMS-45 KN to accommodate the relevantACSR conductor size along with nuts andbolts, washer etc. as required in complete asper direction of the Engineer-in-Charge.
768 No
15
Erection of Polimerik Pin Insulator includingG.I Pin for 11 KV system with mechanicalstrength of 10 KN conforming toISS:731/1971 with hot dip galvanized M.Sforged 11 KV G.I pin alongwith galvanizedhexagonal nuts, G.I flat washer and G.Ispring washer conforming to ISS: 2486(P-II)/1974 etc. as required in complete as perdirection of the Engineer-in-Charge.
786 No
16
Erection of 11 KV, 200 Amps. 1-phase GOSwitch complete i/c fixing horizontally &vertically operating pipe & operating handlewith nuts & bolts etc. as required.
14 Set
17Erection of 11 KV 1-phase DO Fusecomplete with nuts & bolts etc. as required.
7 Set
18
Erection of 9 KV, 5 KA single pole metaloxide gapless type Lightening Arrestor i/c.necessary connection complete as perdirection of the Engineer-in Charge.
77 Set
19
Laying, hoisting & stringing of ACSR(6/1/2.59 mm) Weasel Conductor includingbinding, jumpering, etc. as reqduired & as per direction of the Engineer-in-Charge.
52 Km
20
Laying, hoisting & stringing of 8 SWG G.I.wire as per ISS : 280/1978 amended latestwith heavy coating as per ISS : 4826 I 1968of tensile strength 55 to 95 Kgf/mm i/cfastening with cross arm & metallic parts forearth continuity wire and metal parts to earthelectrode as per direction of the Engineer-in-Charge.
33.5 Km
21
Laying, hoisting and stringing of 1.1 KVClass, LT , Aerial Bunched Cable of size1CX25+1CX16+1X25 sqmm for LT Overhead line on existing pole as required as perdirection of the Engineer-in-Charge.
15 Ckm
22
Erection and fitting fixing of LT InsulationPiercing Connectors (IPC) for makingTee/Tap-off/Service connectors to anABC/Bare Overhead Line suitable for LT ABCable 25 sq mm to 95 sq mm
496 Nos
Signature of Bidder/Condractor Page No 3 of 6
-
23
Erection & fitting fixing of SuspensionAssembly Comprising of 'suspensionbracket', movable connecting links,galvanised suspension clamp, bracket clamp,nuts & bolts (Suitable for 25-95 sq mm baremessenger wire) on existing pole with thehelp of galvanised clamp (made of 2nos,50X6mm Flat) and nuts & bolts includingsupply of galvanised clamp, nuts & bolts etc.for LT AB Cable.
304 Nos
24
Erection & fitting fixing of DeadEnd/Anchoring Assembly comprising oftension bracket wedge type, galvanisedtension clamp, flexible stain steel rope forfixing of tension clamp (Suitable for 25-95 sqmm bare messenger wire) on existing polewith the help of galvanised Clamp (made of2nos, 50X6mm Flat) and nuts & boltsincluding supply of galvanised clamp, nuts &bolts etc. (For LT AB Cable)
420 Nos
25
Erection & Fitting Fixing of galvanised steelmade 'Eye Hook' with hot dip galvanised nuts& bolts.(Suitable for all size cable) for LT ABCable.
730 Nos
26
Erection & Commissioning of pole mounted 1-phase, 200 Amps all weather proof FRP multiconnection LT SERVICE MAINDISTRIBUTION BOXES
124 Nos
27Erection of Pre-Insulated Jointing sleeve for25 sqmm LT AB Cable.
156 Nos
28Erection of Pre-Insulated Bi-metallic Socketfor 25 sqmm LT AB Cable.
156 Nos
29
Supply and erection of Earthing Set as perISS : 3043 of 1966 and with latestamendment if any, 2.5 mtr long G.I. pipe (ISImarked) of 40 mm diameter with suitableholes on pipe circumference including a pairof clamps (made of 50 X 6 mm M.S. flat),galvanized nuts & bolts along with alternatelayers of salt & charcoal including supply of4.0 mtr long, 12mm dia PVC pipe for eachearthing set etc. as required and as perdirection of the Engineer-in-Charge.
184 Set
30
Erection & commissioning of 16 KVA, 50 HZ,outdoor type 11/0.433 KV AC DistributionTransformer on Sub-Station Channel base ata height of 2440 mm (approx) above GroundLevel with required connection by ACSR from11 KV line to Transformer via GOS & DOFfastened straining screw, clamp, nuts & boltsas required as per Technical Specification.
7 Nos
Signature of Bidder/Condractor Page No 4 of 6
-
31
Erection of PVC Cable 70 sqmm i/c fittingfixing 100 Ampere cut out on wooden plankmaking connection from Transformer LT sideto overhead LT Line via fuse unit ofunarmored PVC cable 1100-V gradeconforming to ISS: 1554 (P-I) /1988 of thefollowing sizes and the cables shall beproperly crimped by bi-metallic lugs atcontact areas as per direction of the Engineer-in-Charge. ( Wooden Plank 500X300X25 mmwill be supplied by the Contractor)
7 Job
32
Providing BPL Service Connection along witherection and supply of 1.1KV PVC 2.5 Sq.mm., 1 Core or two 1Core Cable (ServiceWire), GI Wire 10SWG (for ServiceConnection), GI Wire 8SWG (for CoilEarthing), Real Insulator, Single PhaseEnergy Meter, 5-20 Amps (To be Suppliedby TSECL), Cut out 16 Amps., 16 AmpsICDP Main Switch/ Main Switch make Bajaj,Crompton and Havells, 8x12 WoodenBoard, 4x4 Wooden Board, 5 Amps. Switch,5 Amps. Angle Holder, Retrofit LED Lamp 9Watts, Wooden batton 1/PVC Casing (8 MtrLump sum), Wooden Plank etc. as required10 (1 Mtr Lump sum), 1.5 sq. mm. PVC Wire(Single Core 650 Volt grade) with link clip &nails etc. as required, Coil earthing includingmaking of pit, refilling, fabrication, erection,connection etc. as required with supply ofsalt, charcoal & PVC pipe 3 mtr. long to coverearth wire above ground level excludingsupply of G.I. Wire as per direction of theEngineer-in-Charge.
124 No
33
Providing of Sub-Station protective fencing ofsize 2X3 mtr. And height 1.5 mtr. as perengineer requirement by 65X65X6 mm MSAngle post of height 2 mtr. Horizontal bar2X3 mtr and 2X2 mtr. And top angle posts by50X50X6 mm MS angle and two part MSGrill door of size 1.2X1.4 mtr with lockingarrangement i/c necessary grouting andpainted aluminium paint over red oxidepriming of approved quality as required asper Technical Specification.
7 Job
34
Cutting, clearing & disposal of jungle/tree ofany girth from 3(three) meter either side ofHT/LT line of providing required vertical andhorizontal clearance as per provision of I.E.Rule.
62 KM
B Supply of the following materials
1Fabricated bracket clamps 50x6 mm MS Flat(assorted sizes) i/c. holes as per requirementby Drill Machine.
1051 Nos
Signature of Bidder/Condractor Page No 5 of 6
-
2Stay Clamps 50x6 mm MS Flat i/c Nuts &Bolts etc as required.
650 Pair
3 70/95 sq. mm. Bi-metallic Lugs 70 Nos
4 Nuts & Bolts (Assorted Size) 600 Kg
5 Polythin Pipe 1/2" dia. for Pipe Earthing 736 mtr
6 Reel Insulator (4-10 sqmm) 2500 Nos
7Galvanized Steel made Eye Hook with hotdip galvanized nuts & bolts for LT AB Cable
730 Nos
C
Carrying of the following steel tubularPole from Electrical Store Sub-Division,A.D. Nagar, Agartala to work site withinthe administrative jurisdiction ofMungiakami R.D. Block by mechanicaltransport, hand cart & manual labour etcas required i/c. loading, unloading &stacking (i/c. river / cherra crossing ifrequired) etc. as per direction of theEngineer-in-Charge.
1 9 mtr long steel tubular pole 431 nos
2 8 mtr long Steel tubular pole 381 nos
D
Carrying of the Line Materials andTransformer etc from Electrical Store Sub-Division, AD Nagar, Agartala to work sitevia. ESD-Mungiakami storeyard within theadministrative jurisdiction of MungiakamiR.D. Block by mechanical transport,hand cart & manual labour etc. asrequired i/c. loading, unloading, stackingetc as required.
1 Line Materials, Transformer etc. 15 Trips
E
Numbering of Pole/DT with black Japperpaint after applying priming coats by redoxide primer followed by a painting 2 ormore coats with synthetic enamel paint(Yellow Colour) of approved quality withina area of 8"X14" on pole /DT as requiredas per direction of the Engineer-in-Charge.
a 8 mtr Long Steel Tubular Pole 381 Nos
b16 KVA, 1-phase 11/0.433 KV DistributionTransformer
7 Nos
Manager Deputy General ManagerESD-Mungiakami Electrical Division, Teliamura
TSECL, Khowai District TSECL, Khowai District
Total =
Signature of Bidder/Condractor Page No 6 of 6
Sheet3
Comparative Statement
ABSTRACT
Name of work: Extension of 11 KV line by under ground XLPE cable for emergency power connection to the Intake well and treatment plant under Khowai Electrical Sub-division
Ch to : Deposit work
NIT No : DGM/ED-X/KH/12-13/04 dated, 24.04.2013 (Sl. No.: 1)
Estimated Cost Put to the Tender: Rs. 23, 11, 027/-
Tender form sold : 3 (Three)
Tender form received : 2 (Two)
Tender form found formal : 2 (Two)
Tender form found informal : Nil
Sl. No.DescriptionAs per EstimateSri Dilip Kumar Kar [1/2]Sri Sudhangshu Bhattacharjee [2/2]
1Amount of Carrying of PART -'A'000
2Amount of Supply of PART -'B'000
3Amount of Erection of PART-'B'000
4Taxes and dutiesIncludedIncludedIncluded
GRAND TOTAL000
Say,Rs.23, 11, 027/-Rs.25, 25, 994/-Rs.26, 48, 797/-
1st Lowest2nd Lowest
Remarks: With a view to extension of 11 KV line by under ground XLPE cable for emergency power connection to the Intake well and treatment plant under Khowai Electrical Sub-division, a tender vide NIT No: DGM/ED-X/KH/12-13/04 dated, 24.04.2013 (Sl. No.: 1) was invited. After that, 3 (three) numbers of bid documents were sold to the intended bidders namely, 1] Sri Dilip Kumar Kar, 2] Sri Ashish Debnath, and 3] Sri Sudhangshu Bhattacharjee, against receipt of required cost. But only 2 (two) bidders namely, Sri Dilip Kumar Kar and Sri Sudhangshu Bhattacharjee have submitted the filled-in bid document within the stipulated date and time with required documents. On scrutiny, bid documents of both the bidders were found formal. Thereafter, a Comparative Statement (C.S.) has been prepared. From the C. S., it may be seen that Sri Dilip Kumar Kar has become the 1st lowest bidder and his tender value is Rs.25, 25, 994/- (Rupees twenty five lacs twenty five thousand nine hundred and ninety four only) inclusive of all taxes and duties which is 9.302% (approx.) higher than the estimated cost put to the tender. Now, the matter is submitted before the authority for decision please.
Draft Prepared byChecked by
(Er. S. Debnath)(Er. N. Debbarma)(Er. K.L. Das)
Manager (Electrical), Gr. ASr. Manager (Electrical)Deputy General Manager
Electrical Division No-X, KhowaiElectrical Division No-X, KhowaiElectrical Division No-X, Khowai
Sheet2 (2)
Name of work: Extension of HT line with ACSR Conductor and LT line with 25 mm2 Aerial Bunched Cable i/c. installation of 7x16 KVA, Sub-Stations for electrification of 7(seven) nos. of un-electrified habitations having population below 100 at Ataram para habitation of Kakracherra VC, Jugendra para habitation of Haludia VC, Hadukalak para habitation of Kakracherra V.C., Bangaisi para habitation of Haludia VC, Rabi para habitation of Kakracherra VC, Biswamani para habitation of Nunacherra VC and Samprai Bahadur para habitation of Nunacherra VC located under the jurisdiction of Nunacherra Census Village of Mungiakami R.D. Block covered by ESD-Mungiakami. (Revised Estimate)
Ch to: Deposit work with the TTAADC.
SCHEDULE OF WORK
Sl NoDescription of ItemsQty.UnitRate/Unit ()Amount ()
A.Erection of the following items.
1Erection of 9.0 mtr. Long Steel Tubular Poles (Designation 410: SP-54) conforming to ISS: 2713 (P-I & II)-1980 with base plate direct in earth including excavation, refilling and ramming etc. as required (1/6th length of the pole to be embedded in earth) and grouting with CC of ratio 1:2:4 (1 cement : 2 river sand : 4 jhama brick aggregate of 20 mm. nominal size) ilc supply of cement, sand and brick aggregate complete with excavation, refilling of earth, ramming alongwith centering and shuttering as required (@ 0.273 Cum per Steel Tubular Pole as per TSECL specification ) etc. and applying paints with ready mixed primer (two or more coats) and aluminium paint of approved quality to give an even shade etc. as required as per direction of the Engineer-in-Charge.431No
2Erection of 8 mtr. long Steel Tubular Poles (Designation 410: SP-54) conforming to ISS: 2713 (P-I & II)-1980 with base plate direct in earth including excavation, refilling and ramming etc. as required (1/6th length of the pole to be embedded in earth) and grouting with CC of ratio 1:2:4 (1 cement : 2 river sand : 4 jhama brick aggregate of 20 mm. nominal size) ilc supply of cement, sand and brick aggregate complete with excavation, refilling of earth, ramming alongwith centering and shuttering as required (@ 0.273 Cum per Steel Tubular Pole as per TSECL specification ) etc. and applying paints with ready mixed primer (two or more coats) and aluminium paint of approved quality to give an even shade etc. as required as per direction of the Engineer-in-Charge.381No
3Erection of painted Stay Set complete direct in earth with 16 mm. dia. 1.8 mtr. long painted stay rod, anchor plate of size 300 X 300 X 8 mm. thick, turn buckle of length 356 mm. with 300 mm. long threaded adjustable 16 mm. dia. MS rod , thimble, guy insulator as per IS specification, hot dip (heavy duty) galvanized stay stranded wire of size 7/2.5 mm. fastened with stay clamps as required. ( including supply of MS clamp & Nuts & Bolts as reqd) and Grouting of stay set with CC of ratio 1 :2:4 (1 cement: 2 river sand: 4 jhama brick aggregate of 20 mm. nominal size) ilc supply of cement, sand and brick aggregate complete with excavation, refilling of earth, ramming alongwith centering and shuttering as required ( @ 0.119 Cum per stay set as per TSECL Specification)650Set
4Erection of 2.8 mtr. long made of 75 X 40 X 40 X 6 mm. MS Channel for Sub-Station GOS, DOF bracket as per direction of the Engineer-in-Charge.28No
5Erection of .3 mtr. long S/P top bracket made of 75 X 40 X 40 X 6 mm. MS Channel as per direction of the Engineer-in-Charge.127No
6Erection of 1.2 mtr. long S/P bottom bracket made of 75 X 40 X 40 X 6 mm. MS Channel as per direction of the Engineer-in-Charge.127No
7Erection of 2.2 mtr. long D/P bracket made of 75 X 40 X 40 X 6 mm. MS Channel as per direction of the Engineer-in-Charge.136No
8Erection of 2.8 mtr long made of 100x50x50x6 mm. MS Channel for transformer base as per direction of the Engineer-in-Charge.21Nos
9Erection of 0.8 mtr long made of 100x50x50x6 mm. MS Channel for transformer base as per direction of the Engineer-in-Charge.14Nos
10Erection of 2.8 mtr long made of 65x65x6 mm. MS Angle for cross arm for GOS handle bracket as per direction of the Engineer-in-Charge.7No
11Erection of 3.2 mtr. long Sub-Station guard bracket by 65x65x6 mm MS Angle as per direction of the Engineer-in-Charge.7Nos
12Erection of 1.5 mtr. long single pole guard bracket by 65x65x6 mm MS Angle as per direction of the Engineer-in-Charge.127Nos
13Erection of 2.5 mtr. long double pole guard bracket by 65x65x6 mm MS Angle as per direction of the Engineer-in-Charge.136Nos
14Erection of Polimerik Disc Insulator Ball and Socket type for 11 KV system (EMS-45 KN) conforming to ISS:731/1971 in angle and dead end locations including tension fittings of EMS-45 KN to accommodate the relevant ACSR conductor size along with nuts and bolts, washer etc. as required in complete as per direction of the Engineer-in-Charge.768No
15Erection of Polimerik Pin Insulator including G.I Pin for 11 KV system with mechanical strength of 10 KN conforming to ISS:731/1971 with hot dip galvanized M.S forged 11 KV G.I pin alongwith galvanized hexagonal nuts, G.I flat washer and G.I spring washer conforming to ISS: 2486(P-II)/1974 etc. as required in complete as per direction of the Engineer-in-Charge.786No
16Erection of 11 KV, 200 Amps. 1-phase GO Switch complete i/c fixing horizontally & vertically operating pipe & operating handle with nuts & bolts etc. as required.14Set
17Erection of 11 KV 1-phase DO Fuse complete with nuts & bolts etc. as required.7Set
18Erection of 9 KV, 5 KA single pole metal oxide gapless type Lightening Arrestor i/c. necessary connection complete as per direction of the Engineer-in Charge.77Set
19Laying, hoisting & stringing of ACSR (6/1/2.59 mm) Weasel Conductor including binding, jumpering, etc. as reqduired & as per direction of the Engineer-in-Charge.52Km
20Laying, hoisting & stringing of 8 SWG G.I. wire as per ISS : 280/1978 amended latest with heavy coating as per ISS : 4826 I 1968 of tensile strength 55 to 95 Kgf/mm i/c fastening with cross arm & metallic parts for earth continuity wire and metal parts to earth electrode as per direction of the Engineer-in-Charge.33.5Km
21Laying, hoisting and stringing of 1.1 KV Class, LT , Aerial Bunched Cable of size 1CX25+1CX16+1X25 sqmm for LT Overhead line on existing pole as required as per direction of the Engineer-in-Charge.15Ckm
22Erection and fitting fixing of LT Insulation Piercing Connectors (IPC) for making Tee/Tap-off/Service connectors to an ABC/Bare Overhead Line suitable for LT AB Cable 25 sq mm to 95 sq mm496Nos
23Erection & fitting fixing of Suspension Assembly Comprising of 'suspension bracket', movable connecting links, galvanised suspension clamp, bracket clamp, nuts & bolts (Suitable for 25-95 sq mm bare messenger wire) on existing pole with the help of galvanised clamp (made of 2nos, 50X6mm Flat) and nuts & bolts including supply of galvanised clamp, nuts & bolts etc. for LT AB Cable.304Nos
24Erection & fitting fixing of Dead End/Anchoring Assembly comprising of tension bracket wedge type, galvanised tension clamp, flexible stain steel rope for fixing of tension clamp (Suitable for 25-95 sq mm bare messenger wire) on existing pole with the help of galvanised Clamp (made of 2nos, 50X6mm Flat) and nuts & bolts including supply of galvanised clamp, nuts & bolts etc. (For LT AB Cable)420Nos
25Erection & Fitting Fixing of galvanised steel made 'Eye Hook' with hot dip galvanised nuts & bolts.(Suitable for all size cable) for LT AB Cable.730Nos
26Erection & Commissioning of pole mounted 1-phase, 200 Amps all weather proof FRP multi connection LT SERVICE MAIN DISTRIBUTION BOXES124Nos
27Erection of Pre-Insulated Jointing sleeve for 25 sqmm LT AB Cable.156Nos
28Erection of Pre-Insulated Bi-metallic Socket for 25 sqmm LT AB Cable.156Nos
29Supply and erection of Earthing Set as per ISS : 3043 of 1966 and with latest amendment if any, 2.5 mtr long G.I. pipe (ISI marked) of 40 mm diameter with suitable holes on pipe circumference including a pair of clamps (made of 50 X 6 mm M.S. flat), galvanized nuts & bolts along with alternate layers of salt & charcoal including supply of 4.0 mtr long, 12mm dia PVC pipe for each earthing set etc. as required and as per direction of the Engineer-in-Charge.184Set
30Erection & commissioning of 16 KVA, 50 HZ, outdoor type 11/0.433 KV AC Distribution Transformer on Sub-Station Channel base at a height of 2440 mm (approx) above Ground Level with required connection by ACSR from 11 KV line to Transformer via GOS & DOF fastened straining screw, clamp, nuts & bolts as required as per Technical Specification.7Nos
31Erection of PVC Cable 70 sqmm i/c fitting fixing 100 Ampere cut out on wooden plank making connection from Transformer LT side to overhead LT Line via fuse unit of unarmored PVC cable 1100-V grade conforming to ISS: 1554 (P-I) /1988 of the following sizes and the cables shall be properly crimped by bi-metallic lugs at contact areas as per direction of the Engineer-in-Charge. ( Wooden Plank 500X300X25 mm will be supplied by the Contractor)7Job
32Providing BPL Service Connection along with erection and supply of 1.1KV PVC 2.5 Sq. mm., 1 Core or two 1Core Cable (Service Wire), GI Wire 10SWG (for Service Connection), GI Wire 8SWG (for Coil Earthing), Real Insulator, Single Phase Energy Meter, 5-20 Amps (To be Supplied by TSECL), Cut out 16 Amps., 16 Amps ICDP Main Switch/ Main Switch make Bajaj, Crompton and Havells, 8x12 Wooden Board, 4x4 Wooden Board, 5 Amps. Switch, 5 Amps. Angle Holder, Retrofit LED Lamp 9 Watts, Wooden batton 1/PVC Casing (8 Mtr Lump sum), Wooden Plank etc. as required 10 (1 Mtr Lump sum), 1.5 sq. mm. PVC Wire (Single Core 650 Volt grade) with link clip & nails etc. as required, Coil earthing including making of pit, refilling, fabrication, erection, connection etc. as required with supply of salt, charcoal & PVC pipe 3 mtr. long to cover earth wire above ground level excluding supply of G.I. Wire as per direction of the Engineer-in-Charge.124No
33Providing of Sub-Station protective fencing of size 2X3 mtr. And height 1.5 mtr. as per engineer requirement by 65X65X6 mm MS Angle post of height 2 mtr. Horizontal bar 2X3 mtr and 2X2 mtr. And top angle posts by 50X50X6 mm MS angle and two part MS Grill door of size 1.2X1.4 mtr with locking arrangement i/c necessary grouting and painted aluminium paint over red oxide priming of approved quality as required as per Technical Specification.7Job
34Cutting, clearing & disposal of jungle/tree of any girth from 3(three) meter either side of HT/LT line of providing required vertical and horizontal clearance as per provision of I.E. Rule.62KM
BSupply of the following materials
1Fabricated bracket clamps 50x6 mm MS Flat (assorted sizes) i/c. holes as per requirement by Drill Machine.1051Nos
2Stay Clamps 50x6 mm MS Flat i/c Nuts & Bolts etc as required.650Pair
370/95 sq. mm. Bi-metallic Lugs70Nos
4Nuts & Bolts (Assorted Size)600Kg
5Polythin Pipe 1/2" dia. for Pipe Earthing736mtr
6Reel Insulator (4-10 sqmm)2500Nos
7Galvanized Steel made Eye Hook with hot dip galvanized nuts & bolts for LT AB Cable730Nos
CCarrying of the following steel tubular Pole from Electrical Store Sub-Division, A.D. Nagar, Agartala to work site within the administrative jurisdiction of Mungiakami R.D. Block by mechanical transport, hand cart & manual labour etc as required i/c. loading, unloading & stacking (i/c. river / cherra crossing if required) etc. as per direction of the Engineer-in-Charge.
19 mtr long steel tubular pole431nos
28 mtr long Steel tubular pole381nos
DCarrying of the Line Materials and Transformer etc from Electrical Store Sub-Division, AD Nagar, Agartala to work site via. ESD-Mungiakami storeyard within the administrative jurisdiction of Mungiakami R.D. Block by mechanical transport, hand cart & manual labour etc. as required i/c. loading, unloading, stacking etc as required.
1Line Materials, Transformer etc.15Trips
ENumbering of Pole/DT with black Japper paint after applying priming coats by red oxide primer followed by a painting 2 or more coats with synthetic enamel paint (Yellow Colour) of approved quality within a area of 8"X14" on pole /DT as required as per direction of the Engineer-in-Charge.
a8 mtr Long Steel Tubular Pole381Nos
b16 KVA, 1-phase 11/0.433 KV Distribution Transformer7Nos
Total =
ManagerDeputy General Manager
ESD-MungiakamiElectrical Division, Teliamura
TSECL, Khowai DistrictTSECL, Khowai District
&LSignature of Bidder/Condractor&CPage No &P of 6