© 2020 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com Page 1/8 Rev. 12/15/20 COL-SRP-ins Scaler™ Instruction Manual Scaler EDGE-LIT FLAT PANEL IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following: • READ AND FOLLOW ALL SAFETY INSTRUCTIONS. • Do not use outdoors (this item may be omitted if the product is suitable for outdoor use). • Do not mount near gas or electric heaters. • Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel. • The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. • Do not use this equipment for other than intended use. WARNINGS: • This product contains chemicals known to the state of California to cause cancer, birth defects and/or other reproductive harm. Thoroughly wash hands after installing, handling, cleaning, or otherwise touching this product. • Contact Hubbell Lighting, Inc. for information and direction before relamping or replacing this light fixture. • Disconnect power before installing or servicing. Observe all precautions usually followed when dealing with high voltage equipment when installing or servicing this light fixture. • The product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and the hazards involved. • Protect all wiring connections with approved insulators rated 600V / 90°C (by others). • Selected fixture voltage must match supply line voltage. SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE Upon receipt of this fixture, thoroughly inspect it for any damage. If any is found, the carrier should be notified and held accountable. NOTE: Components shown in images are representative only and may vary based on the configuration ordered. CONTENTS: 1. Labeling & Markings 2. T-Grid installation Diagram 3. Installation Method 1: Recessed Mounting a. Wiring Connection 4. Installation Method 2: Luminaire Fitting a. Wiring Connection 5. Installation Method 3: Cable Mount — Non-Power Feed Suspension Kit 6. Installation Method 4: Cable Mount — Power Feed Suspension Kit 7. NX Distributed Intelligence™ Controls 8. Battery Backup Option (ELL14) 9. Battery Backup Self-Test Option (ELL14ST)

Upload: others

Post on 02-Mar-2021

15 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Scaler - hubbellcdn.com · volts xxxxxxxxxxxxxxxxxxxx hz xxxxx amps xxxxxxxxxxxxxxxxxxxxx lamp xxxxx xxxxxxxxxxxxxx suitable for xxxx locations.min xxxx supply conductors. max mntg

© 2020 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 1/8 Rev. 12/15/20COL-SRP-ins

Scaler™ Instruction Manual

ScalerEDGE-LIT FLAT PANEL

IMPORTANT SAFEGUARDSWhen using electrical equipment, basic safety precautions should always be followed including the following:• READ AND FOLLOW ALL SAFETY INSTRUCTIONS.• Do not use outdoors (this item may be omitted if the product is suitable for outdoor use).• Do not mount near gas or electric heaters.• Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.• Do not use this equipment for other than intended use.

WARNINGS:• This product contains chemicals known to the state of California to cause cancer, birth defects and/or other reproductive harm. Thoroughly wash

hands after installing, handling, cleaning, or otherwise touching this product.• Contact Hubbell Lighting, Inc. for information and direction before relamping or replacing this light fixture.• Disconnect power before installing or servicing. Observe all precautions usually followed when dealing with high voltage equipment when installing

or servicing this light fixture.• The product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the

product and the hazards involved.• Protect all wiring connections with approved insulators rated 600V / 90°C (by others).• Selected fixture voltage must match supply line voltage.

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCEUpon receipt of this fixture, thoroughly inspect it for any damage. If any is found, the carrier should be notified and held accountable.

NOTE: Components shown in images are representative only and may vary based on the configuration ordered.

CONTENTS:

1. Labeling & Markings2. T-Grid installation Diagram3. Installation Method 1: Recessed Mounting

a. Wiring Connection4. Installation Method 2: Luminaire Fitting

a. Wiring Connection5. Installation Method 3: Cable Mount — Non-Power Feed Suspension Kit6. Installation Method 4: Cable Mount — Power Feed Suspension Kit7. NX Distributed Intelligence™ Controls8. Battery Backup Option (ELL14)9. Battery Backup Self-Test Option (ELL14ST)

Page 2: Scaler - hubbellcdn.com · volts xxxxxxxxxxxxxxxxxxxx hz xxxxx amps xxxxxxxxxxxxxxxxxxxxx lamp xxxxx xxxxxxxxxxxxxx suitable for xxxx locations.min xxxx supply conductors. max mntg

© 2020 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 2/8 Rev. 12/15/20COL-SRP-ins

Scaler™ Instruction Manual

ScalerEDGE-LIT FLAT PANEL

LABELING & MARKINGS(Actual labeling position may vary)

T-GRID INSTALLATION DIAGRAM(Actual grid installation conditions may vary)

93113962

CAUTION

THIS UNIT HAS MORE THAN ONE POWER SUPPLY

CONNECTION POINT. TO REDUCE THE RISK OF

ELECTRIC SHOCK, DICONNECT BOTH THE BRANCH

CIRCUIT BREAKERS OR FUSES AND

EMERGENCY POWER SUPPLIES BEFORE SERVICING.

ATTENCION

RISQUE DE CHOC COUPER L'ALIMENTATION ET

NEUTRALISER LA BATTERIE D'ACUMULATEURS

AVANT DE PROCEDUER A LA REPARATION DU

BALLASTNECESSITE LA RECONNEXION DE

CONDUCTEURS QUI PEUVENT ETRE SOUS TENSION

93113963

EMERGENCY LIGHTINGAND POWER EQUIPMENT

LUMIÈRES DʼURGENCE ETÉQUIPEMENT DE PUISSANCE

E82903 56B5 TJ

(93098509)

CAT NO. XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXVOLTS XXXXXXXXXXXXXXXXXXXX Hz XXXXXAMPS XXXXXXXXXXXXXXXXXXXXXLAMP XXXXX XXXXXXXXXXXXXXSUITABLE FOR XXXX LOCATIONS. MIN XXXX SUPPLYCONDUCTORS. MAX MNTG HGT 22-FTOUTPUT OPERATES LUMINAIRE 90 MINUTES.CONVIENT AUX ENDROITS XXXX. APROPIADO PARAXXXX.LES FILS D'ALIMENTATION XXXX MIN.CONDUCTORES DE SUMINISTRO MIN XXXX.HAUTEURMAXIMUM DE MONTAGE 6.7M. LA SORTIE FONCTIONNELE LUMINAIRE 90 MINUTES.

XXX XX XXXX

XXXXXXXXXXXXXXX

SRP FIXTURE - LABELING & MARKINGS(Actual labeling position may vary)

Hubbell Lighting Inc.

This device complies with Part 15 of the FCC Rules.

Operation is subject to the following conditions:

(1) This device may not cause harmful interferences, and

(2) This device must accept any interference received,

including interference that may cause undesired

operation.

93113962

CAUTION

THIS UNIT HAS MORE THAN ONE POWER SUPPLY

CONNECTION POINT. TO REDUCE THE RISK OF

ELECTRIC SHOCK, DICONNECT BOTH THE BRANCH

CIRCUIT BREAKERS OR FUSES AND

EMERGENCY POWER SUPPLIES BEFORE SERVICING.

ATTENCION

RISQUE DE CHOC COUPER L'ALIMENTATION ET

NEUTRALISER LA BATTERIE D'ACUMULATEURS

AVANT DE PROCEDUER A LA REPARATION DU

BALLASTNECESSITE LA RECONNEXION DE

CONDUCTEURS QUI PEUVENT ETRE SOUS TENSION

93113963

EMERGENCY LIGHTINGAND POWER EQUIPMENTLUMIÈRES DʼURGENCE ETÉQUIPEMENT DE PUISSANCEE82903 56B5 TJ

(93098509)

CAT NO. XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXVOLTS XXXXXXXXXXXXXXXXXXXX Hz XXXXXAMPS XXXXXXXXXXXXXXXXXXXXXLAMP XXXXX XXXXXXXXXXXXXXSUITABLE FOR XXXX LOCATIONS. MIN XXXX SUPPLYCONDUCTORS. MAX MNTG HGT 22-FTOUTPUT OPERATES LUMINAIRE 90 MINUTES.CONVIENT AUX ENDROITS XXXX. APROPIADO PARAXXXX.LES FILS D'ALIMENTATION XXXX MIN.CONDUCTORES DE SUMINISTRO MIN XXXX.HAUTEURMAXIMUM DE MONTAGE 6.7M. LA SORTIE FONCTIONNELE LUMINAIRE 90 MINUTES.

XXX XX XXXX

XXXXXXXXXXXXXXX

Hubbell Lighting Inc.

This device complies with Part 15 of the FCC Rules.

Operation is subject to the following conditions:

(1) This device may not cause harmful interferences, and

(2) This device must accept any interference received,

including interference that may cause undesired

operation.

Product LabelCaution Label(EM-Pack Option only)

NX DSP QR (optional)NX Wireless Radio QR (optional)

NX Controller QR (optional)

Compliance Label

EM Fixture Label(EM-Pack Option only)

SRP FIXTURE - T-GRID INSTALLATION(Actual grid installation conditions may vary)

2.0"52mm

.5"13mm

.5"12mm

2.0"52mm

FIGURE 3bLABELING DETAIL

FIGURE 3cT-GRID INSTALL.

93113962

CAUTION

THIS UNIT HAS MORE THAN ONE POWER SUPPLY

CONNECTION POINT. TO REDUCE THE RISK OF

ELECTRIC SHOCK, DICONNECT BOTH THE BRANCH

CIRCUIT BREAKERS OR FUSES AND

EMERGENCY POWER SUPPLIES BEFORE SERVICING.

ATTENCION

RISQUE DE CHOC COUPER L'ALIMENTATION ET

NEUTRALISER LA BATTERIE D'ACUMULATEURS

AVANT DE PROCEDUER A LA REPARATION DU

BALLASTNECESSITE LA RECONNEXION DE

CONDUCTEURS QUI PEUVENT ETRE SOUS TENSION

93113963

EMERGENCY LIGHTINGAND POWER EQUIPMENT

LUMIÈRES DʼURGENCE ETÉQUIPEMENT DE PUISSANCE

E82903 56B5 TJ

(93098509)

CAT NO. XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXVOLTS XXXXXXXXXXXXXXXXXXXX Hz XXXXXAMPS XXXXXXXXXXXXXXXXXXXXXLAMP XXXXX XXXXXXXXXXXXXXSUITABLE FOR XXXX LOCATIONS. MIN XXXX SUPPLYCONDUCTORS. MAX MNTG HGT 22-FTOUTPUT OPERATES LUMINAIRE 90 MINUTES.CONVIENT AUX ENDROITS XXXX. APROPIADO PARAXXXX.LES FILS D'ALIMENTATION XXXX MIN.CONDUCTORES DE SUMINISTRO MIN XXXX.HAUTEURMAXIMUM DE MONTAGE 6.7M. LA SORTIE FONCTIONNELE LUMINAIRE 90 MINUTES.

XXX XX XXXX

XXXXXXXXXXXXXXX

SRP FIXTURE - LABELING & MARKINGS(Actual labeling position may vary)

Hubbell Lighting Inc.

This device complies with Part 15 of the FCC Rules.

Operation is subject to the following conditions:

(1) This device may not cause harmful interferences, and

(2) This device must accept any interference received,

including interference that may cause undesired

operation.

93113962

CAUTION

THIS UNIT HAS MORE THAN ONE POWER SUPPLY

CONNECTION POINT. TO REDUCE THE RISK OF

ELECTRIC SHOCK, DICONNECT BOTH THE BRANCH

CIRCUIT BREAKERS OR FUSES AND

EMERGENCY POWER SUPPLIES BEFORE SERVICING.

ATTENCION

RISQUE DE CHOC COUPER L'ALIMENTATION ET

NEUTRALISER LA BATTERIE D'ACUMULATEURS

AVANT DE PROCEDUER A LA REPARATION DU

BALLASTNECESSITE LA RECONNEXION DE

CONDUCTEURS QUI PEUVENT ETRE SOUS TENSION

93113963

EMERGENCY LIGHTINGAND POWER EQUIPMENTLUMIÈRES DʼURGENCE ETÉQUIPEMENT DE PUISSANCEE82903 56B5 TJ

(93098509)

CAT NO. XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXVOLTS XXXXXXXXXXXXXXXXXXXX Hz XXXXXAMPS XXXXXXXXXXXXXXXXXXXXXLAMP XXXXX XXXXXXXXXXXXXXSUITABLE FOR XXXX LOCATIONS. MIN XXXX SUPPLYCONDUCTORS. MAX MNTG HGT 22-FTOUTPUT OPERATES LUMINAIRE 90 MINUTES.CONVIENT AUX ENDROITS XXXX. APROPIADO PARAXXXX.LES FILS D'ALIMENTATION XXXX MIN.CONDUCTORES DE SUMINISTRO MIN XXXX.HAUTEURMAXIMUM DE MONTAGE 6.7M. LA SORTIE FONCTIONNELE LUMINAIRE 90 MINUTES.

XXX XX XXXX

XXXXXXXXXXXXXXX

Hubbell Lighting Inc.

This device complies with Part 15 of the FCC Rules.

Operation is subject to the following conditions:

(1) This device may not cause harmful interferences, and

(2) This device must accept any interference received,

including interference that may cause undesired

operation.

Product LabelCaution Label(EM-Pack Option only)

NX DSP QR (optional)NX Wireless Radio QR (optional)

NX Controller QR (optional)

Compliance Label

EM Fixture Label(EM-Pack Option only)

SRP FIXTURE - T-GRID INSTALLATION(Actual grid installation conditions may vary)

2.0"52mm

.5"13mm

.5"12mm

2.0"52mm

FIGURE 3bLABELING DETAIL

FIGURE 3cT-GRID INSTALL.

Figure 1ALabeling detail

Figure 1BT-Grid Install

STEP 1Raise unit into ceiling.

STEP 2Bend T-bar clips into position.

INSTALLATION METHOD 1: RECESSED MOUNTING

Page 3: Scaler - hubbellcdn.com · volts xxxxxxxxxxxxxxxxxxxx hz xxxxx amps xxxxxxxxxxxxxxxxxxxxx lamp xxxxx xxxxxxxxxxxxxx suitable for xxxx locations.min xxxx supply conductors. max mntg

ScalerEDGE-LIT FLAT PANEL

© 2020 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 3/8 Rev. 12/15/20COL-SRP-ins

Scaler™ Instruction Manual

STEP 1Open access plate. Use knockouts to connect power access using appropriately-sized electrical fittings.

STEP 2Make wiring connections.

WIRING CONNECTION*Wiring connection of both installation methods above are the same.

STEP 1Snap corner bracket to extruded rails, making sure that mounting flanges are on opposite sides.

STEP 2Attach frame to ceiling structure.

STEP 3Remove one non-mounting frame side and slide in flat-panel. Make all electrical connections using appropriate fittings.

STEP 4Reinstall frame side to complete.

INSTALLATION METHOD 2: LUMINAIRE FITTING*Finished installation depth is 2.5" from the ceiling surface.NOTE: The maximum load for SRPSMK-14 is 9.92 lbs. The maximum load for SRPSMK-22 is 10.14 lbs. The maximum load for SRPSMK-24 is 14.99 lbs.

Page 4: Scaler - hubbellcdn.com · volts xxxxxxxxxxxxxxxxxxxx hz xxxxx amps xxxxxxxxxxxxxxxxxxxxx lamp xxxxx xxxxxxxxxxxxxx suitable for xxxx locations.min xxxx supply conductors. max mntg

ScalerEDGE-LIT FLAT PANEL

© 2020 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 4/8 Rev. 12/15/20COL-SRP-ins

Scaler™ Instruction Manual

INSTALLATION METHOD 3: CABLE MOUNT — NON-POWER FEED SUSPENSION KIT

CAUTION • All connections and assembled components need to be tightened and securely fastened. Do not remove die cast end from cable. Crimps are factory

pressed onto cable for maximum strength. Hubbell will not be responsible for damage or injuries which occur due to the cable/crimp alterations.• This product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the

product and the hazards involved.

STEP 1Thread one end of gripper cross cable through safety stop 10 , then through fixture bracket hole, and back though safety stop to complete loop as shown in picture. Secure with screws. Repeat on other side.

STEP 2 (CHOOSE J-BOX BRACKET OR T-BAR CLIP)J-box bracket option: Securely install J-box bracket 1 onto the junction box with the two #8-32 screws 2 . Install the 1/4-20 threaded stud 3 into center hole of the bracket. Leave approx. 1/2"-3/4" exposed thread. Install the ground screw 4 , which will be used later.

T-bar clip option: Place 1/4-20 stud into square opening on the bottom of T-bar clip 5 as pictured. Position T-bar clip on ceiling grid at required location. Secure clip to structural member by inserting support wire through 1/4" diameter hole located at the top of the clip (support wire not included).

STEP 3Thread cable with stop 8 through top threaded end of barrel coupler 7 and pull cable until stop is seated inside coupler.

STEP 4Place 5" canopy 6 over mounting stud on T-bar and hold canopy against ceiling surface. Thread barrel coupler 7 onto stud and secure.

STEP 5Feed open end of cable through top plunger end of cable gripper. Gripper will engage around cable to prevent slipping. Adjust cable gripper position by pressing top plunger down. With the plunger depressed the gripper will move freely to any position.

STEP 6Lift fixture to ceiling and thread cable completely through gripper. After the final cable gripper position is determined, trim excess cable no less than 3" beyond cable gripper outlet.

1

2

3

4

5

6

7

8

9

10

(J-box bracket option)

(T-bar clip option)

J-box bracket option Item Description QTY

1 J-Box Bracket 12 #8-32 screws 23 1/4-20 Threaded Stud 14 Ground Screw 16 5” Canopy 17 Barrell Coupler 18 Cable with stop 19 Gripper with cross cable 110 Safety Stop 1

T-bar clip option Item Description QTY

5 T-Bar Clip 16 5” Canopy 17 Barrell Coupler 18 Cable with stop 19 Gripper with cross cable 110 Safety Stop 1

Page 5: Scaler - hubbellcdn.com · volts xxxxxxxxxxxxxxxxxxxx hz xxxxx amps xxxxxxxxxxxxxxxxxxxxx lamp xxxxx xxxxxxxxxxxxxx suitable for xxxx locations.min xxxx supply conductors. max mntg

ScalerEDGE-LIT FLAT PANEL

© 2020 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 5/8 Rev. 12/15/20COL-SRP-ins

Scaler™ Instruction Manual

INSTALLATION METHOD 4: CABLE MOUNT — POWER FEED SUSPENSION KIT(Universal voltage only)

STEP 1Thread one end of gripper cross cable through safety stop 12 , then through fixture bracket hole, and back though safety stop to complete loop as shown in picture. Secure with screws. Repeat on other side.

STEP 2Securely install J-box bracket 1 onto the junction box with the two #8-32 screws 2 . Install the 1/4-20 threaded stud 3 into center hole of the bracket. Leave approx. 1/2"-3/4" exposed thread. Install the ground screw 4 , which will be used later.

STEP 3Insert the cord set 10 into the junction box and make the connections per all the appropriate electrical codes. For T-bar ceilings, the junction box installation is not covered in these instructions, but code requirements must be followed.

STEP 4Thread cable with stop 9 through top threaded end of barrel coupler 7 and pull cable until stop is seated inside coupler.

STEP 5Feed cord set through larger canopy hole and secure canopy to 1/4-20 stud with barrel coupler. You may need to adjust the height of the 1/4-20 stud.

STEP 6Use pliers to install strain relief bushing 6 around cord set and into canopy hole.

STEP 7Thread cable through top plunger end of gripper. Insert cable completely through cable gripper. Gripper will engage around cable to prevent slipping. Adjust cable gripper position by pressing top plunger down, with the plunger depressed the gripper will move freely to any position.

STEP 8Determine the final position of the fixture and the length of the cord set and cable that are required for the application. If necessary, trim the cord set length and adjust cord guide as appropriate to the fixture design. After the final cable gripper position is determined, trim excess cable no less than 3" beyond cable gripper outlet. Cord set can be secured to cable with provided cable ties 8 .

STEP 9Make electrical connections in the lighting fixture as appropriate. Be sure to follow all local and national code requirements.

J-box bracket option Item Description QTY

1 J-Box Bracket 12 #8-32 screws 23 1/4-20 Threaded Stud 14 Ground Screw 15 5” Canopy 16 Strain Relief Bushing 27 Coupler 18 Cable tie 19 Cable with stop 110 18/5 SJT Cord set 111 Gripper with cross cable 112 Safety Stop 1

1

2

3

4

5

67

8

9

10

11

12

Note: Approved electrical box must be attached appropriately and by qualified person. Installation must comply with local and/or national code. Check local building codes prior to installation.Warning: Risk of electric shock. Cable kit installation requires knowledge of lighting luminaire electric systems. If not qualified, do not attempt installation—contact qualified electrician.Warning: Install this cable kit securely only with a lighting luminaire that has been designed or modified to accommodate the components supplied with this kit and secured to a structural member.Notice: Turn off the electrical power to the lighting luminaire circuit during the installation process.

CAUTION • All connections and assembled components need to be tightened and securely fastened.

Do not remove die cast end from cable. Crimps are factory pressed onto cable for maximum strength. Hubbell will not be responsible for damage or injuries which occur due to the cable/crimp alterations.

• This product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and the hazards involved.

Page 6: Scaler - hubbellcdn.com · volts xxxxxxxxxxxxxxxxxxxx hz xxxxx amps xxxxxxxxxxxxxxxxxxxxx lamp xxxxx xxxxxxxxxxxxxx suitable for xxxx locations.min xxxx supply conductors. max mntg

ScalerEDGE-LIT FLAT PANEL

© 2020 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 6/8 Rev. 12/15/20COL-SRP-ins

Scaler™ Instruction Manual

NX DISTRIBUTED INTELLIGENCE™ CONTROLS

NOTE: 1. NX Control Devices are Voltage Specific.2. NX cables are used to control modules to other family devices and are orientation specific. See Figures 1–4 below.3. SRP fixture is NOT for wet location applications.

SRPINSTALLATION INSTRUCTIONS

Hubbell Lighting, Inc. Doc. No. 93113967A subsidiary of Hubbell Incorporated Revision B701 Millennium Drive • Greenville, SC 29607 Page 9 Phone (864) 678-1000

(NXWE)WIRELESS ACCESS OPTION

CONTROLLER: NXFM-I OR NXFM-LVWIRELESS RADIO RECEIVER: NXRM-H

FROM SMARTPORT

(NXE)DAISYCHAIN OPTION

CONTROLLER: NXFM-I OR NXFM-LVDUAL SMARTPORT ADAPTER: NXDSP

(NXWD)WIRELESS/SENSORED OPTION

CONTROLLER: NXFM-I OR NXFM-LVWIRELESS RADIO RECEIVER: NXRM-HDUAL SMARTPORT ADAPTER: NXDSP

NXDSPDUAL SMARTPORT

(BOTTOM VIEW)

NX CONTROLS

1. NX Control Devices are Voltage Specific.2. NX cables are used to control modules to other family devicesand are orientation specific - Fig. 12-15.3. SRP fixture is NOT for wet location applications.

FIGURE 12

FIGURE 13

FIGURE 14 FIGURE 15

SRPINSTALLATION INSTRUCTIONS

Hubbell Lighting, Inc. Doc. No. 93113967A subsidiary of Hubbell Incorporated Revision B701 Millennium Drive • Greenville, SC 29607 Page 9 Phone (864) 678-1000

(NXWE)WIRELESS ACCESS OPTION

CONTROLLER: NXFM-I OR NXFM-LVWIRELESS RADIO RECEIVER: NXRM-H

FROM SMARTPORT

(NXE)DAISYCHAIN OPTION

CONTROLLER: NXFM-I OR NXFM-LVDUAL SMARTPORT ADAPTER: NXDSP

(NXWD)WIRELESS/SENSORED OPTION

CONTROLLER: NXFM-I OR NXFM-LVWIRELESS RADIO RECEIVER: NXRM-HDUAL SMARTPORT ADAPTER: NXDSP

NXDSPDUAL SMARTPORT

(BOTTOM VIEW)

NX CONTROLS

1. NX Control Devices are Voltage Specific.2. NX cables are used to control modules to other family devicesand are orientation specific - Fig. 12-15.3. SRP fixture is NOT for wet location applications.

FIGURE 12

FIGURE 13

FIGURE 14 FIGURE 15

SRPINSTALLATION INSTRUCTIONS

Hubbell Lighting, Inc. Doc. No. 93113967A subsidiary of Hubbell Incorporated Revision B701 Millennium Drive • Greenville, SC 29607 Page 9 Phone (864) 678-1000

(NXWE)WIRELESS ACCESS OPTION

CONTROLLER: NXFM-I OR NXFM-LVWIRELESS RADIO RECEIVER: NXRM-H

FROM SMARTPORT

(NXE)DAISYCHAIN OPTION

CONTROLLER: NXFM-I OR NXFM-LVDUAL SMARTPORT ADAPTER: NXDSP

(NXWD)WIRELESS/SENSORED OPTION

CONTROLLER: NXFM-I OR NXFM-LVWIRELESS RADIO RECEIVER: NXRM-HDUAL SMARTPORT ADAPTER: NXDSP

NXDSPDUAL SMARTPORT

(BOTTOM VIEW)

NX CONTROLS

1. NX Control Devices are Voltage Specific.2. NX cables are used to control modules to other family devicesand are orientation specific - Fig. 12-15.3. SRP fixture is NOT for wet location applications.

FIGURE 12

FIGURE 13

FIGURE 14 FIGURE 15

Figure 2

Figure 3

Figure 4 Figure 5

Page 7: Scaler - hubbellcdn.com · volts xxxxxxxxxxxxxxxxxxxx hz xxxxx amps xxxxxxxxxxxxxxxxxxxxx lamp xxxxx xxxxxxxxxxxxxx suitable for xxxx locations.min xxxx supply conductors. max mntg

ScalerEDGE-LIT FLAT PANEL

© 2020 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 7/8 Rev. 12/15/20COL-SRP-ins

Scaler™ Instruction Manual

BATTERY BACK-UP OPTION (ELL14)

CAUTION: 1. Follow OEM instructions provided regarding all warnings and guidelines connection and operation.2. The unit engage connector pins must be connected for the emergency driver and AC driver to operate normally.3. Wiring diagram provided is for reference only. For labeling, refer to page 2.4. Make sure the necessary branch circuit wiring is available. An unswitched source of power is required. The emergency driver must be fed from the

same branch circuit as the AC driver.5. To prevent high voltage from being present on yellow & yellow/black output leads prior to installation, converter connector must be open. Do not

join converter connector until installation is complete and AC power is supplied to the emergency driver.

NOTE: For short-term testing of the emergency function, the battery must be charge for at least one hour. The emergency driver must be charged for at least 24 hours before conducting a long-term test.

NOTE: SRP fixtures equipped with integral ELL14 option require remote test switch via PLRTS device ordered separately.

SRPINSTALLATION INSTRUCTIONS

Hubbell Lighting, Inc. Doc. No. 93113967A subsidiary of Hubbell Incorporated Revision B701 Millennium Drive • Greenville, SC 29607 Page 10 Phone (864) 678-1000

For additional information on SRP, please visit our website: www.hubbell.com

BATTERY BACK-UP (ELL14) OPTION

1. Follow OEM instructions provided regarding all warnings and guidelines connection and operation.

NOTE: The unit engage connector pins must be connected for the emergency driver and AC driver to operate normally.

2. Wiring diagram provided is for reference only. Labeling refer to page 3.

FIGURE 13

! NOTE !SRP fixtures equipped with integral ELL14 option requireremote test switch via PLRTS device ordered separately.

Figure 62-Wire Integrated Test Switch

Figure 7Step Dimming Installation

NOTE: Typical schematics only. May be used with other drivers. Consult the factory for other wiring diagrams.

Page 8: Scaler - hubbellcdn.com · volts xxxxxxxxxxxxxxxxxxxx hz xxxxx amps xxxxxxxxxxxxxxxxxxxxx lamp xxxxx xxxxxxxxxxxxxx suitable for xxxx locations.min xxxx supply conductors. max mntg

ScalerEDGE-LIT FLAT PANEL

© 2020 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 8/8 Rev. 12/15/20COL-SRP-ins

Scaler™ Instruction Manual

BATTERY BACKUP SELF-TEST OPTION (ELL14ST)

CAUTION: 1. Follow OEM instructions provided regarding all warnings and guidelines connection and operation.2. The unit engage connector pins must be connected for the emergency driver and AC driver to operate normally.3. Wiring diagram provided is for reference only. For labeling, refer to page 2.4. Make sure the necessary branch circuit wiring is available. An unswitched source of power is required. The emergency driver must be fed from the

same branch circuit as the AC driver.5. To prevent high voltage from being present on yellow & yellow/black output leads prior to installation, converter connector must be open. Do not

join converter connector until installation is complete and AC power is supplied to the emergency driver.

NOTE: Connections with * are Class 2 rated outputs. Connections with # are Class 2 rated inputs only.

NOTE: For short-term testing of the emergency function, the battery must be charge for at least one hour. The emergency driver must be charged for at least 24 hours before conducting a long-term test.

NOTE: SRP fixtures equipped with integral ELL14ST option require remote test switch via PLRTS device ordered separately.

SRPINSTALLATION INSTRUCTIONS

Hubbell Lighting, Inc. Doc. No. 93113967A subsidiary of Hubbell Incorporated Revision B701 Millennium Drive • Greenville, SC 29607 Page 11 Phone (864) 678-1000

For additional information on SRP, please visit our website: www.hubbell.com

BATTERY BACK-UP SELF-TEST (ELL14ST) OPTION

1. Follow OEM instructions provided regarding all warnings and guidelines connection and operation.

NOTE: The unit engage connector pins must be connected for the emergency driver and AC driver to operate normally.

2. Wiring diagram provided is for reference only. Labeling refer to page 3.

FIGURE 14

! NOTE !SRP fixtures equipped with integral ELL14ST option require

remote test switch via PLRTS device ordered separately.

Figure 8 Figure 9With Thermal Protector

NOTE: Typical schematics only. May be used with other drivers. Consult the factory for other wiring diagrams.