Technical Specication
DatasheetSCADAPack Smart RTUCompact, versatile controller for telemetry and remote SCADA solutions
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
2/54
01
SCADAPackSmart RTUs that combine the monitoring and
communications capabilities of remote terminal units
(RTU) with the processing and data-logging power of
programmable logic controllers (PLC), providing superior
functionality wherever remote processes require
automatic supervision and autonomous control.
SCADAPack Smart RTUs are the foundation for a range of
solutions offering specific software and configuration
tools to enhance performance in oil and gas and water/wastewater applications.
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
3/54
• Modbus core database, DNP3 level 2 layer, optional DF1 support
• Programming and conguration: TelePACE Studio, IEC61131-3, C/C++
SCADAPack 100, 300, 32
314 330 334 350 357 32P 32 P4 32 P4A 32 P4B 100
Analog Inputs
On-board1 8: 0-20mA,4-20mA
0-5V 0-10V
n/a 8: 0-20mA,4-20mA
0-5V 0-10V
5: 0-10V,0-20mA
1: 0-32.7VDC
5: 0-10V,0-20mA
1: 0-32.7VDC8: 0-20mA,
4-20mA 0-10V
0-5V
n/a 8: 0-20/4-20mA
or 0-5/1-5V
8: 0-20mA/ 0-10V
1: 0-32.768V
8: 0-20/4-20mA
0-5/0-10V
3: 0-20/4-20mA
0-5/1-5 VDC1: 0-32.7
VDC
Analog Outputs
On-board1 2: 0-20mA 4-20mA Optional
n/a 2: 0-20mA 4-20mA Optional
2 or 4:0-20mA 4-20mA Optional
n/a 2: 0-20mA 4-20mA Optional
n/a
Digital Inputs
On-board1 16: 12/24V 48V
115/125V 240V
n/a 16: 12/24V 48V
115/125V 240V
8: Drycontact,
Shared withoutput points.
8: Drycontact,
shared withoutput points32: (12/24V,
48V,115/125V,
240V)
3: 24VAC/30VDC,
shared withCounterinputs1: 30V
interrupt
3: 24VAC/30VDC,
shared withCounterinputs1: 30V
interrupt16:
12-24/120/220V-VAC
3: 24VAC/30VDC,
shared withCounterinputs1: 30V
interrupt32: drycontact
Shared withoutputs
3: 24VAC/30VDC
Shared withCounterinputs,1: 30V
interrupt input32: 12/24V,
48V,115/125V,
240V
6: selectableas input or
output
Digital Outputs
On-board1 10: drycontact or
10:solid-state
n/a 10: drycontact
or solid-state
8: open drain,Shared withinput points.
8: open drain,Shared withinput points.
16: drycontact
1: ControllerStatus Output
1: ControllerStatus Output
12: Drycontact
1: ControllerStatus Output
32: drycontact
Shared withinputs
1: ControllerStatus Output
16: Drycontact
6: selectableas input or
output
Frequency Inputs
On-board1 1: 0-10Hz or 0-5kHz (dry contact) 3: 0-5 kHz shared with digital inputs, 1: 0-500Hz, interrupt input 1: 0-6 kHzturbine
or dry contact
General
TurbineInputs
2: 0-10kHz (turbine or dry contact) n/a 1
Serial Ports 2: RS232/ RS485
2: RS232/RS4851: RS232
1: RS485, 1: RS232/RS485,1: RS232
2: RS2321: RS232/
RS485
3: RS232, 1: RS232/RS485 2: RS2321: RS232/
RS485
1: RS2321: RS232/
RS485
USB Ports 1: Peripheral 1: Host, 1: Peripheral n/a
EthernetPorts
n/a 1, 10/100BaseT 1: 10BaseT n/a
EFM FlowRuns
4 10 1
ProgrammingSoftware
TP Studio, IEC61131-3, C++ TP Studio,IEC61131, C
Modbus Master and Slave: Modbus RTU, Modbus ASCII, Modbus/TCP, Modbus UDP
DNP3 Level 2 Slave
1 Number of on-board I/O may be further expanded for any SCADAPack using Expansion I/O Modules.
Refer to individual product data sheets for detailed specifications.
02
Selection Guide
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
4/54
03
Contents
SCADAPack Smart RTU
SCADAPack 314
Specifications ............................................................................................. 4
Model Code ............................................................................................... 5
SCADAPack 330 | 334
Specifications 330 ...................................................................................... 6
Specifications 334 ...................................................................................... 7
Model Code ............................................................................................... 8
SCADAPack 350 | 357
Specifications 350 .................................................................................... 10
Specifications 357 .................................................................................... 11
Model Code ............................................................................................. 12
SCADAPack 32
Specifications P4A ................................................................................... 14 Specifications P4 ...................................................................................... 15
Specifications P4B ................................................................................... 16
Model Code ............................................................................................. 17
SCADAPack 100
Specifications ........................................................................................... 18
Model Code ............................................................................................. 19
I/O Expansion Modules*
Analog Input Modules
5502 - Differential analog input module ..................................................... 20
5504 - Thermocouple input module ......................................................... 21
5505 - RTD input module ......................................................................... 22
5506 - Analog input module ..................................................................... 23
Analog Output Modules
5302 - Analog output module ................................................................... 24
5304 - Analog output module ................................................................... 25
Digital Input Modules
5403 - High level digital input module ....................................................... 26
5404 - High level digital input module ....................................................... 27
5405 - Digital input module ...................................................................... 28
5410 - High speed counter/accumulator .................................................. 29
5414 - Compact digital input module ....................................................... 30
Digital I/O Modules 5401 - Configurable digital I/O module ..................................................... 31
5402 - Configurable digital input or output module ................................... 32
Digital Output Modules
5406A - Dry contact relay out module ...................................................... 33
5407 - Dry contact relay out module ........................................................ 34
5408 - Triac digital output module .............................................................35
5409 - FET digital output module ............................................................. 36
5411 - Digital output module .................................................................... 37
5415 - Compact relay digital output module ............................................. 38
Combination I/O Modules
5606 - Analog/digital I/O module .............................................................. 39
5607 - Analog/digital I/O module .............................................................. 40
I/O Simulator Modules
5421 - Toggle switch digital input module ................................................. 41
5521 - Potentiometer input module .......................................................... 42
UPS Power Supply
5103 - Uninterruptible Power Supply ........................................................ 43
Non-Programmable Controller Modules
5201 - RS-485 communication controller ................................................. 44
5202 - RS-232 communication controller ................................................. 45
Communication Modules
Modems, Interface Modules & Gateways5901 - Dial-up modem ............................................................................. 46
5902 - Bell 202 radio or leased line modem ............................................. 47
5904 - HART interface module ..................................................................48
5908 - Wireless data transceiver .............................................................. 49
5908-WO2 - Wireless data transceiver ..................................................... 50
5910 - Ethernet switch ............................................................................. 51
5915 - SDI-12 interface module ............................................................... 52
* IO Expansion Module Compatibility Notes:
The SCADAPack 100 does not support IO Expansion modules.
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
5/54
P314: 5212 controller board and integrated 56O7 I/O board
Controller
Processors • CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer
• Microcontroller co-processor, 20 MHz clock
Memory 16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM
Non-Volatile RAM CMOS SRAM with lithium battery retains contents for 2 years with no power
Datalog Capacity 465k words
I/O
Analog Inputs • 8 software congurable: 0-20/4-20mA / 0-5/0-10V (15-bit)• 3 internal: measure incoming power supply voltage for solar applications, battery voltage, and controller temperature
Analog Outputs • Standard: None• 2 with optional 5305 on 5607 I/O board: 0-20/4-20mA (12-bit)
Digi tal I/O • 16 digi tal inputs: 12/24V, 48V, 115/125V, 240V• 10 relay outputs: dry contact or DC solid state, dry contact rating: 3A, 30VDC or 240VAC (resistive),
DC solid state rating: 3A, 60 VDC
Counter Inputs • 1 dry contact: 0-10Hz or 0-5kHz
• 2 turbine or dry contact: 0-10kHz
Communications
Serial Ports COM1, COM2 • RS-232 port, 8-pin modular RJ45 jack, full or half-duplex, or• RS-485 port, 2-wire, half-duplex
Baud Rates 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200
Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1
Serial Protocol Modes Slave, Master, Master/Slave, Store and Forward
USB Peripheral Port USB 2.0 compliant B-type receptacle
Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2
General
I/O Terminations 5, 6, and 9-pole removable terminal blocks, 12 to 22AWG, 15A contacts
Dimensions 5.65 inch (144mm) wide, 6.50 inch (165mm) high, 2.80 inch (72mm) deep
Packaging Corrosion resistant, zinc-plated steel with black enamel paint
Environment 5% RH to 95%, non-condensing, –40°C (–40°F) to 70°C (158°F)
Power
5212 Controller Board • 11 - 30VDC, 30mW at 12V during sleep mode.• 500mW at 12V during normal operation. 32MHz, LEDs off, no expansion, and USB disabled• 300mW at 12V during reduced power mode operation. 12MHz, LEDs off, no expansion, USB disabled• Add 190mW when enabling the USB port• Add 30 to 90mW when enabling the LEDs• 8.5W at 24V maximum, 5V supply fully-loaded
5607 I/O Module • 11 - 30VDC, 10.3mA plus analog outputs• 235mA (max.) at 5V required from 5212 controller board
Warranty 3 years on parts and labor
Certifications
Hazardous LocationsNorth America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certied to therequirements of:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations• UL Std. No. 1604 - Hazardous (Classied) Locations
Hazardous LocationsEurope
ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.
Hazardous Locations IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2). Does not include Wireless versions.
1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
Product Data Sheet SCADAPack 314Specications
04
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
6/54
TBUP314-1A20-AB00 represents a sample code for a SCADAPack 314, 5607 I/O board and Modbus protocol emulation
Model Select: Controller
TBUP314 SCADAPack 314 , 32 Bit controller, 8 Analog Inputs, 16 Digital Inputs, 10 Digital Outputs, 3 Accumulators
Code Future Option
1 None
Code Select: Gas Flow Run-Time Option
A None
Flow Computer Runs
G 2 Run Gas Flow
F 4 Run Gas Flow
V 2 Run Gas Flow - Gas Transmission Version (Requires Realo 6.72+)
W 4 Run Gas Flow - Gas Transmission Version (Requires Realo 6.72+)
Code Select: Protocol Option
2 Modbus and DNP 3.0 (Level 2) protocol emulation
Code Select: Programming Environment
0 Telepace Ladder Logic and C Language rmware loaded - IEC enabled (programming tools sold separately)1 IEC 61131-3 and C Language rmware loaded - Telepace enabled (programming tools sold separately)
Code Select: Analog Inputs
A 8 selectable as 0-20, 4-20mA, 0-5V or 0-10V
Code Select: Digital Inputs/Outputs
B 16 DI (12/24V) and 10 dry contact relays
D 16 DI (120V) and 10 dry contact relays
F 16 DI (12/24V) and 10 DC solid-state relays, ATEX and IECEx certication
H 16 DI (120V) and 10 solid state relays
Code Select: Analog Outputs
0 None
1 2 channel analog output option, 0 - 20mA
Code Select: Integrated Communication Interfaces
0 None
FreeWave & MDS Radios (requires one RS232 port)
1 900Mhz FreeWave Spread Spectrum Radio
A 900MHz MDS Spread Spectrum Radio
Trio Radios - 900MHz (requires one RS232 port)
B 900MHz Trio Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)
C 900MHz Trio Spread Spectrum Radio with encryption, 915-928MHz (AUS)
D 900MHz Trio Spread Spectrum Radio, 915-928MHz (BRAZIL)
E 900MHz Trio Spread Spectrum Radio, 921-928MHz (NZ)
Trio Radios - 2.4GHz (requires one RS232 port)
J 2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)
K 2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)
L 2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)
Product Data Sheet SCADAPack 314Model Code
05
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
7/54
P330: 5210 controller board only
Controller
Processors • CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer
• Microcontroller co-processor, 20 MHz clock
Memory 16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM
Non-Volatile RAM CMOS SRAM with lithium battery retains contents for 2 years with no power
Datalog Capacity 465k words
I/O
Counter Inputs • 1, 0-10Hz or 0-5kHz (dry contact)• 2, 0-10kHz (turbine or dry contact)
Communications
Serial Ports COM1, COM2 • RS-232 port, 8-pin modular RJ45 jack, full or half duplex, or• RS-485 port, 2-wire, half duplex
Serial Port COM3 • RS-232 port, 8-pin modular RJ45 jack, full or half duplex with RTS/CTS control and operator interface power control
Baud Rates 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200
Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1
Serial Protocol Modes Slave, Master, Master/Slave, Store and Forward
Ethernet Port RJ45, 10/100BaseT
Ethernet Protocols Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP
Network Protocols IP, ARP, TCP, TFTP, UDP and ICMP
USB Host Port USB 2.0 compliant “A”-type receptacle, provides up to 100mA at 5V
USB Peripheral Port USB 2.0 compliant “B”-type receptacle
Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2
General
I/O Terminations 6-pole removable terminal block, 12 to 22AWG, 15A contacts
Dimensions 5.65 inch (144mm) wide, 5.00 inch (127mm) high, 1.80 inch (45mm) deep
Packaging Corrosion resistant zinc-plated steel with black enamel paint
Environment 5% RH to 95%, non-condensing, –40°C (–40°F) to 70°C (158°F)
Power Input • 11 - 30VDC, 15mW at 12V dur ing Sleep• 500mW at 12V during normal operation. 32MHz, LEDs off, no expansion, LAN and USB disabled• 300mW at 12V during reduced power mode operation. 12MHz, LEDs off, no expansion, LAN and USB disabled• Add 800mW when enabling LAN• Add 190mW when enabling USB• Add 25 to 100mW when enabling the LEDs• 8.5W at 24V maximum, 5V supply fully loaded
Warranty 3 years on parts and labor
Certifications
Hazardous LocationsNorth America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certied to therequirements of:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations.• UL Std. No. 1604 - Hazardous (Classied) Locations.
Hazardous Locations - Europe ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.
Hazardous Locations IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.
1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
Product Data Sheet SCADAPack 330Specications
06
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
8/54
P334: 5210 controller board and integrated 5607 I/O board
Controller
Processors • CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer
• Microcontroller co-processor, 20 MHz clock
Memory 16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM
Non-Volalite RAM CMOS SRAM with lithium battery retains contents for 2 years with no power
Datalog Capacity 465k words
I/O
Analog Inputs 8, 0-20/4-20mA / 0-5/0-10V (15-bit) software congurable
Analog Outputs • Standard: None• 2, 0-20/4-20mA (12-bit) with optional 5305 on 5607 I/O board
Digi tal I/O • 16, 12/24V, 48V, 115/125V, 240V digital inputs• 10 relay outputs: dry contact or DC solid state, dry contact rating: 3A, 30VDC or 240VAC (resistive),
DC solid state rating: 3A, 60 VDC
Counter Inputs 1, 0-10Hz or 0-5kHz (dry contact); 2, 0-10kHz (turbine or dry contact)
Communications
Serial Ports COM1, COM2 • RS-232 port, 8-pin modular RJ45 jack, full or half duplex, or• RS-485 port, 2-wire, half duplex
Serial Port COM3 RS-232 port, 8-pin modular RJ45 jack, full or half duplex with RTS/CTS control and operator interface power control
Baud Rates 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200
Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1
Serial Protocol Modes Slave, Master, Master/Slave, Store and Forward
Ethernet Port RJ45, 10/100BaseT
Ethernet Protocols Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP
Network Protocols IP, ARP, TCP, TFTP, UDP and ICMP
USB Host Port USB 2.0 compliant “A”-type receptacle, provides up to 100mA at 5V
USB Peripheral Port USB 2.0 compliant “B”-type receptacle
Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2
GeneralI/O Terminations 5, 6 and 9-pole removable terminal blocks, 12 to 22AWG, 15A contacts
Dimensions 5.65 inch (144mm) wide, 6.50 inch (165mm) high, 2.80 inch (72mm) deep
Packaging Corrosion resistant zinc-plated steel with black enamel paint
Environment 5% RH to 95%, non-condensing, –40°C (–40°F) to 70°C (158°F)
Power
5210 Controller Board • 11 - 30VDC, 15mW at 12 V during Sleep• 500mW at 12V during normal operation. 32MHz, LEDs off, no expansion, LAN and USB disabled• 300mW at 12V during reduced power mode operation. 12MHz, LEDs off, no expansion, LAN and USB disabled• Add 800mW when enabling LAN• Add 190mW when enabling USB• Add 25 to 100mW when enabling the LEDs• 8.5W at 24V maximum, 5V supply fully loaded
5607 I/O Module • 11 - 30VDC, 10.3mA plus analog outputs• 325mA (max.) at 5V required from 5210 controller board
Warranty 3 years on parts and labor
Certifications
Hazardous LocationsNorth America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certied to the require-ments of:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations.• UL Std. No. 1604 - Hazardous (Classied) Locations.
Hazardous Locations - Europe ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.
Hazardous Locations IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.
1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
07
Product Data Sheet SCADAPack 334Specications
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
9/54
TBUP334-1A20-AB00 represents a sample code for a SCADAPack334, 5607 I/O board and Modbus protocol emulation
Model Select: Controller
TBUP330 SCADAPack 330, 32 Bit controller, 3 Accumulators
TBUP334 SCADAPack 334, with Model 5607 I/O board, comes with above I/O plus 8 Analog I/P, 16 Digital I/P and 10 Digital O/P
Code Future Option
1 None
Code Select: Gas Flow Run-Time Option
A None
Flow Computer Runs
G 2 Run Gas Flow
F 4 Run Gas Flow
V 2 Run Gas Flow - Gas Transmission Version (Requires Realo 6.72+)
W 4 Run Gas Flow - Gas Transmission Version (Requires Realo 6.72+)
Code Select: Protocol Option
2 Modbus and DNP 3.0 (Level 2) protocol emulation
Code Select: Programming Environment
0 Telepace Ladder Logic and C Language rmware loaded - IEC enabled (Programming Tools sold separately)
1 IEC 61131-3 and C Language rmware loaded - Telepace enabled (Programming Tools sold separately)
Code Select: Analog Inputs
A P330: None – P334: 8 selectable as 0-20, 4-20mA, 0-5V or 0-10V
Code Select: Digital Inputs/Outputs
A P330 - None
B P334 - 16 DI (12/24V) and 10 dry contact relays
D P334 - 16 DI (120V) and 10 dry conta ct relays
F P334 - 16 DI (12/24V) and 10 DC solid state relays, ATEX and IECEx certication
H P334 - 16 DI (120V) and 10 solid state relays
Code Select: Analog Outputs
0 None
1 P334 only - 2 channel analog output option, 0 - 20mA
Model codes continue on next page
08
Product Data Sheet SCADAPack 330 | 334Model Code
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
10/54
TBUP334-1A20-AB00 represents a sample code for a SCADAPack334, 5607 I/O board and Modbus protocol emulation
Code Select: Integrated Communication Interfaces
0 None
FreeWave & MDS Radios (requires one RS232 port)
1 900Mhz FreeWave Spread Spectrum Radio
A 900MHz MDS Spread Spectrum Radio
Trio Radios - 900MHz (requires one RS232 port)
B 900MHz Trio Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)
C 900MHz Trio Spread Spectrum Radio with encryption, 915-928MHz (AUS)
D 900MHz Trio Spread Spectrum Radio, 915-928MHz (BRAZIL)
E 900MHz Trio Spread Spectrum Radio, 921-928MHz (NZ)
Trio Radios - 2.4GHz (requires one RS232 port)
J 2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)
K 2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)
L 2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)
Product Data Sheet SCADAPack 330 | 334Model Code
09
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
11/54
P350: 5209 controller board only
Controller
Processors • CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer
• Two Microcontroller co-processors, 20 MHz clock
Memory 16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM
Non-Volatile RAM CMOS SRAM with lithium battery retains contents for 2 years with no power
Datalog Capacity 465k words
I/O
Analog Inputs • 5, user selectable 0-10V (15-bit) or 0-20mA plus overrange (14-bit)• 1, 0-32.7VDC (15-bit)
Analog Outputs • Standard: None• 2, 0-20/4-20mA (12-bit) with optional 5305
Digital I/O 8, user selectable as dry contact inputs or open drain outputs
Counter Inputs • 1, 0-10Hz (dry contact)• 2, 0-10kHz (turbine or dry contact)
CommunicationsSerial Port COM1 RS-485 port, 2-pole removable terminal block, 2-wire, half duplex
Serial Port COM2 • RS-232 port, 8-pin modular RJ45 jack, full or half duplex, or• RS-485 port, 2-wire, half duplex
Serial Port COM3 RS-232 port, 8-pin modular RJ45 jack, half duplex with RTS/CTS control and operator interface power control
Baud Rates 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200
Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1
Serial Protocol Modes Slave, Master, Master/Slave, Store and Forward
Ethernet Port RJ45, 10/100BaseT
Ethernet Protocols Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP
Network Protocols IP, ARP, TCP, TFTP, UDP and ICMP
USB Host Port USB 2.0 compliant “A”-type receptacle, provides up to 100mA at 5V
USB Peripheral Port USB 2.0 compliant “B”-type receptacle
Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2
General
I/O Terminations 6 and 12- pole removable terminal blocks, 12 to 22AWG, 15A contacts
Dimensions 8.40 inch (213mm) wide, 5.00 inch (127mm) high, 1.80 inch (45mm) deep
Packaging Corrosion resistant zinc-plated steel with black enamel paint
Environment 5% RH to 95%, non-condensing, –40°C (–40°F) to 70°C (158°F)
Power Input • 11 - 30VDC, 12mW at 12V dur ing Sleep• 510mW at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN and USB disabled.• 320mW at 12V during reduced power mode operation. 12MHz., LEDs off, no expansion, LAN and USB disabled• 1.2W at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN enabled and USB disabled• Add 25 to 100mW when enabling the LED• 12W at 24V maximum. 5V supply fully loaded and Vloop on and boosted, fully loaded
Voltage Converter 12VDC to 24VDC
Warranty 3 years on parts and labor
Certifications
Hazardous LocationsNorth America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4, UL listed and CSA certiedto the requirements of:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations.• UL Std. No. 1604 - Hazardous (Classied) Locations.
Hazardous Locations - Europe ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.
Hazardous Locations IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.
1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
Product Data Sheet SCADAPack 350Specications
10
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
12/54
P357: 52O9 controller board and integrated 56O6 I/O board
Controller
Processors • CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer
• Microcontroller co-processor, 20 MHz clock
Memory 16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM
Non-Volatile RAM CMOS SRAM with lithium battery retains contents for 2 years with no power
Datalog Capacity 465k words
I/O
Analog Inputs • 5, user selectable 0-10V (15-bit) or 0-20mA plus overrange (14-bit)• 1, 0-32.7VDC (15-bit) ; 8, 0-20/4-20mA / 0-5/0-10V (15-bit) software congurable
Analog Outputs • Standard: None• 2, 0-20/4-20mA (12-bit) with optional 5305 on 5209 controller board• 2, 0-20/4-20mA (12-bit) with optional 5305 on 5606 I/O board
Digital I/O • 8, user selectable as dry contact inputs or open drain outputs• 32, 12/24V, 48V, 115/125V, 240V digital inputs; 16, relay outputs - dry contact or DC solid state
Counter Inputs 1, 0-10Hz (dry contact); 2, 0-10kHz (turbine or dry contact)
Communications
Serial Port COM1 RS-485 port, 2-pole removable terminal block, 2-wire, half duplex
Serial Port COM2 • RS-232 port, 8-pin modular RJ45 jack, full or half duplex RS-232, or• RS-485 port, 2-wire, half duplex
Serial Port COM3 RS-232 port, 8-pin modular RJ45 jack, half duplex with RTS/CTS control and operator interface power control
Baud Rates 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200
Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1
Serial Protocol Modes Slave, Master, Master/Slave, Store and Forward
Ethernet Port RJ45, 10/100BaseT
Ethernet Protocols Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP
Network Protocols IP, ARP, TCP, TFTP, UDP and ICMP
USB Host Port USB 2.0 compliant “A”-type receptacle, provides up to 100mA at 5V
USB Peripheral Port USB 2.0 compliant “B”-type receptacle
Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2
GeneralI/O Terminations 5, 6, 9, 10 and 12-pole removable terminal blocks, 12 to 22AWG, 15A contacts
Dimensions 8.40 inch (213mm) wide, 6.13 inch (155mm) high, 2.80 inch (72mm) deep
Packaging Corrosion resistant zinc-plated steel with black enamel paint
Environment 5% RH to 95%, non-condensing, –40°C (–40°F) to 70°C (158°F)
Power
5209 Controller Board • 11 - 30VDC, 12mW at 12V during Sleep• 510mW at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN and USB disabled• 320mW at 12V during normal operation. 12MHz., LEDs off, no expansion, LAN and USB disabled• 1.2W at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN enabled and USB disabled• Add 25 to 100mW when enabling the LEDs• 12W at 24V maximum. 5V supply fully loaded and Vloop on and boosted, fully loaded
5606 I/O Module • 600mA (max.) at 5V required from 5209 controller board• 11 - 30VDC, 12mA plus analog outputs
Voltage Converter 12VDC to 24VDC
Warranty 3 years on parts and laborCertifications
Hazardous LocationsNorth America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4, UL listed and CSA certiedto the requirements of:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations.• UL Std. No. 1604 - Hazardous (Classied) Locations.
Hazardous Locations - Europe ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.
Hazardous Locations IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless version
1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
11
Product Data Sheet SCADAPack 357Specications
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
13/54
TBUP357-1A20-AB00 represents a sample code for a SCADAPack 357, 5606 I/O board and Modbus protocol emulation
Model Select: Controller
TBUP350 SCADAPack 350 , 32 Bit controller, 5 Analog Inputs, 8 congurable Digital I/O, 3 Accumulators
TBUP357 SCADAPack 357, with Model 5606 I/O board, comes with above I/O plus 8 Analog I/P, 32 Digital I/P and 16 Digital O/P
Code Future Option
1 None
Code Select: Gas Flow Run-Time Option
A None
Flow Computer Runs
G 2 Run Gas Flow
F 4 Run Gas Flow
V 2 Run Gas Flow - Gas Transmission Version (Requires Realo 6.72+)
W 4 Run Gas Flow - Gas Transmission Version (Requires Realo 6.72+)
Code Select: Protocol Option
2 Modbus and DNP 3.0 (Level 2) protocol emulation
Code Select: Programming Environment
0 Telepace Ladder Logic and C Language rmware loaded - IEC enabled (Programming Tools sold separately)
1 IEC 61131-3 and C Language rmware loaded - Telepace enabled (Programming Tools sold separately)
Code Select: Analog Inputs
A P350: 5 selectable as 0-10V or 0-20mA inputs. P357: adds another 8 selectable as 0-20, 4-20mA, 0-5V or 0-10V
Code Select: Digital Inputs/Outputs
A P350 - 8 congurable Digital I/O, individually selectable as DI (Dry Contact) or DO (Open Drain)
B P357 - Includes P350 I/O plus 32 DI (12/24V) and 16 Dry Contact Relay Outputs on 5606 I/O board
D P357 - Includes P350 I/O plus 32 DI (120V) and 16 Dry Contact Relay Outputs on 5606 I/O board
F P357 - Includes P350 I/O plus 32 DI (12/24V) and 16 Solid State Relay Outputs on 5606 I/O board, ATEX and IECEx certication
H P357 - Includes P350 I/O plus 32 DI (120V) and 16 Solid State Relay Outputs on 5606 I/O board
Code Select: Analog Outputs
0 None
1 P350 or P357 - 2 channel analog output option, 0 - 20mA (P357 - 2 channel A/O option on the 5606)
2 P357 only - 4 channel analog output option, 0 - 20mA (consists of the 2 channel A/O option board on both modules)
Model codes continue on next page
12
Product Data Sheet SCADAPack 350 | 357Model Code
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
14/54
TBUP357-1A20-AB00 represents a sample code for a SCADAPack 357, 5606 I/O board and Modbus protocol emulation
Code Select: Integrated Communication Interfaces
0 None
FreeWave & MDS Radios (requires one RS232 port)
1 900Mhz FreeWave Spread Spectrum Radio
A 900MHz MDS Spread Spectrum Radio
Trio Radios - 900MHz (requires one RS232 port)
B 900MHz SCADAWave Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)
C 900MHz SCADAWave Spread Spectrum Radio with encryption, 915-928MHz (AUS)
D 900MHz SCADAWave Spread Spectrum Radio, 915-928MHz (BRAZIL)
E 900MHz SCADAWave Spread Spectrum Radio, 921-928MHz (NZ)
Trio Radios - 2.4GHz (requires one RS232 port)
J 2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)
K 2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)
L 2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)
Product Data Sheet SCADAPack 350 | 357Model Code
13
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
15/54
P4A, integrated 56O4 I/O board
Controller
Processor Hitachi SH-3 32-bit CMOS microcontroller, 120MHz clock, integrated watchdog timer
Memory 8 Mb SDRAM, 4 Mb FLASH, 1 Mb CMOS RAM
Non Volatile RAM CMOS RAM with lithium battery retains contents for 2 years with no power
I/O
Analog Inputs • 8, user selectable 0 - 10V (15 bit) or 0 - 20mA (14 bit)• 1, 0 - 32.678V (10 bit)
Analog Outputs 2 with optional 5305 analog output module, output range 0-20mA
Digital Inputs 4 on controller board - 3 Digital Input/Counter, 1 Interrupt with optical isolation
Digi tal Outputs 1, 30V / 60mA (used as status output)
Digital I/O (5604 I/O board) 32 congurable as input or output (1 Amp DC max output / dry contact input)
Communications
Serial Port COM1 Congurable RS-232 or RS-485, 2 wire half duplex or 4 wire full/half duplex
Serial Ports COM2, COM4 • RS-232, DTE, 8 pin modular jack, full or half duplex with RTS/CTS control• Implemented Td, Rd, CTS, RTS, DCD, DTR, +5V
Serial Port COM3 Located on 5604 I/O module. Same specications as COM2 and COM4
Baud RatesCOM1, COM2, COM4
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200
Baud Rate COM3 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200
Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1, PPP
Ethernet Port RJ45, 10BaseT
Network Protocols IP: ARP, TCP, TFTP, UDP, ICMP
Ethernet Port Protocols Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP
Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2
General
I/O Terminations 6, 8, 9 and 10 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts
Dimensions 8.40 inch (213mm) wide, 6.13 inch (155mm) high, 2.80 inch (72mm) deep
Packaging Corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, –40°C (–40°F) to 70°C (158°F)
Power Input 11 - 30 VDC, 4.3W typical (10.8W ful l I/O capacity in use )
Warranty 3 years on parts and labor
Certifications
Hazardous LocationsNorth America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certied to therequirements of:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations• UL Std. No. 1604 - Hazardous (Classied) Locations
Safety CSA ( cCSA us ) certied to the requirements of: CSA C22.2 No. 142-M1987 and UL508. (Process Control Equipment,Industrial Control Equipment) UL ( cULus ) listed: UL508 (Industrial Control Equipment)
1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
Product Data Sheet SCADAPack 32Specications
14
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
16/54
P4, integrated 56O1A I/O board
Controller
Processor Hitachi SH-3 32-bit CMOS microcontroller, 120MHz clock, integrated watchdog timer
Memory 8 Mb SDRAM, 4 Mb FLASH, 1 Mb CMOS RAM
Non Volatile RAM CMOS RAM with lithium battery retains contents for 2 years with no power
I/O
Analog Inputs 8, user selectable 0 - 5V (15 bit) or 0 - 20mA (14 bit)
Analog Outputs 2 with optional 5303 analog output module, output range 0-20mA
Digital Inputs • 4 on controller board - 3 Digital Input/Counter, 1 Interrupt with optical isolation• 16 on 5601A I/O module - 6.5mA typical at 24V and 3.5mA typical at 115V
Digital Outputs • 1 on controller board , 30V, 60mA (used as status output)• 12 on 5601A I/O module - Sealed mechanical relay: • 0.4A at 125 Vrms, 2A at 30V resistive loads • 1.0A at 30V, 0.2A at 125Vrms inductive load with pf=0.4, L/R=7ms • 250Vrms, 220V maximum operating voltage
Communications
Serial Port COM1 Congurable RS-232 or RS-485, 2 wire half duplex or 4 wire full/half duplex
Serial Ports COM2, COM4 RS-232, DTE, 8 pin modular jack, full or half duplex with RTS/CTS control. Implemented Td, Rd, CTS, RTS, DCD, DTR, +5V
Serial Port COM3 Located on 5601A I/O module. Same specications as COM2 and COM4
Baud RatesCOM1, COM2, COM4
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200
Baud Rate COM3 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200
Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1, PPP
Ethernet Port 10BaseT, RJ45
Network Protocols IP:ARP, TCP, TFTP, UDP, ICMP
Ethernet Port Protocols Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP
Wireless1 Spread spectrum radio at 900MHz2 and 2.4 GHz2
GeneralI/O Terminations 6, 8, 9 and 10 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts
Dimensions 8.40 inch (213mm) wide, 6.13 inch (155mm) high, 2.80 inch (72mm) deep
Packaging Corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, –40°C (–40°F) to 70°C (158°F)
Power Input: 11 - 30 VDC, 3.5W typical all relays off, 6.5W typical all relays on
Warranty 3 years on parts and labor
Certifications
Hazardous LocationsNorth America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certied to therequirements of:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations• UL Std. No. 1604 - Hazardous (Classied) Locations
Safety CSA ( cCSA us ) certied to the requirements of: CSA C22.2 No. 142-M1987 and UL508. (Process Control Equipment,
Industrial Control Equipment) UL ( cULus ) listed: UL508 (Industrial Control Equipment)
1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
15
Product Data Sheet SCADAPack 32Specications
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
17/54
P4B, integrated 56O6 I/O board
Controller
Processor Hitachi SH-3 32-bit CMOS microcontroller, 120MHz clock, integrated watchdog timer
Memory 8 Mb SDRAM, 4 Mb FLASH, 1 Mb CMOS RAM
Non Volatile RAM CMOS RAM with lithium battery retains contents for 2 years with no power
I/O
Analog Inputs 8, single-ended, software selectable 0-5V / 0-10 V or 0-20mA / 4-20mA (15 bit resolution)
Analog Outputs 2 with optional 5305 analog output module, output range 0-20mA
Digital Inputs 4 on controller board - 3 Digital Input/Counter, 1 Interrupt with optical isolation,32 on 5606 I/O module:• 0.67 mA typical at 24V on the 12/24V range• 0.37 mA typical at 48V on the 48V range• 0.35 mA typical at 120V on the 115/125V range• 0.35 mA typical at 240V on the 240V range
Digital Outputs 1 on controller board, 30V, 60mA (used as status output)16 relay outputs on 5606 I/O module - dry contact or DC solid state:• Dry contact rating: 3A, 30VDC or 240VAC (Resistive)
• DC solid state rating: 3A, 60 VDC
Communications
Serial Port COM1 Congurable RS-232 or RS-485, 2 wire half duplex or 4 wire full/half duplex
Serial Ports COM2, COM4 RS-232, DTE, 8 pin modular jack, full or half duplex with RTS/CTS controlImplemented Td, Rd, CTS, RTS, DCD, DTR, +5V
Baud RatesCOM1, COM2, COM4
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200
Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1, PPP
Ethernet Port RJ45, 10BaseT
Network Protocols IP: ARP, TCP, TFTP, UDP, ICMP
Ethernet Port Protocols Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP
Wireless1 Spread spectrum radio at 900MHz2 and 2.4 GHz2
General
I/O Terminations 5, 6, 8, 9 and 10 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts
Dimensions 8.40 inch (213mm) wide, 6.48 inch (164mm) high, 2.80 inch (72mm) deep
Packaging Corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, –40°C (–40°F) to 70°C (158°F)
Power Input: 11 - 30 VDC, 4.3W typical (10.8W ful l I/O capacity in use )
Warranty 3 years on parts and labor
Certifications
Hazardous LocationsNorth America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4UL Listed and CSA certied to the following standards:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations• UL Std. No. 1604 - Hazardous (Classied) Locations
Hazardous LocationsEurope Model “5606 SSR, 24DI version only” ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2)Does not include Wireless versions.
Hazardous Locations Model “5606 SSR version only” IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.
1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
16
Product Data Sheet SCADAPack 32Specications
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
18/54
TBUP4-102-02-0-0 represents a sample code for a P4 with DNP, 0-5V inputs, 12-24V outputs
Model Select: Controller
TBUP4 SCADAPack 32, 32 Bit controller with Integrated Ethernet Port
Code Select: Lower I/O Module
5601A lower I/O module, includes 16 Digital Inputs, 12 Digital Outputs and 8 Analog Inputs (see options below)
A 5604 lower I/O module, includes 32 congurable Digital I/O and 8 selectable Analog Inputs (0-10v or 0-20mA)
B 5606 lower I/O module, includes 32 D/I, 16 Dry Contact D/O and 8 software congurable A/I
C 5606-A lower I/O module, includes 32 D/I, 16 Solid State Relay D/O and 8 software congurable A/I
N No lower I/O module (provides controller module only)
Code Select: Communications Serial Ports
1 TBUP4/P4A/P4N: 3 RS232, 1 RS232/485, 1 Ethernet TBUP4B/P4C: 2 RS232, 1 RS232/485, 1 Ethernet
Integrated FreeWave & MDS Radios (requires one RS232 port)
A 900Mhz FreeWave Spread Spectrum Radio Consult CMI for availability in your market area
3 900MHz MDS Spread Spectrum Radio Consult CMI for availability in your market area
Trio Radios - 900MHz (requires one RS232 port)
B 900MHz Trio Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)
C 900MHz Trio Spread Spectrum Radio with encryption, 915-928MHz (AUS)
D 900MHz Trio Spread Spectrum Radio, 915-928MHz (BRAZIL)
E 900MHz Trio Spread Spectrum Radio, 921-928MHz (NZ)
Trio Radios - 2.4GHz (requires one RS232 port)
J 2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)
K 2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)
L 2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)
Code Select: Gas Flow Run-time Option
0 None
Flow Computer Runs
G 2 Run Gas Flow
F 4 Run Gas Flow
T 10 Run Gas Flow
Flow Computer Runs - Gas Transmission Version (Requires Realflo 6.72+) V 2 Run Gas Flow
W 4 Run Gas Flow
Code Select: Protocol Option/Programming Environment
2 Modbus and DNP 3.0 (Level 2) protocol with Telepace Ladder Logic and C Language rmware loaded - IEC enabled
5 Modbus and DNP 3.0 (Level 2) protocol with IEC 61131-3 and C Language rmware loaded - Telepace enabled
Code Select: Analog Inputs
01 0-20mA, single ended (On TBUP4 & TBUP4A, Default on TBUP4B which is software congurable to 0-5v or 0-10v)
02 0-5 volt, single ended (TBUP4 Only)
03 0-10 volt, single ended (TBUP4A Only)
Code Select: Digital Inputs/Outputs
0 24 volt D/I TBUP4 & TBUP4B: Dry Contact D/O TBUP4C: SS Relay D/O TBUP4A: Cong I/O TBUP4N: No I/O
1 120 volt D/I TBUP4 & TBUP4B: Dry Contact D/O TBUP4C: Solid State Relay D/O (Not for TBUP4A or TBUP4N)
Code Select: Analog Outputs0 None (required for TBUP4N)
1 2 channel Analog Output option, 0-20 mA
Product Data Sheet SCADAPack 32Model Code
17
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
19/54
SCADAPack 100
Controller
Processors • 16-bit CMOS micro-controller, 14.74MHz clock, integrated watchdog timer
• micro-controller co-processor: 14.74MHz clock
Memory • 256KBytes CMOS RAM (control ler ID number A182921 or less)• 1024KBytes CMOS RAM (controller ID number A182922 or greater)• 512kBytes ash ROM, 1kBytes EEPROM
Non-volatile RAM CMOS RAM with lithium battery retains contents for 2 years with no power
I/O
Analog Inputs • 3 at 5V/20mA: 250W resistance user congurable with jumper link• 1 at 32.768V
Resolution 12 bits over the 5V and 32.768V measurement range
Digital I/O 6 points, each point is an input and an output, dry contact input, 1.0A max output rating
Counter Inputs 1, maximum frequency 5kHz, dry contact input, wetting current typically 5mA with 24V input power
Communications
Communication Port COM1 RS-485 serial port, 2 pole removable terminal block, 2 wire half duplex, bias resistors installed
Communication Port COM1 RS-232 compatible serial port (CMOS), Data Terminal Equipment (DTE), 8 pin modular jack, full or half duplex,implemented Td, Rd, +5V
Communication Port COM2 RS-232 compatible serial port (CMOS), Data Terminal Equipment (DTE), 8 pin modular jack, full or half duplex with RTS/CTScontrol, implemented Td, Rd, CTS, RTS, DCD, DTR, +5V
Baud Rates COM1 & COM2 300, 600, 1200, 2400, 4800, 9600, 19200, 38400
Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1
Serial Protocol Modes Slave, Master, Master/Slave, Store and Forward
Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2
General
I/O Terminations 5 and 12 pole, removable terminal blocks. 12 to 22 AWG 15A contacts Screw termination 6 lb.-in. (0.68 Nm) torque
Dimensions 5.65 inch (144mm) wide, 5.00 inch (127mm) high, 1.80 inch (45mm) deep
Packaging Corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, –40°C (–40°F) to 70°C (158°F)
DC Power Input: 30V maximum, 10.0 to 11.5V turn on, 9.5V typical turn off, UL508 rated 13.75-28Vdc. Class 2, less than 500mW (at 12V) LEDs off,2.9W maximum
Output Capacity 5V at 0.425A capacity, 5V at 0.060A required by 5208 controller, 5V at 0.365A available on COM1 and COM2
Warranty 3 years parts and labor
Certifications
Hazardous LocationsNorth America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations.Temperature Code T4 per CSA Std C22.2 No. 213-M1987 / UL1604 UL listed and CSA certied to the following standards:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations• UL Std. No. 1604 - Hazardous (Classied) Locations
Hazardous Locations ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2) Does not include Wireless versions
Safety CSA ( cCSA us ) certied to the requirements of: CSA C22.2 No. 142-M1987 and UL508. (Process Control Equipment,Industrial Control Equipment) UL ( cULus ) listed: UL508 (Industrial Control Equipment)
1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
Product Data Sheet SCADAPack 100Specications
18
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
20/54
TBUP100-1A20-AA00 represents a sample code for a TBUP100 with DNP, 0-5V inputs
Model Select: Controller
TBUP100 SCADAPack 100, comes with 3 Analog Inputs, 6 congurable Digital I/O, 1 Accumulator
TBUP110 SCADAPack 100, Gas Flow Controller with 1 Gas Flow Run (I/O as above)
Code Select: Communication Serial Ports
1 2 Communication Ports (RJ45 Type) : 1 RS-232 and 1 RS232/485
Code Select: Memory Configuration
A 1 MB CMOS RAM (512K OS, 512K APP), 512K FLASH ROM
Code Select: Protocol Option
2 Modbus and DNP 3.0 (Level 2) protocol emulation
Code Select: Programming Environment
0 Telepace Ladder Logic and C Language rmware loaded - IEC enabled (Programming Tools sold separately)
1 IEC 61131-3 and C Language rmware loaded - Telepace enabled (Programming Tools sold separately)
Code Select: Analog Inputs A 3 Analog Inputs, individually selectable as 0-20mA or 0-5 volts
Code Select: Digital Inputs/Outputs
A 6 congurable Digital I/O, individually selectable as Digital Input (Dry Contact) or Digital Output (Open Drain)
Code Select: Analog Outputs
0 None
Code Select: Integrated Communication Interfaces
0 None
FreeWave & MDS Radios (requires one RS232 port)
1 900Mhz FreeWave Spread Spectrum Radio – consult CMI for availability in your market area
A 900Mhz MDS Spread Spectrum Radio – consult CMI for availability in your market area
Trio Radios - 900MHz (requires one RS232 port)
B 900MHz SCADAWave Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)
C 900MHz SCADAWave Spread Spectrum Radio with encryption, 915-928MHz (AUS)
D 900MHz SCADAWave Spread Spectrum Radio, 915-928MHz (BRAZIL)
E 900MHz SCADAWave Spread Spectrum Radio, 921-928MHz (NZ)
Trio Radios - 2.4GHz (requires one RS232 port)
J 2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)
K 2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)
L 2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)
Product Data Sheet SCADAPack 100Model Code
19
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
21/54
Product Data Sheet 5502 – Differential analog input moduleSpecications
20
5502 Differential analog input module
General
Input Points 8: voltage or current inputs, each input is switch selectable as voltage or current
Ranges Voltage -10V to +10V, Current -20mA to +20mA
Resolution Voltage 1.22mV, Current 4.88µA
Input Resistance Voltage > 10MΩ, Current 250Ω
Converter Type 13-bit plus sign successive approximation
Accuracy • +/- 0.1% of full scale at 25°C (77°F)• +/- 0.2% of full scale over temperature range
Isolation • 550VAC from any input to the chassis or the system power supplies.• 140VAC/200VDC between inputs
Common Mode Rejection • >96dB at 50/60Hz, >50dB at 10KHz. with 1KΩ imbalance• >50dB at 1KHz. with 10KΩ imbalance
Normal Mode Rejection >45dB at 50/60Hz
Transient Protection • Transient suppressors and fuses on each input• 2.5kV surge withstand capability as per ANSI/IEEE, C37.90.1-1989
Over-Scale Input Capacity 12VDC maximum. Exceeding 12V will cause the fuse to blow.
Input Fuses 1/8 Amp.
Reading Update Time 170ms with 60Hz. rejection selected. 185mS with 50Hz rejection selected.
Power Requirements 5V @ 100mA
Terminations 2: 8 pole, removable terminal blocks, 12 - 22 AWG, 15A contacts
Dimensions 144mm wide x 118mm high x 44mm deep (5.65in. x 4.625in. x 1.75in.)
Mounting 7.5 x 35 DIN rail
Packaging Corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety Class 1, Division 2 for use in hazardous locations
Part Number TBUX297211
This IO Expansion module is not supported by the SCADAPack E RTU.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
22/54
Product Data Sheet 5504 – Thermocouple input moduleSpecications
21
5504 Thermocouple input module
General
Input Points 8 thermocouples or millivolt signals
Thermocouple Typesand Ranges
J: -200°C to 760°C (-328°F to 1400°F)K: -270°C to 1370°C (-454°F to 2498°F)E: -270°C to 1000°C (-454°F to 1832°F)T: -270°C to 400°C (-454°F to 752°F)mV ±80mV
Resolution 0.004mV, approximately 0.10°C (0.18°F)
Input Resistance 1MΩ
Accuracy Over -40°C to 60°COperating Temperature Range
J: ±0.20% of full scaleK: ±0.20% of full scaleE: ±0.15% of full scaleT: ±0.50% of full scalemV ±0.15% of full scale
Cold Junction Compensation • ±0.5°C (0.9°F) maximum error from 0°C to 60°C (32°F to 140°F)• ±1°C (1.8°F) maximum error from -40°C to 0°C (-40°F to 32°F)
Converter Type ±20000 count, integrat ing
Common Mode Voltage Range ±10V can be applied to the inputs, relative to the -24V power supply input
Isolation 500VAC from the logic power
Transient Protection MOVs on each input
Response Time 0.5 seconds
Power Requirements • > 5V @40mA • > 20 to 28V @ 45mA
Terminations 10 pole and 8 pole, two xed terminal blocks, 12 - 22 AWG, 15 amp contacts
Dimensions 144mm wide x 118mm high x 44mm deep (5.65in. x 4.625in. x 1.75in.)
Mounting 7.5 x 35 DIN rail
Packaging Corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety Class 1, Division 2 for use in hazardous locations
Part Number TBUX297166
This IO Expansion module is not supported by the SCADAPack E RTU.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
23/54
Product Data Sheet 5505 – RTD input moduleSpecications
22
5505 RTD input module
General
Input Points 4, RTD
RTD Type 100-ohm platinum, 3 and 4-wire, auto-detection and compensation
Calibration 0.00385Ω / Ω /°C standard based on ASTM E 1137/E 1137M-04, ITS-90
Ranges 5505: Can be congured to return data in ohms, °C, °F or °K• -200°C to 800°C (-328°F to 1472°F)• 0 to 500Ω5503 Emulation: Dipswitch selectable• 0°C to 200°C (32°F to 392°F)• -100°C to 100°C (-148°F to 212°F)• -200°C to 0°C (-328°F to 32°F)• 0°C to 800°C (32°F to 1472°F)• 0°C to 400°C (32°F to 752°F)• 0 to 400Ω
Data Format • 5505: 32-bi t oating point and 12 status bi ts• 5503 Emulation: 16-bit signed integer
Resolution • 5505: > 17-bit effective
• 5505 Emulation: 15-bitRTD Status • RTD is good (not open)
• RTD in range• RTD 3 or 4-wire• RTD status not available in 5503 Emulation
Accuracy on RTD Ranges Percent of full scale over operational temperature range including linearization errors: +0.10%/-0.05%
Accuracy on 0 to 500ohms Percent of full scale over operational temperature range: ±0.03%
Excitation Current 4mA, 7.2% duty cycle in 4-wire mode, 14.4% in 3-wire mode, 250ms scan interval
Line Resistance 100Ω max., in each line
Converter Type 24-bit delta-sigma
Response Time 380ms typical for 10% to 90% signal change at minimum lter setting
Transient Protection 2.5kV surge-withstand capability as per ANSI/IEEE C37.90.1-1989
Isolation Isolation from logic supply and chassis, voltage 500Vrms
5V Power Requirements 6mA
11 - 30VDCPower Requirements
12V operation: 4mA • plus 0.6mA per 4-wire RTD• plus 1.2mA per 3-wire RTD24V operation: 2.2mA • plus 0.3mA per 4-wire RTD• plus 0.6mA per 3-wire RTD
11-30VDC - Connector Removable. Shared with RTD inputs 0-1
11-30VDC - Isolation Isolation from logic supply and chassis
Terminations 8 and 10 pole, removable terminal block,12 to 22 AWG, 15A contacts
Dimensions 74mm wide x 124mm high x 45mm deep (2.9in. x 4.9in. x 1.8in.)
Mounting 7.5 x 35 DIN rail
Packaging Corrosion-resistant zinc-plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, -40°C to 70°C (-40°F to 158°F) operation, -40°C to 85°C (-40°F to 185°F) storage
Safety • Non-Incendive Electrical Equipment for Use in Class I, Divis ion2• Groups A, B C and D Hazardous Locations• ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2)
Part Number TBUX297318
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
24/54
Product Data Sheet 5506 – Analog input moduleSpecications
23
5506 Analog input module
General
Input Points 8
Ranges • 0-20mA • 4-20mA • 0-5V• 1-5V
LED Indicators 8 red LEDs, indicating current input, voltage input and under or over-range signal applied
Input Conguration Individual inputs congurable with 4mA/1V (20%) offset and for voltage/current operation when congured as a 5506. All inputsdipswitch-selectable with 4mA/1V (20%) offset and for voltage/current operation when congured to emulate a 5501 module.
Input Resistance 250 ohms - Current conguration ; 66k ohms - Voltage conguration
Resolution 15-bits over the 0-5V and 0-20mA measurement range
Type Single-ended
Accuracy ±0.1% of full scale at 25°C (77°F) ; ±0.2% over temperature range
Transient Protection 2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989
Normal Mode Rejection At 60 Hz with 60Hz Scanning
• 53dB with 3Hz lter• 50dB with 6Hz lter• 49dB with 11Hz lter• 45dB with 30Hz lter
Normal Mode Rejection At 50 Hz with 50Hz Scanning
• 73dB with 3Hz lter• 56dB with 6Hz lter• 52dB with 11Hz lter• 49dB with 30Hz lter
Response Time for 10% to90% Signal Change(60Hz Scanning)
• 250ms with 3Hz lter• 130ms with 6Hz lter• 60ms with 11Hz lter• 30ms with 30Hz lter
Response Time for 10% to90% Signal Change(50Hz Scanning)
• 300ms with 3Hz lter• 140ms with 6Hz lter• 80ms with 11Hz lter• 40ms with 30Hz lter
Over-Scale Input Capacity
(without damage)
Continuous: 0.10A/14V on the 20mA inputs ; 0.05A/14V on the 5V inputs
Isolation 500Vac isolation f rom logic supply and chassis
5V Power Requirements • 22mA, LEDs off• 45mA, LEDs on
11-30VDC Power Requirements 11mA
11-30VDC - Connector Removable, 4 positions
11-30VDC - Isolation Isolation from logic supply and chassis
Terminations 10 pole, removable terminal block,12 to 22 AWG, 15A contacts
Dimensions 2.9 inch (74 mm) wide, 4.9 inch (124 mm) high, 1.8 inch (45 mm) deep
Mounting 7.5 x 35 DIN rail
Packaging Corrosion-resistant zinc-plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, -40°C to 70°C (-40°F to 158°F) operation, -40°C to 85°C (-40°F to 185°F) storage
Safety • Non-Incendive Electrical Equipment for Use in Class I, Divis ion2• Groups A, B C and D Hazardous Locations• ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2)
Part Number TBUX297319
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
25/54
Product Data Sheet 5302 – Analog output moduleSpecications
24
5302 Analog output module
General
Output points 4 ( 2 when used with 5201 and 5201 control lers)
Output signal ranges 0-20mA or 4-20mA, switch congurable
Output Type Single ended regulation on positive side with common negative return
Maximum Load Resistance 1000W with 24VDC loop power, 400W with 12VDC loop power , 250Wwith 9VDC loop power
Isolation 1500VAC eld to logic
D/A Resolution 12-bit over the 0-20mA ranges
Absolute Accuracy +/- 0.05% of full scale at 25ºC (77ºF), +/- 0.2% of full scale over temperature range
Noise and Ripple 0.04% maximum
Transient Protection 2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989
Response Time 250ms typical for 10% to 90% signal change
Addressing DIP switch congurable
Power Requirements 5V @ 45mA, 9 - 30V @ 15mA quiescent plus 80mA max.
Terminations 10 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Dimensions 108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting 7.5 x 35 DIN rail
Packaging Corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, -40°C to 70°C (-40°F to 158°F)
Safety cCSA us and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Part Number TBUX297176
This IO Expansion module is not supported by the SCADAPack E RTU.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
26/54
Product Data Sheet 5304 – Analog output moduleSpecications
25
5304 Analog output module
General
Output points 4
Output Modes • Current mode, jumper link selectable• Voltage mode, 5V full scale, jumper link selectable,• Voltage mode, 10V full scale, jumper link selectable
Output signal ranges • 0-20mA or 4-20mA, switch congurable• 0-5V or 1-5V, switch congurable, 0-10V or 2-10V, switch congurable
Output Type Single ended regulation on positive side with common negative return
Maximum Load Resistance 1000Ω with 24VDC loop power, 400Ω with 12VDC loop power, 250Ω with 9VDC loop power
Minimum Load Resistancein Voltage Mode
• 2kΩ for 10V full scale, with min 20VDC power applied• 1kΩ for 5V full scale, with min 15VDC power applied
Isolation 500VAC eld to logic
D/A Resolution 12-bit over the 0-20mA / 0-5V/ 0-10V ranges
Absolute Accuracy +/- 0.05% of full scale at 25ºC (77ºF), +/- 0.2% of full scale over temperature range
Noise and Ripple 0.04% maximum
Transient Protection • 2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989• Inductive load protection diodes included
Response Time 2ms typical to 90% signal change
Addressing DIP switch congurable
12-24V Operating Voltage Limits
• 9V or (20mA x load resistance) +4V (whichever is greater) in current mode• (1.5 x Range / load resistance) + Range + 2.5V in voltage mode, 30V maximum
Power Requirements • 6mA min., 25mA maximum• 15mA quiescent plus 80mA max. in current mode• 15mA quiescent plus 20mA max. in voltage mode
Terminations 10 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Dimensions 108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting 7.5 x 35 DIN rail
Packaging Corrosion resistant zinc plated steel with black enamel paintEnvironment 5% RH to 95% RH, non-condensing, -40°C to 70°C (-40°F to 158°F)
Safety cCSA us and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Model Part Number Description
5304-20 TBUX297248 4 channel isolated analog output module, 0-20mA
5304-10 TBUX297252 4 channel isolated analog output module, 0-10 vol ts
5304-5 TBUX297253 4 channel isolated analog output module, 0-5 volts
5304-C TBUX297254 4 channel isolated analog output module, Custom (specify range of each input)
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
27/54
Product Data Sheet 5403 – High level digital input moduleSpecications
26
5403 High level digital input module
General
Number of Digi tal Inputs 8
Input Logic-HI Level OFF to ON transition threshold is typically 50% of full scale signal range
Over-Voltage Tolerance 150% sustained over-voltage without damage
Input Current 5mA typical
Response Time • OFF to ON: 7ms typical• ON to OFF: 24ms typical
Isolation 1500VAC in groups of 4 inputs
Addressing DIP switch congurable
Power Requirements 5V @ 45mA all LEDs ON, 5V @ 25mA with LEDs disabled
Visual Indicators 16: red LEDs controlled for power reduction
Field Terminations • 1: 10 pole, removable terminal block• 12 to 22 AWG• 15A contacts
Dimensions 108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting 7.5 x 35 DIN rail
Packaging Corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety cCSA us and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Model Part Number Signal range
5403-12 TBUX297110 12 volts AC/DC
5403-24 TBUX297109 24 volts AC/DC
5403-48 TBUX297108 48 volts AC/DC
5403-120 TBUX297107 120 volts AC/DC
5403-240 TBUX297106 240 volts AC/DC
This IO Expansion module is not supported by the SCADAPack E RTU.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
28/54
Product Data Sheet 5404 – High level digital input moduleSpecications
27
5404 High level digital input module
General
Number of Digital Inputs 16
Input Logic-HI Level OFF to ON transition threshold is typically 50% of full scale signal range
Over-Voltage Tolerance 150% sustained over-voltage without damage
Input Current 5mA typical
Response Time • OFF to ON: 7ms typical• ON to OFF: 24ms typical
Isolation 1500VAC in groups of 4 inputs
Addressing DIP switch congurable
Power Requirements 5V @ 80mA all LEDs ON, 5V @ 25mA with LEDs disabled
Visual Indicators 16: red LEDs controlled for power reduction
Field Terminations • 2: 10 pole, removable terminal block• 12 to 22 AWG• 15A contacts
Dimensions 144mm wide x 118mm high x 44mm deep (5.65in. x 4.625in. x 1.75in.)
Mounting 7.5 x 35 DIN rail
Packaging Corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety cCSA us and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Model Part Number Signal range
5404-12 TBUX297158 12 volts AC/DC
5404-24 TBUX297157 24 volts AC/DC
5404-48 TBUX297156 48 volts AC/DC
5404-120 TBUX297155 120 volts AC/DC
5404-240 TBUX297154 240 volts AC/DC
This IO Expansion module is not supported by the SCADAPack E RTU.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
29/54
Product Data Sheet 5405 – Digital input moduleSpecications
28
5405 Digital input module
General
Input Points 32
Ranges 12-24VDC, 16-24VAC, 120VAC/DC
Over-Voltage Tolerance 150% sustained over-voltage without damage
Input Current • 6.0mA typical @ 24VDC on the 24V range• 3.5mA typical @ 24VAC on the 24V range• 2.5mA typical @ 120VDC on the 120V range• 1.5mA typical @ 120VAC on the 120V range
DC Input Logic Levels • OFF to ON transition threshold is typically 7.5VDC on the 24VDC range• OFF to ON transition threshold is typically 55VDC on the 120VDC range
AC Input Levels • OFF to ON transition threshold is typically 6VAC on the 24VAC range• OFF to ON transition threshold is typically 45VAC on the 120VAC range
Transient Protection 2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989
Isolation • Isolated in 4 groups of 8. Inputs 0-15 are on the bottom edge.• Inputs 16-31 are on the top edge. Isolation 500VAC/DC from chassis and logic ground
Power Requirements 5V @ 10mA with all inputs ON
Terminations 4: 9 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts
Dimensions 144mm wide x 127mm high x 45mm deep (5.65in. x 5.00in. x 1.88in.)
Packaging Corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Addressing Congurable with 4 DIP switches
AC/DC Operation 2: DIP switches determine AC/DC and 50/60Hz operation
Visual Indicators 32: Red LED’s, eld powered. Cannot be disabled to conserve power
Safety cCSA us and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Model Part Number Description
5405-120 TBUX297249 32 point , 120V discrete input module
5405-24 TBUX297247 32 point , 12-24V discrete input module
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
30/54
Product Data Sheet 5410 – High speed counter/accumulatorSpecications
29
5410 High speed counter/accumulator
General
Counter Input Points 4
Count Length 32-bit, range is 0 to 4,294,967,295
Over-Voltage Protection Transient suppressor on each input
Input Voltage Range Typical operating inputs 5 to 24V, 3V minimum, 28V maximum
Input Current 8mA typical, 13mA maximum
Input Logic Level OFF to ON threshold is typically 2V
Maximum Input Frequency 10kHz with lters off, 5kHz with quadrature counters, 60Hz with de-bounce lters on
Maximum Pulse High Width • 50 microseconds (µs), 100µs with quadrature counters• 8.3 milliseconds with de-bounce lters
Minimum Pulse Low Width • 50 microseconds (µs), 100µs with quadrature counters• 8.3 milliseconds with de-bounce lters
Isolation 500VAC input to input, 500VAC input to logic circuit
Addressing DIP switch congurable
Terminations 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Visual Indicators • 4: red LEDs• LED on time stretched for easy viewing controlled for power reduction
Power Requirements 5V @ 35mA with all LEDs on, 5V @ 15mA with LEDs disabled
Dimensions 108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting 7.5 x 35 DIN rail
Packaging Corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety Class 1, Division 2 for use in hazardous locations
Part Number TBUX297149
This IO Expansion module is not supported by the SCADAPack E RTU.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
31/54
Product Data Sheet 5414 – Compact digital input moduleSpecications
30
5414 Compact digital input module
General
Number of Digital Inputs 16
Ranges Factory congurable as:• 12/24V• 48V• 115/125V• 240V
Input Current • 0.6 – 0.9mA at 24V on the 12/24V range• 0.3 – 0.4mA at 48V on the 48V range• 0.3 – 0.4mA at 120V on the 115/125V range• 0.3 – 0.4mA at 240V on the 240V range
Over-voltage Tolerance 150% sustained over-voltage without damage
Power Requirements • 5V@6mA with LEDs off• 5V@40mA with LEDs on
Visual Indicators Logic powered LEDs. Can be disabled to conserve power
Field Terminations 12 to 22 AWG, 15A contacts
Dimensions 74mm wide x 124mm high x 45mm deep (2.90in. x 4.90in. x 1.80in.)
Mounting 7.5 x 35 DIN rail
Packaging Corrosion resistant zinc plated steel with black enamel paint
Environment • 5% RH to 95% RH, non-condensing• –40ºC to 70ºC (–40ºF to 158ºF) operation• –40ºC to 85ºC (–40ºF to 185ºF) storage
Safety • Class I, Division 2, Groups A, B, C and D and CSA certied to UL508 standards• ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2) (5414-24 only)• Maximum permitted voltage in Canada or North America is 240VAC• Maximum permitted voltage outside of Canada or North America is 30VAC/42.4PK/60VDC
Model Part Number Signal Range
5414-24 TBUX297378 12/24V AC/DC, ATEX and IECEx
5414-48 TBUX297379 48V AC/DC (Not avai lable outside of North America)
5414-120 TBUX297380 115/125V AC/DC (Not available outside of North America)
5414-240 TBUX297381 240V AC/DC (Not available outside of North America)
Note: Module not supported on 16-bit SCADAPack platform (SCADAPack, SCADAPack Light, SCADAPack Plus, SCADAPack 100 and SCADAPack LP)
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
32/54
Product Data Sheet 5401 – Congurable digital I/O moduleSpecications
31
5401 Congurable digital I/O module
General
Number of Inputs or Outputs 8
Voltage Range See relay specications below
Load Current See relay specicat ions below
Surge Current See relay specicat ions below
Off-State Leakage See relay specications below
Transient Protection Integral to the solid-state relay
Response Time See relay specications below
Isolation 1500VAC
Addressing DIP switch congurable
Input/Output Assignment DIP switch selection for each I/O point
Power Requirements 5V @ 90mA
Visual Indicators 8: red LEDs, permanently enabled
Field Terminations 2: 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Dimensions 108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting 7.5 x 35 DIN rail
Packaging Corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety cCSA us and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
TBUX297121 8-point input or output module (requires solid-state relays)
Model Part Number Solid-State Relays for use with Model 5401
IACM-5 TBUX297122 90-140 VAC/VDC input relay
IACM-5A TBUX297132 180-280 VAC/VDC input relay
IACM-5E TBUX297133 10-32VDC, 15-32VAC, no polarity
IDCM-5 TBUX297124 3-32VDC input relay
OACM-5 TBUX297123 24-140VAC output relay, 3A
OACM-5H TBUX297134 24-280VAC output relay, 5A
ODCM-5 TBUX297125 3-60VDC output relay, 3A
ODCM-5A TBUX297135 10-200VDC, 1A
This IO Expansion module is not supported by the SCADAPack E RTU.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
33/54
Product Data Sheet 5402 – Congurable digital input or output moduleSpecications
32
5402 Congurable digital input or output module
General
Number of Inputs or Outputs 16
Voltage Range See relay specications below
Load Current See relay specicat ions below
Surge Current See relay specicat ions below
Off-State Leakage See relay specications below
Transient Protection Integral to the solid-state relay
Response Time See relay specications below
Isolation 1500VAC
Addressing DIP switch congurable
Input/Output Assignment DIP switch selectable as all inputs or outputs
Power Requirements 5V @ 150mA
Visual Indicators 16: red LEDs, permanently enabled
Field Terminations 4: 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Dimensions 215mm wide x 118mm high x 44mm deep (8.37in. x 4.625in. x 1.75in.)
Mounting 7.5 x 35 DIN rail
Packaging Corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety Class 1, Division 2 for use in hazardous locations
Part Number TBUX297153 - 16-point input or output module (requires solid-state relays)
Model Part Number Solid-State Relays for use with Model 5402
IACM-5 TBUX297122 90-140 VAC/VDC input relay
IACM-5A TBUX297132 180-280 VAC/VDC input relay
IACM-5E TBUX297133 10-32VDC, 15-32VAC, no polarity
IDCM-5 TBUX297124 3-32VDC input relay
OACM-5 TBUX297123 24-140VAC output relay, 3A
OACM-5H TBUX297134 24-280VAC output relay, 5A
ODCM-5 TBUX297125 3-60VDC output relay, 3A
ODCM-5A TBUX297135 10 - 200VDC output relay, 1A
This IO Expansion module is not supported by the SCADAPack E RTU.
Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.
https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/
-
8/17/2019 SCADAPack RTUs Controllers IO Datasheet
34/54
Product Data Sheet 5406A – Dry contact relay out moduleSpecications
33
5406A Dry contact relay out module
General
Number of Relay Outputs 16
Type Sealed mechanical relay, Form A (normally open) contacts
Contact Ratings • 6A @ 250VAC resistive loads, 6A @ 30VDC resistive loads• 3.5A at 30VDC/250VAC inductive load (pf=0.4. L/R=7 ms), 1/4 HP 125VAC• 3A maximum in Class 1, Division 2 hazardous locations
Operating Frequency 18,000 operations/hour mechanically, 1,800 electrically at rated load
Service Life • 1,500,000 operations at 0-250mA loads, 600,000 operations at 1A resistive load• 100,000 operations at 6A resistive load, 300,000 operations at 1A inductive loads (pf=0.4)• 100,000 operations at 3.5A inductive loads (pf=0.4)
Operate Time 10mS maximum, 5mS typical
Release Time 10mS maximum, 2mS typical
Bounce Time 3mS typical
Contact Isolation 1000VAC
Logic Isolation 1500VAC
Addressing DIP switch congurable
Power Requirements • 5V Bus Power - 5V @ 600mA with all LEDs and all relays energized• External Power - 5V @ 65mA with all LEDs and all relays energized
Visual Indicators 16: red LEDs, controlled for power reduction
Field Terminations • 4: 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts• Additional three pins on connector P3 to support external power
Dimensions 215mm wide x 118mm high x 44mm deep (8.37in. x 4.625in. x 1.75in.)
Mounting 7.5 x 35 DIN rail
Packaging Corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety cCSA us and cULus Class I, Division 2 Hazardous Area Rating,