SAP Calculations

Client: FitzArchitectsDraft SAP 08.12.2015

Project: BungalowUndercliff

Contact: Sandra [email protected]

Predicted Energy Assessment Page 2 of 16

Bungalow, Undercliff,Cleadon,SR6 7UX

Dwelling type: Bungalow, DetachedDate of assessment: 08.Dec.2015Produced by: Frank Dixon AssociatesTotal floor area: 530.66 m2

This document is a Predicted Energy Assessment for properties marketed when they are incomplete. It includes a predicted energy rating which might not represent the final energy rating of the property on completion. Once the property is completed, this rating will be updated and an official Energy Performance Certificate will be created for the property. This will include more detailed information about the energy performance of the completed property.

The energy performance has been assessed using the Government approved SAP2012 methodology and is rated in terms of the energy use per square meter of floor area; the energy efficiency is based on fuel costs and the environmental impact is based on carbon dioxide (CO2) emissions.

Energy Efficiency Rating

Very energy efficient - lower running costs

A(92 plus)

B(81-91)

C(69-80)

D(55-68)

E(39-54)

F(21-38)

G(1-20)

Not energy efficient - higher running costs

England EU Directive2002/91/EC

94

Environmental Impact (CO2) Rating

Very environmentally friendly - lower CO2 emissions

A(92 plus)

B(81-91)

C(69-80)

D(55-68)

E(39-54)

F(21-38)

G(1-20)

Not environmentally friendly - higher CO2 emissions

England EU Directive2002/91/EC

95

The energy efficiency rating is a measure of theoverall efficiency of a home. The higher the ratingthe more energy efficient the home is and the lowerthe fuel bills are likely to be.

The environmental impact rating is a measure of ahome's impact on the environment in terms ofcarbon dioxide (CO2) emissions. The higher therating the less impact it has on the environment.

© Elmhurst Energy Systems Limited Registered Office Unit 16, St Johns Business Park, Lutterworth, Leicestershire LE17 4HB

Sandra [email protected]

Summary InformationProperty Reference: 002418 Issued on Date: 08.Dec.2015Survey Reference: 001 Prop Type Ref: Det bungalowProperty: Bungalow, Undercliff, Cleadon, SR6 7UXSAP Rating: 94 AEnvironmental:95 A

CO2 Emissions (t/year): 2.06General Requirements Compliance: Pass

DER: 5.95 PassDFEE:43.06 Pass

TER: 20.24TFEE:61.67

Percentage DER<TER: 70.60 %Percentage DFEE<TFEE: 30.17 %

CfSH Results Version: ENE1 Credits: N/A ENE2 Credits: N/A ENE7 Credits: N/A CfSH Level: N/ASurveyor: Sandra Hardwick, Tel: 01670 359491 Surveyor ID: B578-0001Address: Ridley Avenue, Blyth, Northumberland, NE24 3BAClient:Software Version: Elmhurst Energy Systems SAP2012 Calculator (Design System) version 3.02r10SAP version: SAP 2012, Regs Region: England (Part L1A 2013), Calculation Type: New Dwelling As Designed

SUMMARY FOR INPUT DATA FOR New Build (As Designed) Page 3 of 16

Orientation North East1.0 Property Type Bungalow, Detached2.0 Number of Storeys 13.0 Date Built 20153.0 Property Age Band4.0 Sheltered Sides 25.0 Sunlight/Shade Very little6.0 Measurements

Heat Loss Perimeter Internal Floor Area Average Storey Height

Ground Floor: 175.42 530.66 2.707.0 Living Area 39.738.0 Thermal Mass Parameter Simple calculation - High9.0 External WallsDescription Construction U-Value Kappa Gross Area Nett Area

External wall Cavity wall : dense plaster, dense block, filled cavity, any outside structure 0.15 433.99 228.79

wall to unheated Other 0.15 39.64 39.649.1 Party wallsDescription Construction Kappa Area

10.0 External RoofsDescription Construction U-Value Kappa Gross Area Nett Area

Flat roof Plasterboard, insulated flat roof 0.13 530.66 519.6811.0 HeatLoss FloorsDescription Construction U-Value Kappa Area

ground floor Slab on ground, screed over insulation 0.10 530.6612.0 Opening TypesDescription Data Source Type Glazing Glazing Gap Argon Filled Solar Trans Frame Type Frame Factor U value

Window Manufacturer Window Double Low-E Soft 0.05 0.72 0.95 1.45

external door Manufacturer Half Glazed Door

Double Low-E Soft 0.05 0.63 0.70 1.50

rooflights Manufacturer Roof Window Double Low-E Soft 0.05 0.70 0.90 1.30

13.0 OpeningsName Opening Type Location Orientation Curtain Type Overhang

RatioWide

Overhang Width Height Count Area CurtainClosed

South Window [1] External wall South Net curtain (covering whole window) 0.74 Yes 94.50

© Elmhurst Energy Systems Limited Registered Office Unit 16, St Johns Business Park, Lutterworth, Leicestershire LE17 4HB

SUMMARY FOR INPUT DATA FOR New Build (As Designed) Page 4 of 16

South west shade Window [1] External wall South West Net curtain (covering

whole window) 1.48 Yes 27.00

s west shallow shade Window [1] External wall South West None 0.74 No 15.88

s east deep shade Window [1] External wall South East None 1.00 No 7.29

south unshaded Window [1] External wall South Net curtain (covering

whole window) 0.00 15.12

east Window [1] External wall East Net curtain (covering whole window) 0.00 16.34

north west Window [1] External wall North West Net curtain (covering whole window) 0.00 13.00

North Window [1] External wall North None 0.00 10.40north east Window [1] External wall North East None 0.00 5.67rooflights Roof Window [1] Flat roof Horizontal None 10.9814.0 Conservatory None15.0 Draught Proofing 10016.0 Draught Lobby Yes17.0 Thermal Bridging Calculate Bridges17.1 List of BridgesSource Type Bridge Type Length Psi Imported

Table K1 - Approved E2 Other lintels (including other steel lintels) 79.72 0.300 YesTable K1 - Approved E3 Sill 79.72 0.040 NoTable K1 - Approved E4 Jamb 145.60 0.050 YesTable K1 - Approved E5 Ground floor (normal) 175.42 0.160 YesIndependently assessed E14 Flat roof 175.42 0.050 YesTable K1 - Approved E16 Corner (normal) 21.60 0.090 NoTable K1 - Default R1 Head of roof window 7.84 0.080 YesTable K1 - Default R2 Sill of roof window 7.84 0.060 YesTable K1 - Default R3 Jamb of roof window 22.40 0.080 Yes18.0 Pressure Testing Yes Designed q50 3.00 Property Tested ? As Built q50 Same As Designed ?19.0 Mechanical Ventilation Mechanical Ventilation System Present

Yes

Approved Installation Yes Windows open in hot weather Windows half open Cross ventilation possible Yes Night Ventilation No Air change rate 3.00 Mechanical Ventilation data Type Database Type Mechanical extract ventilation - centralised MV Reference Number 500077 Configuration 6 MVHR Duct Insulated Manufacturer SFP 0.38 Duct Type Semi rigid MVHR Efficiency Wet Rooms 6 Brand, Model20.0 Fans, Open Fireplaces, Flues

MHS SHS Other TotalNumber of Chimneys 0 0 0 0Number of open flues 0 0 2 2Number of intermittent fans 0Number of passive vents 0Number of flueless gas fires 021.0 Cooling System No22.0 Lighting Internal Total number of light fittings 50 Total number of L.E.L. fittings 50 Percentage of L.E.L. fittings 100.00 External

© Elmhurst Energy Systems Limited Registered Office Unit 16, St Johns Business Park, Lutterworth, Leicestershire LE17 4HB

SUMMARY FOR INPUT DATA FOR New Build (As Designed) Page 5 of 16

External lights fitted No Light and motion sensors23.0 Electricity Tariff Standard24.0 Heating Systems Main Heating 1 Database Description Water source HP Percentage of Heat 100 % Main Heating 2 None Description Percentage of Heat % Community Heating Secondary Heating Manufacturer Water Heating Main Heating 1 Flue Gas Heat Recovery System No Waste Water Heat Recovery Instantaneous System 1

No

Waste Water Heat Recovery Instantaneous System 2

No

Waste Water Heat Recovery Storage System

No

Solar Panel No25.0 Main Heating 1 Database Ref. No. 100111 Fuel Type Electricity Main Heating PET TestMethod SAP Code 224 Efficiency ( Split Efficiences ) % Efficiency ( Split Efficiences ) % In Winter 319.2 In Summer 191.4 Model Name Manufacturer Controls CHD Time and temperature zone control PCDF Controls 0 Delayed Start Stat Sap Code 2207 Burner Control Boiler Compensator HETAS approved System Oil Pump Inside FI Case FI Water Flue Type Smoke Control Area Fan Assisted Flue Is MHS Pumped Pump in heated space Heat Emitter Underfloor Underfloor Heating Yes - Pipes in thin screed Flow Temperature Yes - Pipes in thin screed Electric CPSU Temperature Combi boiler type Combi keep hot type Combi store type27.0 Community Heating Space Community Heating PCDF Index Distribution Loss Distribution Loss Value Controls SAP Code Water Community Heating PCDF Index Distribution Loss Distribution Loss Value Charging Linked To Heat Use28.0 Secondary Heating RWM Description Wood Logs RWM Closed room heater SHS efficiency % 70.00 SAP Code 633 HETAS Approved System Yes Smoke Control Area Unknown Test Method BS EN 1266 Manufacturer stovax Model Name stovax29.0 Water Heating HWP From main heating 1

© Elmhurst Energy Systems Limited Registered Office Unit 16, St Johns Business Park, Lutterworth, Leicestershire LE17 4HB

SUMMARY FOR INPUT DATA FOR New Build (As Designed) Page 6 of 16

Water use <= 125 litres/person/day Yes SAP Code 901 Immersion Heater Summer Immersion Suplementary Immersion Immersion Only Heating Hot Water29.1 Flue Gas Heat Recovery System Database ID Brand Model Details29.2 Waste Water Heat Recovery System Total rooms with shower and/or bath30.0 Hot Water Cylinder Hot Water Cylinder Cylinder Stat Yes Cylinder In Heated Space Yes Independent Time Control Yes Insulation Type Measured Loss Insulation Thickness Cylinder Volume 250.00 Loss (kwh/day) 1.57 Pipes insulation Fully insulated primary pipework In Airing Cupboard31.0 Solar Panel Solar Panel Area Area Type Panel Type n0, a1, a2, A/G ratio Orientation Elevation Overshading Solar Storage Volume Pump electrically powered Combined Cylinder32.0 Thermal Store None Thermal Store Pipework33.0 Photovoltaic Unit One Dwelling Apportioned KWh/YearPV Cells kW Peak Orientation Elevation Overshading

4.00 South 30° None Or Little

34.0 Wind Turbines Terrain Type Urban Wind Turbines Count Apportioned Kwh/year Rotor Diameter Hub Height35.0 Small-scale Hydro Electricity Generated Description Apportioned kWh/YearRecommendations None

Further measures to achieve even higher standards None

© Elmhurst Energy Systems Limited Registered Office Unit 16, St Johns Business Park, Lutterworth, Leicestershire LE17 4HB

Sandra [email protected]

Thermal Bridging Page 7 of 16

Property Reference: 002418 Issued on Date: 08.Dec.2015Survey Reference: 001 Prop Type Ref: Det bungalowProperty: Bungalow, Undercliff, Cleadon, SR6 7UXSAP Rating: 94 AEnvironmental:95 A

CO2 Emissions (t/year): 2.06General Requirements Compliance: Pass

DER: 5.95 PassDFEE:43.06 Pass

TER: 20.24TFEE:61.67

Percentage DER<TER: 70.60 %Percentage DFEE<TFEE: 30.17 %

CfSH Results Version: ENE1 Credits: N/A ENE2 Credits: N/A ENE7 Credits: N/A CfSH Level: N/ASurveyor: Sandra Hardwick, Tel: 01670 359491 Surveyor ID: B578-0001Address: Ridley Avenue, Blyth, Northumberland, NE24 3BAClient:Software Version: Elmhurst Energy Systems SAP2012 Calculator (Design System) version 3.02r10SAP version: SAP 2012, Regs Region: England (Part L1A 2013), Calculation Type: New Dwelling As Designed

Junction detail SourceType

Psi(W/mK)

Length(m) Result Reference

External wall E2 Other lintels (including other steel lintels) Table K1 - Approved 0.300 79.72 23.92

External wall E3 Sill Table K1 - Approved 0.040 79.72 3.19External wall E4 Jamb Table K1 - Approved 0.050 145.60 7.28External wall E5 Ground floor (normal) Table K1 - Approved 0.160 175.42 28.07External wall E14 Flat roof Independently

assessed 0.050 175.42 8.77External wall E16 Corner (normal) Table K1 - Approved 0.090 21.60 1.94External roof R1 Head of roof window Table K1 - Default 0.080 7.84 0.63External roof R2 Sill of roof window Table K1 - Default 0.060 7.84 0.47External roof R3 Jamb of roof window Table K1 - Default 0.080 22.40 1.79

Total W/mK: 76.06Y-Value W/m2K: 0.050

Sandra [email protected]

U-value calculator report Page 8 of 16

Property Reference: 002418 Issued on Date: 08.Dec.2015Survey Reference: 001 Prop Type Ref: Det bungalowProject: Bungalow, Undercliff, Cleadon, SR6 7UXSAP Rating: 94 AEnvironmental:95 A

CO2 Emissions (t/year): 2.06General Requirements Compliance: Pass

DER: 5.95 PassDFEE:43.06 Pass

TER: 20.24TFEE:61.67

Percentage DER<TER: 70.60 %Percentage DFEE<TFEE: 30.17 %

CfSH Results Version: ENE1 Credits: N/A ENE2 Credits: N/A ENE7 Credits: N/A CfSH Level: N/ASurveyor: Sandra Hardwick, Tel: 01670 359491 Surveyor ID: B578-0001Address: Ridley Avenue, Blyth, Northumberland, NE24 3BAClient:Software Version: Elmhurst Energy Systems SAP2012 Calculator (Design System) version 3.02r10SAP version: , Regs Region: England (Part L1A 2013), Calculation Type: New Dwelling As Designed

Building Elements:

Roof 000009 - Sedum roofRoof Type: Flat Roof inverted (with corrections)Layer Description Thickness Conductivity Resistance FractionExt surface 0.040Layer 1 single ply membrane

Main construction 10 mm 0.160 0.063 100.00 %Layer 2 Thermaroof TR21 zero ODP (*80mm or less)

Main construction 75 mm 0.027 2.778 100.00 % Corrections - Air Gap: Level 1, Fasteners: None or plastic

Layer 3 PlywoodMain construction 22 mm 0.130 0.169 100.00 %

Layer 4 Earthwool Loft Roll 40 Main construction 200 mm 0.040 5.000 96.02 %Bridging - Timber 200 mm 0.130 3.98 % Corrections - Air Gap: Level 1, Fasteners: None or plastic

Layer 5 Plaster, standardMain construction 15 mm 0.400 0.038 100.00 %

Int surface 0.100Total resistance: Upper limit = 7.955 m2 K/W Lower limit = 7.776 m2 K/W Average = 7.866 m2 K/W

U-value (unrounded) = 0.13 W/m2 KUnheated space: None

Total thickness: 322 mm U-value: 0.13 W/m2 K

© Elmhurst Energy Systems Limited Registered Office Unit 16, St Johns Business Park, Lutterworth, Leicestershire LE17 4HB

Sandra [email protected]

U-value calculator report Page 9 of 16

Property Reference: 002418 Issued on Date: 08.Dec.2015Survey Reference: 001 Prop Type Ref: Det bungalowProject: Bungalow, Undercliff, Cleadon, SR6 7UXSAP Rating: 94 AEnvironmental:95 A

CO2 Emissions (t/year): 2.06General Requirements Compliance: Pass

DER: 5.95 PassDFEE:43.06 Pass

TER: 20.24TFEE:61.67

Percentage DER<TER: 70.60 %Percentage DFEE<TFEE: 30.17 %

CfSH Results Version: ENE1 Credits: N/A ENE2 Credits: N/A ENE7 Credits: N/A CfSH Level: N/ASurveyor: Sandra Hardwick, Tel: 01670 359491 Surveyor ID: B578-0001Address: Ridley Avenue, Blyth, Northumberland, NE24 3BAClient:Software Version: Elmhurst Energy Systems SAP2012 Calculator (Design System) version 3.02r10SAP version: , Regs Region: England (Part L1A 2013), Calculation Type: New Dwelling As Designed

Building Elements:

Wall 000007 - cavity wallLayer Description Thickness Conductivity Resistance FractionExt surface 0.040Layer 1 Brick, outer leaf

Main construction 102 mm 0.770 0.132 82.81 %Bridging - Mortar 102 mm 0.941 17.19 %

Layer 2 Earthwool Dritherm 32 UltimateMain construction 100 mm 0.032 3.125 100.00 % Corrections - Air Gap: Level 1, Fasteners: None or plastic

Layer 3 Earthwool Dritherm 32 UltimateMain construction 100 mm 0.032 3.125 100.00 % Corrections - Air Gap: Level 1, Fasteners: None or plastic

Layer 4 Blockwork, denseMain construction 140 mm 1.590 0.088 100.00 %

Layer 5 Plaster, standardMain construction 15 mm 0.400 0.038 100.00 %

Int surface 0.130Total resistance: Upper limit = 6.674 m2 K/W Lower limit = 6.673 m2 K/W Average = 6.674 m2 K/W

U-value (unrounded) = 0.15 W/m2 KUnheated space: None

Total thickness: 457 mm U-value: 0.15 W/m2 K

Floor 000008 - Ground floorFloor Type: Slab On Ground FloorArea = 530.66 m2, Perimeter = 175.42 m, Wall thickness = 450.00 mm, Soil: ClayHorizontal edge insulation: Width D = 1000.0 mm, Thickness dn = 125.0 mm, Lambda = 0.022Vertical edge insulation: Width D = 150.0 mm, Thickness dn = 25.0 mm, Lambda = 0.022Layer Description Thickness Conductivity Resistance FractionExt surface 0.040Layer 1 Thermafloor

Main construction 150 mm 0.022 6.818 100.00 % Corrections - Air Gap: Level 1, Fasteners: None or plastic

Layer 2 Concrete, denseMain construction 150 mm 2.000 0.075 100.00 %

Layer 3 Screed + self levellingMain construction 50 mm 1.150 0.043 100.00 %

Int surface 0.170Total resistance: Upper limit = 6.937 m2 K/W Lower limit = 6.937 m2 K/W Average = 6.937 m2 K/W

U-value (unrounded) = 0.1 W/m2 KUnheated space: None

© Elmhurst Energy Systems Limited Registered Office Unit 16, St Johns Business Park, Lutterworth, Leicestershire LE17 4HB

Sandra [email protected]

U-value calculator report Page 10 of 16

Property Reference: 002418 Issued on Date: 08.Dec.2015Survey Reference: 001 Prop Type Ref: Det bungalowProject: Bungalow, Undercliff, Cleadon, SR6 7UXSAP Rating: 94 AEnvironmental:95 A

CO2 Emissions (t/year): 2.06General Requirements Compliance: Pass

DER: 5.95 PassDFEE:43.06 Pass

TER: 20.24TFEE:61.67

Percentage DER<TER: 70.60 %Percentage DFEE<TFEE: 30.17 %

CfSH Results Version: ENE1 Credits: N/A ENE2 Credits: N/A ENE7 Credits: N/A CfSH Level: N/ASurveyor: Sandra Hardwick, Tel: 01670 359491 Surveyor ID: B578-0001Address: Ridley Avenue, Blyth, Northumberland, NE24 3BAClient:Software Version: Elmhurst Energy Systems SAP2012 Calculator (Design System) version 3.02r10SAP version: , Regs Region: England (Part L1A 2013), Calculation Type: New Dwelling As Designed

Building Elements:Total thickness: 350 mm U-value: 0.10 W/m2 K

© Elmhurst Energy Systems Limited Registered Office Unit 16, St Johns Business Park, Lutterworth, Leicestershire LE17 4HB

Sandra [email protected]

Condensation Risk Analysis Report Page 11 of 16

Property Reference: 002418 Issued on Date: 08.Dec.2015Survey Reference: 001 Prop Type Ref: Det bungalowProject: Bungalow, Undercliff, Cleadon, SR6 7UXSAP Rating: 94 AEnvironmental:95 A

CO2 Emissions (t/year): 2.06General Requirements Compliance: Pass

DER: 5.95 PassDFEE:43.06 Pass

TER: 20.24TFEE:61.67

Percentage DER<TER: 70.60 %Percentage DFEE<TFEE: 30.17 %

CfSH Results Version: ENE1 Credits: N/A ENE2 Credits: N/A ENE7 Credits: N/A CfSH Level: N/ASurveyor: Sandra Hardwick, Tel: 01670 359491 Surveyor ID: B578-0001Address: Ridley Avenue, Blyth, Northumberland, NE24 3BAClient:Software Version: Elmhurst Energy Systems SAP2012 Calculator (Design System) version 3.02r10SAP version: , Regs Region: England (Part L1A 2013), Calculation Type: New Dwelling As Designed

Roof - 000009

Environmental conditions:

External conditions: Temperature: 5°C Relative Humidity: 95 %Internal conditions: Temperature: 15°C Relative Humidity: 65 %Table of layers:

Layer Thickness

mm

Thermalconduct.

W/m.K

Thermalresistance

m2.K/W

Cumulativethermal

resistancem2.K/W

Vapourresistivity

GN.s/kg.m

Vapourresistance

GN.s/kg.m

Cumulativevapourt

resistanceGN.s/kg.m

External surface - 0.000 0.040 0.040 0.0 0.00 0.001.single ply membrane 10.0 0.160 0.063 0.103 200000.0 2000.00 2000.002.Thermaroof TR21 zero ODP (*80mm orless) 75.0 0.027 2.778 2.880 15.0 1.13 2001.133.Plywood 22.0 0.130 0.169 3.050 450.0 9.90 2011.034.Earthwool Loft Roll 40 200.0 0.040 5.000 8.050 7.0 1.40 2012.435.Plaster, standard 15.0 0.400 0.038 8.087 60.0 0.90 2013.33Internal surface - 0.000 0.100 8.087 0.0 0.00 2013.33

Condensation Risk Analysis Report Page 12 of 16

Vapour pressure table:

Interface - between layers Interfacetemp.

° C

Vapourpressure

Pa

Satur.vapour

pressurePa

Dewpoint

° C

Cond.rate

g/m2 h

Cond.rate

60 daysg/m2 h

Cond.risk

Y/NExternal surface 5.00 828.3 871.9 4.27 0.00 0.00 No1. External surface / single ply membrane 5.05 828.3 874.8 4.3 0.00 0.00 No2. single ply membrane / Thermaroof TR21 zero ODP (*80mm or less) 5.13 879.5 879.5 5.1 0.06 88.71 Yes3. Thermaroof TR21 zero ODP (*80mm or less) / Plywood 8.52 1106.2 1110.6 8.5 0.00 0.00 No4. Plywood / Earthwool Loft Roll 40 8.72 1107.5 1126.3 8.5 0.00 0.00 No5. Earthwool Loft Roll 40 / Plaster, standard 14.83 1107.7 1686.1 8.5 0.00 0.00 NoPlaster, standard / Internal surface 14.88 1107.9 1691.1 8.5 0.00 0.00 NoInternal surface 15.00 1107.9 1691.1 8.48 0.00 0.00 No

Interface temperature / Dew point graphical representation:

Sandra [email protected]

Condensation Risk Analysis Report Page 13 of 16

Property Reference: 002418 Issued on Date: 08.Dec.2015Survey Reference: 001 Prop Type Ref: Det bungalowProject: Bungalow, Undercliff, Cleadon, SR6 7UXSAP Rating: 94 AEnvironmental:95 A

CO2 Emissions (t/year): 2.06General Requirements Compliance: Pass

DER: 5.95 PassDFEE:43.06 Pass

TER: 20.24TFEE:61.67

Percentage DER<TER: 70.60 %Percentage DFEE<TFEE: 30.17 %

CfSH Results Version: ENE1 Credits: N/A ENE2 Credits: N/A ENE7 Credits: N/A CfSH Level: N/ASurveyor: Sandra Hardwick, Tel: 01670 359491 Surveyor ID: B578-0001Address: Ridley Avenue, Blyth, Northumberland, NE24 3BAClient:Software Version: Elmhurst Energy Systems SAP2012 Calculator (Design System) version 3.02r10SAP version: , Regs Region: England (Part L1A 2013), Calculation Type: New Dwelling As Designed

Wall - 000007

Environmental conditions:

External conditions: Temperature: 5°C Relative Humidity: 95 %Internal conditions: Temperature: 15°C Relative Humidity: 65 %Table of layers:

Layer Thickness

mm

Thermalconduct.

W/m.K

Thermalresistance

m2.K/W

Cumulativethermal

resistancem2.K/W

Vapourresistivity

GN.s/kg.m

Vapourresistance

GN.s/kg.m

Cumulativevapourt

resistanceGN.s/kg.m

External surface - 0.000 0.040 0.040 0.0 0.00 0.001.Brick, outer leaf 102.0 0.770 0.132 0.172 50.0 5.10 5.102.Earthwool Dritherm 32 Ultimate 100.0 0.032 3.125 3.297 7.0 0.70 5.803.Earthwool Dritherm 32 Ultimate 100.0 0.032 3.125 6.422 7.0 0.70 6.504.Blockwork, dense 140.0 1.590 0.088 6.511 100.0 14.00 20.505.Plaster, standard 15.0 0.400 0.038 6.548 60.0 0.90 21.40Internal surface - 0.000 0.130 6.548 0.0 0.00 21.40

Condensation Risk Analysis Report Page 14 of 16

Vapour pressure table:

Interface - between layers Interfacetemp.

° C

Vapourpressure

Pa

Satur.vapour

pressurePa

Dewpoint

° C

Cond.rate

g/m2 h

Cond.rate

60 daysg/m2 h

Cond.risk

Y/NExternal surface 5.00 828.3 871.9 4.27 0.00 0.00 No1. External surface / Brick, outer leaf 5.06 828.3 875.5 4.3 0.00 0.00 No2. Brick, outer leaf / Earthwool Dritherm 32 Ultimate 5.26 887.7 887.7 5.3 0.01 9.60 Yes3. Earthwool Dritherm 32 Ultimate / Earthwool Dritherm 32 Ultimate 9.94 904.0 1222.2 5.5 0.00 0.00 No4. Earthwool Dritherm 32 Ultimate / Blockwork, dense 14.62 913.2 1662.9 5.7 0.00 0.00 No5. Blockwork, dense / Plaster, standard 14.75 1096.1 1677.1 8.3 0.00 0.00 NoPlaster, standard / Internal surface 14.81 1107.9 1683.2 8.5 0.00 0.00 NoInternal surface 15.00 1107.9 1683.2 8.48 0.00 0.00 No

Interface temperature / Dew point graphical representation:

Sandra [email protected]

Condensation Risk Analysis Report Page 15 of 16

Property Reference: 002418 Issued on Date: 08.Dec.2015Survey Reference: 001 Prop Type Ref: Det bungalowProject: Bungalow, Undercliff, Cleadon, SR6 7UXSAP Rating: 94 AEnvironmental:95 A

CO2 Emissions (t/year): 2.06General Requirements Compliance: Pass

DER: 5.95 PassDFEE:43.06 Pass

TER: 20.24TFEE:61.67

Percentage DER<TER: 70.60 %Percentage DFEE<TFEE: 30.17 %

CfSH Results Version: ENE1 Credits: N/A ENE2 Credits: N/A ENE7 Credits: N/A CfSH Level: N/ASurveyor: Sandra Hardwick, Tel: 01670 359491 Surveyor ID: B578-0001Address: Ridley Avenue, Blyth, Northumberland, NE24 3BAClient:Software Version: Elmhurst Energy Systems SAP2012 Calculator (Design System) version 3.02r10SAP version: , Regs Region: England (Part L1A 2013), Calculation Type: New Dwelling As Designed

Floor - 000008

Environmental conditions:

External conditions: Temperature: 5°C Relative Humidity: 95 %Internal conditions: Temperature: 15°C Relative Humidity: 65 %Table of layers:

Layer Thickness

mm

Thermalconduct.

W/m.K

Thermalresistance

m2.K/W

Cumulativethermal

resistancem2.K/W

Vapourresistivity

GN.s/kg.m

Vapourresistance

GN.s/kg.m

Cumulativevapourt

resistanceGN.s/kg.m

External surface - 0.000 0.040 0.040 0.0 0.00 0.001.Thermafloor 150.0 0.022 6.818 6.858 100.0 15.00 15.002.Concrete, dense 150.0 2.000 0.075 6.933 200.0 30.00 45.003.Screed + self levelling 50.0 1.150 0.043 6.977 0.0 0.00 45.00Internal surface - 0.000 0.170 6.977 0.0 0.00 45.00

Condensation Risk Analysis Report Page 16 of 16

Vapour pressure table:

Interface - between layers Interfacetemp.

° C

Vapourpressure

Pa

Satur.vapour

pressurePa

Dewpoint

° C

Cond.rate

g/m2 h

Cond.rate

60 daysg/m2 h

Cond.risk

Y/NExternal surface 5.00 828.3 871.9 4.27 0.00 0.00 No1. External surface / Thermafloor 5.06 828.3 875.3 4.3 0.00 0.00 No2. Thermafloor / Concrete, dense 14.60 921.5 1660.6 5.8 0.00 0.00 No3. Concrete, dense / Screed + self levelling 14.70 1107.9 1671.9 8.5 0.00 0.00 NoScreed + self levelling / Internal surface 14.76 1107.9 1678.5 8.5 0.00 0.00 NoInternal surface 15.00 1107.9 1678.5 8.48 0.00 0.00 No