RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD OPEN WEB TRUSS F4545.04 STC 62 IIC 56 CONSTRUCTION Armstrong 1.5mm Vinyl Sheet Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York PB Truss L/360 Open Web Truss @ 24" O.C. RSIC-1 Installed @ 24"x48" Clark Dietrich 087F125-18 Furring Channel @ 24" O.C. National Gypsum Gold Bond Fire-Shield C Gypsum Board STC 62 Test Number F4545.04 IIC 56 ©2016 PAC International, LLC. All Rights Reserved. • (866) 774-2100 • Fax (866) 649-2710 RSIC® is a registered Trade Mark of PAC International, LLC. STC IIC 1 Hour See www.UL.com World Leader in Noise Control Solutions

Upload: others

Post on 15-Feb-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

  • RSIC ACOUSTIC ASSEMBLY

    FLOOR CEILING ASSEMBLY

    DIRECT FIX TO WOOD OPEN WEB TRUSS

    F4545.04 STC 62 IIC 56

    CONSTRUCTIONArmstrong 1.5mm Vinyl SheetHacker Industries, Inc. Firm-Fill Gypsum ConcreteHacker Industries, Inc. Firm-Fill SCM-250 Sound Control MatOriented Strand Board SheathingGuardian Faces R-13 Fiberglass InsulationYork PB Truss L/360 Open Web Truss @ 24" O.C.RSIC-1 Installed @ 24"x48"Clark Dietrich 087F125-18 Furring Channel @ 24" O.C.National Gypsum Gold Bond Fire-Shield C Gypsum Board

    STC 62Test Number F4545.04 IIC 56

    ©2016 PAC International, LLC. All Rights Reserved. • (866) 774-2100 • Fax (866) 649-2710RSIC® is a registered Trade Mark of PAC International, LLC.

    ST

    C

    IIC

    1 HourSee www.UL.com

    World Leader in Noise Control

    Solutions

  • 56

    F4545.04-113-11-R1

    ACOUSTICAL PERFORMANCE TEST REPORT

    ASTM E 90 AND ASTM E 492

    Rendered to

    HACKER INDUSTRIES INC.

    Series/Model: FIRM-FILL® Brand Gypsum Concrete and FIRM-FILL® SCM-250

    Sound Control Mat - Armstrong® Vinyl Sheet

    Specimen Type: Open Web Truss - 457 mm

    Overall Size: 3023 mm by 3632 mm

    STC 62

    IIC

    Test Specimen Identification:

    Floor Topping: 1.5 mm Armstrong® Vinyl Sheet

    Subfloor Topping: 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete

    Subfloor Underlayment: 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat

    Subfloor: 18.8 mm Oriented Strand Board Sheathing

    Insulation: 88.9 mm Guardian Faced R-13 Fiberglass Insulation

    Truss: 457.2 mm York PB Truss L/360 Open Web Truss

    Ceiling Isolation: 28 mm PAC International RSIC-1 Classic Isolation Clips

    Ceiling Isolation: 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel

    Ceiling: 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board

    Reference should be made to Intertek-ATI Report F4545.04-113-11 for complete test specimen

    description. This page alone is not a complete report.

    130 Derry Courtaa

    York, PA 17406aa

    p. 717.764.7700

    f. 717.764.4129www.archtest.com · www.intertek.com/building

  • F4545.04-113-11-R1

    Page 1 of 5

    Acoustical Performance Test Report

    HACKER INDUSTRIES INC.

    1600 Newport Center Drive, Suite 275

    Newport Beach, California 92660

    Report F4545.04-113-11

    Test Date 02/02/16

    Report Date 04/29/16

    Revision Date 04/29/16

    Project Scope

    Architectural Testing, Inc., a subsidiary of Intertek (Intertek-ATI), was contracted to conduct

    airborne sound transmission loss and impact sound transmission tests. The complete test data is

    included as attachments to this report. The client provided the test specimen. The specimen was

    constructed on the date of testing.

    Test Methods

    The acoustical tests were conducted in accordance with the following standards. The equipment

    listed in the attachments meets the requirements of the following standards.

    ASTM E 90-09, Standard Test Method for Laboratory Measurement of Airborne Sound

    Transmission Loss of Building Partitions

    ASTM E 413-10, Classification for Rating Sound Insulation

    ASTM E 492-09, Standard Test Method for Laboratory Measurement of Impact Sound

    Transmission Through Floor-Ceiling Assemblies Using the Tapping Machine

    ASTM E 989-06 (2012), Classification for Determination of Impact Insulation Class (IIC)

    ASTM E 2235-04 (2012) Standard Test Method for Determination of Decay Rates for Use in

    Sound Insulation Test Methods

    Test Procedure

    All testing was conducted in the VT test chambers at Intertek-ATI located in York,

    Pennsylvania. The microphones were calibrated before conducting the tests.

    The airborne transmission loss test was conducted in accordance with the ASTM E 90 test

    method using the single direction method. Two background noise sound pressure level and five

    sound absorption measurements were conducted at each of five microphone positions. Four

    sound pressure level measurements were made simultaneously in both rooms, at each of five

    microphone positions.

    130 Derry Courtaa

    York, PA 17406aa

    p. 717.764.7700

    f. 717.764.4129www.archtest.com · www.intertek.com/building

  • F4545.04-113-11-R1

    Page 2 of 5

    Test Procedure (Continued)

    The impact sound transmission test was conducted in accordance with the ASTM E 492 test

    method. Two background noise sound pressure level, two sound pressure level measurements

    with the tapping machine operating at each position specified by ASTM E 492, and five sound

    absorption measurements were conducted at each of five microphone positions.

    The air temperature and relative humidity conditions were monitored and recorded during all

    measurements.

    Test Conditions

    Source Room Receive Room

    Average Temperature 17.9°C Average Temperature 16.7°C

    Average Relative Humidity 66% Average Relative Humidity 65%

    Test Calculations

    The STC (Sound Transmission Class) and IIC (Impact Insulation Class) ratings were calculated

    in accordance with ASTM E 413 and ASTM E 989, respectively.

    Test Specimen Materials and Installation Details

    MaterialDimensions

    (mm)

    Thickness

    (mm)Manufacturer and Series Quantity

    Average

    Weight

    Vinyl Sheet3632 by 3023 1.5 Armstrong® 10.98 m² 3.39 kg/m²

    Note: Loose laid

    Gypsum Concrete3632 by 3023 25.4

    Hacker Industries, Inc. FIRM-

    FILL® Brand10.98 m² 47.85 kg/m²

    Note: The gypsum concrete was allowed to cure for a minimum of 14 days. The gypsum layer had a

    closed cell foam perimeter isolation. The product name was specified by client.

    Sound Control Mat1219 by 3023 6.4

    Hacker Industries, Inc. FIRM-

    FILL® SCM-25010.98 m² 0.49 kg/m²

    Note: The SCM was installed as per manufacturer's specifications with seams overlapping and taped.

    Oriented Strand

    Board Sheathing

    1219 by 2438 18.8 N/A 10.98 m² 13.82 kg/m²

    Note: The OSB was adhered to the trusses with Loctite PL 400 Subfloor adhesive. It was attached

    with 9D nails on 203 mm centers along perimeter and 305 mm centers along trusses.

    Fiberglass Insulation2962 by 584 88.9 Guardian Faced R-13 10.98 m² 1.33 kg/m²

    Note: Installed in the cavity between trusses flush with the OSB. Hanger wire was used to keep

    insulation secure on 305mm

    Open Web Truss88.9 by 2933.7 457.2 York PB Truss L/360 7 m² 19.05 kg/m²

    Note: Installed on 610 centers using JUS414 hanger brackets.

  • F4545.04-113-11-R1

    Page 3 of 5

    Test Specimen Materials and Installation Details (Continued)

    MaterialDimensions

    (mm)

    Thickness

    (mm)Manufacturer and Series Quantity

    Average

    Weight

    Isolation Clips76.9 by 35.6 28.0 PAC International RSIC-1 Classic 24 clips 0.06 kg/clip

    Note: Fastened to joists in a 610 mm by 1220 mm traditional pattern.

    Furring/Hat Channel3657.6 by 76.2 22.3 ClarkDietrich 087F125-18 29.1 lin m 0.48 kg/m

    Note: Installed into the PAC International RSIC-1 Classic, spaced 610 mm on center.

    Gypsum Board1219 by 3023 15.9

    National Gypsum Gold Bond®

    Fire-Shield C™10.35 m² 10.74 kg/m²

    Note: Fastened to furring channels on 305 mm centers with 25.4 mm type S screws. Seams finished

    with joint compound. Perimeter sealed with acoustical caulk.

    Comments

    The total weight of the floor/ceiling assembly was 994.4 kg. Intertek-ATI will store samples of

    the test specimen for four years. A photograph of the test specimen is included in the

    attachments. A drawing of the test specimen is included in the attachments.

  • F4545.04-113-11-R1

    Page 4 of 5

    Intertek-ATI will service this report for the entire test record retention period. Test records,

    such as detailed drawings, datasheets, representative samples of test specimens, or other

    pertinent project documentation, will be retained by Intertek-ATI for the entire test record

    retention period. The test record retention period ends four years after the test date.

    This report does not constitute certification of this product nor an opinion or endorsement by

    this laboratory. It is the exclusive property of the client so named herein and relates only to the

    specimen tested. This report is intended to help in the client’s quality assurance program, but it

    does not represent a continuous or exhaustive evaluation of the specimen tested or of other

    products or materials that were not evaluated. The statements and data provided herein do not

    constitute approval, disapproval, certification, or acceptance of performance or materials.

    This report may not be reproduced, except in full, without the written approval of

    Intertek-ATI.

    FOR INTERTEK-ATI:

    David M. Dacheux Jordan Strybos

    Technician II - Acoustical Testing Project Manager - Acoustical Testing

    Attachments (7 Pages): This report is complete only when all attachments are included.

    * Stated by Client/Manufacturer

    N/A - Non Applicable

  • F4545.04-113-11-R1

    Page 5 of 5

    Revision Log

    Revision Date Page(s) Description

    R0 03/03/16 N/A Original Report Issue

    R1 04/29/16 Page 3 Clip spacing installation note corrected

    This report produced from controlled document template ATI 00629(d), Revised 02/09/15.

  • F4545.04-113-11-R1

    Attachments

    Instrumentation

    Instrument Manufacturer Model ATI NumberDate of

    Calibration

    Data Acquisition Unit National Instruments PXI-1033 63763 06/14 *

    Microphone Calibrator Norsonic 1251 Y002919 07/15

    Receive Room Microphone Scantek 378B20 63748 05/15

    Receive Room Microphone PCB Piezotronics 378B20 63744 05/15

    Receive Room Microphone PCB Piezotronics 378B20 63745 05/15

    Receive Room Microphone PCB Piezotronics 378B20 63746 05/15

    Receive Room Microphone PCB Piezotronics 378B20 63747 05/15

    Receive Room Environmental

    IndicatorComet T7510

    63810

    63811

    10/15

    10/15

    Source Room Microphone PCB Piezotronics 378B20 63738 04/15

    Source Room Microphone PCB Piezotronics 378B20 63739 04/15

    Source Room Microphone PCB Piezotronics 378B20 63740 04/15

    Source Room Microphone PCB Piezotronics 378B20 63742 04/15

    Source Room Microphone Scantek 378B20 63741 04/15

    Source Room Environmental

    IndicatorComet T7510 63812 11/15

    Tapping Machine Look Line s.r.l. EM50 (TM50) 65351 11/15

    * The calibration frequency for this equipment is every two years per the manufacturer's recommendation.

    Test Chambers

    VT Receive Room Volume 155.77 m³

    VT Source Room Volume 190 m³

    Page 1 of 7

  • STC Rating (Sound Transmission Class)

    Deficiencies (Sum of Deficiencies)

    F4545.04-113-11-R1

    AIRBORNE SOUND TRANSMISSION LOSS

    ASTM E 90

    Test Date 02/02/16

    Data File No. F4545.04

    Client Hacker Industries Inc.

    Description 1.5 mm Armstrong® Vinyl Sheet, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.4 mm Hacker Industries, Inc.FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass

    Insulation, 457.2 mm York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm

    ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board

    Specimen Area 10.98 m²

    Technician David M. Dacheux

    FreqBackground

    AbsorptionSource Receive Specimen

    TL

    95% Number

    SPL SPL SPL Confidence of

    (Hz) (dB) (m²) (dB) (dB) (dB) Limit Deficiencies

    50 46.7 26.4 100 65 32 3.80 -

    63 47.3 24.5 101 64 34 3.70 -

    80 52.9 17.2 108 69 39 4.50 -

    100 41.4 13.4 106 66 40 1.80 -

    125 40.1 9.8 106 65 42 1.00 4

    160 30.7 8.9 108 64 45 1.30 4

    200 25.8 10.7 105 58 48 1.10 4

    250 28.5 10.2 104 53 52 1.00 3

    315 26.2 10.2 106 54 53 0.70 5

    400 22.2 8.2 104 50 56 0.50 5

    500 26.2 7.7 104 48 59 0.40 3

    630 23.3 7.5 105 47 62 0.60 1

    800 23.2 7.2 104 45 62 0.20 2

    1000 23.4 7.2 104 43 64 0.50 1

    1250 22.8 7.3 104 40 67 0.30 0

    1600 20.3 7.4 104 39 69 0.30 0

    2000 12.2 8.3 104 39 67 0.40 0

    2500 8.4 9.2 102 36 68 0.30 0

    3150 7.5 10.0 103 32 72 0.50 0

    4000 7.5 11.4 104 31 73 0.50 0

    5000 6.6 13.5 104 28 75 0.50 -

    6300 6.8 17.1 98 19 78 0.70 -

    8000 7.4 22.3 97 15 81 0.80 -

    10000 7.4 28.1 92 8 81 0.60 -

    62

    32

    Notes: 1) Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.

    2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.

    3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied

    ATI 00614 Revised 02/09/15 Page 2 of 7

  • F4545.04-113-11-R1

    AIRBORNE SOUND TRANSMISSION LOSS

    ASTM E 90

    Test Date 02/02/16

    Data File No. F4545.04

    Client Hacker Industries Inc.

    Description 1.5 mm Armstrong® Vinyl Sheet, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.4 mm Hacker Industries, Inc.FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass

    Insulation, 457.2 mm York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm

    ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board

    Specimen Area 10.98 m²

    Technician David M. Dacheux

    ATI 00614 Revised 02/09/15 Page 3 of 7

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    63

    125

    250

    500

    100

    0

    200

    0

    400

    0

    800

    0

    Sou

    nd

    Tra

    nsm

    issi

    on

    Loss

    (d

    B)

    Frequency (Hz)

    Airborne Sound Transmission Loss

    Specimen TL

    Contour Curve

  • IIC Rating (Impact Insulation Class)

    Deficiencies (Sum of Deficiencies)

    F4545.04-113-11-R1

    IMPACT SOUND TRANSMISSION

    ASTM E 492

    Test Date 02/02/16

    Data File No. F4545.04

    Client Hacker Industries Inc.

    Description 1.5 mm Armstrong® Vinyl Sheet, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.4 mm Hacker Industries, Inc.FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass

    Insulation, 457.2 mm York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm

    ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board

    Specimen Area 10.98 m²

    Technician David M. Dacheux

    Freq Background SPL AbsorptionNormalized Impact

    SPL

    95% Number

    Confidence of

    (Hz) (dB) (m²) (dB) Limit Deficiencies

    50 47.1 26.4 69 1.7 -

    63 47.7 26.3 63 1.9 -

    80 53.2 17.0 61 2.8 -

    100 43.7 12.8 59 2.0 3

    125 39.6 9.9 58 1.7 2

    160 26.9 9.1 59 1.0 3

    200 23.8 10.6 59 0.7 3

    250 27.5 10.3 57 0.6 1

    315 25.2 10.2 59 1.0 3

    400 21.7 8.4 57 0.4 2

    500 24.4 7.8 58 0.1 4

    630 22.3 7.5 57 0.3 4

    800 22.9 7.3 56 0.2 4

    1000 23.3 7.1 53 0.1 2

    1250 24.3 7.2 49 0.4 1

    1600 21.5 7.3 42 0.1 0

    2000 13.5 8.4 37 0.3 0

    2500 8.9 9.1 28 0.2 0

    3150 8.4 9.9 17 0.4 0

    4000 8.3 11.4 9 0.2 -

    5000 6.9 13.4 6 0.2 -

    6300 7.1 17.0 7 0.3 -

    8000 7.7 22.6 8 0.4 -

    10000 7.7 27.8 9 0.4 -

    56

    32

    Note: Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.

    ATI 00615 Revised 02/09/15 Page 4 of 7

  • F4545.04-113-11-R1

    IMPACT SOUND TRANSMISSION

    ASTM E 492

    Test Date 02/02/16

    Data File No. F4545.04

    Client Hacker Industries Inc.

    Description 1.5 mm Armstrong® Vinyl Sheet, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.4 mm Hacker Industries, Inc.FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass

    Insulation, 457.2 mm York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm

    ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board

    Specimen Area 10.98 m²

    Technician David M. Dacheux

    ATI 00615 Revised 02/09/15 Page 5 of 7

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    1100

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    63

    125

    250

    500

    100

    0

    200

    0

    400

    0

    800

    0

    Imp

    act

    In

    sula

    tion

    Cla

    ss (

    IIC

    )

    So

    un

    d P

    ress

    ure

    Lev

    el (

    dB

    )

    Frequency (Hz)

    Impact Sound Transmission

    Normalized Impact SPL

    Contour Curve

  • Photograph

    F4545.04-113-11-R1

    Source Room View of Test Specimen Installation

    Page 6 of 7

  • F4545.04-113-11-R1

    Drawing

    1-Floor Topping

    2-Subfloor Topping

    3-Subfloor Underlayment

    4-Subfloor

    5-Insulation

    6-Truss

    7-Ceiling Isolation

    8-Ceiling

    Page 7 of 7

    2016-04-29T06:28:39-0400David Dacheux

    2016-05-02T09:50:50-0400Jordan Strybos

    2016-04-29T06:19:44-0400Sobell, Janine