Technical Guidelines
SeaRoxMarine & OffshoreInsulation
SEAROX 08/2012TECHNICAL GUIDELINES - MARINE & OFFSHORE INSULATION
NEWPRODUC
T NAME
2012
-
2IntroductionWithin marine and offshore we offer a wide range of tested and approved products and constructions specially developed for marine and offshore. We offer competitive solutions within e.g. fire, sound and thermal insulation and insulation of tech-nical installations. A dedicated team of specialists is daily working to optimize our range of products and constructions. The development and sale are taking place in close cooperation with the local Rock-wool companies and a world wide net of agents and dealers.
One of our main tasks is to assist and guide our customers with the right information and advice about our products, constructions and the practical insulation work.
This manual combines all relevant information on marine and offshore insulation and is designed to keep you updated on our knowledge within the field.
We hope that you will find the Technical Guidelines useful in your daily work and inspirational to your future work within marine and offshore insulation.
In the Technical Guidelines you will find:
General information about standards and test methods within marine and offshore.
Practical information and advice about insulation and installation procedures.
Detailed information about our range of products and constructions, construction details for e.g. bulkhead, deck and junctions.
Overall information about sound insulation and measurements of our products.
Construction details within thermal and technical insulation.
Overview of our product range and our certificates. The recommendations in this manual should be seen as guidelines only. It is of course important that the insulation work is done according to the IMO rules and regulations from national authorities and classification societies.
Further support and information The manual however forms only a part of our support and in-formation to the market. You are always more than welcome to contact your local Rockwool representative or our marine specialists who are ready to assist you with information and advice. Further information can also be found in our Marine & Offshore brochures e.g. Products & Solutions and Acoustic Manual.
To get the most updated information we recommend the use of our web-site, www.rockwool-rti.com
Insulation worldwide Rockwool Marine & Offshore (RMO) has for many years been one of the leading suppliers of insulation within the shipbuilding industry. As part of a new strategy within the Rockwool Group and a more glo-bal strategic approach, world wide sales of insula-tion for marine and offshore is now part of Rockwool Technical Insulation (RTI). RTI is one of the biggest suppliers of thermal and fire-resistant insulation products for technical insulation, and an indepen-dent entity within the Rockwool Group. More than ever, we want to market a uniform and transparent product range throughout the world from the Uni-ted Kingdom to China.
In the ship building industry, this is crucial. It makes it easier for you to ensure the right material in your own country and for your international projects across borders.
Our focus: SeaRox and ProRox Specifically, Rockwool Technical Insulation (RTI) will now focus on two key markets: marine and off- shore and the process industry. To that end, we have subsumed our product range into two specialist categories. SeaRox comprises the full marine and offshore range. Our ProRox range covers all our thermal, fire-resistant and acoustic insulation solutions for technical installations in the process industry.
-
33
ContentIntroduction 2
SeaRox - the new product name 4
Marine & Offshore Insulation - an overview 6
Insulation in General 8 Preparation 8Cutting 8Installation 9Securing product 10Pins 10Washers 10Vapour barrier 11Storage and stacking 11Calculation of materials 12Choosing the right product 13
Regulations for Fire Insulation 14
Symbol Guide 16
A-constructions 17 Steel bulkhead 17Steel deck 27Aluminium bulkhead 37Aluminium deck 41
H-constructions 45 Steel bulkhead 45Steel deck 51
Jet Fire & Blast Resistance 53 Bulkhead and deck jet fire 30 min. 54Blast resistance 55
Construction Details 57 Stiffeners 58Bulkhead and deck connections 59Installation of surface steel plate 60Corrugated structural steel 61
Additional Fire Protection 63
Draught stoppers 64Penetrations 65B15 extension 66Sprinkler pipes 67
Floating Floor 69
SeaRox SL 480 70SeaRox SL 436 71
Technical Insulation 73
Technical insulation in general 74Insulation with Pipe Section 75Insulation with SeaRox Lamella Mat 76Insulation with SeaRox Wired Mat 77 Insulation with SeaRox Slabs/Batts 78Cladding 78
Sound 79
Rules and regulations 80Sound absorption 81Sound reduction 82Dynamic Stiffness 84SeaRox Acoustic Foil 85
Thermal Insulation of Bulkhead and Deck 87
Solutions for thermal insulation 88Lambda values 89Thermal calculations 90
Certificates 91
Product Guide 95
Product selector 96Products 97Surfaces 103
Aquaduct 105
Health & Safety 106
About Rockwool Technical Insulation (RTI) 107
-
"SeaRox" the new product nameThe SeaRox products have been given new names. This makes it even easier to find the exact product you need quickly, wherever you are working. Each product name is structured in the same clear way:
e.g.: SeaRox WM 960 ALU SC
Product range 2 last digits = refer to other product properties as stated by Rockwool Technical Insulation
Product identifier: WM = Wired MatsSL = SlabPS = Pipe SectionsLM = Lamella Mats MA = Mats
Application code:3 = acoustics; products mainly for sound absorption4 = outfitting; products mainly as components of systems6 = fire; products mainly for fire rated constructions7 = comfort; products mainly for thermal insulation of
accommodations9 = thermal; products mainly for thermal insulation of
technical installations
Product facings
ALU = reinforced aluminiumGW = glass cloth whiteTB = glass tissue black GS = glass scrim
As last part of the name you might find an abbreviation indicating local product specifications
4
-
NEW NAME OLD NAME
Comfort InsulationSeaRox MA 700 GSd Shiprock PlusSeaRox MA 700 ALUd Shiprock Alu SeaRox SL 720 Marine Batts 32SeaRox MA 720 ALU Marine Batts 32 RLSeaRox SL 740 Marine Batts 45SeaRox MA 740 ALU Marine Batts 45 RL
Acoustic Insulation
SeaRox SL 320 Marine Slab 60SeaRox SL 340 Marine Slab 80SeaRox Acoustic Foil Marine Acoustic Foil
Outfitting Insulation
SeaRox SL 436 Marine Slab 140SeaRox SL 440 Marine Slab 150SeaRox SL 470 Marine Slab 180SeaRox SL 480 Marine Slab 200
NEW NAME OLD NAME
Firesafe InsulationSeaRox WM 620 Marine Wired Mat 90 SeaRox WM 640 Marine Wired Mat 105SeaRox SL 620 Marine Firebatts 100SeaRox SL 640 Marine Firebatts 130SeaRox SL 660 HC Firebatts 150 SeaRox WM 660 HC Wired Mat 150 SeaRox PS 620 ALUSC Marine Firebatts 100 PS
Thermal Insulation
SeaRox SL 970 Marine Firebatts 110SeaRox LM 900 ALU Marine Lamella Mat 32
SeaRox WM 950 Marine Wired Mat 80ProRox PS 960 ALU Rockwool 800*
ProRox PS 960 Pipe Sections 850*
Alternative facings may be available
* Part of Rockwool Technical Insulation assortment for process industry, ProRox
5
-
12
3
4
6
7
7
10
6
1 Bridge At the bridge it is important to secure a high level of fire protection and sound insulation.
See page 17-44 for A-constructions See page 69-72 for floating floor See page 79-83 for sound insulation
2 CorridorsCorridors are part of the emergency escape routes on a vessel. The numbers of horizontal fire zones passed by the corridor determine the fire insulation class.
See page 17-44 for A-constructions See page 69-72 for floating floor See page 79-83 for sound insulation
3 Storage and tank rooms In the boiler room, storage rooms and tank rooms it is often important to insu-late surfaces, boilers and pipes.
See page 65 for penetrations See page 73-78 for technical insulation
4 Engine roomThe engine room contains a lot of fire risks so fire protection is essential. The engine room is also source of high and often disturbing noise. It is often filled with pipes, tanks, containers and other equipment where technical insulation is required. It is important to have the insulation protected so oil vapour does not get into the insulation material.
See page 17-44 for A-constructions See page 73-78 for technical insulation See page 79-83 for sound insulation See page 103 for surfaces
5 Control room In the control room fire is to be held out as long as possible as this is the last place where all the technical equipment can be controlled. The sound level needs to be low, as engine crew has to spend a lot of time here. It is moreover important that no vapour gets to the machines and computers and that the room has a rea-sonable sound level.
See page 17-44 for A-constructions See page 79-85 for sound insulation See page 103 for surfaces
6 Disco The discothque, cinema and bar areas onboard cruise ships are big sources of noise. It is important to have the right sound insulation around these areas towards the neighbouring areas.
See page 17-44 for A-constructions See page 69-72 for floating floor See page 79-83 for sound insulation
7 Cabins On board a passenger ship it is essential to have the right insulation between the cabins. It is crucial to have the needed fire protection and it is getting more and more important to have a high level of sound and thermal insulation.
See page 17-44 for A-constructions See page 69-72 for floating floor See page 79-83 for sound insulation
8 StairwaysThe stairways are part of the emergency escape routes on a vessel. The numbers of vertical fire zones passed by the stair-way determine the fire insulation class.
See page 17-44 for A-constructions
9 Galley In the galley you always have a risk of fire, as you have a mixture of heat and flammable materials. In this case it is also necessary to be aware of the facingsas you have oil vapour in the air.
See page 17-44 for A-constructions See page 73-78 for technical insulation See page 103 for surfaces
10 Public areaThe public area is requiring all kinds of insulation, depending on the situation.
See page 17-44 for A-constructions See page 64 for draught stoppers See page 79-85 for sound insulation See page 87-90 for thermal insulation See page 103 for surfaces
11 OffshoreOn offshore applications you have more or less the same conditions as on a ship. Furthermore you have the risk of hydro-carbon fire and need to protect people and material from an HC fire.
See page 45-52 for H-constructions See page 53-56 for Jet Fire and
Blast Resistance
-
7Marine & Offshore Insulation - an overview
5
8
9
1011
-
8Insulation in General
Fig. 1. Welding of pins to the plate (bulkhead/deck). As first step the pins must be welded to the plate and stiffener. Distance between pins should not exceed 300 mm. For fire rated con-structions the position of pins must follow the official drawings.
Fig.3A. Using an electrical saw to cut large amounts of Rockwool SeaRox products. When cutting large quantities of SeaRox insulation it is recommended to use an electrical saw. This will ensure a good and angular surface that is easy to tighten against the next Slabs. 2-5 mm oversize is recommended. The pieces of insulation should be min.150x150 mm.
Fig. 3C. Using a shear to cut Wired Mats Wired Mats should be cut with a large shear. 2-5 mm oversize is recommended. The pieces of insulation should be min. 150x150 mm.
Fig. 2. Painting of the plate. To avoid corrosion the plate can afterwards be painted with anti corrosion paint.
Fig. 3B. Using a Rockwool knife to cut Rockwool SeaRox Insulation Rockwool SeaRox insulation can easily be cut with a Rockwool knife or a similar sharp knife. When the Slabs are cut in 2-5 mm oversize (depending on density) the optimal tension and tightness can be obtained when fitting the wool. The pieces of insulation should be min. 150x150 mm
PREPARATION
CUTTING
The installation of insulation material can be done in different ways. It is up to the insulation contractor to choose the best way for each application. For fire rated constructions the installation has to follow the official drawings according to the fire test. Drawings can be found on our website, www.rockwool-rti.com. In the following you will find a general description of the way the insulation work can be done:
-
9Fig. 6 Fixing the insulation Fix washers on the pins in order to secure fixing of the insulation.
Alternative 1, fig. 4A. Insulation of stiffeners Depending on the construction it is recommended to start with the insulation of the stiffeners. First by filling out the space, behind the stiffener, with SeaRox insulation. The insulation should fit exactly to the profile structure. Afterwards insulate around the stiffener with the required thickness of SeaRox insulation.
Alternative 2, fig. 4A. Insulation between stiffeners Depending on the construction it can be easier to start with insulation of the plate. Joints must be tight and no air gaps must be found. In connection with solutions with more than one layer of insulation, the joints should be staggered by min. 150 mm to ensure that no joints go straight through both layers.
Alternative 1, fig. 5A. Insulation between stiffeners.Insulate the plate between stiffeners with SeaRox insulation. Joints must be tight and no air gaps must be found. In connection with solu-tions with more than one layer of insulation, the joints should be stag-gered by 150 mm to ensure that no joints go straight through both layers.
Alternative 2, fig. 5A. Insulation of stiffeners Insulate with SeaRox insulation around the stiffener. Fill out the space behind the stiffener with SeaRox insulation, the insulation should fit exactly to the profile structure.
INSTALLATION
-
10
Approx 10 mm
Steel pins (coated with copper)Steel constructions
Stainless steel pinsAluminium constructions
3 mm in diameter
Aluminium tip
3 mm in diameter
Black plastic capon black surface
White plastic capon white surface
Approx 40 mm
Securing the productWhen installing the insulation all pieces must be fit firmly with minimum one pin approx 10 mm longer than the nominal thick-ness of the insulation. On A-constructions the material has to be fastened with spring washers.
Different pinsSteel pins are used for steel decks and bulkheads. The steel pins are coated with copper for corrosion protection. Stainless steel pins with aluminium tip are used for aluminium constructions. The pins are normally 3 mm in diameter and can be aquired in different lengths.
WashersThe spring washers used to slide over the pins for securing the insula-tion should be 38 mm in diameter and of corrosion protected material.
Securing H-constructionsOn H-constructions it is some times required that the pins are approx 40 mm longer than the nominal thickness of the insulation and are bent in different directions to ensure that the wool is secured. The additional application of wire mesh is not needed when using new SeaRox H-constructions because the wire mesh is already part of our Wired Mat. On H-constructions the material has to be fastened with spring washers.
Covering the steel washersThe washer can be fit with a plastic cap to cover the steel tip and to create a nice looking surface.
SECURING THE PRODUCT
PINS
Steel spring washersSteel constructions
Stainless steel spring washersAluminium constructions
WASHERS
-
11
VAPOUR BARRIER
STORAGE AND STACKING
Max height
3 m
R
R
R
R
Using tape to ensure an airtight surface between two battsAll joints must be sealed with a tape width of 75-100 mm to ensure an air tight surface. Make sure that there is no grease on the surface before the tape is applied. Pins and washers should be taped.
Stacking of Rockwool SeaRox productsThe products must not be stacked in heights of more than three metres.
Do not sit on the Rockwool SeaRox materialThe products must at all times during storage remain untouched and must not be affected by any kind og treading, sitting or any other similar kind of exposure.
Storage of Rockwool SeaRox insulationThe products must at all times be stored dry indoor in closed ware-house facilities.
In rooms where vapour will enter the insulation as a reason of tem-perature/ pressure differences, a vapour barrier is often a demand. When water vapour is moving from the hot room towards colder surfaces, it will often lead to problems with corrosion. If it is oil vapour this will be collected in the wool and endanger the fire properties of the wool.
To close the surface on the Rockwool SeaRox products there are several options e.g. reinforced alu foil:
All joints must be sealed with a tape width of 75-100 mm to ensure an air tight surface.
Make sure that there is no grease, oil or dirt on the surface before the tape is applied. This will cause the tape to come loose. Make sure all holes in the surface are closed. The surface must have a low flame spread approval if it is used for marine applications.
In order to secure the right conditions for storage of Rockwool marine and offshore products a special set has of conditions been prepared, e.g. the products:
Must at all times be stored dry indoor in closed warehouse facilities. Must not be stacked in more than two layers when delivered on pallets. Must only be stored on the flat side when delivered in packages and must not be stacked in heights of more than three metres. Must at all times during storage remain untouched and must not be affected by any kind of treading, sitting or any other similar kind of exposure. Must be transported in closed compartments, e.g. trailers, contain-ers and other cargo holds in order to avoid exposure to weather elements and/or condensation etc.
-
Calculation of Materials
Below you will find a rough guidance for estimated need of material. Check your drawings for more detailed calculations.
INSULATION
IN GENERAL THE CUSTOMER IS ALWAYS RESPONSIBLE FOR CALCULATIONS
PINS AND WASHERS
TAPE WASTE
Based on a total amount of insulation for plate + stiffeners:
The plate equals 60%. The stiffeners equals 40%
Alternatively the use of pins and washers can be calculated by the total area of plate and stiffener in m2 times min. 18.
Example:A total quantity of 100 m2 plate needs to be in-sulated; also taking the insulation of stiffeners into consideration. Estimated need of pins and washers: 100 m2 x 18 pins/m2 = 1800 pins
As guidance the following amount of waste has to be included:
Insulation area < 100 m2 10% waste
Insulation area > 100 m2 5% waste
Based on a plate of X m2: The amount of Slabs for stiffeners can as guidance be calculated as X times 0.7
Example: of plate needs to be insulated.
Calculation of material for stiffener: 100 m x 0.7 = 70 m2
As guidance the use of pins and washers can be calculated as follows: Plate in m2 times min. 12. Stiffener in m2 times min. 10.
Example: insulation of plate requires x 12 pins/m2 = 1200 pins
100 m insulation of stiffeners requires 100 m2 x 10 pins/m2 = 1000 pins
As guidance the amount of tape for joints can be calculated by the insulated in m2 times 4 stated in running metres
Example:Tape for 100 m2 of insulation; 100 m2 x 4 m/m2 = 400 metres
12
1
1
1 1
2
2
-
Choosing the Right Product
To find the correct product it is necessary to know which application it has to be used for e.g.:
Fire insulation
Sound insulation
Thermal insulation
Insulation of technical installations
Floating floor insulation
Panels
Insulation of sub-sea pipelines
Combinations e.g. fire and sound insulation
When the application is known, the requirements for product characteristics need to be evaluated e.g.:
Fire properties
Sound properties
Thickness
Thermal conductivity
Mechanical strength
In some applications the weight could be of importance. In such cases the lighter products can be chosen, but it is not always the lightest solution that gives the best result. The light products do not protect against noise in the same frequency band as the more heavy products, so here it is necessary to know what result is requested in the end.
All Rockwool SeaRox products have good fire properties, but when using the products on ships or offshore rigs it is necessary to choose the right product fulfilling the needed fire rating.
Furthermore it can be relevant to evaluate the different so-lutions with regard to the working and installation method. Depending on the experience, the labour cost and the prioriti-sation it might be relevant to include parameters as e.g.:
Easy handling
Less cutting
Fast installation
Labour intensity
0575/year
Rockwool Technical Insulation has a large number of certifica-tes for the different products and applications from classifica-tion companies based on fire tests made at IMO approved fire institutes.
When choosing a product it is necessary to choose a product that is approved by the classification company that has to ap-prove the application/newbuilding in the end.
Some customers prefer to work with constructions based on Slabs, securing easy handling of small size and fixed products, others prefer to work with constructions based on Wired Mats. For some customers it is important to have the best and most safe solutions typically based on a two layer solution where other customers tend to focus on easy and fast installation.
Finally, it is important to focus on the right documentation such as:
Type approvals
Type certificates
When using Rockwool SeaRox insulation onboard a vessel carrying an EEA flag make sure that the product has the MED approval symbol (wheelmark).
It is important to make sure that the products and construc-tions have the right approval needed in the specific project, e.g. construction approval, non- combustible approval and low flame spread approval. Remember to check if the certificate is valid at the time where the insulation plan is approved by the classification societies.
13
-
Regulations for Fire Insulation According to SOLAS
The requirements for materials and constructions to meet specified standards of safety are normally prescribed by in-ternational or national laws related to shipping and offshore installations.
In addition to these regulations classification societies such as Det Norske Veritas (DNV) and Lloyds Register of Shipping
(LRS) may have additional requirements.
Approvals and Certification Suppliers of materials and constructions to the marine and offshore industry must prove that their prod-ucts, as a minimum, meet the statutory requirements.
The MED directive (EC Council Directive 96/98/EC - Marine Equipment Directive) has replaced the previous approv-als from the maritime authorities within EEA countries. All products supplied to marine carrying EEA flag must be subject to the MED directive.
MED-certificates are issued by notified bodies accredited by an EEA country. Approved products bear the mark of conformity.
Classification societies issue type approval certificates stat-ing the permission to use specific materials and construc-tions together with any relative restrictions.
If there are special circumstances or requirements for spe-cial details, it may be required to obtain statements from other authorities.
Approval Requirements To satisfy the national authorities and classification socie-ties, materials and constructions must be proven to comply with the national and international requirements. Tests have to be done at internationally recognised test labora-tories.
The tests have to be performed so that the materials or products are exposed to a fire generated under controlled conditions that simulate as closely as possible a worst case scenario.
Test Requirements There are several national and international requirements regarding the use of materials on ships and offshore instal-lations. These classifications are required to prove combus-tibility characteristics and include ignition properties, heat release and development of toxic gases and smoke.
To prove that materials meet the required fire technical classification, tests are carried out at recognised test institutions according to standardised test methods.
Material Test Methods Testing of materials fire resistance is done according to the latest FTP code for non-combustibility and where a facing is applied for low flame spread.
It is important to note that materials which meet the require-ments for non-combustibility do not have to be tested for other fire technical properties.
All Rockwool A- and H-constructions are tested according to FTP-code. FTP-code is describing also the thickness of the test specimen. The decision about the thickness of the structural part is in responsibility of the ship designer and will finally be approved by the responsible class society.
Construction Test MethodsTesting of a constructions fire resistance (decks, bulkheads, structural steel, penetrations etc.) is normally carried out in a standardised test furnace, where the construction specimen is exposed to a fire according to a standardised time/tempera-ture curve.
SOLAS, Chapter II-2, Regulation 5.3.1:Use of non-combustible materialsInsulating materials shall be non-combustible, except in cargo spaces, mail rooms, baggage rooms and refrigerated compartments of service spaces. Vapour barriers and adhesives used in conjunction with insulation, as well as the insulation of pipe fittings for cold service systems, need not be of non-combustible materials, but they shall be kept to the minimum quantity practicable and their exposed surfaces shall have low flame-spread characteristics.
14
-
Class B Fire Divisions Class B fire divisions must be of non-combustible materials and must prevent the propagation of flames for at least 30 minutes during a standard fire test.
The divisions must be insulated so that the average tem-perature on the unexposed side of the division does not exceed 140C above the initial temperature.
Furthermore, the temperature at any single point on the unexposed side must not exceed 225C above the initial temperature within the time limits.
Class A Fire Divisions Class A fire divisions must be of non-combustible materials and insulation materials must be fire tested at a recognised institution. They must be sufficiently braced and must pre-vent the propagation of flames and smoke for a minimum of one hour during a standard fire test.
The divisions must be insulated so that the average temper-ature on the unexposed side of the division does not exceed 140C above the initial temperature.
Furthermore, the temperature at any single point on the unexposed side must not exceed 180C above the initial temperature within the time limits.
Class H Fire Divisions Class H fire divisions must be of non-combustible materials and insulation materials must be fire tested at a recognized institution. They must be sufficiently braced and must pre-vent the propagation of flames and smoke for a minimum of two hours during a standard fire test for a hydrocarbon fire.
The divisions must be insulated so that the average tem-perature on the unexposed side of the division does not exceed 140C above the initial temperature.
Furthermore, the temperature at any single point on the unexposed side must not exceed 180C above the initial temperature within the time limits.
Notified BodyRockwool Technical Insulation is certified according to the MED directive. As notified body we have chosen Det Norske Veritas which also guaranties our quality by running audits.
Fire Classifications of Divisions
Class B-3030 minutes
Class B-1515 minutes
Class B-00 minutes
Class A-6060 minutes
Class A-3030 minutes
Class A-1515 minutes
Class A-00 minutes
Class H-120120 minutes
Class H-6060 minutes
Class H-00 minutes
2x
15
-
16
One layer solutionThe construction is based on a solution where the construction is made with one product in one layer. This leads to faster installation.
Low construction weightThe construction is based on products with a low density and/or low thickness which lead to low total construction weight.
Fast installationThe construction is based on Mats which reduce the cutting especially around stiffeners, and consequently faster installation time.
Safe solutionThe construction is based on a multiple, typical two layer solution which results in more safe solutions especially due to staggered joints.
Optimal sound propertiesThe construction is based on products with higher density and/or more thickness which result in better sound properties.
Easy handlingThe construction is based on Slabs, where the small size and fixed structure of the products give an easy handling in respect to cutting and installation.
Rockwool Technical Insulation has made symbols for all fire rated applications explaining the advantages with each application:
Symbol Guide
SYMBOL GUIDE
-
Index of A-constructions
Steel Bulkhead
Steel - Bulkhead
A-30 SeaRox SL 740 page 18
A-30 SeaRox WM 620 page 19
A-60 SeaRox SL 620 page 20
A-60 SeaRox SL 640 page 21
A-60 SeaRox WM 620 page 22
A-60 SeaRox WM 640 page 23
A-60 restricted, SeaRox SL 620 page 24
A-60 restricted, SeaRox SL 640 page 25
Steel - Bulkhead
17
-
18
A-30 Steel Bulkhead
Construction: Plate between stiffeners insulated with one layer of 50 mm
SeaRox SL 740 Stiffeners insulated with min. 25 mm SeaRox SL 740 Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300 mm distance. Insulation secured with washers of 38 mm.
Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be filled out completely. The pins should exceed the insulation by approx 10 mm. Insulation can be placed on either side of the steel plate.
Advantages:
One layer solution
Low construction weight
Easy handling
Surfaces: Reinforced aluminium foil Glass cloth
Sound: Weigthed sound absorption SeaRox SL 740, 50 mm w = 0.75
Weigthed sound reduction of the A-30 application Rw = 45 dB
4.5 mm steel50 mm SeaRox SL 740
25 mm SeaRox SL 740
3 mm steel pin w. washer
4.5 mm steel50 mm SeaRox SL 740
25 mm SeaRox SL 7403 mm steel pin w. washer
2480
3 mm steel pin w. washer
1000
480
300 mm
300 mm
600 600 600
1000
Product: SeaRox SL 740Density: 45 kg/m3
Thickness: Plate 50 mm insulation Stiffener 25 mm insulation
MED B-7484
TEST: G10148
PINNING
-
300 mm
3 mm steel pin w. washer
19
A-30 Steel Bulkhead
Construction: Plate between stiffeners insulated with one layer of 50 mm
SeaRox WM 620 Stiffeners insulated with min. 30 mm SeaRox WM 620 (min.
340 mm width)Standard steel plate 4.5 mm ( 0.5 mm) thick.3 mm pins fixed with approx 300 mm distance.
Insulation secured with washers of 38 mm.
Application notes:All the connections must be tight, no air gaps.The pins should exceed the insulation by approx 10 mm.Wire mesh must be twisted together at joints.
Insulation can be placed on either side of the steel plate.
Advantages:
Fast installation
Optimal sound properties
Surfaces:Reinforced aluminium foilGlass cloth
Sound: Weigthed sound absorption SeaRox WM 620,
50 mm w = 0.90
Product: SeaRox WM620Density: 90 kg/m3
Thickness: Plate 50 mm insulation Stiffener 30 mm insulation
MED B-7484
PINNING4.5 mm steel50 mm SeaRox WM 620
3 mm steel pin w. washerminimum 340 mm
30 mm SeaRox WM 620
4.5 mm steel50 mm SeaRox WM 620
30 mm SeaRox WM 6203 mm steel pin w. washer
TEST: GV95.33.1
-
20
A-60 Steel Bulkhead
Construction: Stiffeners insulated with min. 25 mm SeaRox SL 620
Plate between stiffeners insulated with one layer of 60 mm SeaRox SL 620Standard steel plate 4.5 mm ( 0.5 mm) thick.3 mm pins fixed with approx 300/400 mm distance.Insulation secured with washers of 38 mm.
Application notes: All the connections must be tight, no air gaps.Gap under the stiffener must be filled out completely.The pins should exceed the insulation by approx 10 mm.The long side of the insulation to be installed vertically.Insulation can be placed on either side of the steel plate.
Advantages:
One layer solution
Low construction weight
Easy handling
Surfaces:Reinforced aluminium foilGlass cloth
Sound: Weigthed sound absorption SeaRox SL 620, 60 mm w = 0.90
Weigthed sound reduction of the A-60 application Rw = 45 dB
4.5 mm steel60 mm SeaRox SL 620
25 mm SeaRox SL 6203 mm steel pin w. washer
4.5 mm steel60 mm SeaRox SL 620
25 mm SeaRox SL 6203 mm steel pin w. washer
3 mm steel pin w. washer
300 mm
400 mm
Product: SeaRox SL 620Density: 100-115 kg/m3
Thickness: Plate 60 mm insulation Stiffener 25 mm insulation
MED B-7487
TEST: 2004cs01428/3
PINNING
-
2480
3 mm steel pin w. washer
1000
480
300 mm
300 mm
600 600 600
1000
21
A-60 Steel Bulkhead
Construction: Plate between stiffeners insulated with two layers of 30 mm SeaRox SL 640. Stiffeners insulated with min. 30 mm SeaRox SL 640.Standard steel plate 4.5 mm ( 0.5 mm) thick.
3 mm pins fixed with approx 300 mm distance.Insulation secured with washers of 38 mm.
Application notes: All the connections must be tight, no air gaps.Gap under the stiffener must be filled out completely.
Joints to be staggered, 150 mm overlap is recommended.The pins should exceed the insulation by approx 10 mm.Insulation can be placed on either side of the steel plate
Advantages:
Safe solution
Optimal sound properties
Easy handling
Surfaces:Reinforced aluminium foilGlass cloth
Sound: Weigthed sound absorption SeaRox SL 640,
2x30 mm w = 0.90 Weigthed sound reduction of the A-60 application
Rw = 48 dB
Product: SeaRox SL 640Density: 130 kg/m3
Thickness: Plate 2x30 mm insulation Stiffener 30 mm insulation
MED B-7487
PINNING4.5 mm steel2x30 mm SeaRox SL 640
30 mm SeaRox SL 6403 mm steel pin w. washer
4.5 mm steel2x30 mm SeaRox SL 640
30 mm SeaRox SL 6403 mm steel pin w. washer
TEST: G10096
-
22
A-60 Steel Bulkhead
Construction: Plate between stiffeners insulated with one layer
of 45 mm SeaRox WM 620. Stiffeners and plate insulated in the same process with min.
45 mm SeaRox WM 620.Standard steel plate 4.5 mm ( 0.5 mm) thick.3 mm pins fixed with approx 300 mm distance.Insulation secured with washers of 38 mm.
Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be filled out completely. Joints to be staggered, 150 mm overlap is recommended. The pins should exceed the insulation by approx 10 mm. Wire mesh must be twisted together at joints. Insulation can be placed on either side of the steel plate.
Advantages:
Fast installation
Safe solution
Optimal sound properties
Surfaces: Reinforced aluminium foilGlass cloth
Sound:Weigthed sound absorption SeaRox WM 620, 2x45 mm w = 0.95Weigthed sound reduction of the A-60 application Rw = 58 dB (with 1 mm steel sheet in front of the insulation)
4.5 mm steel45 mm SeaRox WM 620
45 mm SeaRox WM 620
4.5 mm steel45 mm SeaRox WM 620
45 mm SeaRox WM 6203 mm steel pin w. washer
2480
1000
480
300 mm
600 600 600
1000
3 mm steel pin w. washer
Product: SeaRox WM 620Density: 90 kg/m3
Thickness: Plate 2x45 mm insulation Stiffener 45 mm insulation
MED B-7487
TEST: 2006cs13889-1
PINNING
-
2480
1000
480
300 mm
300 mm
600 600 600
1000
3 mm steel pin w. washer
23
A-60 Steel Bulkhead
Construction:Stiffeners insulated with min. 30 mm SeaRox WM 640.Plate between stiffeners insulated with one layer
of 75 mm SeaRox WM 640.Standard steel plate 4.5 mm ( 0.5 mm) thick.3 mm pins fixed with approx 300 mm distance.Insulation secured with washers of 38 mm.
Application notes:All the connections must be tight, no air gaps.Gap under the stiffener must be filled out
completely.The pins should exceed the insulation by
approx 10 mm. Wire mesh must be twisted together at joints.Insulation can be placed on either side of the steel plate.
Advantages:
One layer solution
Fast installation
Optimal sound properties
Surfaces:Reinforced aluminium foilGlass cloth
Sound:Weigthed sound absorption SeaRox WM 640, 75 mm w = 0.90Weigthed sound reduction of the A-60 application Rw = 47 dB
Product: SeaRox WM 640Density: 105 kg/m3
Thickness: Plate 75 mm insulation Stiffener 30 mm insulation
MED B-7487
PINNING4.5 mm steel75 mm SeaRox WM 640
30 mm SeaRox WM 6403 mm steel pin w. washer
4.5 mm steel75 mm SeaRox WM 640
30 mm SeaRox WM 6403 mm steel pin w. washer
TEST: 2006CS013889-2
-
24
A-60 Steel Bulkhead restricted
Construction: Stiffeners insulated with min. 40 mm SeaRox SL 620. Plate between stiffeners insulated with one layer
of 40 mm SeaRox SL 620. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300/400 mm distance. Insulation secured with washers of 38 mm.
Application notes: Restricted application (fire against insulated side) All the connections must be tight, no air gaps. Gap under the stiffener must be filled out completely. The pins should exceed the insulation by approx 10 mm. Insulation must be placed on fire-exposed side of the steel
plate.
Advantages:
One layer solution
Low construction weight
Easy handling
Surfaces:Reinforced aluminium foil
Glass cloth
Sound: Weigthed sound absorption SeaRox SL 620, 40 mm w = 0.80
Weigthed sound reduction of the A-60 application Rw = 47 dB
4.5 mm steel40 mm SeaRox SL 620
40 mm SeaRox SL 6203 mm steel pin w. washer
4.5 mm steel40 mm SeaRox SL 620
40 mm SeaRox SL 6203 mm steel pin w. washer
2480
3 mm steel pin w. washer
1000
480
300 mm400 mm
600 600 600
1000
Product: SeaRox SL 620Density: 100-115 kg/m3
Thickness: Plate 40 mm insulation Stiffener 40 mm insulation
MED B-7487
TEST: 2004cs014787
PINNING
-
2480
3 mm steel pin w. washer
1000
480
300 mm
300 mm
600 600 600
1000
25
A-60 Steel Bulkhead restricted
Construction:Plate between stiffeners insulated with one layer of 50 mm SeaRox SL 640.Stiffeners insulated with min. 50 mm SeaRox SL 640.Standard steel plate 4.5 mm ( 0.5 mm) thick.3 mm pins fixed with approx 300 mm distance.Insulation secured with washers of 38 mm.
Application notes:Restricted application (fire against insulated side)All the connections must be tight, no air gaps.Gap under the stiffener must be filled out completely.The pins should exceed the insulation by approx 10 mm. Insulation must be placed on fire exposed side of the steel plate.
Advantages:
One layer solution
Low construction weight
Easy handling
Surfaces:Reinforced aluminium foilGlass cloth
Sound:Weigthed sound absorption SeaRox SL 640, 50 mm w = 0.80
Product: SeaRox SL 640 Density: 130 kg/m3
Thickness: Plate 50 mm insulation Stiffener 50 mm insulation
MED B-7487
PINNING
4.5 mm steel50 mm SeaRox SL 640
50 mm SeaRox SL 640
3 mm steel pin w. washer
4.5 mm steel50 mm SeaRox SL 640
50 mm SeaRox SL 640
3 mm steel pin w. washer
TEST: G10095/5993
-
26
-
Index of A-constructions
Steel Deck
Steel - Deck
A-15 SeaRox MA 700 GSd page 28
A-30 SeaRox SL 740 page 29
A-30 SeaRox WM 620 page 30
A-60 SeaRox SL 620 page 31
A-60 SeaRox SL 640 page 32
A-60 SeaRox WM 620 page 33
A-60 Floating Floor SeaRox SL 480 page 34
A-60 Floating Floor SeaRox SL 436 page 35
Steel - Deck
27
-
28
A-15 Steel Deck
Construction:Plate and stiffeners insulated with one layer of SeaRox MA 700 GSd in 50 mm.Standard steel plate 4.5 mm ( 0.5 mm) thick.3 mm pins fixed with approx 300 mm distance.Insulation secured with washers of 38 mm.
Application notes:All the connections must be tight, no air gaps. The pins should exceed the insulation by approx 10 mm.
Advantages:
One layer solution
Low construction weight
Easy handling
Surfaces:Glass net 10x10 mm
Sound:Weigthed sound reduction index Rw = 45 dB
4.5 mm steel
40 mm SeaRox MA 700 GS3 mm steel pin w. washer
4.5 mm steel
40 mm SeaRox MA 700 GS3 mm steel pin w. washer
3 mm steel pin w. washer
400 mm
Product: SeaRox MA 700 GSd
Density: 27 kg/m3
Thickness: Plate 50 mm insulation Stiffener 50 mm insulation
MED B-7491
PINNING
-
3 mm steel pin w. washer
300 mm
300 mm
400 mm
29
A-30 Steel Deck
Construction:Stiffeners insulated with min. 30 mm SeaRox SL 740.Plate between stiffeners insulated with one layer
of 50 mm SeaRox SL 740.Standard steel plate 4.5 mm ( 0.5 mm) thick.3 mm pins fixed with approx 300 mm distance.Insulation secured with washers of 38 mm.
Application notes:All the connections must be tight, no air gaps. Gap under the stiffener must be filled out completely.The pins should exceed the insulation by approx 10 mm.
Advantages:
One layer solution
Low construction weight
Easy handling
Surfaces:Reinforced aluminium foilGlass cloth
Sound: Weigthed sound absorption
SeaRox SL 740, 50 mm w = 0.75 Weigthed sound reduction of the A-30 application
Rw = 45 dB
Product: SeaRox SL 740Density: 45 kg/m3
Thickness: Plate 50 mm insulation Stiffener 30 mm insulation
MED B-7485
PINNING
4.5 mm steel50 mm SeaRox SL 740
30 mm SeaRox SL 7403 mm steel pin w. washer
4.5 mm steel50 mm SeaRox SL 740
30 mm SeaRox SL 7403 mm steel pin w. washer
TEST: PG10985
-
30
A-30 Steel Deck
Construction:Plate between stiffeners insulated with one layer of 30 mm SeaRox WM 620.Stiffeners insulated with min. 30 mm SeaRox WM 620.Standard steel plate 4.5 mm ( 0.5 mm) thick.3 mm pins fixed with approx 300 mm distance.Insulation secured with washers of 38 mm.
Application notes:All the connections must be tight, no air gaps.Gap under the stiffener must be filled out completely.The pins should exceed the insulation by approx 10 mm.Wire mesh must be twisted or clamped together at joints.
Advantages:
One layer solution
Fast installation
Surfaces:Reinforced aluminium foilGlass cloth
4.5 mm steel30 mm SeaRox WM 620
30 mm SeaRox WM 6203 mm steel pin w. washer
4.5 mm steel
30 mm SeaRox WM 620
30 mm SeaRox WM 620
3 mm steel pin w. washer
2480
1000
480
300 mm
600 600 600
1000
3 mm steel pin w. washer
Product: SeaRox WM 620Density: 90 kg/m3
Thickness: Plate 30 mm insulation Stiffener 30 mm insulation
MED B-7485
PINNING
TEST: GH95.15.1
-
3 mm steel pin w. washer
250 mm
250 mm
31
A-60 Steel Deck
Construction: Plate between stiffeners insulated with one layer
of 40 mm SeaRox SL 620. Stiffeners insulated with min. 25 mm SeaRox SL 620. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 250 mm distance. Insulation secured with washers of 38 mm.
Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be filled out completely. The pins should exceed the insulation by approx 10 mm.
Advantages:
One layer solution
Low construction weight
Easy handling
Surfaces:Reinforced aluminium foilGlass cloth
Sound: Weigthed sound absorption
SeaRox SL 620, 40 mm w = 0.80 Weigthed sound reduction of the A-30 application
Rw = 46 dB
Product: SeaRox SL 620Density: 100-115 kg/m3
Thickness: Plate 40 mm insulation Stiffener 25 mm insulation
MED B-7488
PINNING
4.5 mm steel
40 mm SeaRox SL 620
25 mm SeaRox SL 620
3 mm steel pin w. washer
4.5 mm steel40 mm SeaRox SL 620
25 mm SeaRox SL 6203 mm steel pin w. washer
TEST: 96-DG-348-TO
-
32
A-60 Steel Deck
Construction:Plate between stiffeners insulated with one layer of 40 mm SeaRox SL 640.Stiffeners insulated with min. 40 mm SeaRox SL 640.Standard steel plate 4.5 mm ( 0.5 mm) thick.3 mm pins fixed with approx 300 mm distance.Insulation secured with washers of 38 mm.
Application notes:All the connections must be tight, no air gaps. Gap under the stiffener must be filled out completely.The pins should exceed the insulation by approx 10 mm..
Advantages:
One layer solution
Optimal sound properties
Easy handling
Surfaces:Reinforced aluminium foil
Glass cloth
Sound: Weigthed sound absorption SeaRox SL 640, 40 mm w = 0.75Weigthed sound reduction of the A-60 application Rw = 56 dB (with 1 mm steel sheet in front of the insulation)
4.5 mm steel40 mm SeaRox SL 640
40 mm SeaRox SL 6403 mm steel pin w. washer
4.5 mm steel
40 mm SeaRox SL 640
3 mm steel pin w. washer
2480
3 mm steel pin w. washer
1000
480
300 mm
200 mm
400 mm
600 600 600
1000
Product: SeaRox SL 640Density: 130 kg/m3
Thickness: Plate 40 mm insulation Stiffener 40 mm insulation
MED B-7488
TEST: G10141/6025
PINNING
-
300 mm
400 mm
3 mm steel pin w. washer
33
A-60 Steel Deck
Construction: Plate and stiffeners insulated with one layer of
45 mm SeaRox WM 620. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300 mm distance. Insulation secured with washers of 38 mm.
Application notes: All the connections must be tight, no air gaps. Wire mesh must be twisted together at joints The pins should exceed the insulation by approx 10 mm.
Advantages:
One layer solution
Low construction weight
Fast installation
Surfaces:Reinforced aluminium foilGlass cloth
Sound:Weigthed sound absorption SeaRox WM 620, 45 mm w = 0.90Weigthed sound reduction of the A-60 application Rw = 46 dB
Product: SeaRox WM 620 Density: 90 kg/m3
Thickness: Plate 45 mm insulation Stiffener 45 mm insulation
MED B-7488
PINNING
4.5 mm steel45 mm SeaRox WM 620
45 mm SeaRox WM 6203 mm steel pin w. washer
4.5 mm steel45 mm SeaRox WM 620
3 mm steel pin w. washer
TEST: PG10984/8384
-
34
A-60 Floating Floor
Construction: Standard steel plate 4.5 mm ( 0.5 mm) thick. The floor insulated with two layers of 30 mm
SeaRox SL 480. Insulation covered by a 2 mm steel plate spot welded
at c/c 150 mm.
Application notes: First layer insulation is with butted joints. Second layer with butted and staggered joints to avoid
overlapping joints. Do not step directly on the wool during installation. Always
use a board or similar when moving around on the wool. To avoid sound from travelling it is recommended to fin-
ish the construction with a rigid Rockwool product placed edgeways and sealed with a flexible sealant.
Advantages:
Safe solution
Optimal sound properties
Easy handling
Surfaces: The wool must be covered by a minimum 2 mm thick steel plate
Top layer must be evaluated according to static calculations.
Max. load on insulation material: 40 kN/m2
Read more on page 70
2 mm steel
SeaRox SL 480
Flexible sealant
2x30 mm SeaRox SL 480
2 mm steel
4.5 mm steel
2x30 mm SeaRox SL 480
2480
1000
480
600 600 600
1000
Steel deck 5 mm
Flatbar 30 x 3 mm
Stainless steel plate
Product: SeaRox SL 480 Density: 200 kg/m3
Thickness: Plate 2x30 mm insulation Top plate min. 2 mm steel plate
MED B-7488
TEST: 103020,44
PINNING
-
2480
1000
480
600 600 600
1000
Steel deck 5 mm
Flatbar 30 x 3 mm
Stainless steel plate
35
A-60 Floating Floor
Construction: Standard steel plate 4.5 mm ( 0.5 mm) thick. The floor insulated with SeaRox SL 436 in 60 mm thickness. Insulation covered by 1.5 mm + 3 mm steel plate.
Application notes: Insulation installed with butted joints. Do not step directly on the wool during installation. Always
use a board or similar when moving around on the wool. To avoid sound from travelling it is recommended to fin-
ish the construction with a rigid Rockwool product placed edgeways and sealed with a flexible sealant.
This solution is not recommended in areas with load on the deck.
The first layer of steel plate must be 1.5 mm thick, installed with 50 mm overlap and secured with pop rivets. The sec-ond layer (top layer) must be 3 mm steel plate with butted joints and spot welded at c/c 150 mm.
Advantages:
Safe solution
Optimal sound properties
Easy handling
Surfaces: The wool must be covered by a minimum 1.5 + 3 mm thick steel plate
Max. load on insulation material: 12 kN/m2
Product: SeaRox SL 436 Density: 140 kg/m3
Thickness: Plate 60 mm insulation Top plates 1.5 + 3 mm steel plate
MED B-7488
PINNING
1.5 mm steel3 mm steel
4.5 mm steel
60 mm SeaRox SL 436
1.5 mm steel
SeaRox SL 436
Flexible sealant
3 mm steel
60 mm SeaRox SL 436
TEST: 22N002.07D
Read more on page 71
Thickness of Marine Slab 140 [mm]
Dynamic Stiffness N/m3
y = 0.0025x2 - 0.5591x + 35.426
30,0y
x
25,0
20,0
15,0
10,0
5,0
0,020 40 60 80 100
Dynamic Stiffness N/m
.
ickness of Marine Slab 140 [mm]
-
36
-
Index of A-constructions
Aluminium Bulkhead
Aluminium Bulkhead
A-60 SeaRox SL 640 page 38
A-60 SeaRox SL 620 page 39
A-60 Restricted SeaRox SL 640 page 40
Aluminium Bulkhead
37
-
38
A-60 Aluminium Bulkhead
Construction:Plate between stiffeners insulated with two layers of 30 mm SeaRox SL 640. Insulation on both sides of the alu plate.Stiffeners insulated with two layers of min. 30 mm SeaRox SL 640. Standard alu plate min. 6 mm ( 0.5 mm) thick.Stiffeners 9 mm alu.3 mm alu tipped stainless steel pins fixed with
approx 300 mm distance.Insulation secured with stainless steel washers of 38 mm.
Application notes:All the connections must be tight, no air gaps.Gap under the stiffener must be filled out completely. Joints must be staggered, 150 mm overlap is recommended
Advantages:
Safe solution
Optimal sound properties
Easy handling
Surfaces:Reinforced aluminium foilGlass cloth
Sound: Weigthed sound absorption SeaRox SL 640, 2x30 mm w = 0.90
2x30 mm SeaRox SL 6403 mm alu tipped stainlesssteel pin w. washer
6 mm alu
9 mm alu
2x30 mm SeaRox SL 640
2x30 mm SeaRox SL 640
3 mm alu tipped stainlesssteel pin w. washer
2480
3 mm alu tipped stainless steel pin w. washer
1000
480
300 mm300 mm
600 600 600
1000
Product: SeaRox SL 640 Density: 130 kg/m3
Thickness: Plate 2x30 mm insulation on both sides Stiffener 2x30 mm
MED B-7489
TEST: PG10699/7735
PINNING
-
3 mm alu tipped stainless steel pin w. washer
300 mm
400 mm
39
A-60 Aluminium Bulkhead
Construction: Stiffeners insulated with two layers of min. 30 mm
SeaRox SL 620. Plate between stiffeners insulated with two layers of 30 mm
SeaRox SL 620. Insulation on both sides of the alu plate. Standard alu plate min. 6 mm ( 0.5 mm) thick. Stiffeners 9 mm alu. 3 mm alu tipped stainless steel pins fixed with approx 300
mm distance. Insulation secured with stainless steel washers of 38 mm.
Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be filled out completely. Joints must be staggered, 150 mm overlap is recommended
Advantages:
Safe solution
Low construction weight
Easy handling
Surfaces:Reinforced aluminium foilGlass cloth
Sound: Weigthed sound absorption
SeaRox SL 620, 60 mm w = 0.90 Weigthed sound reduction of the A-60 application
Rw = 40 dB
Product: SeaRox SL 620 Density: 100-115 kg/m3
Thickness: Plate 2x30 mm insulation on both sides Stiffener 2x30 mm
MED B-7489
PINNING
6 mm alu
9 mm alu
2x30 mm SeaRox SL 620
2x30 mm SeaRox SL 620
3 mm alu tipped stainlesssteel pin w. washer
2x30 mm SeaRox SL 6203 mm alu tipped stainlesssteel pin w. washer
TEST: 22N002.07D
-
4040
A-60 Aluminium Bulkhead restricted
Construction:Plate between stiffeners insulated with two layers of 30 mm SeaRox SL 640.Stiffeners insulated with two layers of min. 30 mm SeaRox SL 640. Standard alu plate min. 6 mm ( 0.5 mm) thick.Stiffeners 9 mm alu.3 mm alu tipped stainless steel pins fixed with approx 300 mm distance.Insulation secured with stainless steel washers of 38 mm.
Application notes:Restricted application (fire against insulated side)All the connections must be tight, no air gaps.Gap under the stiffener must be filled out completely. Joints must be staggered, 150 mm overlap is recommendedThe pins should exceed the insulation by approx 10 mm.
Advantages:
Safe solution
Optimal sound properties
Easy handling
Surfaces:Reinforced aluminium foilGlass cloth
Sound: Weigthed sound absorption SeaRox SL 640, 2x30 mm w = 0.90
2x30 mm SeaRox SL 6403 mm alu tipped stainless steel pin w. washer
6 mm alu
9 mm alu
2x30 mm SeaRox SL 640
3 mm alu tipped stainless steel pin w. washer
2480
3 mm alu tipped stainless steel pin w. washer
1000
480
300 mm300 mm
600 600 600
1000
Product: SeaRox SL 640 Density: 130 kg/m3
Thickness: Plate 2x30 mm insulation Stiffener 2x30 mm
MED B-7489
TEST: PG10125/5996
PINNING
-
Index of A-constructions
Aluminium Deck
Aluminium Deck
A-30 SeaRox SL 740/ SeaRox WM 620 page 42
A-60 SeaRox SL 640 page 43
A-60 SeaRox SL 620 page 44
Aluminium - Deck
41
-
42
A-30 Aluminium Deck
Construction:Stiffeners insulated with min. 45 mm SeaRox WM 620Plate insulated with one layer of 50 mm SeaRox SL 740Standard alu plate min. 6 mm ( 0.5 mm) thick. Stiffeners 9 mm alu.3 mm alu tipped stainless steel pins fixed with approx 300 mm distance.Insulation secured with stainless steel washers of 38 mm.
Application notes:All the connections must be tight, no air gaps.Gap under the stiffener must be filled out completely.The pins should exceed the insulation by approx 10 mm.
Advantages:
One layer solution
Fast installation
Optimal sound properties
Easy handling
Surfaces:Reinforced aluminium foilGlass cloth
Sound: Weigthed sound absorption SeaRox WM 620, 45 mm w = 0.90SeaRox SL 740, 50 mm w = 0.75
6 mm alu
9 mm alu
50 mm SeaRox SL 740
45 mm SeaRox WM 6203 mm alu tipped stainless steel pin with washer
6 mm alu50 mm SeaRox SL 740
45 mm SeaRox WM 620
3 mm alu tipped stainless steel pin w. washer
9 mm alu
2480
1000
480
400 mm
600 600 600
1000
300 mm
300 mm
3 mm alu tipped stainless steel pin w. washer
Product: SeaRox SL 740/ SeaRox WM 620 Density: 45/90 kg/m3
Thickness: Plate 50 mm insulation Stiffener 45 mm insulation
MED B-7486
TEST: PG11045
PINNING
-
2480
3 mm alu tipped stainless steel pin with washer
300 mm
300 mm
400 mm
600 600 600
1000
43
A-60 Aluminium Deck
Construction:Stiffeners insulated with two layers of min. 30 mm SeaRox SL 640Plate between stiffeners insulated with two layers of 30 mm SeaRox SL 640.Standard alu plate min. 6 mm ( 0.5 mm) thick.Stiffeners 9 mm alu.3 mm alu tipped stainless steel pins fixed with approx 300/400 mm distance.Insulation secured with stainless steel washers of 38 mm.
Application notes:All the connections must be tight, no air gaps.Gap under the stiffener must be filled out completely. Joints must be staggered, 150 mm overlap is recommendedThe pins should exceed the insulation by approx 10 mm.
Advantages:
Safe solution
Optimal sound properties
Easy handling
Surfaces:Reinforced aluminium foilGlass cloth
Sound: Weigthed sound absorption
SeaRox SL 640, 2x30 mm w = 0.90
Product: SeaRox SL 640 Density: 130 kg/m3
Thickness: Plate 2x30 mm insulation Stiffener 2x30 mm insulation
MED B-7490
PINNING
6 mm alu
9 mm alu
2x30 mm SeaRox SL 640
3 mm alu tipped stainless steel pinwith washer
2x30 mm SeaRox SL 640
3 mm alu tipped stainless steel pinwith washer
TEST: PG10765
-
3 mm alu tipped stainless steel pin w. washer
300 mm
400 mm
A-60 Aluminium Deck
Construction: Stiffeners insulated with two layers of min. 30 mm
SeaRox SL 620. Plate between stiffeners insulated with two layers of 30 mm
SeaRox SL 620. Standard alu plate min. 6 mm ( 0.5 mm) thick. Stiffeners 9 mm alu. 3 mm alu tipped stainless steel pins fixed with approx
300/400 mm distance. Insulation secured with stainless steel washers of 38 mm.
Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be filled out completely. Joints must be staggered, 150 mm overlap is recommended The pins should exceed the insulation by approx 10 mm.
Advantages:
Safe solution
Low construction weight
Easy handling
Surfaces:Reinforced aluminium foilGlass cloth
Sound: Weigthed sound absorption
SeaRox SL 620, 60 mm w = 0.90 Weigthed sound reduction of the A-60 application
Rw = 40 dB
Product: SeaRox SL 620 Density: 100-115 kg/m3
Thickness: Plate 2x30 mm insulation Stiffener 2x30 mm insulation
MED B-7490
PINNING
6 mm alu
9 mm alu
2x30 mm SeaRox SL 620
3 mm alu tipped stainless steel pinwith washer
2x30 mm SeaRox SL 6203 mm alu tipped stainless steel pinwith washer
44
-
45
Index of H-constructions
Steel Bulkheadrestricted
Steel Bulkhead restricted
H-60 SeaRox SL 660/ SeaRox WM 660 page 46
H-120 SeaRox SL 660/ SeaRox WM 660 page 47
Corrugated Steel Bulkhead restricted non-load bearing
H-60 SeaRox SL 660/ SeaRox WM 660 page 48
H-120 SeaRox SL 660/ SeaRox WM 660 page 49
45
Steel - Bulkhead
-
2480
1000
480
290 mm
400 mm
600 600 600
1000
3 mm steel pin with washer
H-60 Steel Bulkhead restricted
Construction:Plate insulated with one layer of 30 mm SeaRox SL 660 and one layer of 40 mm SeaRox WM 660.
Stiffeners insulated in the same process with min. 40 mm of SeaRox WM 660.Standard steel plate 4.5 mm ( 0.5 mm) thick.
3 mm pins fixed with approx 300 mm distance. Insulation secured by washers of 38mm.
Application notes: Restricted application (fire against insulated side) All the connections must be tight, no air gaps. Gap under the stiffener must be filled out completely. Joints between layers must be staggered, 150 mm overlap is recommended.
The pins should exceed the insulation by approx 10 mm. Wire mesh must be twisted together at joints.
Advantages:
Safe solution
Optimal sound properties
Fast installation
Surfaces:Reinforced aluminium foil
Sound: Weigthed sound reduction of the application
Rw = 48 dB
Product: SeaRox SL 660 SeaRox WM 660 Density: 150 kg/m3
Thickness: Plate 30 mm + 40 mm insulation Stiffener 40 mm insulation
PINNING4.5 mm steel
30 mm SeaRox SL 660
40 mm SeaRox WM 660
3 mm steel pin with washer
4.5 mm steel30 mm SeaRox SL 660
40 mm SeaRox WM 660
46
-
47
2480
1000
480
250 mm
600 600 600
1000
3 mm steel pin with washer
400 mm
H-120 Steel Bulkhead restricted
Construction: Stiffeners insulated with min. 2x40 mm SeaRox WM 660.
Second layer in the same process as insulation of the plate. Plate insulated with one layer of 30 mm SeaRox SL 660 and
one layer of 40 mm SeaRox WM 660 Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300 mm distance. Insulation secured by washers of 38 mm
Application notes: Restricted application (fire against insulated side) All the connections must be tight, no air gaps. Gap under the stiffener must be filled out completely. Joints between layers must be staggered, 150 mm overlap is recommended.
The pins should exceed the insulation by approx 10 mm. Wire mesh must be twisted together at joints. Insulation can be placed on either side of the steel plate.
Advantages:
Safe solution
Optimal sound properties
Fast installation
Surfaces:Reinforced aluminium foil
Sound: Weigthed sound reduction of the application
Rw = 49 dB
Product: SeaRox SL 660 SeaRox WM 660 Density: 150 kg/m3
Thickness: Plate 30 mm + 40 mm insulation Stiffener 2x40 mm insulation
PINNING4.5 mm steel30 mm SeaRox Sl 66040 mm SeaRox WM 660
3 mm steel pin with washer
4.5 mm steel30 mm SeaRox SL 660
40 mm SeaRox WM 660
-
2480
3 mm steel pin w. washer
1000
480
600 600 600
300 mm
250 mm
H-60 corrugated Steel Bulkhead restrictednon-load bearing
Construction:Corrugated steel plate insulated with 50 mm SeaRox SL 660 and 40 mm SeaRox WM 660.Corrugated steel plate of min. 1.5 mm.3 mm pins fixed with approx 300 mm distance.Pins fixed on top of corrugated steel plate by washers of 38 mmNo fill of corrugation
Application notes:All the connections must be tight, no air gaps. Joints must be staggered, 150 mm overlap is recommended.The pins should exceed the insulation by approx 10 mmWire mesh twisted together of joints.Same solution as H-120.
Advantages:
Safe solution
Optimal sound properties
Fast installation
Surfaces:Reinforced aluminium foil
Sound:Weigthed sound reduction of the application Rw = 44 dB
Product: SeaRox SL 660 SeaRox WM 660Density: 150 kg/m3
Thickness: Plate 50 mm + 40 mm insulation
PINNING
1.5 mm steel
45 mm
50 mm SeaRox SL 6603 mm steel pin w. washer
250 mm40 mm SeaRox WM 660
48
-
2480
3 mm steel pin w. washer
1000
480
600 600 600
300 mm
250 mm
PINNING
1.5 mm steel
45 mm
50 mm SeaRox SL 6603 mm steel pin w. washer
250 mm40 mm SeaRox WM 660
49
H-120 corrugated Steel Bulkhead restrictednon-load bearing
Construction: Corrugated steel plate insulated with 50 mm SeaRox SL 660
and 40 mm SeaRox WM 660. Corrugated steel plate of min. 1.5 mm. 3 mm pins fixed with approx 300 mm distance. Pins fixed on top of corrugated steel plate by washers of 38 mm No fill of corrugation
Application notes: All the connections must be tight, no air gaps. Joints must be staggered, 150 mm overlap is recommended. The pins should exceed the insulation by approx 10 mm Wire mesh twisted together of joints. Same solution as H-60.
Advantages:
Safe solution
Optimal sound properties
Fast installation
Surfaces:Reinforced aluminium foil
Sound: Weigthed sound reduction of the application
Rw = 44 dB
Product: SeaRox SL 660 SeaRox WM 660 Density: 150 kg/m3
Thickness: Plate 50 mm + 40 mm insulation
-
50
-
51 51
Index of H-constructions
Steel Deck
Steel Deck
H-60 SeaRox SL 660 page 52
51
Steel - Deck
-
52
2480
3 mm steel pin with washer
400 mm
1000
H-60 Steel Deck
Construction: Stiffeners insulated with min. 2x50 mm SeaRox SL 660. Plate insulated with two layers of 50 mm SeaRox SL 660. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 100/400 mm distance
Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be filled out completely. The pins should exceed the insulation by approx 10 mm. Joints to be staggered, 150 mm overlap is recommended.
Advantages:
Safe solution
Optimal sound properties
Easy Handling
Surfaces:Reinforced aluminium foil
Sound:Weigthed sound absorption SeaRox SL 660, 2 x 50 mm w = 0.90Weigthed sound reduction of the application Rw = 48 dB
Product: SeaRox SL 660Density: 150 kg/m3
Thickness: Plate 50 mm + 50 mm insulation Stiffener 50 + 50 mm insulation
PINNING
4.5 mm steel
3 mm steel pin w. washer
2x50 mm SeaRox SL 660
4.5 mm steel
2x50 mm SeaRox SL 6603 mm steel pin with washer
-
53
Index of
Jet Fire & Blast Resistance
Jet Fire & Blast Resistance
Bulkhead and Deck Jet Fire 30 min. page 54
Blast Resistance page 55
53
Jet Fire & Blast Resistance
-
54
Supports at 500 mm c/c 500 mm c/c
Support angle
Stainless steel plate
35
65
50
35
50
35 503550
135Aluminium foil 0.05 mmSupport pl. 30x3 at 1000 mm c/c(vertically)
SS. screws at 150 mm c/c
Ceramic paper
L40x20x4 mm welded to support plate
Butt jointed stainless steel plate
Galvanised wire mesh
Reinforced aluminium foil 0.05 mm
Construction: Plate and stiffener must be insulated with 35 mm and 50 mm SeaRox SL 660. First layer, 35 mm, with reinforced aluminium foil. The foil must be placed so it is between the two layers of insulation.
Standard steel plate 5 mm. Standard pins or stainless steel pins 3 mm. Insulation secured with washers of 38 mm. Insulation secured with galvanised wire mesh. Wire mesh must be covered with reinforced aluminium foil. The construction must be covered with 0.8-1.0 mm stain-less steel plate.
All joints in the stainless steel plate must be against a back-up steel angle 40 x 20 x 4 mm, covered with ceramic paper.
Stainless steel plate fixed with self-tapping screws at 150 mm c/c.
For further details check official drawing.
Bulkhead and Deck Jet Fire 30 min.
Application notes: Joints between the two layers of SeaRox SL 660 must be staggered, 150 mm overlap is recommended. Wire mesh clamped or twisted at joints Pins must be bent over the fixing washers Test duration 30 min.
Advantages:
Safe solution
Product: SeaRox SL 660Density: 150 kg/m3
Thickness: Plate 85 mm (35+50) insulation
MED B-4134
-
55
General arrangement prior to testing - blast resistance - class H
The regulatory requirements for the blast behaviour of fire rated bulkheads are not normally well documented. It is considered a general requirement that all parts of fire divisions maintain the same fire and explosion resistance and proof of this must be documented through physical testing.
General arrangement after testing - recommended design limits
SeaRox SL 660 with heavy duty stainless mesh and bent pins: Peak overpressure: 0.7 bar Duration (positive phase): 35 ms Explosion wind: 300 m/s
Galvanised mesh and bent pins: Peak overpressure: 0.6 bar Duration (positive phase) 35 ms Explosion wind: 300 m/s
Galvanised mesh and standard pins: Peak overpressure: 0.4 bar Duration (positive phase): 50 ms Explosion wind: 300 m/s
Strength of covering steel plate must be calculated by designer
Blast Resistance
Test results on H-0 rated insulation
Test construction Load characteristics Critical damage
50+35 mm SeaRox WM 660 with: Pmax(bar) Uxx(m/s) ta(m)
Heavy duty stainless steel mesh with pins bent over washers 0.34 240 54 None
Heavy duty stainless steel mesh with pins bent over washers 0.68 300 33 None
Galvanised wire mesh with pins bent over washers 0.33 240 50 None
Galvanised wire mesh with pins bent over washers 0.58 300 35 None
Galvanised wire mesh with standard pins and washers 0.37 270 49 None
All the above tests were carried out without any significant damage to the insulation material. According to the Norwegian Fire Research Laboratory (SINTEF) a fire will not affect the fire integrity or stability of the insulation.
Due to the test methods used, SINTEF has assessed the above results to be conservative.
Rockwool, in association with SINTEF (NBL) in Norway, has performed extensive testing on H-rated Rockwool insulation systems, using controlled gas explosions. The test results below refer to the same insulation construction with various types of wire mesh.
-
5656
-
Index of
Construction Details
Construction Details
Stiffeners page 58
Bulkhead and Deck Connections page 59
Installation of Surface Protections Steel Plate
page 60
Corrugated Structural Steel page 61
Construction Details
57
-
58
Stiffeners
Stiffener
450 mm
Stiffener
450 mm
Stiffener
450 mm
Solas requires that the stiffeners must be insulated*. One way is to insulate without filling the space behind the stiffeners.
In other situations the insulation can follow the shape of the stiffener or the void behind the stiffener can be filled out.
If the stiffener is more than 450 mm wide the insulation can be stopped at 450 mm. The insulation of stiffeners should be finally approved by local surveyor.
450
mm
450
mm
450
mm
450
mm
450
mm
450
mm
450
mm
450
mm
450
mm
450
mm
In most bulkhead and deck constructions stiffeners are used to secure the necessary strength in the construction. In order to prevent heat transmission it is important to secure the right insulation. In general insulation of the stiffeners must follow the official drawings as carried out in the fire tests.
Insulation of stiffener with SeaRox SL 620
Insulation of stiffener with SeaRox SL 740
Insulation of stiffener with SeaRox SL640
Insulation of stiffener with SeaRox WM 640
Insulation of stiffener withSeaRox WM 620
Insulation of stiffener with SeaRox SL 620
* acc. to SOLAS MSC/circ. 1120 annex reg. 9.3.4
-
59
Bulkhead and Deck Connections
Deck
Bulkhead
Min.450 mm
Deck
Bulkhead
Min. 450 mmMin. 450 mm
225 mm225 mm
225 mm225 mm
When two plates are connected in a corner, the heat bridge should always be kept in mind when insulating. The structure must have insulation so that heat transfer can not occur from one unexposed surface through the structure and onto another unexposed surface. The heat must always go minimum 450 mm under the insulation before reaching an unexposed surface (acc. to SOLAS MSC/circ. 1120 annex reg. 9.3.4).
Bulkhead and Deck - Construction detailsIn connection with insulation it is important to pay special attention to the details related to junctions, corners etc. in order to avoid potential heat bridges. Below you will find examples of construction details:
Connections between A-60 and A-0 construc-tions should be insulated by adding a layer of A-60 insulation on the A-0 construction in a minimum width of 450 mm. This is to minimize the effect of the heat bridge.
Another alternative to insulate the heat bridge can be done by installing min. 450 mm* of insulation on the other side of the construction. This will reduce the transferred heat and thereby minimise the risk of self ignition inside the connecting room.
Steel Bulkhead/DeckA60
Bul
khea
d or
Dec
k
Additional insulation
A0
Min. 450
Steel Bulkhead/Deck
Additional insulation
A0
A60
Bul
khea
dor
Dec
k
Min. 450
Insulation on either side of Bulkhead/Deck
Corner example Junction example 1 Junction example 2
Insulation on the outside of Bulkhead/Deck
* Rockwool recommends 900 mm to secure that the heat always go min. 450 mm under the insulation before reaching an unexposed surface.
Insulation on the inside of Bulkhead/Deck
Steel Bulkhead/Deck
Additional insulation
A60 Steel Bulkhead or Deck
A60
Min
. 450
Steel Bulkhead/Deck
Additional insulation
A60 Steel Bulkhead or Deck
A60
A0
Min. 450 Steel Bulkhead/Deck
A60 Bulkhead or Deck
Additional insulation
A0/ A
60
Min
. 450
-
60
Installation of Surface Steel Plate
A surface protection of sheet metal can be installed in different ways, depending on the layout of the stiffeners and the amount of insulation.
It is important to make the fixing in a way that minimises the heat bridges and structural noise transmitted via the hull.
Surface steel
L- Steel
Surface steel
L- Steel
Flat steel
Max. 500 mm
Max.150 mm
40 mm
10 mm
40 mm
65 mm Flat steel
L- Steel
Surface steel
Flat steel
L- Steel
Surface steel
Surface steel
L- Steel
Surface steel
L- Steel
Flat steel
Max. 500 mm
Max.150 mm
40 mm
10 mm
40 mm
65 mm Flat steel
L- Steel
Surface steel
Flat steel
L- Steel
Surface steel
Surface steel
L- Steel
Surface steel
L- Steel
Flat steel
Max. 500 mm
Max.150 mm
40 mm
10 mm
40 mm
65 mm Flat steel
L- Steel
Surface steel
Flat steel
L- Steel
Surface steel
Surface steel
L- Steel
Surface steel
L- Steel
Flat steel
Max. 500 mm
Max.150 mm
40 mm
10 mm
40 mm
65 mm Flat steel
L- Steel
Surface steel
Flat steel
L- Steel
Surface steel
L - Steel
Flat steel
Surface steel
Fixing of surface steel where space is needed for pipes etc.
Fixing of surface steel taking large stiffeners into consideration.
Fixing of surface steel as close to the steel plate as possible.
Fixing of surface with no stiffeners or stiffeners on the other side of steel plate.
1
3
2
4
-
61
Corrugated Structural Steel
A-60 Fire Rated ConstructionsIn some projects the standard IMO structural core is replaced with a light structural core consisting of a corrugated steel plate.
To ease the insulation Rockwool Technical Insulation has got an assessment from DBI (Danish Fire Institute) which allows insulation using our standard fire rated constructions without filling out the corrugation.
The assessments are valid for A-60 fire rated constructions as follows:
SeaRox WM 640, 75 mm, 1 layer
SeaRox WM 620, 45 mm, 2 layer
SeaRox SL 640, 30 mm, 2 layer
SeaRox SL 620, 60 mm, 1 layer
The assessment is provided under the following restrictions:
Products as described in test report
Structural core towards the fire
The height of the corrugation may not exceed 100 mm and the thickness of the corrugated steel plating is not below 1.9 mm.
The joint between the corrugated steel sheets must be fully welded to insure air tightness.
The corrugated steel structural core should not carry any vertical load.
Pin pattern according to the description in the assessment
Corrugated steel
Insulation
Steel pin
Single layer system 75 mm SeaRox WM 640
Single layer system 60 mm SeaRox SL 620
Double layer system 2 x 45 mm SeaRox WM 620
Double layer system 2 x 30 mm SeaRox SL 640
Double layer Single layer
Max.100 mm Max.100 mm
Double layer Single layer
Max.100 mm Max.100 mm
-
62
-
Index of
Additional FireProtection
Additional Fire Protection
Draught Stoppers page 64
Penetrations page 65
B-15 Extension page 66
Sprinkler Pipes page 67
63
B-15 Extension Draught Stoppers
Sprinkler Pipes
Penetrations
-
64
Draught Stoppers
Draught stoppers are used above ceilings to avoid the spread of smoke and flames in case of fire. Normally the classifica-tion companies request a B-0 fire insulation above the ceiling. This can be made from SeaRox WM 640 or SeaRox SL 620 after request from the local surveyor or the customer. Construction
SeaRox WM 640, min. 50 mm, with reinforced aluminium foil or... SeaRox SL 620, min. 60 mm, with reinforced aluminium foil.
SeaRox SL 620 must be covered with wire mesh. Insulation fixed with 3 mm pins and secured with 38 mm washers.
InstallationStep 1: First the pins are welded vertically to the underside of
the deck in alignment with the required position of the Draught Stopper.
Step 2: The pins are then bent 90 in a staggered pattern as shown.
Step 3: The Rockwool product and wire mesh are then pushed over the pins so that they protrude by a minimum of 25 mm. The insulation is secured by spring steel washers.
Penetrations Penetrations through the Draught Stopper are simply made by cutting out the shape of the penetrating items in the Rockwool product, for example, pipes, HVAC ducts and cable racks.
The cut edge of the Wired Mat must fit tightly to the edge of the penetrating item and the slit in the insulation must be stitched/taped back together using steel wire/alu tape.
This solution can be used for any type of penetration includ-ing multiple penetrations.
Deck construction
Fixing pins
Rockwool fire and smoke stop
Service penetration
Internal partition
Suspended ceiling
Ceiling void
Step 1
Deck construction100 mm
Step 2
Step 3
Deck construction
Service penetration
Suspended ceiling
Cut around penetrationand wire mesh stitched together along joint
SOLAS, Part C, Chapter II-2, Regulation 8, sec 4 :
Air spaces enclosed behind ceilings, panelling or linings shall be divided by close-fitting Draught Stops spaced not more than 14 m apart. In the vertical direction, such enclosed air spaces, including those behind linings of stairways, trunks, etc., shall be closed at each deck.
The interpretation of the rules given by IMO in MSC/circ. 847 reg 35.
-
65
Penetrations
Penetrations of fire protectionWhen pipes, ducts or other go through a bulkhead or deck it is called a penetration. There are special rules regarding insulation when the decks or bulkheads with fire class are penetrated.
The pipe going through a fire classed structure must be made of steel and must have a length of minimum 900 mm. IMO suggests to use min. 450 mm on each side of the construction.
The min. 900 mm insulation must have the same insulation class weight as the structure that is penetrated.
SOLAS, Chapter II-2, Regulation 9, sec 3:The duct spool must be insulated with A-rated fire insulation for a distance of either side of the bulkhead or deck (L1 + L2 = 900 mm)
Rockwool Fire Insulation
Steel pipe
A-60 insulation
L1 + L2 = min. 900 mm
L1 L2
Steel min. 3 mm thick
-
66
B-15 Extension
B-15 extension is used as a B-15 wall extension above the ceiling. The B-15 extension prevents smoke and fire to spread above the ceiling. The B-15 extension solution has passed a B-15 fire test with SeaRox SL 470, 25 mm which fulfils the IMO demands.
B-15 wall extension/separation of adjacent spaces
Product: SeaRox SL 470, 25 mm Density: 180 kg/m3
Vessels have screens between the cabins with a fire class of B-0, B-15, A-15 or A30. When a B-0 or B-15 seperation is requested Rockwool recommends using a B-15 construction.
This construction consists of a normal B-15 wall and above the ceiling a 25 mm SeaRox SL 470.
Construction:B-15 Lining panel as wall between cabins. B-15 Screen made of 25 mm SeaRox SL 470 above the ceiling.
Deck construction
B-15 extension
B-15 lining panel
Top steel profile
1
2
3
730 mm
1800
Steel angle bar40x40x2 mm
Top steel intermediary profile with pins included
Spot weldingfor fixing
Spot weldingfor fixing
Top steel profil
Spot welding for fixing
Self locker washer
Steel angle bar25x25x2 mm
B-15 screen of SeaRox SL 470, 25 mm
B-15 screen SeaRox SL 470, 25 mm
1800
Steel angle bar40x40x2 mm
Top steel intermediary profile with pins included
Spot weldingfor fixing
Spot weldingfor fixing
Top steel profil
Spot welding for fixing
Self locker washer
Steel angle bar25x25x2 mm
B-15 screen of SeaRox SL 470, 25 mm
B-15 screen SeaRox SL 470, 25 mm
1800
Steel angle bar40x40x2
Spot weldingfor fixing
Top steel profile
Spot welding for fixing
Steel angle bar25x25x2 mm
Spring washer
Steel angle bar25x25x2
B15 screen mineral wool density 180 kg/m3 thick. 25 mm
B-15 screen SeaRox SL 470, 25 mm
20 mm
30 mm50 mm
2
1
3
-
67
Fire Protection of Sprinkler Pipes
New amendment to SOLAS regulation about protection of sprinkler pipes on passenger vessels Seen in the light of the increasing sizes of passenger ships and growing number of passengers, an amendment to SOLAS regulation Safe return to port is applicable to all passenger ships built on or after 1st July 2010 stating that sprinkler pipes on passenger vessels need to remain operational in case of fire.
The amendment is valid for:
All passenger ships of 120 m or more, or...
Having three or more main vertical zones
Applicable also for ROPAX vessels and large offshore accommodations.
Safe return to port
Regulation 21.4
Wet steel pipes carrying water bas
ed liquids and passing through an
d not serving
spaces affected by a re casualty a
re considered to remain operation
al, provided
they are of substantial thickness (
ref. ICLL 66 Reg. 22(3) as interpr
eted by IACS
UI LL36/Rev.1 paragraph (b)) or
insulated to class A-60 and fully w
elded.
If provided with ttings, they are
to be tested according to IACS U
R P2.11.5.5.6
re test.
SeaRox PS 620 ALUSC To fulfil the requirement Rockwool Technical Insulation has introduced a Pipe Section called SeaRox PS 620 ALUSC. This product may be used not only for thermal insulation but also for fire protection according to IMO FTP code. By using the already A-60 approved basis product, SeaRox SL 620. in approved thicknesses for Bulkhead and Deck, just cut into Pipe Sections the product is fulfilling the requirements.
The solution secures the following advantages:
Fire protection of steel pipes as required by IMO MSC Resolution MSC 216(82).
Standard Pipe Section also for fire protection - basis product tested and approved for A-60.
Easy assortment and installation.
-
68
-
69
Index of
Floating Floor
Floating Floor
SeaRox SL 440 page 70
SeaRox SL 436 page 71
69
Floating Floor
-
70
Floating Floor Constructions Class A-60
MED-B-7488 includes two different types of A-60 Deck class Floating Floor constructions.
1) SeaRox SL 480This solution consists of two layers SeaRox SL 480, each of 30 mm thickness, covered by minimum 2 mm steel plate, spot welded at c/c 150 mm.
This construction combines the excellent properties of fire protection, noise reduction, high compression strength and thermal insulation.
The max free area recommended is 8 x 8 m. If larger free areas are to be made, division flat bars should be made. This allows the insulation to stay in position without the need of gluing. It is recommended to make full overlap of the two layers. All joints of the Slabs have to be tight butted joints. Smaller weld marks, dents, etc. of an approx max diameter of 50 mm and 10 mm height will be absorbed.
If the deck is undulating, an approved self levelling compound or floor screed will have to be used as first layer; a fire retard-ant PE compound, cement based filler or similar. If a water based floor screed or levelling compound is used, it must be given sufficient time to cure before the floating construction is installed. It is very important to ensure not to encapsulate water/moisture, as this will enhance corrosion and limit the expected life time of the construction.
Min. 2 mm Steel Top Plate
30 mm
30 mm
SeaRox SL 480, 2 layersSteel Deck Plate
The top layer has to be made of minimum one layer of 2 mm steel plate, according to the fire approvals.
Final floor covering has to be decided based upon require-ments for mechanical strength and floor finish.
As flooring solution, this one is a safe solution, in the sense that a SeaRox SL 480 of 200 kg/m3 is very ridged and strong, and combined with a medium thick steel plate this is normally adequate for all normal accommodation load up to 40 kN/m2.
-
71
2) SeaRox SL 436This solution consists of one layer of SeaRox SL 436, 60 mm thickness, covered by minimum 1.5 + 3 mm steel plate. The construction gives in addition to the excellent properties of fire protection, noise reduction and thermal insulation, also reduc-tion of structural noise/vibrations in the steel deck.
SeaRo