rnc155 spec. sheet rev. arnc 155 heat recovery ventilator engineering data thermally conductive,...

1
(HVI certified) Net supply airflow in cfm (L/s) against external static pressure @ 0.1 (25 Pa) 184 (87 L/s) @ 0.2 (50 Pa) 163 (77 L/s) @ 0.3 (75 Pa) 146 (69 L/s) @ 0.4 (100 Pa) 132 (62 L/s) @ 0.5 (125 Pa) 115 (54 L/s) @ 0.6 (150 Pa) 92 (43 L/s) @ 0.7 (175 Pa) 60 (28 L/s) Max. Temperature Recovery 86% 32°F (0°C ) 84% Sensible Effectiveness @ 64 cfm (30 L /s) Sensible Efficiency @ 64 cfm (30 L /s) 32°F (0°C ) 75% Sensible Efficiency @ 64 cfm (30 L/s) -13°F (-25°C ) 72% 120 66 118 1.4 Performance RNC 155 HEAT RECOVERY VENTILATOR ENGINEERING DATA THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The counter-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each airstream has one centrifugal blower driven by a common PSC motor with multiple fan speed operations. FILTERS Washable air filters in exhaust and supply airstreams. MOUNTING THE HRV Threaded inserts at corners of the cabinet designed to accept the “S” hooks and hanging straps supplied with the unit. DEFROST Recirculating damper defrost system. CASE 20 gauge prepainted galvanized steel for superior corrosion resistance, insulated to prevent exterior condensation. Drain connections: Two 1/2 in (12 mm) OD. Balancing ports arelocated on unit. INSTALLER SELECTABLE HIGH SPEED SETTINGS Adjustable DIP switches are located on the circuit board, Hi3 is the factory setting. Refer to the Installation manual for the adjustment instructions. ELECTRONICS The optional controls can be wall mounted in a central location of the home. 3 wire 20 gauge (min.) 100 ft length (max.). CONTROL OPTIONS WEIGHT 71 lbs (32.5 kg) SHIPPING WEIGHT 73 lbs (33.5 kg) External Stac Pressure Airflow in in in in in in in cfm cfm cfm cfm cfm cfm cfm VAC @ 60Hz Was / Low speed Was / High speed Amp rating Sensible Efficiency: Thermal Effecveness: Based on temperature differenal between the 2 airstreams Efficiency: Takes into account all power inputs Airflow (cfm) 20 40 60 80 100 120 140 0 0 0.1 0.2 0.3 0.4 0.5 0.6 1 Low 2 3 160 Static Pressure (in w.g.) 0.7 0.8 180 200 Units carry a lifeme warranty on the HRV core and a 5 year replacement parts warranty. _ _ _ _ _ _ _ _ _ Date: Tag: Qty: Project: Engineer: Contractor: Supplier: Quote #: Submied By: NOTE: All specifications are subject to change without notice. All units conform to CSA and UL standards Side View 18 3/4 in (476 mm) 14 3/4 in (375 mm) Note: Front clearance of 25 in (635 mm) is recommended for servicing unit. All ducts use 6 in (152 mm) connections. Stale Air To Outside Removable Heat Recovery Core Recirculating Defrost Damper Fresh Air From Outside Stale Air From Inside 33 5/8 in (854 mm) Condensate Drain Front View Filter Fresh Air To Inside Motor Blower DIMENSIONS RNC155 ACCESSORY OPTIONS 99-163 Duct Heater w/Electronic SCR Thermostat - 1 kW, 6 in (152 mm) 99-186 Weatherhoods - Two 6 in (152 mm) TIMER OPTIONS 99-DET01 Lifebreath 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or 60 minutes. 99-BC03 Lifebreath Ventilation Control Continuous Low fan speed Humidity control through adjustable Dehumidistat 3 modes of operation: Ventilation, Recirculation, 20/40 Compatible with 99-DET02 Wireless Timers 3 wire connection 99-DXPL02 Lifebreath Digital Control 5 speed operation on each mode Humidity control through adjustable Dehumidistat 5 user selectable operational modes: Continuous Ventilation, Continuous Recirculation, 20 ON/40 OFF, 10 ON/50 OFF, 20 ON/40 Recirculation 20/40/60 min. High speed override button Compatible with 99-DET02 Wireless Timers 3 wire connection 99-BC02 Lifebreath Ventilation Control 2 speed fan setting (Low/High) Humidity control through adjustable Dehumidistat Compatible with 99-DET02 Wireless Timers 3 wire connection between timer and main wall control if timer is out of range. 99-BC04 Lifebreath Ventilation Control 2 speed fan setting (Low/High) 2 modes of operation: Ventilation, 20/40 Compatible with 99-DET02 Wireless Timers 3 wire connection 99-DH01 Lifebreath Dehumidistat Humidity control through adjustable Dehumidistat 3 wire connection 3 wire connecon. 99-DET02 Lifebreath WIRELESS 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or 60 minutes. Wirelessly connects to main control for ease of installation. 40' approximate range. 99-RX02 Lifebreath WIRELESS Repeater - Used to extend range of 99-DET02 Wireless Timers. Plugs into 120V power outlet. Wirelessly connects to main control and 99-DET02. Install at halfway point

Upload: others

Post on 12-Feb-2020

14 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RNC155 Spec. Sheet Rev. ARNC 155 HEAT RECOVERY VENTILATOR ENGINEERING DATA THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The counter-flow heat recovery core transfers heat between

(HVI certified)Net supply airflow in cfm (L /s ) against external s tatic pressure

@ 0.1 (25 P a) 184 (87 L/s)

@ 0.2 (50 P a) 163 (77 L/s)

@ 0.3 (75 P a) 146 (69 L/s)

@ 0.4 (100 P a) 132 (62 L/s)

@ 0.5 (125 P a) 115 (54 L/s)

@ 0.6 (150 P a) 92 (43 L/s)

@ 0.7 (175 P a) 60 (28 L/s)

Max. T emperature R ecovery 86%

32°F (0°C ) 84%Sensible Effectiveness @ 64 cfm (30 L /s)Sensible Efficiency @ 64 cfm (30 L /s) 32°F (0°C ) 75%

Sensible Efficiency@ 64 cfm (30 L /s ) -13°F (-25°C ) 72%

120

66

118

1.4

Performance

RNC 155 HEAT RECOVERY VENTILATOR

ENGINEERING DATA

THERMALLY CONDUCTIVE, PATENTED ALUMINUM COREThe counter-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.MOTORS AND BLOWERSEach airstream has one centrifugal blower driven by a common PSC motor with multiple fan speed operations.FILTERSWashable air filters in exhaust and supply airstreams.MOUNTING THE HRVThreaded inserts at corners of the cabinet designed to accept the “S” hooks and hanging straps supplied with the unit.DEFROSTRecirculating damper defrost system.CASE20 gauge prepainted galvanized steel for superior corrosion resistance, insulated to prevent exterior condensation. Drain connections: Two 1/2 in (12 mm) OD. Balancing ports arelocated on unit.INSTALLER SELECTABLE HIGH SPEED SETTINGSAdjustable DIP switches are located on the circuit board, Hi3 is the factory setting. Refer to the Installation manual for the adjustment instructions.ELECTRONICSThe optional controls can be wall mounted in a central location of the home. 3 wire 20 gauge (min.) 100 ft length (max.).CONTROL OPTIONS

WEIGHT 71 lbs (32.5 kg) SHIPPING WEIGHT 73 lbs (33.5 kg)

External Static Pressure Airflow

in

in

in

in

in

in

in

cfm

cfm

cfm

cfm

cfm

cfm

cfm

VAC @ 60Hz

Watts / L ow speed

Watts / High speed Amp rating

Sensible Efficiency: ThermalEffectiveness: Based on temperature differential between the 2 airstreamsEfficiency: Takes into account all power inputs

Air

flow

(cf

m)

20

40

60

80

100

120

140

00

0.1 0.2 0.3 0.4 0.5 0.6

1

Low

2

3

160

Static Pressure (in w.g.)0.7 0.8

180

200

Units carry a lifetime warranty on the HRV core anda 5 year replacement parts warranty.

_

__

_

_

_

_

_

_

Date:

Tag: Qty:

Project:

Engineer:

Contractor:

Supplier:

Quote #:

Submitted By:

NOTE: All specifications are subject to change without notice.

All units conform to CSA and UL standards

Side View

18 3

/4 in

(476 m

m)

14 3/4 in (375 mm)

Note: Front clearance of 25 in (635 mm) isrecommended for servicing unit. All ducts use 6 in (152 mm) connections.

Stale Air To

Outside

Removable Heat

Recovery Core

Recirculating Defrost Damper

Fresh Air

From Outside Stale Air

From Inside

33 5/8 in (854 mm)

Condensate Drain Front View

Filter

Fresh Air To Inside

Motor

Blower

DIMENSIONS RNC155

ACCESSORY OPTIONS99-163 Duct Heater w/Electronic SCR Thermostat - 1 kW, 6 in (152 mm)99-186 Weatherhoods - Two 6 in (152 mm)

TIMER OPTIONS99-DET01 Lifebreath 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or 60 minutes.

99-BC03 Lifebreath Ventilation Control••

Continuous Low fan speedHumidity control through adjustable Dehumidistat3 modes of operation: Ventilation, Recirculation, 20/40

• Compatible with 99-DET02 Wireless Timers• 3 wire connection

99-DXPL02 Lifebreath Digital Control• 5 speed operation on each mode• Humidity control through adjustable

Dehumidistat• 5 user selectable operational modes: Continuous

Ventilation, Continuous Recirculation, 20 ON/40 OFF, 10 ON/50 OFF, 20 ON/40 Recirculation

• 20/40/60 min. High speed override button• Compatible with 99-DET02 Wireless Timers• 3 wire connection

99-BC02 Lifebreath Ventilation Control• 2 speed fan setting (Low/High)• Humidity control through adjustable

Dehumidistat• Compatible with 99-DET02 Wireless Timers• 3 wire connection

between timer and main wall control if timer is out of range.

99-BC04 Lifebreath Ventilation Control• 2 speed fan setting (Low/High)• 2 modes of operation: Ventilation, 20/40• Compatible with 99-DET02 Wireless

Timers• 3 wire connection

99-DH01 Lifebreath Dehumidistat• Humidity control through adjustable

Dehumidistat• 3 wire connection

3 wire connection.99-DET02 Lifebreath WIRELESS 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or 60

minutes. Wirelessly connects to main control for ease of install ation. 40' approximate range.99-RX02 Lifebreath WIRELESS Repeater - Used to extend range of 99-DET02 Wireless Timers. Plugs into

120V power outlet. Wirelessly connects to main control and 99-DET02. Install at halfway point