Page 1: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

RL Circuit Analysis

Applied to Transformers

with Tap Changers

Zensol Automation Inc

By: Mohamed Boudour, Ing

24/08/2013

Zensol Automation Inc, 514 333 3488

Page 2: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

Contents

� RL circuit theory

� Response of an RL circuit to a voltage transient

� Adding/removing an RL branch from the circuit

� Adding a resistor to circuit

� Applications on OLTCs

Zensol Automation Inc, 514 333 3488

Page 3: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

RL Circuit Theory

� Response of an RL circuit to a voltage transient

Figure 1 : RL circuit with a time constant of 1/20

second

Zensol Automation Inc, 514 333 3488

Page 4: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

RL Circuit Response

� The coil opposes any variation in current

� At t=0s, S1 is closed : the current will increase exponentially to its final

value :

� Where τ is the time constant

� We will be more interested by 5τ : i(5τ)=0.9932V/R

)1()( /τte

R

Vti

−=

Zensol Automation Inc, 514 333 3488

Page 5: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

By reducing Ton, we

will obtain only a part

of the waveform of

i(t)

Figure 2 : results of the simulationZensol Automation Inc, 514 333 3488

Page 6: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

RL test, using the cbv

Exponential shape of

the curent

Voltage accros the

power supplie

Curves shapes, given by CBV-19

Zensol Automation Inc, 514 333 3488

Page 7: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

Effect of opening an RL circuit

Zensol Automation Inc, 514 333 3488

Voltage accros L¨:

Over-voltage

captured by ZVS-300

Over voltage phenomenon: detected by ZVS-300

Page 8: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

Adding or removing an RL

branch from the circuit

Figure 3 : Adding an RL branch to the circuitZensol Automation Inc, 514 333 3488

Page 9: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

� S1 is closed for 500 ms, then is opened and S2 is closed.

� Since the coil has inertia with respect to current, we see the instant

fall of the current, which creates a voltage spike across L.

� The current then increases to its new value, according to the new

time constant: L_total/R_total

Zensol Automation Inc, 514 333 3488

Page 10: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

Adding a resistor only

Figure 4 : Adding or removing a resistor to the RL circuit

Zensol Automation Inc, 514 333 3488

Page 11: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

THERE IS NO SUDDEN CHANGE IN THE CURRENT, SO THERE IS NO

VOLTAGE SPIKE ACROSS THE COIL.

Figure 5 : Effect of adding or removing a resistor from

the circuit

Zensol Automation Inc, 514 333 3488

Page 12: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

Effect of adding an RL branch to the

circuit

An over voltage

when opening the

circuit

Effect of adding an

RL branch

Effect of adding an RL branch to the circuit: Tested

by CBV-19

No Over voltage

when removing an

RL without opening

the circuit

Zensol Automation Inc, 514 333 3488

Page 13: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

Applications to Transformers

with Tap Changers

Zensol Automation Inc, 514 333 3488

Page 14: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

PTCC principle of operation

Zensol Automation Inc, 514 333 3488

Page 15: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

Step 1

i(t) : current flowing in the circuit

H is in position 7

Zensol Automation Inc, 514 333 3488

Page 16: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

Step 2

i(t) : current flowing in the circuit

H has moved from

7 to 5

No change in

current

Zensol Automation Inc, 514 333 3488

Page 17: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

Step 3 : Adding Ry

i(t) : current flowing in the circuit

Zensol Automation Inc, 514 333 3488

Page 18: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

Step 4 : Ry and Ru in parallel

i(t) : current flowing in the circuit

Zensol Automation Inc, 514 333 3488

Page 19: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

Step 5: removing Ry from the circuit

i(t) : current flowing in the circuit

Zensol Automation Inc, 514 333 3488

Page 20: RL Circuit Analysis Applied to Transformers with Tap Changers · capturedby ZVS-300 Over voltage phenomenon: detectedby ZVS-300. Adding or removing an RL branch from the circuit Zensol

Step 6 : removing Ru

i(t) : current flowing in the circuit

Zensol Automation Inc, 514 333 3488