    ELECTRICAL INSTALLATION IN BUILDINGS

    FOR

    RETAIL SERVICE STATIONS

    Engen Petroleum Limited

    Revision 8

    June 2008

  • RETAIL BUILDING ELECTRICAL STANDARD

    Revision 8 June 2008

    This Standard w as compiled for ENGEN Petroleum Ltd: by

    De Villiers & Khan Inc.

    207 Broad Road Medicentre

    Broad Road

    WYNBERG (CAPE) 7800

    South Africa

    Telephone: + 27-21-7620153

    Facsimile: + 27-21-7620169

    Cell: 083-4555787

    e-mail: off [email protected]

    All inquiries about the contents or the applicat ion of this Specif icat ion must be directed

    to the above off ice, for the attention of Willem de Villiers or Yusuf Khan.

    THIS DOCUMENT MAY NOT BE MODIFIED WITHOUT THE PERMISSION OF THE ENGEN

    RETAIL ENGINEERING MANAGER.

    SPECIFIC ATTENTION IS DRAWN TO THE COMMENT REGARDING THE GENERAL

    NATURE OF THE DOCUMENT IN PART 2.

    COPYRIGHT

    The copyright for this standard resides w ith Engen Petroleum Limited or companies

    aff iliated thereto and may not be copied or distributed in any form w ithout the w rit ten

    approval of the Engen Retail Engineering Manager.

  • RETAIL BUILDING ELECTRICAL STANDARD

    Revision 8 June 2008

    CONTENTS

    PART DESCRIPTION

    1.0 GENERAL

    2.0 DESIGN

    3.0 LIGHTING, POWER AND TELEPHONE INSTALLATION

    4.0 CABLE INSTALLATION

    5.0 DISTRIBUTION BOARDS

    6.0 ATTACHMENTS

  • RETAIL BUILDING ELECTRICAL STANDARD

    PART 1:GENERAL

    Revision 8 June 2008

    1

    PART 1

    GENERAL

    1.0 SCOPE

    This specif icat ion covers the supply, installat ion, test ing, commissioning and hand-over

    of the building and site (including the forecourt canopy) electrical, data and

    telecommunication installat ions of ENGEN Petroleum Limited service stat ions. The scope

    of work shall be as follows (Only main items are described, but the contractor shall

    provide all materials, equipment and services to ensure a complete working installat ion):

    Power connection to site and arrangements w ith the supply authority.

    All distribut ion boards, meter panels and data/telephone panels, but excluding the

    forecourt DB-F.(NOTE: The emergency stops, f ire man' s sw itches, photocell and

    exterior light ing (including the under-canopy light ing and signage) on the building are

    part of the Contractor' s responsibility and are connected to DB-F). DB-F and its

    associated circuits external to the building w ill unless otherw ise indicated, be the

    responsibility of the Electrical Contractor w ho is subcontracted to the pump and

    tank contractor.

    The above distribut ion boards include a mini-DB for the automation system DB-AUT

    as indicated on the single line diagrams and located in the automation equipment

    area.

    All connections to signage.

    The surge protect ion elements that are indicated on the draw ings in DB-M and

    connected to the earthing system.

    Power distribut ion cabling and w iring in or on the building, including the connection to

    DB-F.

    Power outlet equipment such as socket outlets and sw itches as well as light ing

    outlets and luminaires internally to the building and on the building but not in or on

    the canopy or feeder section or the site.

    Conduits and sleeves for the Telephone and Data installat ions.

    Cabling for the data installat ion inside the building.

    Earthing for the installat ion as well as lightning protect ion if required. The

    requirements of SANS 10142 must be complied w ith and the automation system

    earthing must be provided as per the draw ings and to the automation suppliers

    approval.

    Sound system where required.

    All checklists and as-built documentation w hich shall include a valid cert if icate of

    compliance in terms of the OHS Act.

    The follow ing is specif ically excluded from the Contractors scope of supply (unless

    specif ied or indicated to the contrary):

    Cabling and connections to the outside light ing, dispensers and submersibles (see

    note above re DB-F).

    UPS equipment.

  • RETAIL BUILDING ELECTRICAL STANDARD

    PART 1:GENERAL

    Revision 8 June 2008

    2

    Signage f it t ings.

    Air condit ioning equipment.

    Appliances such as Freezers, Kitchen equipment.

    Emergency generator for the site w here required.

    2.0 DAMAGE TO OTHER SERVICES

    The Contractor w ill be fully responsible and held accountable for damage to other

    services caused by any person direct ly or indirect ly in his employ.

    Other building services w ill be carried out simultaneously w ith the work for which the

    Contractor w ill be responsible. It shall be required of the Contractor that he w orks in

    close liaison w ith other contractors on the site in order to prevent damage and abort ive

    work.

    3.0 COMPLETION

    At the complet ion of the contract the Contractor shall provide ENGEN w ith a complete

    set of as built documentat ion ref lect ing the f inal state of the electrical installat ion.

    The follow ing shall be included as a minimum:

    Layout draw ings indicat ing all equipment and circuit references.

    Schematic circuit diagrams, show ing colour coding, w ire numbers and terminal

    numbers.

    The test sheets as specif ied.

    A cert if icate of compliance. If there is no design engineer responsible for the specif ic

    site, the installat ion shall be taken to be the design and supply responsibility of the

    contractor who shall make the necessary arrangements to satisfy the section 5.1

    design requirements of the cert if icate of compliance.

    Check lists.

    Technical information of the equipment supplied and maintenance instruct ions.

    The draw ings shall be of good quality for reproducing purposes and tw o paper copies of

    each draw ing shall be provided.

    Two copies of all other documentation shall be provided.

    4.0 STANDARDS AND SPECIFICATIONS

    4.1 All equipment and material used in the electrical installat ion shall have the required

    statutory approval in terms of the OHS Act 85/1993 and shall comply w ith the relevant

    SANS specif icat ions (including but not limited to SANS 10142) and shall bear the SABS

    mark or an alternative acceptable mark scheme such as VDE or BS.

  • RETAIL BUILDING ELECTRICAL STANDARD

    PART 1:GENERAL

    Revision 8 June 2008

    3

    4.2 Equipment and materials shall in all cases be new and be used and installed in

    accordance with the equipment manufacturers recommendations.

    4.3 Equipment and materials purchased by the Contractor whether they bear the SABS mark

    or not, are subject to prior approval by ENGEN.

    4.4 The nature, design, erection and workmanship of the installation shall comply with the

    latest edition of the South African Occupational Health and Safety Act 85/1993 and the

    regulations contained therein and the requirements of this specification and drawings.

    Specif ic reference shall also be made to SANS 10142: Code of Practice for the Wiring of

    Premises. The installat ion shall also comply fully w ith the requirements of the local

    authorit ies of the region or the country in w hich the work is undertaken.

    4.5 Workmanship shall be of a high standard, and qualif ied staff under proper supervision of

    competent and experienced supervisors shall carry out the w ork.

    4.6 Where any details regarding method, workmanship and materials are not clear the matter

    shall be referred to the equipment supplier and ENGEN for clarif icat ion.

    5.0 POWER SUPPLY

    5.1 Unless otherw ise stated the electrical system w ill be nominally 400/230 volt , 3 phase, 4

    w ire, 50 Hz alternating current, rated as per Part 2.

    5.2 Variat ions in supply voltage w ill be generally be in the range of 85% to 110% of nominal

    and all equipment shall be suitable for operation at any voltage w ithin this range, as well

    as w ith the surges and interruptions associated w ith the national netw ork and that

    caused by standby generating plant. Care shall be taken to ensure that the installat ion is

    suitable for local voltage and frequency variat ions that fall outside the above range. The

    contractor shall make sure that he is fully conversant w ith such local condit ions.

    5.3 The installat ion shall be suitable for a standby generator if so indicated on the draw ings.

    The generator shall provide power to the system w hen the mains voltage falls outside the

    allowable pre-set range described in 5.2 above

  • RETAIL BUILDING ELECTRICAL STANDARD

    PART 2: DESIGN

    Revision 8 June 2008

    1

    PART 2

    DESIGN

    1.0 GENERAL

    This Part defines guidelines w ith regard to specif ic service stat ion related requirements

    that shall be incorporated in the service stat ion electrical installat ion.

    The information provided in this document and on typical draw ings shall be adapted t o

    suit the requirements of the specif ic installat ion. Where specif ic project related

    information is not provided the contractor shall interpret the requirements of this

    document and apply the same to provide a ' design and build' installat ion. In such cases

    The Retail Engineering Manager' s approval shall be obtained fo