resource offer commitment parameters structured market trials august 23, 2013 gay anthony spp market...
TRANSCRIPT
Resource Offer Commitment Parameters
Structured Market Trials August 23, 2013
Gay AnthonySPP Market Design
Resource Offer Commitment Parameters• What are the Parameters?
• How are they used in SMT?
• Parameter Relationships
• How the Parameters are used for Commitment
• Examples
2Gay Anthony
Resource Offer Commitment ParametersWhat are the Parameters?•Time-Related Parameters for Resource Commitment
• Minimum Run Time
• Maximum Run Time
• Minimum Down Time
• Min-To-Off Time
• Sync-To-Min Time
• Hot-to-Cold Time
• Hot-to-Intermediate Time
3Gay Anthony
Commitment Reminders• DA Market, DA RUC, and ID RUC processes use the Current
Operating Plan (COP) for determining if a Resource has satisfied submitted “Commitment Parameters”
• Commit Times are communicated as “Start” or “Stop” notifications • Indicates when SPP expects the resource to be at minimum
• PLEASE NOTE: During SMT, the COP True-Up process is performed after DA RUC and run every two hours throughout an OD• DA Market will be affected by EIS Market commitments
• Example: Resource with Max Run Time of 24 hours but shows as online for a week due COP True Up
» DA Market will decommit the resource
4Gay Anthony
Resource Offer Commitment Parameters
5
Markets User Interface
Gay Anthony
Resource Offer Commitment Parameters
6
Parameter Relationships
Commit Time
De-Commit TimeMinimum
Run Time
Min-To-Off Time
Minimum Down Time
Commit Time
Sync-To Min Time
Start-up order issued by SPP
Hot-to-Cold Time
Hot-to-Intermediate Time
Commit Time
Commit Time Maximum
Run Time
Gay Anthony
Resource Offer Commitment Parameters
7
Minimum Run Time• A Resource’s physical min run time begins when the resource is
synchronized and is the amount of time a resource must remain synchronized. (Sync to Off)
• The MP’s submitted Min Run Time used by the Market should be the physical min run time minus the Sync-to-Min time and Min-to-Off time
• SCUC does NOT consider Sync-to-Min and Min-to-Off when evaluating Min Run Time for commitment purposes
Gay Anthony
Resource Offer Commitment Parameters
8
Maximum Run Time• A Resource’s physical max run time begins when the resource is
synchronized but has a limit for how long it can remain synchronized. (Sync to Off)
• The MP’s submitted Max Run Time used by the market should be the physical max run time minus the Sync-to-Min time and Min-to-Off time
• SCUC does NOT consider Sync-to-Min and Min-to-Off when evaluating Max Run Time for commitment purposes
Gay Anthony
Resource Offer Commitment Parameters
9
Minimum Down Time• A resource’s physical min down time begins when the resource is
de-synchronized and ends when the resource is physically able to synchronize again. • The MP’s submitted Min Down Time used by the market should be the physical • min down time of the resource. (completely offline)
• SCUC automatically adds Sync-to-Min and Min-to-Off time to the value entered for Min Down Time• This sum represents the “effective” Min Down Time, which is
evaluated by SCUC for commitment purposes
Gay Anthony
Example
Resource Offer Commitment Parameters
10
Resource Aphysical min run time: 5 hoursphysical max run time: 10 hoursphysical min down time: 3 hoursSync-to-Min Time: 1 hourMin-to-Off Time: 15 minutes
Gay Anthony
Example
Resource Offer Commitment Parameters
11
Resource Aphysical min run time: 5 hoursphysical max run time: 10 hoursphysical min down time: 3 hoursSync-to-Min Time: 1 hourMin-to-Off Time: 15 minutes
Markets UI – Resource A (MP-submitted)
Min Run Time - 3:45Max Run Time - 8:45Min Down Time - 1:45Sync-to-Min Time - 1:00Min-to-Off Time - :15
Gay Anthony
Resource Offer Commitment ParametersStart-Up Parameters
•In the Start-Up Offer, MPs submit a hot, intermediate and cold start-up price
•In the Resource Offer, MPs submit two time-related parameters:• Hot-to-Cold Time
• Hot-to-Intermediate Time
•These parameters are used to determine which start-up price is applied
12Gay Anthony
Resource Offer Commitment Parameters• Hot-to-Cold Time
• A resource’s physical hot-to-cold Time begins when the resource is de-synchronized and represents the amount of time required before the next synchronization after which a cold start-up offer will apply.
• The MP-submitted Hot-to-Cold Time should be equal to the sum of the physical hot-to-cold time, the Sync-To-Min Time and the Min-To-Off Time
• No programmatic summing of parameters is performed in determining start-up times for applying start-up price
13
Gay Anthony
Resource Offer Commitment Parameters• Hot-to-Intermediate Time
• A resource’s physical hot-to-intermediate Time begins when the resource is de-synchronized and represents the amount of time required before the next synchronization after which an intermediate start-up offer will apply.
• The MP-submitted Hot-to-Intermediate Time should be equal to the sum of the physical Hot-To-Intermediate time, the Sync-To-Min Time and the Min-To-Off Time
• No programmatic summing of parameters is performed in determining start-up times for applying start-up price
14
Gay Anthony
Hot-To-Cold Time Example
If the Resource’s De-Commit Time is 10:00 AM, the Cold Start-Up Offer price would apply for Resource commitments after 8:00 PM.
Resource Offer Commitment Parameters
15
Resource Aphysical hot-to-cold time: 8 hoursSync-to-Min Time: 1 hourMin-to-Off Time: 1 hour
Markets UI – Resource A (MP-submitted)Hot-to-Cold Start-Up Time: 10 hours
Gay Anthony
Hot-To-Intermediate Time Example
If the Resource’s De-Commit Time is 10:00 AM, the Intermediate Start-Up Offer price would apply for Resource commitments between 4:00 PM and 8:00 PM. The Hot Start-Up Offer price would apply for Resource commitments prior to 4:00PM.
Resource Offer Commitment Parameters
16
Resource Aphysical hot-to-intermediate time: 4 hoursSync-to-Min Time: 1 hourMin-to-Off Time: 1 hour
Markets UI – Resource A (MP-submitted)Hot-to-Intermediate Time: 6 hours
Gay Anthony
Resource Offer Commitment ParametersSummary•The MP’s submitted Min Run Time should be the Resource’s physical min run time minus the Sync-to-Min time and Min-to-Off time
•The MP’s submitted Max Run Time should be the Resource’s physical max run time minus the Sync-to-Min time and Min-to-Off time
•The MP’s submitted Min Down Time should be equal to the physical min down time.
•The MP’s submitted time-related start-up parameters should be equal to the physical start-up time plus Sync-to-Min and Min-to-Off Time.
• These parameters are used to determine which Start-Up price to use
17Gay Anthony