residential plan review

11
RESIDENTIAL PLAN REVIEW MAY 8 th DOHERTY INN CLARE, MICHIGAN

Upload: tanner

Post on 11-Jan-2016

46 views

Category:

Documents


0 download

DESCRIPTION

RESIDENTIAL PLAN REVIEW. MAY 8 th DOHERTY INN CLARE, MICHIGAN. MISCONCEPTION:. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: RESIDENTIAL PLAN REVIEW

RESIDENTIAL PLAN REVIEW

MAY 8th

DOHERTY INN

CLARE, MICHIGAN

Page 2: RESIDENTIAL PLAN REVIEW

MISCONCEPTION:

• Construction documents are not required for the following: 1. One-and two-family dwellings when the heating system input rating is 375,000 Btu’s or less. 2. When alterations and repair work are determined by the mechanical official to be of a minor nature. 3. Business, mercantile and storage buildings having HVAC equipment only, with one fire area and not more than 3,500 square feet. 4. Work completed by a governmental subdivision or state agency costing less than $15,000.

Page 3: RESIDENTIAL PLAN REVIEW

LAWSUIT WAS AGAINST BCC

• A lawsuit was filed in Ingham County Circuit Court against the Bureau and other State defendants over the threshold requirement imposed for the submission of plans. Discussions between the parties led to a settlement of the lawsuit and modifications in the threshold requirement. The new provision includes a base line in Btu input rating of mechanical heating equipment, rather than building size. This new criteria provides a better representation of the complexity of the heating system, based on equipment size rather than building area. This new development provides for a threshold of more than 375,000 Btu input rating before plans would be required for one-and two-family dwellings

Page 4: RESIDENTIAL PLAN REVIEW

If you copy BCC mechanical permit application this automatically happens:

• The Bureau of Construction Codes has established, based on the requirements of section 106.3.1 of the Code and the State Construction Code Act, a threshold for one- and two- family dwellings at 3,500 square feet in area. This threshold has been in place for

several years. • Permit applications used by the Bureau will

reflect this modification as follows:

Page 5: RESIDENTIAL PLAN REVIEW

So what does the code say?• M1401.3 Sizing. Heating and cooling equipment

shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies.

Page 6: RESIDENTIAL PLAN REVIEW

DUCT DESIGN FOR RESIDENTIAL

• M1601.1 Duct design. Duct systems serving heating, cooling and ventilation equipment shall be fabricated in accordance with the provisions of this section and ACCA Manual D or other approved methods.

Page 7: RESIDENTIAL PLAN REVIEW

DEVIL’S ADVOCATE

• So let’s say you abide by State parameter.• So section M1403.1 & M1603.1 does not apply?• So we can undersize duct & oversize or undersize

HVAC equipment? • The only thing the statement says no plans are

required to obtain a permit.• What happens when you get on a job you find

some serious design problems?

Page 8: RESIDENTIAL PLAN REVIEW

What do look for in a residential plan review? Manual “J”

• Perform a room by room heat gain and heat loss calculated for each space based upon its orientation, exposed surfaces and building assembly U-values, appliance loads, occupancy, ventilation requirements, duct loss, and the activity and function of the room.

Page 9: RESIDENTIAL PLAN REVIEW
Page 10: RESIDENTIAL PLAN REVIEW
Page 11: RESIDENTIAL PLAN REVIEW

On line calculator

• http://www.loadcalc.net/