SupplyNet June 2010 ® Flow lpm/gpm 75 (5.2) K-factor VK466, Part No. 13781 Tech Data Page Sprinkler 141j Room Size m/ft 3.7 x 3.7 (12 x 12) 34 (9.0) 0.58 (8.4) N/A N/A 4.3 x 4.3 (14 x 14) 38 (10.0) 0.72 (10.4) N/A N/A 3.7 x 3.7 (12 x 12) 45 (12.0) 0.54 (7.8) 68 (18.0) 1.21 (17.5) 4.3 x 4.3 (14 x 14) 49 (13.0) 0.63 (9.1) 68 (18.0) 1.21 (17.5) 4.9 x 4.9 (16 x 16) 49 (13.0) 0.63 (9.1) 68 (18.0) 1.21 (17.5) 5.5 x 5.5 (18 x 18) 64 (17.0) 1.08 (15.6) N/A N/A 6.1 x 6.1 (20 x 20) 80 (21.0) 1.64 (23.9) N/A N/A

TRANSCRIPT

Page 1: Residential CPVC Catalogue June 2010_UK

SupplyNet®

Residential Sprinkler Systems

June 2010

Page 2: Residential CPVC Catalogue June 2010_UK

Pendent and Recessed Pendent SprinklersAvailable in 68°C and 79°C; Recessed Adjustment up to 16mm (5/8”)

45 (3.1) K-factor

3.7 x 3.7 (12 x 12) 34 (9.0) 0.58 (8.4) N/A N/A

4.3 x 4.3 (14 x 14) 38 (10.0) 0.72 (10.4) N/A N/A

3.7 x 3.7 (12 x 12) 53 (14.0) 0.50 (7.2) 76 (20.0) 1.02 (14.8)

4.3 x 4.3 (14 x 14) 53 (14.0) 0.50 (7.2) 76 (20.0) 1.02 (14.8)

4.9 x 4.9 (16 x 16) 53 (14.0) 0.50 (7.2) 76 (20.0) 1.02 (14.8)

5.5 x 5.5 (18 x 18) 64 (17.0) 0.74 (10.7) 761 (20.0) 1.02 (14.8)

6.1 x 6.1 (20 x 20) 76 (20.0) 1.02 (14.8) 761 (20.0) 1.02 (14.8)1 Flows shown for 68°C (155°F); 79°C (175°F).

3.7 x 3.7 (12 x 12) 61 (16.0) 0.58 (8.5) 80 (21.0) 1.01 (14.6)

4.3 x 4.3 (14 x 14) 72 (19.0) 0.82 (11.9) 80 (21.0) 1.01 (14.6)

4.9 x 4.9 (16 x 16) 72 (19.0) 0.82 (11.9) 80 (21.0) 1.01 (14.6)

5.5 x 5.5 (18 x 18) 80 (21.0) 1.01 (14.6) 83 (22.0) 1.10 (16.0)

6.1 x 6.1 (20 x 20) 91 (24.0) 1.31 (19.0) 106 (28.0) 1.79 (25.9)

3.7 x 3.7 (12 x 12) 45 (12.0) 0.54 (7.8) 68 (18.0) 1.21 (17.5)

4.3 x 4.3 (14 x 14) 49 (13.0) 0.63 (9.1) 68 (18.0) 1.21 (17.5)

4.9 x 4.9 (16 x 16) 49 (13.0) 0.63 (9.1) 68 (18.0) 1.21 (17.5)

5.5 x 5.5 (18 x 18) 64 (17.0) 1.08 (15.6) N/A N/A

6.1 x 6.1 (20 x 20) 80 (21.0) 1.64 (23.9) N/A N/A

VK435, Part No. 13203Tech Data Page Sprinkler 140e

• Lowest listed flows 75.7 lpm (20 gpm)• Can optimize NFPA 13 residential designs when combined with larger K factor residential sprinklers.

62 (4.3) K-factor VK430, Part No. 09530Tech Data Page Sprinkler 140a

• Continually listed by UL since 1995

71 (4.9) K-factor VK468, Part No. 13637Tech Data Page Sprinkler 149m• Listed with beam ceilings up to 6.1m x 6.1m (20”)

75 (5.2) K-factor VK466, Part No. 13781Tech Data Page Sprinkler 141j

• Listed with beam ceilings up to 6.1m x 6.1m (20”)

79 (5.5) K-factor VK432, Part No. 10050Tech Data Page Sprinkler 141a

• Continually listed by UL since 1997

107 (7.4) K-factor VK458, Part No. 13230Tech Data Page Sprinkler 140w

• Larger K-Factor provides lowest starting pressure in NFPA 13 applications (0.1 density)

3.7 x 3.7 (12 x 12) 49 (13.0) 0.48 (7.0) 80 (21.0) 1.27 (18.4)

4.3 x 4.3 (14 x 14) 49 (13.0) 0.48 (7.0) 80 (21.0) 1.27 (18.4)

4.9 x 4.9 (16 x 16) 49 (13.0) 0.48 (7.0) 80 (21.0) 1.27 (18.4)

5.5 x 5.5 (18 x 18) 64 (17.0) 0.83 (12.0) 80 (21.0) 1.27 (18.4)

6.1 x 6.1 (20 x 20) 76 (20.0) 1.15 (16.7) 80 (21.0) 1.27 (18.4)

3.7 x 3.7 (12 x 12) 76 (20.0) 0.50 (7.3) 761 (20.0) 0.50 (7.3)

4.3 x 4.3 (14 x 14) 76 (20.0) 0.50 (7.3) 761 (20.0) 0.50 (7.3)

4.9 x 4.9 (16 x 16) 76 (20.0) 0.50 (7.3) 761 (20.0) 0.50 (7.3)

5.5 x 5.5 (18 x 18) 83 (22.0) 0.61 (8.8) 871 (23.0) 0.67 (9.7)

6.1 x 6.1 (20 x 20) 91 (24.0) 0.73 (10.5) 911 (24.0) 0.73 (10.5)1 Flows shown for 68°C (155°F); see data page for flows at 79°C (175°F).

Room Sizem/ft

Horizontal Ceiling Sloped Ceiling 33.7°Flow

lpm/gpmPressurebar/psi

Flowlpm/gpm

Pressurebar/psi

June 2010www.vikinggroupinc.com

Residential Sprinkler Range

3.7 x 3.7 (12 x 12) 61 (16.0) 0.52 (7.6)

4.3 x 4.3 (14 x 14) 61 (16.0) 0.52 (7.6)

4.9 x 4.9 (16 x 16) 61 (16.0) 0.52 (7.6)

5.5 x 5.5 (18 x 18) 64 (17.0) 0.59 (8.6)

6.1 x 6.1 (20 x 20) 80 (21.0) 0.90 (13.1)

84 (5.8) K-factor VK472, Part No. 16130Tech Data Page Sprinkler 148o

• Larger K-Factor provides lowest starting pressure in NFPA 13 applications (0.1 density)

Page 3: Residential CPVC Catalogue June 2010_UK

Flat Plate Concealed Pendent SprinklersCover Plate Temp = 57°C (135°F); Adjustment up to 15mm (1/2”)

Room Sizem/ft

Slope up to 9.5° (2/12) Slope up to 33.7° (8/12)Flow

lpm/gpmPressurebar/psi

Flowlpm/gpm

Pressurebar/psi

75 (5.2) K-factor VK466, Part No. 13781A-XTech Data Page Sprinkler 141r-w

• Sprinkler Temp = 68°C (155°F), unless otherwise noted

3.7 x 3.7 (12 x 12) 53 (14) 0.50 (7.2) 87 (23) 1.35 (19.6)

4.3 x 4.3 (14 x 14) 53 (14) 0.50 (7.2) 87 (23) 1.35 (19.6)

4.9 x 4.9 (16 x 16) 53 (14) 0.50 (7.2) 87 (23) 1.35 (19.6)

5.5 x 5.5 (18 x 18) 64 (17) 0.74 (10.7) 87 (23) 1.35 (19.6)

6.1 x 6.1 (20 x 20) 76 (20) 1.02 (14.8) 87 (23) 1.35 (19.6)

VK458, Part No. 13230ABX, 12207Tech Data Page Sprinkler 140q

• Sprinkler Temp = 68°C (155°F)• Larger K-Factor provides lowest starting pressure in NFPA 13 applications (0.1 density)

107 (7.4) K-factor 3.7 x 3.7 (12 x 12) 76 (20) 0.50 (7.3) 83 (22) 0.61 (8.8)

4.3 x 4.3 (14 x 14) 76 (20) 0.50 (7.3) 83 (22) 0.61 (8.8)

4.9 x 4.9 (16 x 16) 76 (20) 0.50 (7.3) 83 (22) 0.61 (8.8)

5.5 x 5.5 (18 x 18) 87 (23) 0.67 (9.7) 106 (28) 0.99 (14.3)

6.1 x 6.1 (20 x 20) 106 (28) 0.99 (14.3) 106 (28) 0.99 (14.3)

VK457, Part No. 14694ATech Data Page Sprinkler 147v

• Sprinkler Temp = 74°C (165°F)• Available with either standard, large or square cover plate

71 (4.9) K-factor 3.7 x 3.7 (12 x 12) 49 (13) 0.48 (7.0) 107 (26) 1.94 (28.2)

4.3 x 4.3 (14 x 14) 49 (13) 0.48 (7.0) 107 (26) 1.94 (28.2)

4.9 x 4.9 (16 x 16) 49 (13) 0.48 (7.0) 107 (26) 1.94 (28.2)

5.5 x 5.5 (18 x 18) 64 (17) 0.83 (12.0) 117 (31) 2.76 (40.0)

6.1 x 6.1 (20 x 20) 76 (20) 1.15 (16.7) 117 (31) 2.76 (40.0)

Domed Concealed Pendent SprinklersCover Plate Temp = 57°C (135°F); Adjustment up to 15mm (1/2”)

VK468, Part No. 13637A-X, 12207Tech Data Page Sprinkler 149q

• Sprinkler Temp = 68°C (155°F) and 79°C (175°F)

71 (4.9) K-factor 3.7 x 3.7 (12 x 12) 49 (13) 0.48 (7.0) 981 (26) 1.94 (28.2)

4.3 x 4.3 (14 x 14) 49 (13) 0.48 (7.0) 981 (26) 1.94 (28.2)

4.9 x 4.9 (16 x 16) 49 (13) 0.48 (7.0) 981 (26) 1.94 (28.2)

5.5 x 5.5 (18 x 18) 64 (17) 0.83 (12.0) 981 (26) 1.94 (28.2)

6.1 x 6.1 (20 x 20) 77 (20) 1.15 (16.7) 981 (26) 1.94 (28.2)1 Sloped ceiling listing for 68°C (155°F) only.

VK456, Part No. 13620A, 13750Tech Data Page Sprinkler 147e

• Sprinkler Temp = 60°C (140°F)

71 (4.9) K-factor 3.7 x 3.7 (12 x 12) 49 (13) 0.48 (7.0) 64 (17) 0.83 (12.0)

4.3 x 4.3 (14 x 14) 49 (13) 0.48 (7.0) 64 (17) 0.83 (12.0)

4.9 x 4.9 (16 x 16) 53 (14) 0.56 (8.2) 64 (17) 0.83 (12.0)

5.5 x 5.5 (18 x 18) 64 (17) 0.83 (12.0) 98 (26) 1.94 (28.2)

6.1 x 6.1 (20 x 20) 87 (23) 1.52 (22.0) 98 (26) 1.94 (28.2)

June 2010 www.vikinggroupinc.com

VK474, Part No. 15709ATech Data Page Sprinkler 148h

• Sprinkler Temp = 74°C (165°F)• Available with either standard, large or square cover plate

84 (5.8) K-factor 3.7 x 3.7 (12 x 12) 61 (16) 0.52 (7.6) N/A N/A

4.3 x 4.3 (14 x 14) 61 (16) 0.52 (7.6) N/A N/A

4.9 x 4.9 (16 x 16) 61 (16) 0.52 (7.6) N/A N/A

5.5 x 5.5 (18 x 18) 72 (19) 0.74 (10.7) N/A N/A

6.1 x 6.1 (20 x 20) 87 (23) 1.10 (15.7) N/A N/A

71 (4.9) K-factor VK476, Part No. 15630Tech Data Page Sprinkler 145h

3.7 x 3.7 (12 x 12) 49 (13) 0.48 (7.6) 91 (24) 1.65 (24)

4.3 x 4.3 (14 x 14) 49 (13) 0.48 (7.6) 91 (24) 1.65 (24)

4.9 x 4.9 (16 x 16) 49 (13) 0.48 (7.6) 91 (24) 1.65 (24)

5.5 x 5.5 (18 x 18) 64 (17) 0.83 (12) 91 (24) 1.65 (24)

6.1 x 6.1 (20 x 20) 80 (21) 1.27 (18.4) 91 (24) 1.65 (24)

Room Sizem/ft

Slope up to 9.5° (2/12) Slope up to 18.4° (4/12)

Flowlpm/gpm

Pressurebar/psi

Flowlpm/gpm

Pressurebar/psi

Flush Pendent SprinklersAvailable in 74°C (165°F); Vertical Adjustment up to 16mm (5/8”)

• Sprinkler Temp = 74°C (165°F)• Listed for ceilings with beams up to 35,6 cm (14”) in depth. See datasheet for complete design and installation guidelines.• Sprinkler and outer ring sold together

Page 4: Residential CPVC Catalogue June 2010_UK

58 (4.0) K-factor

60 (4.2) K-factor

VK453, Part No. 13389Tech Data Page Sprinkler 143w

• Patent-pending “flow shaper” design provides the ultimate combination of low flows and starting pressures

VK450, Part No. 12357Tech Data Page Sprinkler 143j

• Unique offset orifice design (patent pending)• Only residential horizontal sidewall to offer a 6.7m (22’) throw

Down the slope up to 9.5° (2/12)

3.7 x 3.7 (12 x 12) 42 (11) 0.52 (7.6) 46 (12) 0.62 (9.0)

4.3 x 4.3 (14 x 14) 46 (12) 0.62 (9.0) 49 (13) 0.73 (10.6)

4.9 x 4.9 (16 x 16) 61 (16) 1.10 (16.0) 61 (16) 1.10 (16.0)

4.9 x 5.5 (16 x 18) 61 (16) 1.10 (16.0) 641 (17) 1.25 (18.1)

4.9 x 6.1 (16 x 20) 87 (23) 2.28 (33.1) 91 (24) 2.48 (36.0)

4.9 x 6.7 (18 x 18) 72 (19) 1.56 (22.6) 72 (19) 1.56 (22.6)

5.5 x 6.1 (18 x 20) 92 (24) 2.48 (36.0) 91 (24) 2.48 (36.0)1 Flows shown for 68°C (155°F); 79°C (175°F) available at 68.1 (18.0) / 1.39 (20.3).

Down the slope up to 9.5° (2/12)

3.7 x 3.7 (12 x 12) 45 (12) 0.56 (8.2) 76 (20) 1.56 (22.7)

4.3 x 4.3 (14 x 14) 53 (14) 0.77 (11.1) 76 (20) 1.56 (22.7)

4.9 x 4.9 (16 x 16) 68 (18) 1.27 (18.4) 76 (20) 1.56 (22.7)

4.9 x 5.5 (16 x 18) 68 (18) 1.27 (18.4) 76 (20) 1.56 (22.7)

4.9 x 6.1 (16 x 20) 83 (22) 1.89 (27.4) 95 (25) 2.44 (35.4)4.9 x 6.71 (16 x 22) 98 (26) 2.64 (38.3) N/A N/A

1 Sprinkler available in 68°C (155°F) only and is surface mounted only.

Across the slope up to 18.4° (4/12)

3.7 x 3.7 (12 x 12) 68 (18) 1.27 (18.4) 76 (20) 1.56 (22.7)

4.3 x 4.3 (14 x 14) 68 (18) 1.27 (18.4) 76 (20) 1.56 (22.7)

4.9 x 4.9 (16 x 16) 68 (18) 1.27 (18.4) 76 (20) 1.56 (22.7)

Horizontal Sidewall and Recessed Horizontal Sidewall SprinklersAvailable in 68°C (155°F) and 79°C (175°F); Recessed Adjustment up to 16mm (5/8”)

June 2010www.vikinggroupinc.com

58 (4.0) K-factor VK452, Part No. 13140Tech Data Page Sprinkler 143g

• Patent-pending “flow shaper” design provides the ultimate combination of low flows and starting pressures

Room Sizem/ft

102-152mm down from ceiling 152-305m down from ceiling

Flowlpm/gpm

Pressurebar/psi

Flowlpm/gpm

Pressurebar/psi

Down the slope up to 9.5° (2/12)

3.7 x 3.7 (12 x 12) 42 (11) 0.52 (7.6) 46 (12) 0.62 (9.0)

4.3 x 4.3 (14 x 14) 46 (12) 0.62 (9.0) 50 (13) 0.73 (10.6)

4.9 x 4.9 (16 x 16) 57 (15) 0.97 (14.0) 57 (14) 0.97 (14.0)1 Flows shown for 68°C (155°F); 79°C (175°F) available at 68.1 (18.0) / 1.39 (20.3).

Down the slope up to 33.7° (8/12)

3.7 x 3.7 (12 x 12) 45 (12) 0.56 (8.2) 76 (20) 1.56 (22.7)

4.3 x 4.3 (14 x 14) 53 (14) 0.77 (11.1) 76 (20) 1.56 (22.7)

4.9 x 4.9 (16 x 16) 68 (18) 1.27 (18.4) 76 (20) 1.56 (22.7)

4.9 x 5.5 (16 x 18) 68 (18) 1.27 (18.4) 76 (20) 1.56 (22.7)

4.9 x 6.1 (16 x 20) 83 (22) 1.89 (27.4) 95 (25) 2.44 (35.4)1 Sprinkler available in 68°C (155°F) only and is surface mounted only.

62 (4.3) K-factor VK440, Part No. 09787Tech Data Page Sprinkler 142d

Down the slope up to 9.5° (2/12)

3.7 x 3.7 (12 x 12) 72 (19) 1.35 (19.5) N/A N/A

4.3 x 4.3 (14 x 14) 80 (21) 1.64 (23.9) N/A N/A

Down the slope up to 33.7° (8/12)

3.7 x 3.7 (12 x 12) 72 (19) 1.35 (19.5) N/A N/A

58 (4.0) K-factor VK480, Part No. 16116ACTech Data Page Sprinkler 153a

3.7 x 3.7 (12 x 12) 421 (11) 0.52 (7.6) 462 (12) 0.62 (9)

4.3 x 4.3 (14 x 14) 491 (13) 0.73 (10.6) 532 (14) 0.84 (12.3)

4.9 x 4.9 (16 x 16) 611 (16) 1.10 (16.0) 612 (16) 1.10 (16)

5.5 x 5.5 (18 x 18) 641 (17) 1.25 (18.1) 682 (18) 1.40 (20.3)1 Centreline of sprinkler located 4-3/8” to 6-3/8” below the ceiling.2 Centreline of sprinkler located 6-3/8” to 12-3/8” below the ceiling.

Room Sizem/ft

102-152mm down from ceiling 152-305m down from ceiling

Flowlpm/gpm

Pressurebar/psi

Flowlpm/gpm

Pressurebar/psi

Flat Plate Concealed HSW SprinklersCover Plate Temperature = 57°C (135°F)

• Sprinkler Temp = 74°C (165°F)• Uses large cover plate (3-5/16” diameter, p/n 16207

Page 5: Residential CPVC Catalogue June 2010_UK

Horizontal Sidewall and Recessed Horizontal Sidewall Sprinklers (continued)Available in 68°C (155°F) and 79°C (175°F); Recessed Adjustment up to 16mm (5/8”)

79 (5.5) K-factor VK442, Part No. 12119Tech Data Page Sprinkler 146a

3.7 x 3.7 (12 x 12) 80 (21) 1.01 (14.6) 80 (21) 1.01 (14.6)

4.3 x 4.3 (14 x 14) 83 (22) 1.01 (14.6) 83 (22) 1.10 (16.0)

4.9 x 4.9 (16 x 16) 91 (24) 1.31 (19.0) N/A N/A

4.9 x 5.5 (16 x 18) 102 (27) 1.66 (24.1) N/A N/A

Room Sizem/ft

102-152mm down from ceiling 102-305m down from ceiling

Flowlpm/gpm

Pressurebar/psi

Flowlpm/gpm

Pressurebar/psi

Down the slope up to 9.5° (2/12)

84 (5.8) K-factor VK460, Part No. 13933Tech Data Page Sprinkler 152d

• Patent-pending “flow shaper” design provides the ultimate combination of low flows and starting pressures• Larger K-Factor provides lowest starting pressure in NFPA 13 applications (0.1 density)

Room Sizem/ft

102-152mm down from ceiling 102-305m down from ceiling

Flowlpm/gpm

Pressurebar/psi

Flowlpm/gpm

Pressurebar/psi

Down the slope up to 9.5° (2/12)

3.7 x 3.7 (12 x 12) 61 (16) 0.52 (7.6) 61 (16) 0.52 (7.6)

4.3 x 4.3 (14 x 14) 61 (16) 0.52 (7.6) 68 (18) 0.67 (9.7)

4.9 x 4.9 (16 x 16) 76 (20) 0.82 (11.9) 91 (24) 1.27 (18.4)

4.9 x 5.5 (16 x 18) 83 (22) 0.99 (14.4) 102 (27) 1.49 (21.7)

4.9 x 6.1 (16 x 20) 98 (26) 1.39 (20.1) 121 (32) 2.10 (30.4)

4.9 x 6.71 (16 x 22) 117 (31) 1.97 (28.6) 140 (37) 2.81 (40.7)

5.5 x 5.5 (18 x 18) 87 (23) 1.10 (15.7) 110 (29) 1.70 (25.0)

5.5 x 6.1 (18 x 20) 110 (29) 1.70 (25.0) 133 (35) 2.51 (36.4)

6.1 x 6.1 (20 x 20) 114 (30) 1.80 (26.8) 136 (36) 2.66 (38.5)

4.9 x 7.3 (16 x 24) 144 (38) 2.96 (42.9) 159 (42) 3.62 (52.4)

4.3 x 7.9 (14 x 26) 159 (42) 3.62 (52.4) 174 (46) 4.34 (62.9)1 Flows shown for 68°C (155°F); 79°C (175°F).

Down the slope up to 33.7° (8/12)

3.7 x 3.7 (12 x 12) 80 (21) 1.01 (14.6) N/A N/A

4.3 x 4.3 (14 x 14) 83 (22) 1.01 (14.6) N/A N/A

4.9 x 4.9 (16 x 16) 91 (24) 1.31 (19.0) N/A N/A

4.9 x 5.5 (16 x 18) 106 (28) 1.79 (25.9) N/A N/A

www.vikinggroupinc.comJune 2010

Installation & Removal Tools

Mirage® Concealed Cover Installer Tool. Enables the installation of a flat concealed cover plate from the floor without the need to use a ladder. Two sizes available p/n 14412 regular diameter, p/n 14867 large diameter.

Escutcheon Installer Tool Designed to install Viking Model E-1 Recessed and F-1 Adjustable Escutcheons from the floor without the need for a ladder, p/n 15166

Cabinet Wrench & Sprinkler Cap Removal Tool Designed to install Viking Concealed Residential Sprinklers VK456, VK457 & VK474 from floor without the need for a ladder. Optional for the removal of Sprinkler Caps, p/n 13619

Installation tools and a length of CPVC pipe (all sold separately)

Page 6: Residential CPVC Catalogue June 2010_UK

E-1 Slip-On (Part No. 11123, 06419A, 06420AE-2 Threaded (Part No. 11038, 11625F-2 Adjustable (Part No. 06911A, 06912A)(Refer to sprinkler datasheet for approved escutcheons)

•••

G-1 Sloped (p/n 14315), Slip-OnThe Model G-1 Recessed Escutcheon allows horizontal sidewall sprinklers to be recessedup to 12.7 mm (½”) for sloped ceiling applications with ceilings sloped up to a maximum of 33.7° (8/12)

Recessed and Sloped Ceiling EscutcheonsTech Data Page Sprinkler 135a

White Ivory BlackBrushed Brass

Brushed Copper Brushed Chrome Polished ChromeBright BrassAntique Brass

Flat Cover Plate FinishesResidential flat cover plates are available in nine standard finishes.

Prices and lead times may vary. Flat cover plates are 70mm (2¾”) diameter.

June 2010www.vikinggroupinc.com

Custom Coloursavailable for cover plates and frame style sprinklers.*

Special Painted Cover Plates and Frame Style Sprinklers*Special order only. Additional charges will apply. Orders covering special painted products are not subject to cancellation except by written permission and then only upon agreementto make payment for work already performed. Viking reserves the right to over ship special painted products produced in excess of order quantity at no charge. No return of theseproducts is allowed. Changes to products may result in the loss of listings or approvals.

Standard (left)Part No. 1375070mm (2¾” )

Large Part No. 14934Part No. 16207(for VK480)

For systems designed to NFPA 13D and 13R, or designed to NFPA 13 prior to 1999 Edition: Apply the listed areas of coverage and minimum water supply requirements shown in themost recent data sheet.For systems designed to the 1999 and 2002 editions of NFPA 13: The minimum required discharge from each of the design sprinklers is to be the greater of the following:• The flow rates given in the appropriate data page for NFPA 13D and 13R applications for each listed maximum area of coverage; or• A minimum discharge of 0.1 gpm/sq. ft. over the “design area” for each of the design sprinklers.NOTE: The As = S x L method must be used to determine the sprinkler protection area of coverage. See 2002 NFPA 13 paragraphs 8.5.2.1 and 11.2.3.5 (2).All data pages showing complete details of listings are available on the Viking web site at www.vikinggroupinc.com.In some cases, Sprinkler Identification Numbers may apply to more than one sprinkler. Please use part numbers when placing orders.

Cover PlatesTech Data Page 136a

SquarePart No. 1539484mm (3-5/16”)

DomedPart No. 1220780mm (3-1/8”)

Page 7: Residential CPVC Catalogue June 2010_UK

Size Part Number Box Qty.

DN20 V5011-007 250

DN25 V5011-010 100

DN32 V5011-012 25

DN40 V5011-015 25

Size Part Number Box Qty.

Tee (continued)

2” V5011-020 2

2-1/2” V5011-025 1

3” V5011-030 1

Tee

Size Part Number Box Qty.

DN20 x DN20 x DN25 V5011R-102 10

DN25 x DN20 x DN20 V5011R-125 100

DN25 x DN20 x DN25 V5011R-126 10

DN25 x DN25 x DN20 V5011R-131 100

DN32 x DN25 x DN20 V5011R-157 5

DN32 x DN25 x DN25 V5011R-158 25

DN32 x DN25 x DN32 V5011R-159 5

DN32 x DN32 x DN20 V5011R-167 25

DN32 x DN32 x DN25 V5011R-168 25

DN32 x DN32 x DN40 V5011R-169 5

DN40 x DN32 x DN20 V5011R-201 5

DN40 x DN32 x DN25 V5011R-202 5

DN40 x DN40 x DN20 V5011R-210 25

DN40 x DN40 x DN25 V5011R-211 25

Size Part Number Box Qty.

Reducing Tees (continued)

DN40 x DN40 x DN32 V5011R-212 5

DN40 x DN40 x DN50 V5011R-213 5

DN50 x DN50 x DN20 V5011R-248 2

DN50 x DN50 x DN25 V5011R-249 10

DN50 x DN50 x DN32 V5011R-250 2

DN50 x DN50 x DN40 V5011R-251 2

DN65 x DN65 x DN25 V5011R-289 1

DN65 x DN65 x DN32 V5011R-290 1

DN65 x DN65 x DN40 V5011R-291 1

DN65 x DN65 x DN50 V5011R-292 1

DN80 x DN80 x DN40 V5011R-337 1

DN80 x DN80 x DN50 V5011R-338 1

DN80 x DN80 x DN65 V5011R-339 1

Reducing Tee

BlazeMaster® CPVC fittings are manufactured/supplied for Viking SupplyNet by NIBCO, Inc.

Manufactured by Viking Plastics

CPVC Pipe

Size Part Number

DN20 34PIPE10

DN25 1PIPE10

DN32 114PIPE10

DN40 112PIPE10

DN50 2PIPE10

DN65 212PIPE10

DN80 3PIPE10

Test Plug Size Part Number Box Qty.

DN15 V450-005 50

CPVC Standard Fittings

CPVC Pipe, Fittings and Accessories

‘Refer to manufacturers datasheets and design manual for technical specifications, approval information and installation instructions’

June 2010 www.vikinggroupinc.com

Page 8: Residential CPVC Catalogue June 2010_UK

June 2010www.vikinggroupinc.com

45° Elbow Size Part Number Box Qty.

DN20 V5006-007 250

DN25 V5006-010 100

DN32 V5006-012 5

DN40 V5006-015 5

Size Part Number Box Qty.

45° Elbow (continued)

DN50 V5006-020 2

DN65 V5006-025 1

DN80 V5006-030 1

Cross Size Part Number Box Qty.

DN20 V5035-007 10

DN25 V5035-010 100

DN32 V5035-012 5

DN40 V5035-015 6

DN50 V5035-020 4

Size Part Number Box Qty.

Cross (continued)

DN65 V5035-025 4

DN80 V5035-030 1

DN25 x DN25 x DN32 x DN32 V5035R-131 10

Coupling Size Part Number Box Qty.

DN20 V5001-007 250

DN25 V5001-010 100

DN32 V5001-012 25

DN40 V5001-015 25

Size Part Number Box Qty.

Coupling (continued)

DN50 V5001-020 10

DN65 V5001-025 1

DN80 V5001-030 1

Reducing Coupling Size Part Number Box Qty.

DN25 x DN20 V5001R-131 10

DN32 x DN25 V5001R-168 5

DN40 x DN20 V5001R-210 5

DN40 x DN25 V5001R-211 5

Size Part Number Box Qty.

Reducing Coupling (continued)

DN40 x DN32 V5001R-212 5

DN50 x DN25 V5001R-249 2

DN50 x DN40 V5001R-251 2

Bushing Size Part Number Box Qty.

DN25 x DN20 V5018-131 100

DN32 x DN20 V5018-167 25

DN32 x DN25 V5018-168 25

DN40 x DN20 V5018-210 5

DN40 x DN25 V5018-211 25

DN40 x DN32 V5018-212 25

DN50 x DN20 V5018-248 2

DN50 x DN25 V5018-249 2

Size Part Number Box Qty.

Bushing (continued)

DN50 x DN32 V5018-250 2

DN50 x DN40 V5018-251 2

DN65 x DN32 V5018-290 1

DN65 x DN40 V5018-291 1

DN65 x DN50 V5018-292 1

DN80 x DN50 V5018-338 1

DN80 x DN65 V5018-339 1

Cap Size Part Number Box Qty.

DN20 V5017-007 250

DN25 V5017-010 100

DN32 V5017-012 5

DN40 V5017-015 5

Size Part Number Box Qty.

Cap (continued)

DN50 V5017-020 2

DN65 V5017-025 1

DN80 V5017-030 1

90° Elbow Size Part Number Box Qty.

DN20 V5007-007 250

DN25 V5007-010 100

DN32 V5007-012 25

DN40 V5007-015 25

DN50 V5007-020 10

Size Part Number Box Qty.

90° Elbow (continued)

DN65 V5007-025 1

DN80 V5007-030 1

DN25 x DN20 V5007R-131 100

‘Refer to manufacturers datasheets and design manual for technical specifications, approval information and installation instructions’

Page 9: Residential CPVC Catalogue June 2010_UK

Spigot Female Sprinkler Head Adapter with Metal Thread Insert

Sprinkler Head 90 with Metal Thread Insert

Sprinkler Head Tee with Metal Thread Insert

Size Part Number Box Qty.

DN25 x DN25 x DN25 V5012SBI-010 50

DN20 x DN20 x DN15 V5012SBI-101 10

DN25 x DN25 x DN15 V5012SBI-130 50

DN32 x DN32 x DN15 V5012SBI-166 5

DN40 x DN40 x DN15 V5012SBI-209 5

DN50 x DN50 x DN15 V5012SBI-247 2

Size Part Number Box Qty.

Sprinkler Head Tee w/Metal Thread Inserts (continued)

DN25 x DN20 x DN15 V5012RSBI-124 10

DN32 x DN25 x DN15 V5012RSBI-156 5

DN40 x DN32 x DN15 V5012RSBI-199 5

DN50 x DN40 x DN15 V5012RSBI-237 2

DN25 x DN15 x DN25* V5014RSBI-122* 10

*Socket x FNPT x Socket

Spigot Female Adapter with Metal Thread Insert

Size Part Number Box Qty.

DN20 V50032BI-007 10

DN25 V50032BI-010 10

Female Adapter with Metal Thread Insert

Size Part Number Box Qty.

DN20 V5003BI-007 10

DN25 V5003BI-010 50

DN32 V5003BI-012 5

Size Part Number Box Qty.

Female Adapter w/Metal Thread Inserts (continued)

DN40 V5003B1-015 5

DN50 V5003B1-020 2

Size Part Number Box Qty.

DN20 x DN15 V50073SBI-101 100

DN25 x DN15 V50073SBI-130 50

DN25 x DN20 V50073SBI-131 10

DN32 x DN15 V50073SBI-166 5

Sprinkler Head Back to Back Cross with Metal Thread Insert

Back to Back Tee with Metal Threads Insert

Size Part Number Box Qty.

DN15 x DN15 x DN25 1-1/8” V501133SBIS-075 48

DN15 x DN15 x DN25 1-15/16” V501133SBIL-075 48

Size Part Number Box Qty.

DN25 x DN25 x DN15 x DN15 1-1/8” V50283SBIS-130 1

DN25 x DN25 x DN15 x DN15 1-15/16” V50283SBIL-130 1

Size Part Number Box Qty.

DN20 x DN15 V50032SBI-101 100

DN25 x DN15 V50032SBI-130 50

Female Sprinkler Head Adapter with Metal Thread Insert

Size Part Number Box Qty.

DN20 x DN15 V5003SBI-101 100

DN25 x DN15 V5003SBI-130 50

DN25 x DN20 V5003SBI-131 10

CPVC Sprinkler Head Adapters

CPVC Transition Fittings

‘Refer to manufacturers datasheets and design manual for technical specifications, approval information and installation instructions’

June 2010 www.vikinggroupinc.com

Page 10: Residential CPVC Catalogue June 2010_UK

June 2010www.vikinggroupinc.com

‘Refer to manufacturers datasheets and design manual for technical specifications, approval information and installation instructions’

Grooved Coupling Adapter Size Part Number Box Qty.

DN32 V5001G-012 30

DN40 V5001G-015 25

DN50 V5001G-020 15

Size Part Number Box Qty.

Grooved Coupling Adapter (continued)

DN65 / 76mm V5001G-065 10

DN80 V5001G-030 8

Standard Union

Size Part Number Box Qty.

DN20 V5004BI-007 10

DN25 V5004BI-010 10

DN32 V5004BI-012 5

Size Part Number Box Qty.

Male Adapter w/Metal Thread Inserts (continued)

DN40 V5004BI-015 5

DN50 V5004BI-020 2

Male Adapter with Metal Thread Insert

Size Part Number Box Qty.

DN20 V5033E-007 1

DN25 V5033E-010 1

DN32 V5033E-012 1

DN40 V5033E-015 1

Size Part Number Box Qty.

Standard Union (continued)

DN50 V5033E-020 1

DN65 V5033E-025 1

DN80 V5033E-030 1

Transition Union with Metal Thread Insert

Size Part Number Box Qty.

Transition Union w/Metal Thread Inserts (continued)

DN50 V5033E3-020 1

DN80 V5033E3-030 1

Size Part Number Box Qty.

DN20 V5033E3-007 1

DN25 V5033E3-010 1

DN32 V5033E3-012 1

DN40 V5033E3-015 1

Flange - Solid Size Part Number Box Qty.

Flange - Solid (continued)

DN50 V5051H-020 1

DN65 V5051H-025 1

DN80 V5051H-030 1

Size Part Number Box Qty.

DN20 V5051H-007 1

DN25 V5051H-010 1

DN32 V5051H-012 1

DN40 V5051H-015 1

Blind Flange - Solid Size Part Number Box Qty.

Blind Flange - Solid (continued)

DN50 V5019H-020 1

DN65 V5019H-025 1

DN80 V5019H-030 1

Size Part Number Box Qty.

DN20 V5019H-007 1

DN25 V5019H-010 1

DN32 V5019H-012 1

DN40 V5019H-015 1

Flange - Van Stone with Socket Size Part Number Box Qty.

DN80 V5051A-030 1

Flange - Van Stone with Spigot Size Part Number Box Qty.

DN80 V50512A-030 1

Page 11: Residential CPVC Catalogue June 2010_UK

Standard Threaded - VSR-SFT

Wheel Cutter (Quick Release)

Size Part Number

DN25 / 1”

DN32 / 1¼”

DN40 / 1½”

DN50 / 1”

VSR-SFG

Standard Glued - VSR-SFG

Minimum Pipe Size Maximum Pipe Size Part Number

10 mm 63 mm 31647

25 mm 75 mm 36592

50 mm 110 mm 31657

Reamers (Internal & External)

Strap Clamp

Deburrer (Internal / External)

Waterflow Switches for CPVC Pipe

Tools for CPVC Pipe

Chain Vise

Size Part Number

DN25 / 1”

DN32 / 1¼”

DN40 / 1½”

DN50 / 1”

VSR-SFT

Minimum Pipe Size Maximum Pipe Size Part Number

32 mm 100 mm 04430

40 mm 76 mm 64962

100 mm 100 mm 64967

Minimum Pipe Size Maximum Pipe Size Part Number

6 mm 36 mm 29993

12 mm 54 mm 20101

Minimum Pipe Size Maximum Pipe Size Part Number

DN20 / ¾” DN80 / 3” 02247

Minimum Pipe Size Maximum Pipe Size Part Number

DN20 / ¾” DN100 / 4” 04452

Clamped - VSR

Size Part Number

DN50 / 2” VSRF0200

DN65 / 2½” VSRF0250

DN80 / 3” VSRF0300

June 2010 www.vikinggroupinc.com

Includes one spare wheel in knob

Page 12: Residential CPVC Catalogue June 2010_UK

June 2010www.vikinggroupinc.com

Hanger/Restrainer “Stand-Off” Size Part Number Box Qty.

DN20 / ¾” 597811 100

DN25 / 1” 597812 100

DN32 / 1¼” 597813 100

DN40 / 1½” 597814 100

DN50 / 2” 597815 100

Hanger/Restrainer 109 Size Part Number Box Qty.

DN20 / ¾” 597827 100

DN25 / 1” 597828 100

DN32 / 1¼” 597829 100

DN40 / 1½” 597831 100

DN50 / 2” 597832 100

Hanger/Restrainer 107 Size Part Number Box Qty.

DN20 / ¾” 597816 100

DN25 / 1” 597817 100

DN32 / 1¼” 597818 100

DN40 / 1½” 597819 100

DN50 / 2” 597821 100

Size Part Number Box Qty.

DN20 / ¾” 597822 100

DN25 / 1” 597823 100

DN32 / 1¼” 597824 100

DN40 / 1½” 597825 100

DN50 / 2” 597826 100

Hanger/Restrainer 108

Hangers & Pipe Clamps for CPVC Pipe

Pipe Clamp with Insulation 240Easy one-hand installation

Size Part Number Box Qty.

DN20 / ¾” 400081 100

DN25 / 1” 400082 75

DN32 / 1¼” 400083 50

DN40 / 1½” 400085 50

DN50 / 2” 400086 50

Loop Hanger Model FCN112 Size Thread Part Number Box Qty.

DN65 / 2½” M10 297920* 100

DN80 / 3” M10 297930 50

DN100 / 4” M10 297940 50

DN125 / 5” M12 297950 25

DN150 / 6” M12 297960** 20

DN200 / 8” M12 297970 15

Size Thread Part Number Box Qty.

DN15 / ½” M10 297860 100

DN20 / ¾” M10 297870 100

DN25 / 1” M10 297880 100

DN32 / 1¼” M10 297890 100

DN40 / 1½” M10 297900 100

DN50 / 2” M10 297910 100

The FCN112 has a unique design that allows the hanger to be used with both CPVC and steel pipes.* Suitbale for 73.0 mm & 76.1 mm** Suitable for 165 mm & 168 mm

Page 13: Residential CPVC Catalogue June 2010_UK

June 2010 www.vikinggroupinc.com

Size Part Number

75 mm / 3” V5097

20 mm Dauber

Size Part Number

20 mm / ¾” V5093-S

37 mm Dauber Cap

Size Part Number

25 mm / 1” V5096

Size Part Number

37 mm / 1½” V5093-L

75 mm Roller

25 mm Brush Cap

Size Part Number

473 ml / 1 US Pint V5097P

946 ml / 1 US Quart V5097Q

FP-1000 One-Step Cement

Accessories for CPVC Pipe

Size Part Number

300ml Tube P35860-323

“Caulk&Walk” Firestopping Sealant for CPVC Piping

Page 14: Residential CPVC Catalogue June 2010_UK

SupplyNet®

Viking SupplyNet Ltd.G6 Bellwin HouseBellwin DriveFlixborough Industrial EstateFlixboroughScunthorpeNorth Lincolnshire DN15 8SN

Tel.: 01724 295 300Fax: 01724 295 301

E-mail: [email protected]: www.vikinggroupinc.com