research design and high technology · the operating limit of fda series - fan type is design to...

106
Soler & Palau Sales Department C/ Llevant, 4 – Polígono Industrial Llevant 08150 Parets del Vallès (Barcelona) - SPAIN Tel. +34935719420 Fax +34935719421 e-mail: [email protected] Web: http://www.solerpalau.com Research Design and High Technology

Upload: others

Post on 23-Mar-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

Soler & PalauSales Department

C/ Llevant, 4 – Polígono Industrial Llevant

08150 Parets del Vallès (Barcelona) - SPAIN

Tel. +34935719420

Fax +34935719421

e-mail: [email protected]

Web: http://www.solerpalau.com

ResearchDesign andHigh Technology

Page 2: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

Double InletCentrifugal Fan

FDA

with Forward Wheels

Page 3: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

2

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

S&P - LA EMPRESADesde su fundación en el año 1951, en la localidad de Ripoll (España),

Soler & Palau, S.A. se ha convertido, desde hace ya bastantes años, en

uno de los líderes mundiales en la fabricación y venta de todo tipo de

equipos de ventilación y de extracción de aire.

Ocho plantas productivas y once empresas filiales propias de comer-

cialización, ubicadas en diversos países y continentes constituyen

el actual Grupo S&P que, con un cualificado equipo de más de 1300

personas, ejerce su actividad en todos los países del mundo.

S&P - LA ESTRATEGIAInvestigación y Desarrollo de productos y tecnología propios; Calidad de

producción por encima de la media de su campo de actividad y Vocación

de Expansión sostenible son, y han sido entre otros, tres de los pilares

fundamentales sobre los que descansa la trayectoria de Soler & Palau, S.A.

Contar hoy con más de 60 Ingenieros titulados en las áreas de

Investigación, Desarrollo, Innovación y Producción; Certificaciones

ISO 9001:2000 y 14001:1996 acrediatadas por AENOR (Soler & Palau

fue la primera empresa registrada en España). Laboratorios propios de

ensayo con certificación oficial EN-45001-89 y crecimientos anuales,

sostenidos en las últimas décadas, muy superiores a los de su mercado

son algunos de los logros de la correcta aplicación de la mencionada

estrategia de empresa.

Nuevos y apasionantes proyectos que verán la luz muy en breve, están

hoy en marcha en el Grupo S&P.

IntroducciónIntroduction

S&P - THE COMPANYSoler & Palau was founded in 1951 in Ripoll (Spain) and since this

date has become one of the world’s leading companies engaged

in the manufacture, sales and distribution of all types of ventilating

and air moving products. Today Soler & Palau has eight production

plants and eleven wholly owned commercial subsidiary companies

located across the globe. Supporting the design, development

production and commercial facilities are a professional team of

more than 1300 employees who ensure that Soler & Palau continue

to have an active presence in all global market sectors.

S&P - THE STRATEGYAt the heart of Soler & Palau’s company strategy is the continued

substantial investment in product and manufacturing research,

development and quality control. Since 1951 the sustained

investment in these critical areas has enabled Soler & Palau to

offer to its customers products with unparalleled quality and

reliability. These critical elements of success today form the

fundamental cornerstones of the company’s strategy for growth

within increasingly competitive global markets.

Today Soler & Palau has more than 60 highly qualified engineers

working in areas such as product and manufacturing technology

research, development, innovation and production. The engineers

work closely with international safety standards agencies to

ensure that all of Soler & Palau’s products are manufactured and

supplied in accordance with only the very latest mechanical and

electrical safety standards. All products are extensively tested

with the company’s comprehensive in-house airflow, acoustic

and environmental test laboratories which have been officially

certified by AENOR to EN-45001- 89 standards. Currently Soler &

Palau hold both ISO 9001:2000 and ISO 14001:1996 certifications

and were also the first company in Spain to be registered to the

original ISO 9000 standards.

Through operating a continual rigorous program of new and

existing product development and improvement means that Soler

& Palau’s customers are assured that they will continue to receive

products of only the very highest quality and reliability both now

and in the future.

Page 4: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

Soler & Palau S.A. certifies that the FDA series:version S, C, T and X - model 200 to 1000shown herein is licensed to bear the AMCA Seal.The ratings shown are based on tests and proceduresperformed in accordance with AMCA publication211 and AMCA publication 311 and comply with therequirements of the AMCA Certified Ratings Program.

FDA SeriesDOUBLE INLET CENTRIFUGAL FAN with Forward Wheels

Page 5: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

4

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

FDA SeriesDouble Inlet Forward Curved Centrifugal Fans

The FDA series is DIDW centrifugal fans with forward curved impellers. The fans are suitable for supply or extract applications in commercial, process and industrial HVAC systems.

Sizes of this series are in accordance withAMCA standard 99-0098-76 and DIN 323 R20.

Fan size 160 to 710

Volume 1.000 to 50.000 m3/h

TotalPressure

up to 1.400 Pa

Type C

This type has a frame fitted on both sides of the fan which gives better strength and rigidity. It allows mounting in four different orientations.

Performance of 160 and 180 are not AMCA licensed.

Fan size 160 to 710

Volume 1.000 to 50.000 m3/h

TotalPressure

up to 1.400 Pa

Type S

This type is supplied with mounting feet and can be mounted in three different orientations. The construction is mainly for OEM application which only subject to testing and approval.

Performance of 160 and 180 are not AMCA licensed.

Fan size 250 to 1.000

Volume 2.500 to 100.000 m3/h

TotalPressure

up to 1.600 Pa

Type T

This type has a welded frame giving increased stiffness and rigidity required for higher operating performance.

Fan size 560 to 1.000

Volume 15.000 to 130.000 m3/h

TotalPressure

up to 1.800 Pa

Type X

The structure is similar to type T but utilizes

enhanced bearings to support higher dynamic load

necessary for the increased performance.

Type / Operating Limit

Each fan type has its maximum operating speed and power due to its mechanical design.

The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69.

The FDA series is available in type S, C, T and X.

Model 160 to 710

Type S-C I Model 800 to 1.000

Type T II I

Type X III II

Page 6: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

5

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

FDA Twin FanFDA series are also available in twin fan version, with two double inlet fans mounted on the same shaft. To select for twin fans, use the curves of single fan with the following factors:

– Volume x 2– Absorbed Power x 2.15– Speed x 1.05– Noise + 3 dB

This series is available in Type S2, C2 or T2, fig. 2 shows the sizes and type available.

Performances of twin fan series are not AMCA licensed.

Wheel

The wheel of FDA series has forward curved blades manufactured in galvanised sheet steel.

Housing

For all sizes, the housing is manufactured in galvanized sheet steel with the housing fixed to the side plates in “pittsburg lock” form system.

Frame

The frame is manufactured with galvanized angular bars for type “C”. For type “T” and “X”, they are manufactured with sections of steel and finished with polyester powder coating.

Shaft

Shafts are manufactured from C45 carbon steel using an automatic process for positioning and cutting of the keyways. All dimensional tolerances of the shaft are fully checked to ensure a precision fit and then coated with an anti-corrosion varnish after assembly.

Type S2

Fan size 250 to 500

Volume 5.000 to 50.000 m3/h

Type C2

Fan size 250 to 500

Volume 5.000 to 50.000 m3/h

Type T2

Fan size 355 to 630

Volume 10.000 to 80.000 m3/h

Page 7: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

6

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

The bearings are lubricated for life and maintenance-free.

If re-lubrication is necessary, it is recommended to use lithium base grease suitable for all temperatures within the operational limits.

Balancing Quality

All wheels are statically and dynamically balanced to ISO1940 and AMCA 204 – G2.5 standards.

Paintings

Special powder-paint coatings of various thicknesses can be supplied on request.

AccessoriesCasing Drain

This option is available when using fans exposed to the atmosphere or operating in high humidity conditions.

Outlet Flanges

Outlet flanges are available upon request.

Inspection Doors

The inspection door can be supplied upon request. It can be supplied in one of the three position (P3, P4 & P5).

Guards

Inlet guards, discharge guards and non-drive end shaft guards are available on request.

Mounted in a rubber housing Mounted on cast iron supports with grease point

Fan Type

S C T X

Bearing Duty

SL Light Duty CL Light Duty TL Light Duty -

SM Medium Duty CM Medium Duty TM Medium Duty XM Medium Duty

eg. Model FDA 450 C M TX Extra Heavy Duty XX Extra Heavy Duty

Model FDA 450 C M

Fan Bearing Duty (L, M, X)

Fan type (S, C, T, X, Z)

Fan Size (315, 355, 400,...1400)

Bearings

Bearings used are either deep groove ball bearing type with an eccentric locking collar or an adapter sleeve, or spherical roller bearings type sealed at both sides for different duty application as classified below:

Page 8: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

7

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

Fan Rotation and Discharge

The rotation and discharge of the fan is in accordance with AMCA standard 99-2406-83.

The direction of rotation is determined from the drive side of the fan [refer Fig. 3]: -

CW - clockwise rotationCCW - counter-clockwise rotation

Motor Selection

The power curve shown on each performance curve represents the absorbed power at the shaft of the fan measured in kW.

To determine the power of the motor to be installed, a correction factor as shown in fig. 5 should be applied to compensate for transmission losses.

For conversion to horsepower (HP), use multiplying factor 1.34.Utpat. Ostionsequat volutat illaor iurercil essequat. Pit nibh exer alis nit acilla commy nis am nibh exerostrud tat lore faci tatisi blamcommod duis nulla facilit lute

Fig. 4 - Motor Position

Fig. 5 – Recommended for compensation

Motor power output (kW)

Co

rrec

tion

Fac

tor,

% m

oto

r p

ow

er o

utp

ut

CW

90º 180º 270º 360º

CCW

Fig. 3 - Fan rotation and discharge

Motor Position

The position of the motor for belt drive centrifugal fan is in accordance with AMCA standard 99-2407-66.

Location of motor is determined by facing the drive side of fan and designating the positions by letters W, X, Y, or Z .

[refer to Fig.4]

Page 9: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

8

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

Dynamic Pressure

The dynamic pressure and outlet air velocity shown on each curve are calculated on the full air discharge area, i.e. ducted outlet conditions.

With free outlet conditions, the velocity pressure is higher. To determine this new value, multiply the velocity pressure of the ducted outlet obtained from the fan curve by the following correction factor “K”.

Fan performances calculate with this correction factors are not licensed by AMCA.

[ K = 2.6 ]

Performance

The performance data shown on each diagram has been tested and measured in accordance to AMCA Standard 210 – Fig 12 – installation type B (free inlet and ducted outlet conditions).

Ratings are referred to the standard air density with the total pressure as a function of the air volume, using logarithmic scales.

It is essential that, the same installation type and test standards are used at all times, when comparing fan performances.

Noise

The noise level shown on each diagram refer to the sound power “A-weighted” and the data on the inlet side has been measured in accordance with AMCA Standard 300 diag. 2 - configuration “B”. The noise levels of the fans are determined as follows:

– Sound power level - (“A” scale): Lw (A) as catalogue.

– Octave band spectrum: Lw = Lw(A) + Lw rel. dB [refer to Soler & Palau S.A. for more details].

– Sound pressure level:

a) free field Lp(A) = Lw(A) - (20log10d) -11

b) room conditions Lp(A) = Lw(A) - (20log10d) -7

where d = distance of fan (m)

Page 10: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

9

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

Example of Selection

Air Volume Q = 20000 m3/h

Outlet Velocity V = 13.6 m/s

Dynamic Pressure Pd = 114 Pa

Total Pressure Pt = 737 Pa

Fan Speed N = 828 rpm

Absorbed Power W = 6.5 kW

Total Efficiency = 62 %

Sound Power Level Lw(A) = 95.3 dB(A)

S-C T

FDA 500

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 11: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

10

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

- MODEL FDA160 IS NOT LICENSED TO BEAR THE AMCA CERTIFIED RATINGS SEAL.

FDA 160

Page 12: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

11

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

FDA 180

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

- MODEL FDA180 IS NOT LICENSED TO BEAR THE AMCA CERTIFIED RATINGS SEAL.

Page 13: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

12

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

FDA 200

Page 14: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

13

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

FDA 225

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 15: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

14

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

FDA 250

Page 16: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

15

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

FDA 280

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 17: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

16

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

FDA 315

Page 18: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

17

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

FDA 355

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 19: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

18

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

FDA 400

Page 20: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

19

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

FDA 450

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 21: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

20

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

FDA 500

Page 22: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

21

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

FDA 560

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 23: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

22

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

FDA 630

Page 24: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

23

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

FDA 710

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 25: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

24

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

FDA 800

Page 26: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

25

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

FDA 900

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 27: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

26

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

FDA 1000

Page 28: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

27

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

FDA ‘S’

Model A B C D E F G J K L M h1 h2 h3ød

CL CM uxs

450 816 722 486 568 568 200 322 608 648 814 123 336 518 407 35 35 13x18

500 906 794 538 638 638 225 352 678 718 924 143 375 568 448 35 35 13x18

560 1016 886 603 714 714 250 390 764 814 1000 143 416 634 502 40 40 13x18

630 1142 992 679 800 800 280 434 850 900 1092 146 468 707 571 40 45 13x18

710 1286 1114 765 898 898 315 484 948 998 1234 168 531 797 636 50 50 13x18

All Dimensions in mm.

FDA 160-400 ‘S’

FDA 450-710 ‘S’

Model A B C D E F G J K L M h1 h2 h3ød

CL CM uxs

160 292 282 172 204 204 180 140 224 244 368 82 150 204 150 20 - 11x16

180 328 312 192 228 228 180 152 248 268 392 82 164 224 164 20 20 11x16

200 364 342 215 256 256 224 164 281 306 420 82 181 245 184 20 20 11x16

225 408 380 243 288 288 224 180 313 338 452 82 197 274 204 20 20 11x16

250 452 416 270 322 322 224 194 347 372 486 82 210 299 227 20 20 11x16

280 508 464 302 360 360 280 214 390 420 556 98 236 331 255 25 25 11x16

315 572 516 340 404 404 280 236 434 464 600 98 261 370 283 25 25 11x16

355 644 576 383 452 452 315 260 492 532 672 110 274 411 320 30 30 11x16

400 724 644 432 506 506 355 290 546 586 726 110 302 462 359 30 30 11x16

All Dimensions in mm.

A

B

DC

G h3

F

h1h2

J

K

M E

L

M

uxs

A

CD

G

B

F F

h1

h3

h2

M

t1

K

J

uxs

L

E M

w

Ød-g6

t

z

Page 29: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

28

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

FDA ‘C’

Model A B C D E F G H J K L M P Rød

uxsCL CM

180 336 323 192 228 228 180 152 294 248 268 392 62 29 5 20 20 9x12

200 370 343 215 256 256 224 164 306 281 306 420 57 37 4 20 20 11x16

225 415 382 243 288 288 224 180 348 313 338 452 57 34 3 20 20 11x16

250 460 418 270 322 322 224 194 383 347 372 486 57 35 4 20 20 11x16

280 518 466 302 360 360 280 214 432 390 420 556 68 34 5 25 25 13x18

315 578 518 340 404 404 330 236 480 434 464 600 68 38 3 25 25 13x18

355 654 578 383 452 452 368 260 548 492 532 672 70 30 6 30 30 13x18

400 736 650 432 506 506 402 290 612 546 586 726 70 38 5 30 30 13x18

All Dimensions in mm.

Model A B C D E F F1 G H J K L M P Rød

CL CM uxs

450 827 726 486 568 568 200 111 322 681 608 648 814 83 45 5 35 35 13x18

500 918 800 538 638 638 245 120 352 750 678 718 924 103 50 5 35 35 13x18

560 1030 892 603 714 714 280 125 390 844 764 814 1000 93 48 7 40 40 13x18

630 1157 998 679 800 800 328 110 434 945 850 900 1092 96 53 6 40 45 13x18

710 1302 112 765 898 898 360 150 484 1057 948 998 1234 118 63 7 50 50 17x22

All Dimensions in mm.

FDA 450-710 ‘C’

FDA 180-400 ‘C’

=

D

A

=

P

C

R

G

H

F =

=F

B

=

M

KJ

uxs

E

L

M=

=

F=

P

DR

A

C

G

=

H

F1 F =

B

FF

1F

=

M

t1

JK

E

L

uxs

M=

Ød-g6

w

z

t

Page 30: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

29

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

Model A B C D E F F1 G H J K L M P Rød

TL TM uxs

450 827 726 486 568 568 200 111 322 681 608 648 878 115 45 5 40 40 13x18

500 918 800 538 638 638 245 120 352 750 678 718 956 119 50 5 40 45 13x18

560 1030 892 603 714 714 280 125 390 844 764 814 1080 133 48 7 45 45 13x18

630 1157 998 679 800 800 328 110 434 945 850 900 1166 133 53 6 50 50 13x18

710 1302 1120 765 898 898 360 150 484 1057 948 998 1280 141 63 7 50 55 17x22

800 1468 1254 862 1006 1006 405 171 540 1180 1056 1106 1388 141 74 7 55 55 17x22

900 1648 1408 971 1130 1130 455 189 604 1319 1180 1230 1566 168 89 7 60 60 17X22

1000 1810 1540 1066 1266 1266 500 200 656 1450 1316 1366 1724 179 90 9 60 70 17x22

All Dimensions in mm.

FDA 450-1000 ‘T’

Model A B C D E F G H J K L M P Rød

TL TM uxs

250 460 418 270 322 322 224 194 383 347 372 538 83 35 4 25 25 11x16

280 518 466 302 360 360 280 214 432 390 420 588 84 34 5 30 30 13x18

315 578 518 340 404 404 330 236 480 434 464 632 84 38 3 30 30 13x18

355 654 578 383 452 452 368 260 548 492 532 718 93 30 6 35 35 13x18

400 736 650 432 506 506 402 290 612 546 586 772 93 38 5 35 35 13x18

All Dimensions in mm.

FDA ‘T’FDA 250-400 ‘T’

D

C

GL

uxs

JK

B

=F

=

= F =

HP

A

R M E M= =

=

A

P

=F1

H

F F

F=

F1

D

C

R

G

B

F=

M

KJ

uxs

= E

L

M=

Page 31: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

30

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

Model A B C D E F F1 G H J K L M P R ød uxs

560 1030 892 603 714 714 280 125 390 844 764 814 1138 162 48 7 55 13x18

630 1157 998 679 800 800 328 110 434 945 850 900 1286 193 53 6 60 13x18

710 1302 1120 765 898 898 360 150 484 1057 948 998 1390 196 63 7 65 17x22

800 1468 1254 862 1006 1006 405 171 540 1180 1056 1106 1498 196 74 7 65 17x22

900 1648 1408 971 1130 1130 455 189 604 1319 1180 1230 1660 215 89 7 70 17X22

1000 1810 1540 1066 1266 1266 500 200 656 1450 1316 1366 1845 239.5 90 9 80 17x22

All Dimensions in mm.

FDA ‘X’FDA 560-1000 ‘X’

D

A

=

P

CR

G

F F1

H

F =

=F

F1

F

B

=

M =

KJ

uxs

E

L

= M

Page 32: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

31

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

FDA ‘S2’FDA 250-400 ‘S2’

FDA 450-500 ‘S2’

Model A B C D E F G J K L M N V h1 h2 h3 ød uxs

250 452 416 270 322 322 224 194 347 944 994 100 250 225 210 299 227 25 11x16

280 508 464 302 360 360 280 214 390 1060 1110 110 280 250 236 331 255 30 11x16

315 572 516 340 404 404 280 236 434 1183 1233 110 315 285 261 370 283 30 11x16

355 644 576 383 452 452 315 260 492 1339 1389 130 355 315 274 411 320 35 11x16

400 724 644 432 506 506 355 290 546 1492 1542 130 400 360 302 462 359 35 11x16

All Dimensions in mm.

Model A B C D E F G J K L M N V h1 h2 h3 ød uxs

450 816 722 486 568 568 200 322 608 1666 1726 140 450 410 336 518 407 40 13x18

500 906 794 538 638 638 225 352 678 1856 1916 140 500 460 375 568 448 40 13x18

All Dimensions in mm.

J

K

M E

L

J

EN

V

A

B

D

C

G h3

h1h2

uxs

F

B

C

A

D

G

h1h2

J

h3

M E

uxs

K

V J

N

L

E

F F

Page 33: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

32

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

Model A B C D E F G H J K L M N P R V ød uxs

250 460 418 270 322 322 224 194 383 347 939 1019 75 250 35 4 220 25 11x16

280 518 466 302 360 360 280 214 432 390 1060 1140 80 280 34 5 250 30 13x18

315 578 518 340 404 404 330 236 480 434 1183 1263 80 315 38 3 285 30 13x18

355 654 578 383 452 452 368 260 548 492 1339 1429 90 355 30 6 315 35 13x18

400 736 650 432 506 506 402 290 612 546 1492 1582 90 400 38 5 360 35 13x18

All Dimensions in mm.

FDA ‘C2’FDA 250-400 ‘C2’

Model A B C D E F F1 G H J K L M N P R V ød uxs

560 827 726 486 568 568 200 111 322 681 608 1666 1766 100 450 45 5 410 40 13x18

630 918 800 538 638 638 245 120 352 750 678 1856 1956 100 500 50 5 460 40 13x18

All Dimensions in mm.

FDA 450-500 ‘C2’

L

J

K

M E

J

EN

V

DC

G

B

=F

=

= =

HP

A

R

uxs

F

= =

=

A

D

CR

B

G

= F1F =F

HP

FF1

F=

=M E N E =

L

J V J

K

uxs

Page 34: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

33

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

FDA ‘T2’FDA 355-400 ‘T2’

Model A B C D E F G H J K L M N P R V ød uxs

355 654 578 383 452 452 368 260 548 492 1339 1449 110 355 30 6 315 40 13x18

400 736 650 432 506 506 402 290 612 546 1492 1602 110 400 38 5 360 40 13x18

All Dimensions in mm.

Model A B C D E F F1 G H J K L M N P R V ød uxs

450 827 726 486 568 568 200 111 322 681 608 1666 1801 135 450 45 5 410 45 13x18

500 918 800 538 638 638 245 120 352 750 678 1856 1991 135 500 50 5 460 50 13x18

560 1030 892 603 714 714 280 125 390 844 764 2088 2228 140 560 48 7 510 50 13x18

630 1157 998 679 800 800 328 110 434 945 850 2330 2470 140 630 53 6 580 55 13x18

All Dimensions in mm.

FDA 450-630 ‘T2’

L

J

K

M E

J

EN

V

uxs

DC

G

B

=F

=

= F =

HP

A

R= =

B

G

P= F F1 F

H

=

uxs

K

E =NE=M

L

R

=F

F1

F=

A

D

C

V JJ

Page 35: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

34

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

Shaft

ød t t1 w z

20 6 6 30 22.5

25 8 7 40 28

30 8 7 40 33

35 10 8 50 38

40 12 8 70 43

45 14 9 70 48.5

50 14 9 90 53.5

55 16 10 90 59

60 18 11 90 64

70 20 12 110 74.5

75 20 12 110 79.9

80 22 14 110 85

85 22 14 110 90

90 25 14 140 95

All Dimensions in mm.

w

t1

t

z

Ød-g6

Page 36: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

35

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

FDASeries

Operational Limits - “FDA”

160 180 200 225 250 280 315 355 400 450 500 560 630 710 800 900 1000

MaximumAbsorbedPower

S-C kW 2 2 2.5 3 3 4 5.5 5.5 7.5 7.5 11 11 15 18.5

T kW 7.5 11 11 15 15 18.5 18.5 22 22 25 25 30 37

X kW 37 37 45 45 75 75

S2-C2 kW 6 8 8 11 11 13 13

T2 kW 20 20 22 24 28 28

Maximum Fan Speed

S-C rpm 4200 3700 3300 2900 2700 2400 2100 1800 1600 1400 1200 1100 900 800

T rpm 3000 2700 2200 2000 1800 1600 1300 1200 1000 900 750 650 600

X rpm 1300 1100 1000 800 700 650

S2-C2 rpm 2200 2000 1600 1500 1200 1000 900

T2 rpm 1700 1400 1200 1000 900 750

TemperatureRange Min.-20oC

S-C Max.ºC 85 85 85 85 85 85 85 85 85 85 85 85 85 85

T-X Max.ºC 100 100 100 100 100 100 100 100 100 100 100 100 100

S2-C2 Max.ºC 85 85 85 85 85 85 85

T2 Max.ºC 100 100 100 100 100 100

Wheel

Diameter mm 160 180 200 225 250 280 315 355 400 450 500 560 630 710 800 900 1000

Weight kg 1.4 1.6 1.7 1.9 2.8 3.6 4.8 5.7 9.7 11.7 18.5 24.5 33 41.5 65 76 92

J = PD2/4 kgm2 0.01 0.011 0.014 0.02 0.04 0.06 0.1 0.15 0.33 0.5 0.95 1.6 2.7 4.4 8.7 13.1 19.4

Fan weight

S kg 7 8 9 10.6 12 17 22 28 37 48 69 81 101 118

C kg 9.5 10.5 12 15 20 24 32 41 51 74 93 104 127

T kg 21 27 30 45 55 61 81 110 140 192 240 293 340

X kg 138 175 227 281 326 384

S2 kg 25 35 45 59 77 100 142

C2 kg 32 43 52 69 88 108 155

T2 kg 116 145 166 207 273 334

Page 37: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

Soler & PalauSales Department

C/ Llevant, 4 – Polígono Industrial Llevant

08150 Parets del Vallès (Barcelona) - SPAIN

Tel. +34935719420

Fax +34935719421

e-mail: [email protected]

Web: http://www.solerpalau.com

ResearchDesign andHigh Technology

Page 38: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

Double InletCentrifugal Fan

BDB

with Backward Wheels

Page 39: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

2

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

S&P - LA EMPRESADesde su fundación en el año 1951, en la localidad de Ripoll (España),

Soler & Palau, S.A. se ha convertido, desde hace ya bastantes años, en

uno de los líderes mundiales en la fabricación y venta de todo tipo de

equipos de ventilación y de extracción de aire.

Ocho plantas productivas y once empresas filiales propias de comer-

cialización, ubicadas en diversos países y continentes constituyen

el actual Grupo S&P que, con un cualificado equipo de más de 1300

personas, ejerce su actividad en todos los países del mundo.

S&P - LA ESTRATEGIAInvestigación y Desarrollo de productos y tecnología propios; Calidad de

producción por encima de la media de su campo de actividad y Vocación

de Expansión sostenible son, y han sido entre otros, tres de los pilares

fundamentales sobre los que descansa la trayectoria de Soler & Palau, S.A.

Contar hoy con más de 60 Ingenieros titulados en las áreas de

Investigación, Desarrollo, Innovación y Producción; Certificaciones

ISO 9001:2000 y 14001:1996 acrediatadas por AENOR (Soler & Palau

fue la primera empresa registrada en España). Laboratorios propios de

ensayo con certificación oficial EN-45001-89 y crecimientos anuales,

sostenidos en las últimas décadas, muy superiores a los de su mercado

son algunos de los logros de la correcta aplicación de la mencionada

estrategia de empresa.

Nuevos y apasionantes proyectos que verán la luz muy en breve, están

hoy en marcha en el Grupo S&P.

IntroducciónIntroduction

S&P - THE COMPANYSoler & Palau was founded in 1951 in Ripoll (Spain) and since this

date has become one of the world’s leading companies engaged

in the manufacture, sales and distribution of all types of ventilating

and air moving products. Today Soler & Palau has eight production

plants and eleven wholly owned commercial subsidiary companies

located across the globe. Supporting the design, development

production and commercial facilities are a professional team of

more than 1300 employees who ensure that Soler & Palau continue

to have an active presence in all global market sectors.

S&P - THE STRATEGYAt the heart of Soler & Palau’s company strategy is the continued

substantial investment in product and manufacturing research,

development and quality control. Since 1951 the sustained

investment in these critical areas has enabled Soler & Palau to

offer to its customers products with unparalleled quality and

reliability. These critical elements of success today form the

fundamental cornerstones of the company’s strategy for growth

within increasingly competitive global markets.

Today Soler & Palau has more than 60 highly qualified engineers

working in areas such as product and manufacturing technology

research, development, innovation and production. The engineers

work closely with international safety standards agencies to

ensure that all of Soler & Palau’s products are manufactured and

supplied in accordance with only the very latest mechanical and

electrical safety standards. All products are extensively tested

with the company’s comprehensive in-house airflow, acoustic

and environmental test laboratories which have been officially

certified by AENOR to EN-45001- 89 standards. Currently Soler &

Palau hold both ISO 9001:2000 and ISO 14001:1996 certifications

and were also the first company in Spain to be registered to the

original ISO 9000 standards.

Through operating a continual rigorous program of new and

existing product development and improvement means that Soler

& Palau’s customers are assured that they will continue to receive

products of only the very highest quality and reliability both now

and in the future.

Page 40: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

Soler & Palau certifies that the BDB series shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA publication 211 and AMCA publication 311 and comply with the requirements of the AMCA Certified Ratings Program.

BDB SeriesDOUBLE INLET CENTRIFUGAL FAN with Backward Wheels

Page 41: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

4

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

BDB SeriesDouble Inlet Centrifugal Fans – Backward wheels

The BDB series is DIDW centrifugal fans with high efficiency non-overloading backward curved impellers.

The fans are suitable for supply or extract applications in commercial, process and industrial HVAC systems.

Sizes of this series are in accordance withAMCA standard 99-0098-76 and DIN 323 R20.

Model 315 to 710

Type S-C I Model 800 to 1.400

Type T II I

Type X III II

Type Z III

Type / Operating Limit

Each fan type has its maximum operating speed and power due to its mechanical design.

The operating limit of BDB series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69.

The BDB series is available in type S, C, T, X or Z.

Fan size 315 to 710

Volume 1.900 to 50.000 m3/h

TotalPressure

up to 2.000 Pa

Type C

This type has a frame fitted on both sides of the fan which gives better strength and rigidity.

It allows mounting in four different orientations.

Fan size 315 to 1.400

Volume 1.900 to 190.000 m3/h

TotalPressure

up to 2.500 Pa

Type T

This type has a welded frame giving increased stiffness and rigidity required for higher operating performance.

Fan size 315 to 1.400

Volume 1.900 to 260.000 m3/h

TotalPressure

up to 3.200 Pa

Type X/Z

The structure is similar to type T but utilizes enhanced bearings to support higher dynamic load necessary for the increased performance.

Type Z is non-standard, for more information, please consult your nearest Soler & Palau Office for details.

Fan size 315 to 710

Volume 1.900 to 50.000 m3/h

TotalPressure

up to 2.000 Pa

Type S

This type is supplied with mounting feet and can be mounted in three different orientations.

The construction is mainly for OEM application which only subject to testing and approval.

Page 42: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

5

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

BDB Twin FanBDB Series are also available in twin fan version, with two double inlet fans mounted on the same shaft. To select for twin fans, use the curves of single fan with the following factors:

– Volume x 2– Absorbed Power x 2.15– Speed x 1.05– Noise + 3 dB

This series is available in Type S2, C2 or T2.

Performances of twin fan series are not AMCA licensed.

Type S2

Fan size 315 to 500

Volume 5.000 to 50.000 m3/h

Type C2

Fan size 315 to 500

Volume 5.000 to 50.000 m3/h

Type T2

Fan size 355 to 630

Volume 10.000 to 80.000 m3/h

Technical SpecificationWheel

The wheel of BDB series is made of cold rolled sheet steel backward curved blades with polyester powder coating finish.

Housing

For all sizes except 1250 and above, the housing is manufactured in galvanized sheet steel with the housing fixed to the side plates in “pittsburg lock” form system.

Housings for 1250 and 1400 are manufactured in mild steel finished with polyester powder coating.

Fully welded housings are available upon request.

Frame

The frame is manufactured with galvanized angular bars for type “C”. For type “T” and “X”, they are manufactured with sections of steel and finished with polyester powder coating.

Page 43: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

6

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

The bearings are lubricated for life and maintenance-free. If relubrication is necessary, it is recommended to use a lithium base grease suitable for all temperatures within the operational limits.

Balancing Quality

All wheels are statically and dynamically balanced to ISO1940 and AMCA 204 – G2.5 standards.

AccessoriesCasing Drain

This option is available when using fans exposed to the atmosphere or operating in high humidity conditions.

Outlet Flanges

Outlet flanges are available upon request.

Inspection Doors

The inspection door can besupplied upon request. It can be supplied in one of the three positions (P3, P4 & P5).

Guards

Inlet guards, discharge guards and non-drive end shaft guards are available on request.

Paintings

Special powder-paint coatings

of various thicknesses can be supplied on request.

Air flow measurement

Fans can be equipped with an airflow measurement system.

P5

P3

P4

Shaft

Shafts are manufactured from C45 carbon steel using an automatic process for positioning and cutting of the keyways. All dimensional tolerances of the shaft are fully checked to ensure a precision fit and then coated with an anticorrosion varnish after assembly.

Bearings

Bearings used are either deep groove ball bearing type with an adaptor sleeve or spherical roller bearings type sealed at both sides for different duty application classified as below:

Mounted in a rubber housing Mounted on cast iron supports with grease point

Fan Type

S C T X

Bearing Duty

SL Light Duty CL Light Duty TL Light Duty -

SM Medium Duty CM Medium Duty TM Medium Duty XM Medium Duty

eg. Model FDA 450 C M TX Extra Heavy Duty XX Extra Heavy Duty

Model FDA 450 C M

Fan Bearing Duty (L, M, X)

Fan type (S, C, T, X, Z)

Fan Size (315, 355, 400,...1400)

Page 44: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

7

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

Fan Rotation and Discharge

The rotation and discharge of the fan is in accordance with AMCA standard 99-2406-83.

The direction of rotation is determined from the drive side of the fan:

CW - clockwise rotationCCW - counter-clockwise rotation

Motor Position

The position of the motor for belt drive centrifugal fan is in accordance with AMCA standard 99-2407-66.

Location of motor is determined by facing the drive side of fan and designating the positions by letters W, X, Y, or Z

Motor Selection

The power curve shown on each performance curve represents the absorbed power at the shaft of the fan measured in kW.

To determine the power of the motor to be installed, a correction factors should be applied to compensate for transmission losses.

For conversion to horsepower (HP), use multiplying factor 1.34.

Inlet Vane Control

The inlet vane control enable energy saving that varies according to the vane control compared to traditional methods of volume control.

Fig.1 shows the volume reduction corresponding to the vane position.

– With vane fully open (Pos 90°) the volume will be 3% less than the catalogue performance.

– With vane fully closed (Pos 0°) the volume will be reduced by 75%.

Performances of Inlet vane controls are not AMCA licensed.

CW

90º 180º 270º 360º

CCW

Z

Y

X

W

Motor power output (kW)

Co

rrec

tion

Fac

tor,

% m

oto

r p

ow

er o

utp

ut

8

1.5

1

2

3

4

6

40

10

15

20

30

60

80

100

2 Pole

4 & 6 Pole

0.450.2

0.3

0.6

0.75 1.5

2.2 3

4.5 6

7.5 15

22.5 30 45 7560

150

225

300

450

Page 45: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

8

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

Example of Selection

Air Volume Q = 14760 m3/h

Outlet Velocity V = 10.07 m/s

Dynamic Pressure Pd = 62 Pa

Total Pressure Pt = 1515 Pa

Fan Speed N = 1900 rpm

Absorbed Power W = 8 kW

Total Efficiency = 78 %

Sound Power Level Lw(A) = 90.3 dB(A)

1900

S-CCl. I

10M. RPMM. kW

TypeOp Limit

320025004520

XT

Cl. IIICl. II

BDB 500

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 46: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

9

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Type

S-C

T

X

M. kW M. rpm

4 3100

8 4100

16 5100

BDB 315

Page 47: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

10

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

Type

S-C

T

X

M. kW M. rpm

5 2700

11 3500

22 4500

BDB 355

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 48: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

11

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

410028

320014

25006

M. rpmM. kW

X

T

S-C

Type

BDB 400

Page 49: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

12

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

Type M. kW M. rpm

S-C

T

X

8 2200

18 2900

35 3600

BDB 450

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 50: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

13

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Type M. kW M. rpm

S-C

T

X

10 1900

20 2500

45 3200

BDB 500

Page 51: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

14

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

280050

220025

170012

M. rpmM. kW

X

T

S-C

Type

BDB 560

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 52: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

15

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

250060

200030

150014

M. rpmM. kW

X

T

S-C

Type

BDB 630

Page 53: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

16

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

220080

180040

135018

M. rpmM. kW

X

T

S-C

Type

BDB 710

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 54: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

17

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

2000100

160050

120022

M. rpmM. kW

Z

X

T

Type

BDB 800

Page 55: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

18

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

1750120

140060

105030

M. rpmM. kW

Z

X

T

Type

BDB 900

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 56: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

19

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

1600160

130080

100035

M. rpmM. kW

Z

X

T

Type

BDB 1000

Page 57: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

20

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

1400180

1100100

85045

M. rpmM. kW

Z

X

T

Type

BDB 1120

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 58: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

21

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

1250200

1000120

78050

M. rpmM. kW

Z

X

T

Type

BDB 1250

Page 59: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

22

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

BDB 1400

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 60: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

23

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

BDB ‘S’

Model A B C D E F G J K L M h1 h2 h3ød

SL SM uxs

450 816 722 486 568 568 200 322 608 648 814 123 336 518 407 35 35 13x18

500 906 794 538 638 638 225 352 678 718 924 143 375 568 448 35 35 13x18

560 1016 886 603 714 714 250 390 764 814 1000 143 416 634 502 40 40 13x18

630 1142 992 679 800 800 280 434 850 900 1092 146 468 707 571 40 45 13x18

710 1286 1114 765 898 898 315 484 948 998 1234 168 531 797 636 50 50 13x18

All Dimensions in mm.

BDB 315-400 ‘S’

BDB 450-710 ‘S’

Model A B C D E F G J K L M h1 h2 h3ød

SL SM uxs

315 572 516 340 404 404 280 236 434 464 600 98 261 370 283 25 25 11x16

355 644 576 383 452 452 315 260 492 532 672 110 274 411 320 30 30 11x16

400 724 644 432 506 506 355 290 546 586 726 110 302 462 359 30 30 11x16

All Dimensions in mm.

D

A

C

G

B

F

h1

uxs

h3

h2

M

KJ

E

L

M

Ød-h7

F

A

B

F

h1

uxs

D

C

G h3

h2

M

JK

E

L

M

Ød-h7

Page 61: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

24

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

BDB ‘C’

Model A B C D E F G H J K L M P Rød

uxsCL CM

315 578 518 340 404 404 330 236 480 434 464 600 68 38 3 25 25 13x18

355 654 578 383 452 452 368 260 548 492 532 672 70 30 6 30 30 13x18

400 736 650 432 506 506 402 290 612 546 586 726 70 38 5 30 30 13x18

All Dimensions in mm.

Model A B C D E F F1 G H J K L M P Rød

CL CM uxs

450 827 726 486 568 568 200 111 322 681 608 648 814 83 45 5 35 35 13x18

500 918 800 538 638 638 245 120 352 750 678 718 924 103 50 5 35 35 13x18

560 1030 892 603 714 714 280 125 390 844 764 814 1000 93 48 7 40 40 13x18

630 1157 998 679 800 800 328 110 434 945 850 900 1092 96 53 6 40 45 13x18

710 1302 1120 765 898 898 360 150 484 1057 948 998 1234 118 63 7 50 50 17x22

All Dimensions in mm.

BDB 315-400 ‘C’

B

G

R

A

D

C

P

= F F1 F

H

=

=F

F1

F=

L

EM M==

Ød-h7

uxs

JK

BDB 450-710 ‘C’

=D

A

=

P

C

R

G

F=

H

F =

uxs

=

B

M

KJ

E

L

M=

Ød-h7

Page 62: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

25

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

Model A B C D E F F1 G H J K L M P Rød

TL TM uxs

450 827 726 486 568 568 200 111 322 681 608 648 878 115 45 5 40 40 13x18

500 918 800 538 638 638 245 120 352 750 678 718 956 119 50 5 40 45 13x18

560 1030 892 603 714 714 280 125 390 844 764 814 1080 133 48 7 45 45 13x18

630 1157 998 679 800 800 328 110 434 945 850 900 1166 133 53 6 50 50 13x18

710 1302 1120 765 898 898 360 150 484 1057 948 998 1280 141 63 7 50 55 17x22

800 1468 1254 862 1006 1006 405 171 540 1180 1056 1106 1388 141 74 7 55 55 17x22

900 1648 1408 971 1130 1130 455 189 604 1319 1180 1230 1566 168 89 7 60 60 17X22

1000 1810 1540 1066 1266 1266 500 200 656 1450 1316 1366 1724 179 90 9 60 70 17x22

All Dimensions in mm.

BDB 450-1000 ‘T’

BDB ‘T’

Model A B C D E F G H J K L M P Rød

TL TM uxs

315 578 518 340 404 404 330 236 480 434 464 632 84 38 3 30 30 13x18

355 654 578 383 452 452 368 260 548 492 532 718 93 30 6 35 35 13x18

400 736 650 432 506 506 402 290 612 546 586 772 93 38 5 35 35 13x18

All Dimensions in mm.

BDB 315-400 ‘T’

uxs

=

P

C

A

DR

H

B

F

G

=

=F

=

M

JK

= E

L

= M

Ød-h7

B

G

RD

A

C

P H

= F F1 F =

=F

F1

F=

L

E = M=M

Ød-h7

uxs

JK

Page 63: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

26

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

BDB ‘T’BDB 1120-1400 ‘T’

Model A B C D E F G H J K L M N P Rød

TL TM uxs

1120 2033 1725 1200 1422 1422 290 748 1630 1482 1548 1800 193 59 95 9 - 75 17x22

1250 2285 1930 1353 1524 1524 300 830 1831 1599 1674 1975 220 81 99 9 - 80 17x22

1400 2568 2170 1515 1794 1794 310 963 2057 1869 1944 2260 227 89 113 13 - 90-80 17x22

All Dimensions in mm.

==

= = =

= N

L

E=M

JK

uxs

R

A

P H

FF

F=

F

B

G

C

D

Ød-h7

Page 64: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

27

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

BDB ‘X’BDB 315-400 ‘XM’

BDB 450-1000 ‘XM’

Model A B C D E F F1 G H J K L M P R ød uxs

450 827 726 486 568 568 200 111 322 681 608 648 946 149 45 5 45 13x18

500 918 800 538 638 638 245 120 352 750 678 718 1066 174 50 5 50 13x18

560 1030 892 603 714 714 280 125 390 844 764 814 1138 162 48 7 55 13x18

630 1157 998 679 800 800 328 110 434 945 850 900 1286 193 53 6 60 13x18

710 1302 1120 765 898 898 360 150 484 1057 948 998 1390 196 63 7 65 17x22

800 1468 1254 862 1006 1006 405 171 540 1180 1056 1106 1498 196 74 7 65 17x22

900 1648 1408 971 1130 1130 455 189 604 1319 1180 1230 1660 215 89 7 70 17X22

1000 1810 1540 1066 1266 1266 500 200 656 1450 1316 1366 1845 239.5 90 9 80 17x22

All Dimensions in mm.

Model A B C D E F G H J K L M P R ød uxs

315 578 518 340 404 404 330 236 480 434 464 732 134 38 3 35 13x18

355 654 578 383 452 452 368 260 548 492 532 822 145 30 6 40 13x18

400 736 650 432 506 506 402 290 612 546 586 876 145 38 5 40 13x18

All Dimensions in mm.

P

A

RD

C

=

G

H

B

F =

=F

=

uxs

M =

JK

E

L

= M

G

B

= F F1 F =

HP

A

D

C

R

=F

F1

F=

L

E=M = M

uxs

KJ

Page 65: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

28

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

BDB ‘X’BDB 1120-1400 ‘XX’

Model A B C D E F G H J K L M N P R ød uxs

1120 2033 1725 1200 1422 1422 290 748 1630 1482 1548 1916 266 102 95 9 80 17x22

1250 2285 1930 1353 1524 1524 300 830 1831 1599 1674 2035 265 96 99 9 85 17x22

1400 2568 2170 1515 1794 1794 310 963 2057 1869 1944 2295 256 95 113 13 90 17x22

All Dimensions in mm.

=

=F

P

RD

A

G

C

=

H

= F

F=

uxs

B

==

F

M

KJ

E

L

N=

Page 66: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

29

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

BDB ‘S2’BDB 315-400 ‘S2M’

BDB 450-500 ‘S2M’

Model A B C D E F G J K L M V X h1 h2 h3 ød uxs

315 572 516 340 404 404 280 236 434 1183 1233 110 285 315 261 370 283 30 11x16

355 644 576 383 452 452 315 260 492 1339 1389 130 315 355 274 411 320 35 11x16

400 724 644 432 506 506 355 290 546 1492 1542 130 360 400 302 462 359 35 11x16

All Dimensions in mm.

Model A B C D E F G J K L M V X h1 h2 h3 ød uxs

450 816 722 486 568 568 200 322 608 1666 1726 140 410 450 336 518 407 40 13x18

500 906 794 538 638 638 225 352 678 1856 1916 140 460 500 375 568 448 40 13x18

All Dimensions in mm.

A

C

D

F

G

B

h3

h1h2

M

uxs

L

J

E

K

V

X

J

E

G h3

F F

B

A

D

C h2h1

J V J

K

uxs

M E X E

L

Page 67: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

30

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

BDB ‘C2’BDB 315-400 ‘C2M’

Model A B C D E F G H J K L M P R V X ød uxs

315 578 518 340 404 404 330 236 480 434 1183 1263 80 38 3 285 315 30 13x18

355 654 578 383 452 452 368 260 548 492 1339 1429 90 30 6 315 355 35 13x18

400 736 650 432 506 506 402 290 612 546 1492 1582 90 38 5 360 400 35 13x18

All Dimensions in mm.

BDB 450-500 ‘C2M’

Model A B C D E F F1 G H J K L M P R V X ød uxs

450 827 726 486 568 568 200 111 322 681 608 1666 1766 100 45 5 410 450 40 13x18

500 918 800 538 638 638 245 120 352 750 678 1856 1956 100 50 5 460 500 40 13x18

All Dimensions in mm.

G

P

=

C

A

DR

=

H

F =

uxs

=F

B

M =

J V

K

J

E X

L

E =

F1A

P

= F F1

H

=F

=F uxs

G

C

DR

B

F=

M =

J

K

V J

E X

L

E =

Page 68: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

31

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

BDB ‘T2’BDB 355-400 ‘T2’

BDB 450-630 ‘T2’

Model A B C D E F G H J K L M P R V X ød uxs

355 654 578 383 452 452 368 260 548 492 1339 1449 110 30 6 315 355 40 13x18

400 736 650 432 506 506 402 290 612 546 1492 1627 135 38 5 360 400 45 13x18

All Dimensions in mm.

Model A B C D E F F1 G H J K L M P R V X ød uxs

450 827 726 486 568 568 200 111 322 681 608 1666 1801 135 45 5 410 450 50 13x18

500 918 800 538 638 638 245 120 352 750 678 1856 1991 135 50 5 460 500 55 13x18

560 1030 892 603 714 714 280 125 390 844 764 2088 2228 140 48 7 510 560 55 13x18

630 1157 998 679 800 800 328 110 434 945 850 2330 2470 140 53 6 580 630 60 13x18

All Dimensions in mm.

=

P

A

C

DR

G

JF =

H

B

F=

=

=

uxs

M E

JV

K

X

L

E =

B

G

= F F1 F =

HP

=F

F1

F=

RD

A

C

M = E X E =

L

uxs

J V J

K

Page 69: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

32

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

Shaft

ød t t1 w z

25 8 7 40 28

30 8 7 40 33

35 10 8 50 38

40 12 8 70 43

45 14 9 70 48.5

50 14 9 90 53.5

55 16 10 90 59

60 18 11 90 64

70 20 12 110 74.5

75 20 12 110 79.9

80 22 14 110 85

85 22 14 110 90

90 25 14 140 95

All Dimensions in mm.

w

t1

t

z

Ød-h7

Page 70: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

33

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BDBSeries

Operational Limits - “BDB”

315 355 400 450 500 560 630 710 800 900 1000 1120 1250 1400

MaximumAbsorbedPower

S-C kW 4 5 6 8 10 12 14 18

T kW 8 11 14 18 20 25 30 40 22 30 35 45 50 70

X kW 16 22 28 35 45 50 60 80 50 60 80 100 120 160

Z kW 100 120 160 180 200 250

S2-C2 kW 5 6.5 6.5 7.5 7.5

T2 kW 15 15 18 22 22 25

MaximumFan Speed

S-C rpm 3100 2700 2500 2200 1900 1700 1500 1350

T rpm 4100 3500 3200 2900 2500 2200 2000 1800 1200 1050 1000 850 780 680

X rpm 5100 4500 4100 3600 3200 2800 2500 2200 1600 1400 1300 1100 1000 900

Z rpm 2000 1750 1600 1400 1250 1100

S2-C2 rpm 2400 2200 1800 1600 1200

T2 rpm 2800 2400 2200 2000 1550 1300

TemperatureRangeMin. -20oC

S-C Max.oC 85 85 85 85 85 85 85 85

T-X Max.oC 100 100 100 100 100 100 100 100 100 100 100 100 100 100

S2-C2 Max.oC 85 85 85 85 85

T2 Max.oC 100 100 100 100 100 100

Fan weight

S kg 26 37 42 58 74 95 118 174

C kg 27 41 45 62 81 110 141 199

T kg 40 53 67 89 118 158 197 251 299 368 474 687 967 1362

X kg 49 65 82 94 124 166 212 271 323 397 512 755 1064 1430

S2 kg 46 66 76 103 129

C2 kg 53 76 91 117 148

T2 kg 106 132 147 182 235 296

Page 71: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

Soler & PalauSales Department

C/ Llevant, 4 – Polígono Industrial Llevant

08150 Parets del Vallès (Barcelona) - SPAIN

Tel. +34935719420

Fax +34935719421

e-mail: [email protected]

Web: http://www.solerpalau.com

ResearchDesign andHigh Technology

Page 72: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

Single InletCentrifugal Fan

BSB

with Backward Wheels

Page 73: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

2

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

S&P - LA EMPRESADesde su fundación en el año 1951, en la localidad de Ripoll (España),

Soler & Palau, S.A. se ha convertido, desde hace ya bastantes años, en

uno de los líderes mundiales en la fabricación y venta de todo tipo de

equipos de ventilación y de extracción de aire.

Ocho plantas productivas y once empresas filiales propias de comer-

cialización, ubicadas en diversos países y continentes constituyen

el actual Grupo S&P que, con un cualificado equipo de más de 1300

personas, ejerce su actividad en todos los países del mundo.

S&P - LA ESTRATEGIAInvestigación y Desarrollo de productos y tecnología propios; Calidad de

producción por encima de la media de su campo de actividad y Vocación

de Expansión sostenible son, y han sido entre otros, tres de los pilares

fundamentales sobre los que descansa la trayectoria de Soler & Palau, S.A.

Contar hoy con más de 60 Ingenieros titulados en las áreas de

Investigación, Desarrollo, Innovación y Producción; Certificaciones

ISO 9001:2000 y 14001:1996 acrediatadas por AENOR (Soler & Palau

fue la primera empresa registrBSB en España). Laboratorios propios de

ensayo con certificación oficial EN-45001-89 y crecimientos anuales,

sostenidos en las últimas décadas, muy superiores a los de su mercado

son algunos de los logros de la correcta aplicación de la mencionBSB

estrategia de empresa.

Nuevos y apasionantes proyectos que verán la luz muy en breve, están

hoy en marcha en el Grupo S&P.

IntroducciónIntroduction

S&P - THE COMPANYSoler & Palau was founded in 1951 in Ripoll (Spain) and since this

date has become one of the world’s leading companies engaged

in the manufacture, sales and distribution of all types of ventilating

and air moving products. Today Soler & Palau has eight production

plants and eleven wholly owned commercial subsidiary companies

located across the globe. Supporting the design, development

production and commercial facilities are a professional team of

more than 1300 employees who ensure that Soler & Palau continue

to have an active presence in all global market sectors.

S&P - THE STRATEGYAt the heart of Soler & Palau’s company strategy is the continued

substantial investment in product and manufacturing research,

development and quality control. Since 1951 the sustained

investment in these critical areas has enabled Soler & Palau to

offer to its customers products with unparalleled quality and

reliability. These critical elements of success today form the

fundamental cornerstones of the company’s strategy for growth

within increasingly competitive global markets.

Today Soler & Palau has more than 60 highly qualified engineers

working in areas such as product and manufacturing technology

research, development, innovation and production. The engineers

work closely with international safety standards agencies to

ensure that all of Soler & Palau’s products are manufactured and

supplied in accordance with only the very latest mechanical and

electrical safety standards. All products are extensively tested

with the company’s comprehensive in-house airflow, acoustic

and environmental test laboratories which have been officially

certified by AENOR to EN-45001- 89 standards. Currently Soler &

Palau hold both ISO 9001:2000 and ISO 14001:1996 certifications

and were also the first company in Spain to be registered to the

original ISO 9000 standards.

Through operating a continual rigorous program of new and

existing product development and improvement means that Soler

& Palau’s customers are assured that they will continue to receive

products of only the very highest quality and reliability both now

and in the future.

Page 74: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

Soler & Palau S.A. certifies that the BSB seriesshown herein is licensed to bear the AMCA Seal. The ratings shown are based on testsand procedures performed in accordance withAMCA publication 211 and AMCA publication311 and comply with the requirements of the AMCA Certified Ratings Program.

BSB SeriesSINGLE INLET CENTRIFUGAL FAN with Backward Wheels

Page 75: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

4

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB Series

The BSB series is SISW centrifugal fans with high efficiency non-overloading backward curved impellers.

The fans are suitable for supply or exhaust applications in commercial and industrial buildings.

Sizes of this series are in accordance with AMCA standard 99-0098-76 and DIN 323 R20.

Type / Operating Limit

Each fan type has its maximum operating speed and power due to its mechanical design.

The operating limit of BSB series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69.

The BSB series is available in type C, T, X, Z or U.

Model 315 to 630

Type C-U I Model 710 to 1.000

Type T-U II I

Type X-U III II

Type Z-U III

Fan size 315 to 1.400

Volume 1.500 to 100.000 m3/h

TotalPressure

up to 3.000 Pa

Type T

This type has a welded frame giving increased stiffness and rigidity required for higher operating performance.

Fan size 315 to 1.400

Volume 1.500 to 100.000 m3/h

TotalPressure

up to 5.000 Pa

Type X/Z

This structure is similar to Type T but utilizes enhanced bearings to support higher dynamic load necessary for the increased performance.

Type Z is non-standard, for more information, please consult your nearest Kruger office for detail.

Fan size 315 to 1.400

Volume 1.500 to 100.000 m3/h

TotalPressure

up to 5.000 Pa

Type UThis type is manufactured with a special frame with two bearings fixed externally to the airflow eliminating any obstruction to the inlet and allow operation with air temperature up to max. of 180°C.

Fan size 315 to 630

Volume 1.500 to 20.000 m3/h

TotalPressure

up to 2.000 Pa

Type C

This type has a frame fitted on both sides of the fan which gives better strength and rigidity.

It allows mounting in four different orientations.

Single Inlet Centrifugal Fans – Backward wheels

Page 76: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

5

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

Wheel

The wheel of BSB series has backward curved blades manufactured in cold rolled sheet steel with polyester powder coating finish.

Housing

For all sizes except 1250 and above, the housing is manufactured in galvanized sheet steel with the housing fixed to the side plates in “pittsburg lock” form system.

Housing for 1250 and 1400 are manufactured in mild steel finished with polyester powder coating.

Fully welded steel plate housings with painted finish are available for all sizes upon request.

Frame

The frame is manufactured with galvanized angular bars for type “C”. For type “T”, “X” and “U”, they are manufactured with sections of steel and finished with polyester powder coating.

Shaft

Shafts are manufactured from C45 carbon steel using an automatic process for positioning and cutting of the keyways. All dimensional tolerances of the shaft are fully checked to ensure a precision fit and then coated with an anticorrosion varnish after assembly.

Bearings

Bearings used are either deep groove ball bearing type with an adapter sleeve, or spherical roller bearings type sealed at both sides for different duty application classified as below:

Technical Specification

Mounted in a rubber housing Mounted on cast iron supports with grease point

Fan Type

C T X U

Bearing Duty

CM Medium Duty TM Medium Duty XM Medium Duty UM Medium Duty

eg. Model BSB 450 C M TX Extra Heavy Duty XX Extra Heavy Duty UX Extra Heavy Duty

BSB 450 C M

Fan Bearing Duty(L, M, X)

Fan Type(S, C, T, X, Z)

Fan Size(315, 355, 400,...1400)

Page 77: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

6

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

P5

P3

P4

The bearings are lubricated for life and maintenance-free except for TX, XX, UX extra heavy duty bearings. If re-lubrication is necessary, it is recommended to use a lithium base grease suitable for all temperatures within the operational limits.

For type P bearing, please consult your nearest S&P office for detail.

Balancing Quality

All wheels are statically and dynamically balanced to ISO1940 and AMCA 204 – G2.5 standards.

AccessoriesCasing Drain

This option is available when using fans exposed to the atmosphere or operating in high humidity conditions.

Outlet Flanges

Outlet flanges are available upon request.

Inlet Flanges

This option are set against the fan to facilitate installation. It is available in 2 types-“L” flange or “U” flange.

Inspection Doors

The inspection door can be supplied upon request. It can be supplied in one of the three positions (P3, P4 & P5).

Guards

Inlet guard, discharge guards and non-drive end shaft guards are available on request.

Paintings

Special powder-paint coatings of various thicknesses can be supplied on request.

Page 78: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

7

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

7.5

8

0.45

1.5

1

0.2

0.3

2

3

4

6

0.6

0.75 1.5

2.2 3

4.5 6

40

10

15

20

30

60

80

100

15

22.5 30 45 7560

150

225

300

450

2 Pole

4 & 6 Pole

Motor power output (kW)

Co

rrec

tion

Fac

tor,

% m

oto

r p

ow

er o

utp

ut

CW

90º 180º 270º 360º

CCW

Motor Position

The position of the motor for belt drive centrifugal fan is in accordance with AMCA standard 99-2407-66.

Location of motor is determined by facing the drive side of fan and designating the positions by letters W, X, Y, or Z.

Reprinted from AMCA Standard 99-2407-03, Motor Positions for Belt Chain Drive Centrifugal Fans, with the express written permission from the Air Movement and Control Association International, Inc., 30 West 4 University Drive, Arlington Heights, IL 60004-1983.

Motor Selection

The power curve shown on each performance curve represents the absorbed power at the shaft of the fan measured in kW.

To determine the power of the motor to be installed, a correction factors should be applied to compensate for transmission losses.

Fan Rotation and Discharge

The rotation and discharge of the fan is in accordance with AMCA standard 99-2406-83.

The direction of rotation is determined from the drive side of the fan:

CW - clockwise rotationCCW - counter-clockwise rotation

Page 79: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

8

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

Dynamic Pressure

The dynamic pressure and outlet air velocity shown on each curve are both calculated on the full air discharge area, i.e. ducted outlet conditions.

With free outlet conditions the velocity pressure is higher. To determine this new value, multiply the velocity pressure of the ducted outlet obtained from the fan curve by the following correction factor “K”.

[ K = 1.67 ]

Fan Performances calculated with this correction factors are not licensed by AMCA.

Performance

The performance data shown on each diagram has been tested and measured in accordance to AMCA Standard 210 [Fig 12] installation type B (free inlet and ducted outlet condition).

Rating are referred to the standard air density with the total pressure as a function of the air volume, using logarithmic scales.

It is essential that, the same installation type and test standards are used at all times, when comparing fan performances.

Noise

The noise level shown on each diagram refer to the sound power “A-weighted” and the data on the inlet side has been tested and measured in accordance with AMCA Standard 300 diag. 2 - configuration “B”. The noise levels of the fans are determined as follows:

– Sound power level - (“A” scale): Lw (A) as catalogue.

– Octave band spectrum: Lw = Lw(A) + Lw rel. dB [refer to Soler & Palau for more details].

– Sound pressure level:

a) free field Lp(A) = Lw(A) - (20log10d) -11

b) room conditions Lp(A) = Lw(A) - (20log10d) -7

where d = distance of fan (m)

Page 80: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

9

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

Example of Selection

Air Volume Q = 6660 m3/h

Outlet Velocity V = 6.77 m/s

Dynamic Pressure Pd = 27 Pa

Total Pressure Pt = 1250 Pa

Fan Speed N = 1510 rpm

Absorbed Power W = 3.22 kW

Total Efficiency = 71.8 %

Sound Power Level Lw(A) = 81.3 dB(A)

1800

C-UCl. I

6

M. RPMM. kW

TypeOp Limit

290023002613

X-UT-U

Cl. III Cl. II

BSB 560

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 81: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

10

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Op Limit Cl. I Cl. II Cl. IIIType C U T U X UM.kW 2.5 5 10

M.RPM 3200 4200 5300

= 1.22 kg/m3

.2 .3 .4 .5 .6 .8 11 2 3 4 5 6 Q [m3/s]

500 1000 5000 100002000 3000 20000 Q [m3/h]

2 3 4 5 6 8 1010 20 30 40 50 60 80 V [m/s]

1 5 10 50 100 500 1000 Pd [Pa]

100

200

300

400

500

10001000

2000

3000

4000

5000

6000

Pt [Pa]

kW

0.12

0.16

0.2

0.3

0.4

0.5

0.6

0.8

1

1.2

1.6

2

3

4

5

6 8

N [rpm]

1400

1600

1800

2000

2200

2400

2600

2800

3000

3200

3450

3800

4200

4500

4800

5300

48 56 65 70 64 55 41

70

75

80

85

90

95

100

105

Lw (A) [dB(A)]

BSB 315

Page 82: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

11

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB 355

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 83: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

12

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

BSB 400

Page 84: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

13

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB 450

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 85: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

14

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

BSB 500

Page 86: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

15

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB 560

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 87: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

16

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

BSB 630

Page 88: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

17

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB 710

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 89: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

18

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

BSB 800

Page 90: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

19

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB 900

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 91: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

20

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

BSB 1000

Page 92: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

21

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB 1120

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 93: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

22

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

BSB 1250

Page 94: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

23

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB 1400

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.

- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

Page 95: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

24

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB ‘C’BSB 315-400 ‘C’

BSB 450-630 ‘C’

Model A B C D E F G H J K L M N P R S V X Y t t1 w z ød uxs

315 578 518 340 404 223 330 236 480 253 283 451 78 279 38 3 460 319 251 432 8 7 40 28 25 13x18

355 654 578 383 452 247 368 260 548 287 327 479 72 303 30 6 508 359 275 480 8 7 40 33 30 13x18

400 736 650 432 506 274 402 290 612 314 354 506 72 330 38 5 562 404 302 534 8 7 40 33 30 13x18

All Dimensions in mm.

Model A B C D E F F1 G H J K L M N P R S V X Y t t1 w z ød uxs

450 827 726 486 568 308 200 111 322 681 348 388 556 88 364 45 5 624 454 336 596 10 8 50 38 35 13x18

500 918 800 538 638 345 245 120 352 750 385 425 593 88 401 50 5 694 504 373 666 10 8 50 38 35 13x18

560 1030 892 603 714 383 280 125 390 844 433 483 653 100 439 48 7 770 564 411 742 12 8 70 43 40 13x18

630 1157 998 679 800 433 328 110 434 945 483 533 703 100 489 53 6 856 634 461 828 12 8 70 43 40 13x18

All Dimensions in mm.

=

==

z

RA

DC

B

G

FF1

F

= F F1 F

HP

uxs

L

M

X

N

S Y

EJK

V

t1

t

Ød-h7

w

= =

====

P

R

V

H

F uxs

F

YS

L

w

Ød-h7

t1

z

EJK

t

A

DC

B

GX

NM

Page 96: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

25

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB ‘T’

BSB 450-1000 ‘T’

BSB 315-400 ‘T’

Model A B C D E F G H J K L M N P R S V V1 V2 X Y t t1 w z ød uxs

315 578 518 340 404 223 330 236 480 253 283 451 78 279 38 3 460 315 356 395 251 432 8 7 40 28 25 13x18

355 654 578 383 452 247 368 260 548 287 327 481 74 303 30 6 508 355 395 435 275 480 8 7 40 33 30 13x18

400 736 650 432 506 274 402 290 612 314 354 508 74 330 38 5 562 400 438 480 302 534 8 7 40 33 30 13x18

All Dimensions in mm.

Model A B C D E F F1 G H J K L M N P R S V V1 V2 X Y t t1 w z ød uxs

450 827 726 486 568 308 200 111 322 681 348 388 564 96 364 45 5 624 450 487 530 336 596 10 8 50 38 35 13x18

500 918 800 538 638 345 245 120 352 750 385 425 601 96 401 50 5 694 500 541 580 373 666 10 8 50 38 35 13x18

560 1030 892 603 714 383 280 125 390 844 433 483 661 108 439 48 7 770 560 605 646 411 742 12 8 70 43 40 13x18

630 1157 998 679 800 433 328 110 434 945 483 533 711 108 489 53 6 856 630 674 716 461 828 12 8 70 43 40 13x18

710 1302 1120 765 898 479 360 150 484 1057 529 579 763 114 535 63 7 954 710 751 796 507 926 14 9 70 48.5 45 17x22

800 1468 1254 862 1006 533 405 171 540 1180 583 633 817 114 589 74 7 1062 800 837 886 561 1034 14 9 70 48.5 45 17x22

900 1648 1408 971 1130 595 455 189 604 1319 645 695 906 141 651 89 7 1186 900 934 986 623 1158 16 10 90 59 55 17x22

1000 1810 1540 1066 1266 663 500 200 656 1450 713 763 974 141 719 90 9 1322 1000 1043 1086 691 1294 16 10 90 59 55 17x22

All Dimensions in mm.

S

P

=

H

F = ux s=

RD

A

CG

B

F=

V1 V2

E

J

K

w

X

Y

M

L

N

V

Ød-h 7

t1

z

t

S

HP

A

RD

C

G

= F F1 F

F1=

= ux s

FF

=

B

K

N

J

E

Y

X

V2V V1

M

L

Ød -h 7

w

t1

zt

Page 97: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

26

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB ‘T’BSB 1120-1400 ‘T’

= = ==

==

N

X

J

E

K

PF uxs

HF

F

RD

A

C

G

B

F

M

S Y

w

Ød-h7

z

V V2V1

t1

t

L

Model A B C D E F G H J K L M N P R S V V1 V2 X Y t t1 w z ød uxs

1120 2033 1725 1200 1422 744 290 748 1630 804 870 1146 133 800 95 9 1478 1120 1180 1226 772 1450 18 11 90 64 60 17x22

1250 2285 1930 1353 1524 803 300 830 1831 878 953 1232 148 859 99 9 1580 1250 1303 1358 831 1552 18 11 110 69 65 17x22

1400 2568 2170 1515 1794 934 310 963 2057 1009 1084 1381 166 990 113 13 1850 1400 1480 1506 962 1822 20 12 110 74.5 70 17x22

All Dimensions in mm.

Page 98: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

27

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB ‘X’

BSB 450-1000 ‘X’

BSB 315-400 ‘X’

Model A B C D E F G H J K L M N P R S V V1 V2 X Y t t1 w z ød uxs

315 578 518 340 404 223 330 236 480 253 283 457 84 279 38 3 460 315 356 395 251 432 8 7 40 33 30 13x18

355 654 578 383 452 247 368 260 548 287 327 503 96 303 30 6 508 355 395 435 275 480 10 8 50 38 35 13x18

400 736 650 432 506 274 402 290 612 314 354 530 96 330 38 5 562 400 438 480 302 534 10 8 50 38 35 13x18

All Dimensions in mm.

Model A B C D E F F1 G H J K L M N P R S V V1 V2 X Y t t1 w z ød uxs

450 827 726 486 568 308 200 111 322 681 348 388 586 118 364 45 5 624 450 487 530 336 596 12 8 70 43 40 13x18

500 918 800 538 638 345 245 120 352 750 385 425 623 118 401 50 5 694 500 541 580 373 666 12 8 70 43 40 13x18

560 1030 892 603 714 383 280 125 390 844 433 483 667 114 439 48 7 770 560 605 646 411 742 14 9 70 48.5 45 13x18

630 1157 998 679 800 433 328 110 434 945 483 533 717 114 489 53 6 856 630 674 716 461 828 14 9 70 48.5 45 13x18

710 1302 1120 765 898 479 360 150 484 1057 529 579 787 138 535 63 7 954 710 751 796 507 926 14 9 90 53.5 50 17x22

800 1468 1254 862 1006 533 405 171 540 1180 583 633 841 138 589 74 7 1062 800 837 886 561 1034 14 9 90 53.5 50 17x22

900 1648 1408 971 1130 595 455 189 604 1319 645 695 911 146 651 89 7 1186 900 934 986 623 1158 18 11 90 64 60 17x22

1000 1810 1540 1066 1266 663 500 200 656 1450 713 763 979 146 719 90 9 1322 1000 1043 1086 691 1294 18 11 90 64 60 17x22

All Dimensions in mm.

S

P

=

H

F = ux s=

RD

A

CG

B

F=

V1 V2

E

J

K

w

X

Y

M

L

N

V

Ød-h 7

t1

z

t

S

HP

A

RD

C

G

= F F1 F

F1=

= ux s

FF

=

B

K

N

J

E

Y

X

V2V V1

M

L

Ød -h 7

w

t1

zt

Page 99: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

28

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB ‘X’BSB 1120-1400 ‘X’

Model A B C D E F G H J K L M N P R S V V1 V2 X Y t t1 w z ød uxs

1120 2033 1725 1200 1422 744 290 748 1630 804 870 1173 160 800 95 9 1478 1120 1180 1226 772 1450 18 11 110 69 65 17x22

1250 2285 1930 1353 1524 803 300 830 1831 878 953 1250 166 859 99 9 1580 1250 1303 1356 831 1552 20 12 110 74.5 70 17x22

1400 2568 2170 1515 1794 934 310 963 2057 1009 1084 1396 181 990 113 13 1850 1400 1480 1506 962 1822 22 14 110 85 80 17x22

All Dimensions in mm.

= = ==

==

N

X

J

E

K

PF uxs

HF

F

RD

A

C

G

B

F

M

S Y

w

Ød-h7

z

V V2V1

t1

t

L

Page 100: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

29

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB ‘UI’

BSB 450-1000 ‘UI’

BSB 315-400 ‘UI’

Model A B C D E F G H J K L M N P R S V V1 V2 X Y t t1 w z ød uxs

315 578 518 340 404 223 330 236 480 253 705 60 279 38 274 3 460 315 356 395 251 432 8 7 40 28 25 13x18

355 654 578 383 452 247 368 260 548 287 765 60 303 30 300 6 508 355 395 435 275 480 8 7 40 33 30 13x18

400 736 650 432 506 274 402 290 612 314 812 60 330 38 320 5 562 400 438 480 302 534 8 7 40 33 30 13x18

All Dimensions in mm.

Model A B C D E F F1 G H J K L M N P R S V V1 V2 X Y t t1 w z ød uxs

450 827 726 486 568 308 200 111 322 681 348 876 80 364 45 340 5 624 450 487 530 336 596 10 8 50 38 35 13x18

500 918 800 538 638 345 245 120 352 750 385 933 80 401 50 360 5 694 500 541 580 373 666 10 8 50 38 35 13x18

560 1030 892 603 714 383 280 125 390 844 433 1018 90 439 48 378 7 770 560 605 646 411 742 12 8 70 43 40 13x18

630 1157 998 679 800 433 328 110 434 945 483 1090 90 489 53 400 6 856 630 674 716 461 828 12 8 70 43 40 13x18

710 1302 1120 765 898 479 360 150 484 1057 529 1156 90 535 63 420 7 954 710 751 796 507 926 14 9 70 48.5 45 17x22

800 1468 1254 862 1006 533 405 171 540 1180 583 1228 90 589 74 440 7 1062 800 837 886 561 1034 14 9 70 48.5 45 17x22

900 1648 1408 971 1130 595 455 189 604 1319 645 1360 110 651 89 490 7 1186 900 934 986 623 1158 16 10 90 59 55 17x22

1000 1810 1540 1066 1266 663 500 200 656 1450 713 1448 110 719 90 510 9 1322 1000 1043 1086 691 1294 16 10 90 59 55 17x22

All Dimensions in mm.

=P

=

AD

C

=H

F = uxsF

V2 V1 V

RG

B

t1

z

Ød-h7

ML

QEJ

SY

w

XN

t

z

G

B

= F F1 F

H

= UxS

A

DC

R

=F

F1F

=

P

V2 V1 V

N

X

Y S

E

J

K

Q

M

L

t1

t

Ød-h7

w

Page 101: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

30

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB ‘UI’BSB 1120-1400 ‘UI’

Model A B C D E F G H J K L M N P R S V V1 V2 X Y t t1 w z ød uxs

1120 2033 1725 1200 1422 744 290 748 1630 804 1680 110 800 95 572 9 1478 1120 1180 1226 772 1450 18 11 90 64 60 17x22

1250 2285 1930 1353 1524 803 300 830 1831 878 1844 140 859 99 632 9 1580 1250 1303 1356 831 1552 18 11 110 69 65 17x22

1400 2568 2170 1515 1794 934 310 963 2057 1009 2060 140 990 113 717 13 1850 1400 1480 1506 962 1822 20 12 110 74.5 70 17x22

All Dimensions in mm.

VV2 V1

F

P

uxs=

H

F

DA

CR

G

=

B

E

L

J QM

w

Y S

NX

t

Ød-h7

t1

z

F=

=

= = F

Page 102: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

31

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB ‘UII’BSB 315-400 ‘UII’

BSB 450-1000 ‘UII’

Model A B C D E F G H J K L M N P R S V V1 V2 X Y t t1 w z ød uxs

315 578 518 340 404 223 330 236 480 253 705 60 279 38 274 3 460 315 356 395 251 432 8 7 40 28 25 13x18

355 654 578 383 452 247 368 260 548 287 765 60 303 30 300 6 508 355 395 435 275 480 8 7 40 33 30 13x18

400 736 650 432 506 274 402 290 612 314 812 60 330 38 320 5 562 400 438 480 302 534 8 7 40 33 30 13x18

All Dimensions in mm.

Model A B C D E F F1 G H J K L M N P R S V V1 V2 X Y t t1 w z ød uxs

450 827 726 486 568 308 200 111 322 681 348 876 70 364 45 340 5 624 450 487 530 336 596 10 8 50 38 35 13x18

500 918 800 538 638 345 245 120 352 750 385 933 70 401 50 360 5 694 500 541 580 373 666 10 8 50 38 35 13x18

560 1030 892 603 714 383 280 125 390 844 433 1018 90 439 48 378 7 770 560 605 646 411 742 12 8 70 43 40 13x18

630 1157 998 679 800 433 328 110 434 945 483 1090 90 489 53 400 6 856 630 674 716 461 828 12 8 70 43 40 13x18

710 1302 1120 765 898 479 360 150 484 1057 529 1176 110 535 63 420 7 954 710 751 796 507 926 14 9 90 53.5 50 17x22

800 1468 1254 862 1006 533 405 171 540 1180 583 1248 110 589 74 440 7 1062 800 837 886 561 1034 14 9 90 53.5 50 17x22

900 1648 1408 971 1130 595 455 189 604 1319 645 1360 110 651 89 490 7 1186 900 934 986 623 1158 18 11 90 64 60 17x22

1000 1810 1540 1066 1266 663 500 200 656 1450 713 1448 110 719 90 510 9 1322 1000 1043 1086 691 1294 18 11 90 64 60 17x22

All Dimensions in mm.

=P

=

AD

C

=H

F = uxsF

V2 V1 V

RG

B

t1

z

Ød-h7

ML

QEJ

SY

w

XN

t

z

G

B

= F F1 F

H

= UxS

A

DC

R

=F

F1F

=

P

V2 V1 V

N

X

Y S

E

J

K

Q

M

L

t1

t

Ød-h7

w

Page 103: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

32

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

BSB ‘UII’BSB 1120-1400 ‘UII’

Model A B C D E F G H J L M N P Q R S V V1 V2 X Y t t1 w z ød uxs

1120 2033 1725 1200 1422 744 290 748 1630 804 1710 140 800 95 572 9 1478 1120 1180 1226 772 1450 18 11 110 69 65 17x22

1250 2285 1930 1353 1524 803 300 830 1831 878 1844 140 859 99 632 9 1580 1250 1303 1356 831 1552 20 12 110 74.5 70 17x22

1400 2568 2170 1515 1794 934 310 963 2057 1009 2060 140 990 113 717 13 1850 1400 1480 1506 962 1822 22 14 110 85 80 17x22

All Dimensions in mm.

VV2 V1

F

P

uxs=

H

F

DA

CR

G

=

B

E

L

J QM

w

Y S

NX

t

Ød-h7

t1

z

F=

=

= = F

Page 104: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

33

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

AccessoriesInlet Flange

N x Ød

ØA

ØC

ØB

H H

Model A B C H n x d

315 315 356 395 120 8 x 10

355 355 395 435 120 8 x 10

400 400 438 480 120 8 x 10

450 450 487 530 120 8 x 10

500 500 541 580 120 8 x 10

560 560 605 646 120 8 x 10

630 630 674 716 120 8 x 10

710 710 751 796 120 8 x 10

800 800 837 886 120 12 x 12

900 900 934 986 120 12 x 12

1000 1000 1043 1086 120 12 x 12

1120 1120 1180 1226 200 14 x 12

1250 1250 1303 1356 200 16 x 14

1400 1400 1480 1506 200 18 x 14

All Dimensions in mm.

Outlet Flange

Model A B C D E F G

315 223 251 279 404 432 460 28

355 247 275 303 452 480 508 28

400 274 302 330 506 534 562 28

450 308 336 364 568 596 624 28

500 345 373 401 638 666 694 28

560 383 411 439 714 742 770 28

630 433 461 489 800 828 856 28

710 479 507 535 898 926 954 28

800 533 561 589 1006 1034 1062 28

900 595 623 651 1130 1158 1186 28

1000 663 691 719 1266 1294 1322 28

1120 744 772 800 1422 1450 1478 28

1250 803 831 859 1524 1576 1624 50

1400 934 962 990 1794 1860 1920 63

All Dimensions in mm.

CB

A

D

Ø9

G

F E

F E

A

CB

D

G

315-1120

1250-1400

Page 105: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

34

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries

Operational Limits - “BSB”

315 355 400 450 500 560 630 710 800 900 1000 1120 1250 1400

MaximumAbsorbedPower

C kW 2.5 3 3.5 4 5 6 7

T kW 5 6 7 10 11 13 16 9 11 14 16 20 25 35

X kW 10 12 15 18 22 26 32 20 25 30 40 50 55 70

Z kW 40 50 60 80 100 110 150

UI kW 2.5 3 3.5 4 5 6 7 9 11 14 16 20 25 35

UII kW 5 6 7 10 11 13 16 20 25 30 40 50 55 70

UIII kW 10 12 15 18 22 26 32 40 50 60 80 100 110 150

MaximumFan Speed

C rpm 3200 2800 2500 2200 1950 1800 1500

T rpm 4200 3700 3300 2900 2550 2300 2000 1350 1200 1050 950 850 780 680

X rpm 5300 4700 4200 3600 3200 2900 2500 1800 1600 1400 1250 1150 1000 880

Z rpm 2250 2000 1750 1600 1450 1300 1100

UI rpm 3200 2800 2500 2200 1950 1800 1500 1350 1200 1050 950 850 780 680

UII rpm 4200 3700 3300 2900 2550 2300 2000 1800 1600 1400 1250 1150 1000 880

UIII rpm 5300 4700 4200 3600 3200 2900 2500 2250 2000 1750 1600 1450 1300 1100

TemperatureRangeMin. -20oC

C Max.oC 85 85 85 85 85 85 85

T-X-Z Max.oC 100 100 100 100 100 100 100 100 100 100 100 100 100 100

UI-UII-UIII Max.oC 180 180 180 180 180 180 180 180 180 180 180 180 180 180

Fan weight

C kg 19 25 33 42 55 76 101

T kg 33 49 59 71 89 123 152 189 228 285 338 575 769 1048

X kg 35 51 60 73 91 126 154 192 232 289 345 586 782 1068

UI kg 32 45 55 68 83 112 140 180 250 311 366 601 833 1139

UII kg 33 46 55 69 84 113 142 182 252 314 369 606 839 1152

Page 106: Research Design and High Technology · The operating limit of FDA series - fan type is design to meet the requirement of class I, II and III limit as defined in AMCA standard 99-2408-69

35

Technical specifications for information purposes only. Soler & Palau, S.A. reserves the right to change them without any previous notice.

BSBSeries