rembo renewable energy monitoring box -...
TRANSCRIPT
Pôle ENR/ESE
REMBO
Renewable Energy Monitoring Box W. Keilholz, V. Partenay, P. Riederer
CSTB Sophia Antipolis
PERFORMANCE ANALYSIS
Where are the system borders?
Performances measurement (example of a simple geothermal heat pump)
Definition from the SEPEMO project
ECS
Plancher
chauffant
Sonde
géothermique
PAC
Pompe
chauffage
Appoint
électrique
SPF4SPF3
SPF2 SPF1
Pompe
géothermique
PERFORMANCE ANALYSIS
What to measure and where?
Plancher chauffant
Sonde
géothermique
Schéma Type 1
T3T1
Q
T2Ibât2
Is
QT2
T1T3
Cel-aux,s
Cel-PAC
Cel-aux,bât2
Text
Tamb
Performances measurement (example of a simple geothermal heat pump)
Definition from the SEPEMO project
Renewable Energy Monotoring Box – REMBO
Measurement concept
Example of the monitoring of a geothermal heat pump
Measurement architecture
• State measurements (temperatures, pressure, humidity etc.)
• Energy measurements (heating and cooling, electricity)
• Flow measurements (water, gaz, fuel etc.)
• Data acquisition by Modbus or wireless networks directly or
using analogue digital converters
Layout of monitoring and supervision system
Monitoring PC connected to Ethernet / ADSL
Comparison of measured performances
between Monitoring kit and laboratory test bench
Integrated performance factor (PF)
TEST: Cyclic operation of HP
Temperature difference supply-return
Website for the supervision and analysis
First level
Quality assurance
System typologies with sensor identification
Website Valpac-Online
« Performance tool »
Website Valpac-Online
« Project level »
First monitoring results
Example 1
Oversized system
Pump on the building side
is operating continuously
Low efficient pumps
First monitoring results
Example 2
Oversized system
Pump on the building side
is operating continuously
Efficient pumps
First monitoring results
Example 3
Extremely oversized system
Pumps are operating continuously
Example 1
Tcond : 31 °C
Tevap : 7 °C
SPF1 : 5.3
Example 2
Tcond : 35 °C
Tevap : 5 °C
SPF1 4.5
First monitoring results
Impact of system temperatures