REKABENTUK SISTEM
SANITARI
REKABENTUK SISTEM
SANITARI
Jenis Sistem :
Single stack system
Modified single stack system
Ventilated system
Ventilated stack system
Two pipe system
PENGUNAAN JADUAL & GRAF
DIRUJUK DARIPADA :
“PALING – uPVC SOIL, WASTE & VENT
PIPES & FITTINGS SYSTEM”
BASED ON BS 5572:1978
“CODE of PRACTICE FOR SANITARY
PIPEWORK”
PENGUNAAN JADUAL & GRAF
To Determine Discharge Pipe:
TABLE 6 : Probability data & discharge
units for sanitary appliances connected
to sanitary pipe work above ground
TABLE 7 : Maximum number of
discharge unit to be allowed on
horizontal branches
PENGUNAAN JADUAL & GRAF
To Determine Stack Pipe:
Graph 3 : Proportional flow and
discharge units
CONTOH PENGIRAAN
Example 1 :
Determine the peak flow rate and
diameter of discharge pipe required to
carry the discharges from 44 flats if the
stack loading is to be limited to one-fifth
full bore. Each flat has 1 W.C, 1 wash
basin, a bath and a sink.
CONTOH PENGIRAAN
From TABLE 6:
1 W.C = 12 d.u
1 wash basin = 1 d.u
1 bath = 6 d.u
1 sink = 3 d.u
Total discharge unit/floor = 12+1+6+3 = 22
TOTAL = 44 x 22 = 968 discharge units
CONTOH PENGIRAAN
From GRAPH 3 :
968 discharge units are equivalent to a
flow load of approximately 6.2 litres/sec
Use 125 mm stack
( as 125 mm stack at one-fifth loading
can carry 8 litres/sec )
CONTOH PENGIRAAN
Example 2 :
Determine the peak flow rate and
diameter of discharge pipe to receive
the discharge from 20 W.C.’s and 20
wash basins used by females in an
office block.
CONTOH PENGIRAAN
20 W.C’s (female) x 45 = 900
20 wash basins x 5 = 100
Total discharge units 1000
The flow rate for 1000 d.u = 6.4 litres/sec
Use 100 mm stack
( as 100 mm stack at one-quater loading can
carry 7 litres/sec )
PENGUNAAN JADUAL & GRAF
To Determine Branch Pipe:
TABLE 7 : Maximum number of
discharge units to be allowed on
horizontal branches
Branch pipe < = Stack pipe
PENGUNAAN JADUAL & GRAF
To Determine Stack and Vent Pipe:
TABLE 5 / Graph 3 : Diameter of Stack
pipes
TABLE 8 : Diameter of ventilating pipes
CONTOH PENGIRAAN
Tingkat bawah
Tingkat atas
Bilik air
Bilik air
A B
C D
E F
G
H
Stack pipe
PENYELESAIAN
Branch pipe
Pipe AB
Fr tb 6 pg 33 – Discharge unit = 1bath +
1 Shower +
1 basin
= 6+1+1
=8
Fr tb 7 pg 34 – Size = 38mm
PENYELESAIAN
Branch pipe
Pipe CD
Fr tb 6 pg 33 – discharge unit = 1WC
= 12
Fr tb 7 pg 34 – Size = 38mm but the internal dia of a discharge pipe from wc should be not less than the internal dia of the wc pan outlet to which it is attach, with a min internal dia of 75mm. Refer pg 28.
So, use 75mm pipe
PENYELESAIAN
Branch pipe
Pipe EF
Fr tb 6 pg 33 – discharge unit = 1basin
+1shower
= 1+1 = 2
Fr tb 7 pg 34 – Size = 38mm
PENYELESAIAN
Branch pipe
Pipe GH
Fr tb 6 pg 33 – discharge unit = 1 WC
(domestic)
= 12
Fr tb 7 pg 34 – Size = 75mm
PENYELESAIAN
Stack pipe
– Total discharge unit
= AB + CD =20
Fr tb 5 pg 32 – Size = 50mm
SEKIAN