regulation (eu) n. 2016/2281 for comfort chillers...for air-to-water comfort chillers: air flow...

275
Climaveneta Technical Documentation FX2-G04_0252_1593_202008_EN REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS Ecodesign requirements for cooling products AIR COOLED CHILLERS FX2-G04 0252 - 1593 Cooling Capacity Range 252 - 1572 [kW] - (EN14511 VALUE) Nominal Cooling Capacity at TdesignC Range 252 - 1572 [kW]

Upload: others

Post on 25-Mar-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

Climaveneta Technical DocumentationFX2-G04_0252_1593_202008_EN

REGULATION (EU) N. 2016/2281 FOR COMFORTCHILLERSEcodesign requirements for cooling products

AIR COOLED CHILLERS

FX2-G04 0252 - 1593

Cooling Capacity Range 252 - 1572 [kW] - (EN14511 VALUE)Nominal Cooling Capacity at TdesignC Range 252 - 1572 [kW]

Page 2: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

1. REGULATION (EU) N. 2016/2281 FOR COMFORTCHILLERS1.1 Scope of the document 31.2 REGULATION (UE) N. 2016/2281 description 31.3 Description of the data declared by Mitsubishi

Electric Hydronics & IT Cooling Systems3

2. CLIMAVENETA CONTENTS UNIT2.1 Table index 4

3. TECHNICAL PARAMETERS3.1 FX2-G04 /A 53.2 FX2-G04 /SL-A 185

FX2-G04

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 2

Page 3: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0

1. REGULATION (EU) N. 2016/2281 FOR COMFORTCHILLERS1.1 Scope of the documentThis document is compliant with the Commission Regulation (EU) N.2016/2281 regarding “REQUIREMENTS FOR PRODUCT INFORMATION”(Annex II, Point 5). In particular, it deals with comfort chillers and containsinformation required by Table 10 of the above-mentioned regulation, whichis entitled “Information requirements for comfort chillers”.

1.2 REGULATION (UE) N. 2016/2281 descriptionThe COMMISSION REGULATION (EU) N. 2016/2281 of 30 November2016, implementing Directive 2009/125/EC of the European Parliament andof the Council, establishes eco-design requirements for the placing on themarket and/or putting into service of: air heating products with a ratedheating capacity which does not exceed 1MW, cooling products and hightemperature process chillers with a rated cooling capacity which do notexceed 2 MW, and all fan coil units. All these energy-related products aredefined in Article 2 of the Regulation in question.

1.3 Description of the data declared by Mitsubishi Electric Hydronics &IT Cooling Systems

- Comfort chiller: a cooling product designed with the aim of attaining andmaintaining the desired indoor temperature for the thermal comfort ofhuman beings, whose evaporator extracts heat from a water-basedcooling system designed to operate at leaving chilled watertemperatures greater than or equal to +2°C.

- Rated cooling capacity (Prated,c): the cooling capacity of a comfortchiller when providing space cooling at standard rating conditions,expressed in kW.

- Low temperature application: application where the comfort chillerdelivers its declared capacity for cooling at an indoor heat exchangeroutlet temperature of 7°C.

- Medium temperature application: application where the comfort chillerdelivers its declared capacity for cooling at an indoor heat exchangeroutlet temperature of 18°C.

- Seasonal energy efficiency of the space cooling (ηs,c): ratio betweenthe space cooling demand pertaining to the designated cooling season,and the annual energy consumption required to meet this demand,expressed in %.

- Seasonal Energy Efficiency Ratio (SEER): the overall energy efficiencyratio of the comfort chiller, representative for the cooling season,calculated as the reference annual cooling demand divided by theannual energy consumption for cooling.

- Degradation coefficient for chillers: measure of efficiency loss due tocycling of the chiller.

- Off mode: a condition in which the chiller is connected to the mainpower source and is not providing any function.

- Thermostat off-mode: condition corresponding to the hours with nocooling load and activated cooling function, whereby the cooling functionis switched on but the chiller is not operational.

- Crankcase heater mode: condition in which a heating device is activatedto avoid the refrigerant migrating to the compressor so as to limit therefrigerant concentration in oil when the compressor is started.

- Standby mode: condition where the chiller is connected to the mainspower source and depends on energy input from the mains powersource to work as intended. The unit provides only the followingfunctions, which may persist for an indefinite time: reactivation function,or reactivation function and only an indication of enabled reactivationfunction, and/or information or status display.

- Capacity control: the ability of a chiller to change its cooling capacity bychanging the volumetric flow rate of at least one of the fluids needed tooperate the refrigeration cycle.

- Sound power level (LWA): the A-weighted sound power level, indoorsand/or outdoors, expressed in dB.

- Global warming potential (GWP) of the refrigerant: the 100-year climaticwarming potential of one kilogram of a greenhouse gas relative to onekilogram of dioxide (CO2).

3

Page 4: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

2. CLIMAVENETA CONTENTS UNIT2.1 Table indexAIR COOLED CHILLERS

FX2-G04 0252 - 1593Cooling Capacity Range 252 - 1572 [kW]Nominal Cooling Capacity at TdesignC Range 252 - 1572 [kW]

Units Version Size Pag.FX2-G04 A 50252 0252 0252 0252 0252

0252 0252 0252 0252 02520302 0302 0302 0302 03020302 0302 0302 0302 03020322 0322 0322 0322 03220322 0322 0322 0322 03220352 0352 0352 0352 03520352 0352 0352 0352 03520402 0402 0402 0402 04020402 0402 0402 0402 04020452 0452 0452 0452 04520452 0452 0452 0452 04520512 0512 0512 0512 05120512 0512 0512 0512 05120572 0572 0572 0572 05720572 0572 0572 0572 05720652 0652 0652 0652 06520652 0652 0652 0652 06520772 0772 0772 0772 07720772 0772 0772 0772 07720902 0902 0902 0902 09020902 0902 0902 0902 09020972 0972 0972 0972 09720972 0972 0972 0972 09721052 1052 1052 1052 10521052 1052 1052 1052 10521152 1152 1152 1152 11521152 1152 1152 1152 11521243 1243 1243 1243 12431243 1243 1243 1243 12431373 1373 1373 1373 13731373 1373 1373 1373 13731503 1503 1503 1503 15031503 1503 1503 1503 15031593 1593 1593 1593 15931593 1593 1593 1593 1593

FX2-G04 SL-A 1850252 0252 0252 0252 02520302 0302 0302 0302 03020322 0322 0322 0322 03220352 0352 0352 0352 03520402 0402 0402 0402 04020452 0452 0452 0452 04520512 0512 0512 0512 05120572 0572 0572 0572 05720652 0652 0652 0652 06520772 0772 0772 0772 07720902 0902 0902 0902 09020972 0972 0972 0972 09721052 1052 1052 1052 10521152 1152 1152 1152 11521243 1243 1243 1243 12431373 1373 1373 1373 13731503 1503 1503 1503 15031593 1593 1593 1593 1593

FX2-G04

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 4

Page 5: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /0252-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 253,7Seasonal energy efficiency of the space cooling ηs,c [%] 180,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 254Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 187Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 120Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 73,2Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,33Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,10Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,24

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,237Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 91,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 5

Page 6: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /0252-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 253,7Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 254Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 187Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 120Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 73,2Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,39Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,44Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,35Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,237Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 91,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 6

Page 7: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /0252-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 255,0Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 255Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 188Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 121Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 73,2Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,10Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,24

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,237Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 98,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 95688,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 7

Page 8: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /0252-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 255,0Seasonal energy efficiency of the space cooling ηs,c [%] 188,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 255Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 188Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 121Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 73,2Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,36Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,38Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,35Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,237Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 98,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 95688,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 8

Page 9: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /0252-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 255,0Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 255Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 188Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 121Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 73,2Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,10Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,24

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,237Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 98,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 95688,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 9

Page 10: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /0252-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 253,7Seasonal energy efficiency of the space cooling ηs,c [%] 180,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 254Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 187Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 120Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 73,2Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,33Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,10Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,24

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,237Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 91,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 10

Page 11: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /0252-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 253,7Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 254Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 187Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 120Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 73,2Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,39Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,44Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,35Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,237Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 91,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 11

Page 12: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /0252-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 253,7Seasonal energy efficiency of the space cooling ηs,c [%] 180,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 254Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 187Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 120Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 73,2Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,33Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,10Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,24

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,237Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 91,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 12

Page 13: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /0252-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 255,0Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 255Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 188Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 121Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 73,2Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,10Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,24

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,237Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 98,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 95688,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 13

Page 14: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /0252-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 255,0Seasonal energy efficiency of the space cooling ηs,c [%] 188,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 255Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 188Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 121Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 73,2Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,36Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,38Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,35Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,237Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 98,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 95688,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 14

Page 15: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /0302-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 287,9Seasonal energy efficiency of the space cooling ηs,c [%] 178,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 288Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 212Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 136Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 82,6Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,23Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,98Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,38

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,265Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 92,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 15

Page 16: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /0302-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 287,9Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 288Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 212Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 136Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 82,6Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,33Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,71

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,265Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 92,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 16

Page 17: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /0302-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 289,5Seasonal energy efficiency of the space cooling ηs,c [%] 178,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 290Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 213Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 137Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 82,6Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,20Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,98Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,38

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,265Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 95688,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 17

Page 18: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /0302-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 289,5Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 290Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 213Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 137Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 82,6Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,71

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,265Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 95688,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 18

Page 19: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /0302-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 289,5Seasonal energy efficiency of the space cooling ηs,c [%] 178,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 290Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 213Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 137Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 82,6Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,20Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,98Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,38

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,265Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 95688,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 19

Page 20: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /0302-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 287,9Seasonal energy efficiency of the space cooling ηs,c [%] 178,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 288Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 212Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 136Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 82,6Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,23Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,98Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,38

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,265Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 92,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 20

Page 21: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /0302-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 287,9Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 288Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 212Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 136Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 82,6Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,33Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,71

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,265Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 92,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 21

Page 22: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /0302-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 287,9Seasonal energy efficiency of the space cooling ηs,c [%] 178,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 288Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 212Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 136Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 82,6Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,23Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,98Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,38

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,265Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 92,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 22

Page 23: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /0302-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 289,5Seasonal energy efficiency of the space cooling ηs,c [%] 178,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 290Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 213Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 137Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 82,6Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,20Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,98Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,38

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,265Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 95688,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 23

Page 24: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /0302-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 289,5Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 290Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 213Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 137Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 82,6Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,71

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,265Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 95688,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 24

Page 25: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /0322-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 312,8Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 313Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 230Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 148Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 89,5Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,06Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,47

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 92,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 25

Page 26: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /0322-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 312,8Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 313Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 230Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 148Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 89,5Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,35Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,42Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,26Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,79

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 92,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 26

Page 27: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /0322-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 314,7Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 315Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 232Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 149Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 89,5Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,06Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,47

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 95688,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 27

Page 28: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /0322-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 314,7Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 315Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 232Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 149Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 89,5Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,34Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,38Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,26Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,79

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 95688,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 28

Page 29: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /0322-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 314,7Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 315Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 232Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 149Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 89,5Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,06Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,47

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 95688,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 29

Page 30: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /0322-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 312,8Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 313Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 230Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 148Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 89,5Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,06Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,47

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 92,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 30

Page 31: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /0322-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 312,8Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 313Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 230Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 148Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 89,5Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,35Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,42Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,26Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,79

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 92,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 31

Page 32: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /0322-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 312,8Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 313Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 230Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 148Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 89,5Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,06Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,47

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 92,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 32

Page 33: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /0322-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 314,7Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 315Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 232Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 149Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 89,5Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,06Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,47

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 95688,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 33

Page 34: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /0322-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 314,7Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 315Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 232Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 149Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 89,5Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,34Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,38Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,26Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,79

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 95688,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 34

Page 35: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /0352-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 363,5Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 363Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 268Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 172Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 104Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,39Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,27Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 109800,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 35

Page 36: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /0352-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 363,5Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 363Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 268Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 172Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 104Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,44Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,38Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,59

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,102

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 109800,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 36

Page 37: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /0352-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 364,7Seasonal energy efficiency of the space cooling ηs,c [%] 178,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 365Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 269Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 173Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 104Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,39Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,23Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 114840,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 37

Page 38: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /0352-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 364,7Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 365Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 269Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 173Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 104Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,42Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,32Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,59

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,102

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 114840,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 38

Page 39: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /0352-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 364,7Seasonal energy efficiency of the space cooling ηs,c [%] 178,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 365Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 269Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 173Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 104Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,39Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,23Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 114840,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 39

Page 40: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /0352-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 363,5Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 363Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 268Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 172Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 104Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,39Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,27Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 109800,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 40

Page 41: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /0352-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 363,5Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 363Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 268Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 172Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 104Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,44Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,38Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,59

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,102

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 109800,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 41

Page 42: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /0352-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 363,5Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 363Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 268Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 172Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 104Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,39Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,27Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 109800,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 42

Page 43: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /0352-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 364,7Seasonal energy efficiency of the space cooling ηs,c [%] 178,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 365Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 269Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 173Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 104Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,39Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,23Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 114840,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 43

Page 44: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /0352-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 364,7Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 365Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 269Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 173Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 104Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,42Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,32Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,59

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,102

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 114840,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 44

Page 45: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /0402-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 402,4Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 402Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 297Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 191Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 114Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,04Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 109800,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 45

Page 46: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /0402-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 402,4Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 402Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 297Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 191Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 114Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,42Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,23Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,56

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,124

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 109800,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 46

Page 47: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /0402-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 405,0Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 405Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 298Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 192Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 114Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,29Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,04Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 114840,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 47

Page 48: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /0402-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 405,0Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 405Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 298Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 192Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 114Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,39Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,24Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,56

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,124

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 114840,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 48

Page 49: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /0402-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 405,0Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 405Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 298Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 192Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 114Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,29Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,04Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 114840,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 49

Page 50: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /0402-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 402,4Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 402Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 297Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 191Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 114Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,04Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 109800,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 50

Page 51: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /0402-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 402,4Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 402Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 297Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 191Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 114Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,42Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,23Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,56

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,124

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 109800,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 51

Page 52: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /0402-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 402,4Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 402Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 297Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 191Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 114Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,04Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 109800,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 52

Page 53: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /0402-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 405,0Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 405Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 298Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 192Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 114Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,29Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,04Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 114840,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 53

Page 54: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /0402-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 405,0Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 405Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 298Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 192Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 114Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,39Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,24Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,56

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,124

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 114840,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 54

Page 55: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /0452-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 442,8Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 443Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 326Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 210Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 126Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,27Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,45

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 128088,01For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 55

Page 56: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /0452-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 442,8Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 443Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 326Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 210Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 126Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,38Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,29Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,75

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,127

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 128088,01For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 56

Page 57: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /0452-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 445,4Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 445Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 328Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 211Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 126Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,45

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 133992,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 57

Page 58: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /0452-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 445,4Seasonal energy efficiency of the space cooling ηs,c [%] 188,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 445Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 328Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 211Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 126Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,29Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,75

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,127

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 133992,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 58

Page 59: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /0452-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 445,4Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 445Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 328Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 211Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 126Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,45

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 133992,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 59

Page 60: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /0452-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 442,8Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 443Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 326Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 210Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 126Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,27Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,45

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 128088,01For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 60

Page 61: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /0452-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 442,8Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 443Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 326Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 210Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 126Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,38Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,29Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,75

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,127

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 128088,01For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 61

Page 62: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /0452-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 442,8Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 443Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 326Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 210Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 126Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,27Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,45

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 128088,01For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 62

Page 63: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /0452-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 445,4Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 445Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 328Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 211Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 126Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,45

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 133992,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 63

Page 64: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /0452-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 445,4Seasonal energy efficiency of the space cooling ηs,c [%] 188,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 445Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 328Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 211Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 126Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,29Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,75

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,127

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 133992,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 64

Page 65: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /0512-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 516,1Seasonal energy efficiency of the space cooling ηs,c [%] 180,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 516Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 380Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 244Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,46

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 146376,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 65

Page 66: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /0512-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 516,1Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 516Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 380Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 244Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,39Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,14Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,71

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,130

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 146376,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 66

Page 67: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /0512-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 519,2Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 519Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 383Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 246Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,26Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,46

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 153108,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 67

Page 68: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /0512-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 519,2Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 519Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 383Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 246Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,15Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,71

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,130

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 153108,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 68

Page 69: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /0512-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 519,2Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 519Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 383Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 246Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,26Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,46

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 153108,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 69

Page 70: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /0512-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 516,1Seasonal energy efficiency of the space cooling ηs,c [%] 180,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 516Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 380Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 244Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,46

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 146376,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 70

Page 71: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /0512-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 516,1Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 516Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 380Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 244Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,39Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,14Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,71

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,130

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 146376,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 71

Page 72: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /0512-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 516,1Seasonal energy efficiency of the space cooling ηs,c [%] 180,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 516Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 380Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 244Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,46

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 146376,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 72

Page 73: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /0512-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 519,2Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 519Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 383Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 246Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,26Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,46

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 153108,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 73

Page 74: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /0512-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 519,2Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 519Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 383Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 246Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,15Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,71

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,130

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 100,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 153108,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 74

Page 75: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /0572-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 570,4Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 570Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 420Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 270Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 164Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 146376,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 75

Page 76: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /0572-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 570,4Seasonal energy efficiency of the space cooling ηs,c [%] 188,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 570Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 420Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 270Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 164Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,37Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,20Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,130

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 146376,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 76

Page 77: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /0572-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 572,9Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 573Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 422Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 271Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 164Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 102,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 153108,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 77

Page 78: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /0572-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 572,9Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 573Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 422Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 271Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 164Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,32Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,21Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,130

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 102,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 153108,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 78

Page 79: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /0572-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 572,9Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 573Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 422Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 271Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 164Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 102,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 153108,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 79

Page 80: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /0572-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 570,4Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 570Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 420Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 270Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 164Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 146376,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 80

Page 81: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /0572-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 570,4Seasonal energy efficiency of the space cooling ηs,c [%] 188,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 570Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 420Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 270Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 164Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,37Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,20Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,130

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 146376,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 81

Page 82: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /0572-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 570,4Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 570Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 420Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 270Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 164Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 146376,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 82

Page 83: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /0572-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 572,9Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 573Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 422Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 271Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 164Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 102,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 153108,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 83

Page 84: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /0572-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 572,9Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 573Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 422Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 271Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 164Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,32Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,21Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,130

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 102,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 153108,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 84

Page 85: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /0652-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 674,3Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 674Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 497Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 319Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 192Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,26Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,43

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,454Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 182988,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 85

Page 86: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /0652-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 674,3Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 674Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 497Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 319Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 192Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,39Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,21Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,72

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,454Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,136

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 182988,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 86

Page 87: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /0652-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 678,4Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 678Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 500Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 321Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 192Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,27Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,04Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,43

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,454Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 102,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 191412,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 87

Page 88: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /0652-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 678,4Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 678Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 500Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 321Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 192Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,37Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,21Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,72

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,454Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,136

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 102,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 191412,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 88

Page 89: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /0652-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 678,4Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 678Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 500Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 321Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 192Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,27Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,04Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,43

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,454Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 102,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 191412,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 89

Page 90: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /0652-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 674,3Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 674Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 497Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 319Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 192Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,26Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,43

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,454Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 182988,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 90

Page 91: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /0652-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 674,3Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 674Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 497Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 319Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 192Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,39Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,21Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,72

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,454Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,136

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 182988,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 91

Page 92: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /0652-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 674,3Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 674Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 497Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 319Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 192Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,26Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,43

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,454Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 182988,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 92

Page 93: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /0652-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 678,4Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 678Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 500Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 321Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 192Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,27Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,04Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,43

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,454Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 102,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 191412,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 93

Page 94: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /0652-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 678,4Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 678Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 500Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 321Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 192Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,37Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,21Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,72

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,454Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,136

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 102,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 191412,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 94

Page 95: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /0772-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 776,7Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 777Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 572Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 368Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 222Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,08Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,486Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,309

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 96,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 219564,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 95

Page 96: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /0772-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 776,7Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 777Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 572Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 368Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 222Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,37Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,26Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,486Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,142

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 96,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 219564,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 96

Page 97: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /0772-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 781,0Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 781Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 575Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 370Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 222Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,08Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,486Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,309

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 103,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 229680,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 97

Page 98: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /0772-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 781,0Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 781Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 575Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 370Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 222Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,34Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,26Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,486Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,142

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 103,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 229680,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 98

Page 99: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /0772-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 781,0Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 781Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 575Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 370Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 222Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,08Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,486Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,309

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 103,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 229680,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 99

Page 100: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /0772-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 776,7Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 777Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 572Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 368Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 222Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,08Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,486Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,309

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 96,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 219564,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 100

Page 101: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /0772-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 776,7Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 777Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 572Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 368Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 222Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,37Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,26Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,486Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,142

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 96,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 219564,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 101

Page 102: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /0772-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 776,7Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 777Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 572Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 368Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 222Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,08Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,486Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,309

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 96,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 219564,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 102

Page 103: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /0772-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 781,0Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 781Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 575Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 370Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 222Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,08Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,486Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,309

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 103,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 229680,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 103

Page 104: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /0772-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 781,0Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 781Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 575Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 370Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 222Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,34Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,26Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,486Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,142

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 103,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 229680,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 104

Page 105: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /0902-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 896,9Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 897Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 661Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 425Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 256Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,22Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,54

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,681Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,329

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 97,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 219564,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 105

Page 106: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /0902-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 896,9Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 897Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 661Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 425Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 256Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,26Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,18Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,76

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,681Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,162

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 97,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 219564,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 106

Page 107: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /0902-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 902,9Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 903Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 665Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 428Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 256Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,04Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,54

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,681Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,329

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 104,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 229680,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 107

Page 108: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /0902-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 902,9Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 903Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 665Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 428Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 256Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,34Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,18Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,76

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,681Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,162

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 104,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 229680,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 108

Page 109: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /0902-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 902,9Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 903Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 665Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 428Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 256Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,04Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,54

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,681Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,329

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 104,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 229680,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 109

Page 110: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /0902-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 896,9Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 897Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 661Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 425Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 256Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,22Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,54

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,681Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,329

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 97,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 219564,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 110

Page 111: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /0902-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 896,9Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 897Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 661Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 425Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 256Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,26Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,18Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,76

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,681Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,162

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 97,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 219564,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 111

Page 112: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /0902-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 896,9Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 897Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 661Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 425Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 256Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,22Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,54

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,681Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,329

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 97,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 219564,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 112

Page 113: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /0902-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 902,9Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 903Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 665Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 428Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 256Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,04Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,54

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,681Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,329

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 104,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 229680,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 113

Page 114: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /0902-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 902,9Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 903Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 665Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 428Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 256Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,34Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,18Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,76

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,681Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,162

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 104,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 229680,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 114

Page 115: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /0972-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 963,3Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 963Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 710Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 456Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 276Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,23Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,369

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 97,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 256176,02For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 115

Page 116: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /0972-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 963,3Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 963Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 710Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 456Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 276Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,36Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,33Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,27Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,86

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,148

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 97,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 256176,02For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 116

Page 117: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /0972-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 967,1Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 967Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 713Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 458Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 276Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,33Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,21Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,369

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 104,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 267948,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 117

Page 118: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /0972-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 967,1Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 967Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 713Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 458Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 276Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,36Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,28Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,86

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,148

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 104,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 267948,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 118

Page 119: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /0972-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 967,1Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 967Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 713Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 458Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 276Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,33Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,21Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,369

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 104,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 267948,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 119

Page 120: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /0972-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 963,3Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 963Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 710Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 456Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 276Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,23Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,369

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 97,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 256176,02For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 120

Page 121: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /0972-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 963,3Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 963Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 710Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 456Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 276Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,36Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,33Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,27Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,86

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,148

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 97,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 256176,02For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 121

Page 122: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /0972-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 963,3Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 963Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 710Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 456Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 276Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,23Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,369

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 97,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 256176,02For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 122

Page 123: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /0972-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 967,1Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 967Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 713Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 458Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 276Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,33Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,21Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,369

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 104,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 267948,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 123

Page 124: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /0972-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 967,1Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 967Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 713Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 458Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 276Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,36Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,28Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,86

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,148

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 104,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 267948,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 124

Page 125: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /1052-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1051,0Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1051Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 774Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 498Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 302Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,26Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,29Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,680Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 292752,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 125

Page 126: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /1052-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1051,0Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1051Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 774Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 498Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 302Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,40Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,26Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,86

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,680Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,174

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 292752,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 126

Page 127: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /1052-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1057,0Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1057Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 779Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 501Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 302Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,27Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,680Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 306252,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 127

Page 128: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /1052-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1057,0Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1057Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 779Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 501Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 302Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,38Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,26Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,86

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,680Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,174

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 306252,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 128

Page 129: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /1052-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1057,0Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1057Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 779Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 501Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 302Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,27Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,680Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 306252,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 129

Page 130: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /1052-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1051,0Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1051Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 774Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 498Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 302Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,26Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,29Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,680Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 292752,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 130

Page 131: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /1052-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1051,0Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1051Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 774Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 498Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 302Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,40Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,26Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,86

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,680Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,174

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 292752,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 131

Page 132: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /1052-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1051,0Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1051Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 774Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 498Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 302Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,26Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,29Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,680Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 292752,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 132

Page 133: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /1052-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1057,0Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1057Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 779Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 501Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 302Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,27Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,09Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,680Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 306252,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 133

Page 134: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /1052-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1057,0Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1057Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 779Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 501Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 302Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,38Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,26Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,86

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,680Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,174

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 306252,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 134

Page 135: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /1152-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1139,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1139Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 839Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 540Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,27Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,15Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,73

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,640Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 292752,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 135

Page 136: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /1152-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1139,0Seasonal energy efficiency of the space cooling ηs,c [%] 191,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1139Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 839Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 540Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,36Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,32Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,98

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,640Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,174

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 292752,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 136

Page 137: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /1152-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1145,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1145Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 844Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 542Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,15Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,73

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,640Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 306252,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 137

Page 138: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /1152-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1145,0Seasonal energy efficiency of the space cooling ηs,c [%] 191,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1145Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 844Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 542Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,33Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,32Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,98

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,640Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,174

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 306252,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 138

Page 139: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /1152-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1145,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1145Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 844Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 542Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,15Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,73

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,640Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 306252,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 139

Page 140: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /1152-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1139,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1139Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 839Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 540Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,27Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,15Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,73

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,640Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 292752,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 140

Page 141: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /1152-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1139,0Seasonal energy efficiency of the space cooling ηs,c [%] 191,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1139Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 839Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 540Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,36Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,32Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,98

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,640Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,174

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 292752,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 141

Page 142: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /1152-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1139,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1139Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 839Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 540Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,27Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,15Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,73

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,640Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 292752,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 142

Page 143: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /1152-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1145,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1145Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 844Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 542Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,15Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,73

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,640Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 306252,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 143

Page 144: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /1152-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1145,0Seasonal energy efficiency of the space cooling ηs,c [%] 191,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1145Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 844Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 542Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,33Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,32Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,98

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,640Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,174

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 306252,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 144

Page 145: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /1243-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1231,0Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1231Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 907Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 583Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 259Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,96Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,61

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,827Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,451

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 329364,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 145

Page 146: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /1243-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1231,0Seasonal energy efficiency of the space cooling ηs,c [%] 188,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1231Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 907Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 583Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 259Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,12Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,83

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,827Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,203

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 329364,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 146

Page 147: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /1243-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1238,0Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1238Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 912Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 586Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 261Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,96Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,61

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,827Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,451

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 344520,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 147

Page 148: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /1243-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1238,0Seasonal energy efficiency of the space cooling ηs,c [%] 188,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1238Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 912Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 586Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 261Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,34Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,13Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,827Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,203

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 344520,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 148

Page 149: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /1243-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1238,0Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1238Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 912Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 586Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 261Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,96Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,61

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,827Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,451

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 344520,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 149

Page 150: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /1243-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1231,0Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1231Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 907Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 583Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 259Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,96Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,61

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,827Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,451

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 329364,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 150

Page 151: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /1243-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1231,0Seasonal energy efficiency of the space cooling ηs,c [%] 188,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1231Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 907Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 583Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 259Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,12Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,83

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,827Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,203

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 329364,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 151

Page 152: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /1243-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1231,0Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1231Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 907Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 583Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 259Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,96Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,61

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,827Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,451

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 329364,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 152

Page 153: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /1243-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1238,0Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1238Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 912Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 586Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 261Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,96Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,61

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,827Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,451

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 344520,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 153

Page 154: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /1243-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1238,0Seasonal energy efficiency of the space cooling ηs,c [%] 188,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1238Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 912Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 586Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 261Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,34Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,13Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,827Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,203

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 344520,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 154

Page 155: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /1373-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1352,0Seasonal energy efficiency of the space cooling ηs,c [%] 180,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1352Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 996Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 640Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 285Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,22Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,92Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,46

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,451

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 329364,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 155

Page 156: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /1373-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1352,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1352Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 996Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 640Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 285Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,06Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,65

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,203

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 329364,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 156

Page 157: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /1373-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1361,0Seasonal energy efficiency of the space cooling ηs,c [%] 180,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1361Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1003Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 645Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 287Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,93Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,47

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,451

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 344520,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 157

Page 158: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /1373-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1361,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1361Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1003Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 645Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 287Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,33Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,07Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,66

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,203

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 344520,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 158

Page 159: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /1373-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1361,0Seasonal energy efficiency of the space cooling ηs,c [%] 180,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1361Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1003Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 645Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 287Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,93Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,47

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,451

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 344520,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 159

Page 160: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /1373-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1352,0Seasonal energy efficiency of the space cooling ηs,c [%] 180,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1352Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 996Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 640Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 285Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,22Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,92Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,46

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,451

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 329364,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 160

Page 161: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /1373-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1352,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1352Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 996Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 640Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 285Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,06Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,65

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,203

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 329364,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 161

Page 162: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /1373-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1352,0Seasonal energy efficiency of the space cooling ηs,c [%] 180,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1352Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 996Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 640Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 285Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,22Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,92Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,46

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,451

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 329364,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 162

Page 163: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /1373-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1361,0Seasonal energy efficiency of the space cooling ηs,c [%] 180,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1361Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1003Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 645Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 287Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,93Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,47

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,451

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 344520,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 163

Page 164: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /1373-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1361,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1361Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1003Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 645Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 287Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,33Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,07Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,66

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,203

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 344520,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 164

Page 165: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /1503-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1479,0Seasonal energy efficiency of the space cooling ηs,c [%] 184,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1479Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1090Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 701Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 311Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,26Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,98Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,78

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,510

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 347652,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 165

Page 166: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /1503-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1479,0Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1479Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1090Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 701Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 311Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,34Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,13Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,98

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,206

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 347652,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 166

Page 167: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /1503-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1487,0Seasonal energy efficiency of the space cooling ηs,c [%] 184,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1487Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1096Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 704Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 313Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,99Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,77

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,510

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 363636,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 167

Page 168: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /1503-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1487,0Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1487Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1096Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 704Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 313Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,32Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,13Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,97

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,206

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 363636,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 168

Page 169: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /1503-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1487,0Seasonal energy efficiency of the space cooling ηs,c [%] 184,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1487Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1096Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 704Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 313Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,99Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,77

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,510

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 363636,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 169

Page 170: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /1503-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1479,0Seasonal energy efficiency of the space cooling ηs,c [%] 184,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1479Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1090Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 701Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 311Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,26Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,98Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,78

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,510

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 347652,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 170

Page 171: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /1503-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1479,0Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1479Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1090Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 701Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 311Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,34Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,13Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,98

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,206

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 347652,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 171

Page 172: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /1503-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1479,0Seasonal energy efficiency of the space cooling ηs,c [%] 184,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1479Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1090Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 701Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 311Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,26Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,98Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,78

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,510

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 347652,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 172

Page 173: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /1503-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1487,0Seasonal energy efficiency of the space cooling ηs,c [%] 184,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1487Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1096Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 704Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 313Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,99Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,77

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,510

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 363636,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 173

Page 174: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /1503-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1487,0Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1487Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1096Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 704Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 313Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,32Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,13Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,97

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,206

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 363636,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 174

Page 175: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR /1593-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1552,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1552Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1144Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 735Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 327Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,23Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,02Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,511

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 365940,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 175

Page 176: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /NR + EC /1593-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1552,0Seasonal energy efficiency of the space cooling ηs,c [%] 190,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1552Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1144Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 735Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 327Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,26Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,34Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,17Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,04

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,209

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 365940,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 176

Page 177: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /1593-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1560,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1560Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1149Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 739Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,02Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,83

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,511

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 382788,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 177

Page 178: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /EC /1593-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1560,0Seasonal energy efficiency of the space cooling ηs,c [%] 190,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1560Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1149Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 739Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,17Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,02

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,209

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 382788,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 178

Page 179: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /HT /1593-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1560,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1560Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1149Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 739Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,02Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,83

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,511

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 382788,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 179

Page 180: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR /1593-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1552,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1552Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1144Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 735Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 327Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,23Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,02Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,511

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 365940,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 180

Page 181: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + EC /1593-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1552,0Seasonal energy efficiency of the space cooling ηs,c [%] 190,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1552Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1144Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 735Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 327Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,26Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,34Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,17Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,04

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,209

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 365940,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 181

Page 182: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /A /NR + HT /1593-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1552,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1552Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1144Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 735Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 327Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,23Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,02Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,511

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 99,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 365940,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 182

Page 183: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /1593-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1560,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1560Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1149Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 739Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,02Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,83

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,511

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 382788,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 183

Page 184: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /A /EC /1593-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1560,0Seasonal energy efficiency of the space cooling ηs,c [%] 190,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1560Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1149Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 739Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,17Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,02

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,209

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 106,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 382788,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 184

Page 185: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /0252-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 252,0Seasonal energy efficiency of the space cooling ηs,c [%] 180,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 252Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 186Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 119Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 73,2Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,34Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,33Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,10Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,24

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,237Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 87,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 86436,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 185

Page 186: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /0252-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 252,0Seasonal energy efficiency of the space cooling ηs,c [%] 180,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 252Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 186Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 119Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 73,2Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,34Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,33Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,10Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,24

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,237Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 87,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 86436,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 186

Page 187: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /0252-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 252,0Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 252Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 186Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 119Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 73,2Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,40Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,49Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,35Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,237Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 87,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 86436,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 187

Page 188: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /0252-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 252,0Seasonal energy efficiency of the space cooling ηs,c [%] 180,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 252Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 186Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 119Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 73,2Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,34Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,33Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,10Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,24

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,237Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 87,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 86436,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 188

Page 189: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /0252-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 252,0Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 252Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 186Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 119Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 73,2Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,40Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,49Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,35Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,237Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 87,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 86436,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 189

Page 190: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /0302-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 285,9Seasonal energy efficiency of the space cooling ηs,c [%] 178,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 286Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 211Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 135Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 82,6Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,98Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,38

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,265Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 87,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 86436,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 190

Page 191: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /0302-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 285,9Seasonal energy efficiency of the space cooling ηs,c [%] 178,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 286Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 211Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 135Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 82,6Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,98Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,38

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,265Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 87,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 86436,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 191

Page 192: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /0302-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 285,9Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 286Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 211Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 135Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 82,6Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,33Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,38Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,71

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,265Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 87,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 86436,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 192

Page 193: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /0302-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 285,9Seasonal energy efficiency of the space cooling ηs,c [%] 178,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 286Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 211Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 135Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 82,6Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,98Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,38

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,265Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 87,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 86436,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 193

Page 194: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /0302-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 285,9Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 286Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 211Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 135Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 82,6Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,33Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,38Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,71

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,265Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 87,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 86436,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 194

Page 195: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /0322-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 310,4Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 310Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 229Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 147Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 89,5Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,06Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,47

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 87,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 86436,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 195

Page 196: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /0322-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 310,4Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 310Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 229Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 147Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 89,5Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,06Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,47

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 87,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 86436,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 196

Page 197: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /0322-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 310,4Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 310Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 229Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 147Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 89,5Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,34Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,44Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,25Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,79

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 87,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 86436,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 197

Page 198: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /0322-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 310,4Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 310Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 229Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 147Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 89,5Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,28Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,06Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,47

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 87,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 86436,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 198

Page 199: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /0322-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 310,4Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 310Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 229Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 147Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 89,5Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,34Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,44Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,25Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,79

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,099

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 87,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 86436,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 199

Page 200: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /0352-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 361,8Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 362Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 267Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 171Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 104Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,38Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,32Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 88,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 103716,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 200

Page 201: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /0352-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 361,8Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 362Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 267Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 171Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 104Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,38Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,32Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 88,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 103716,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 201

Page 202: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /0352-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 361,8Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 362Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 267Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 171Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 104Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,43Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,45Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,59

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,102

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 88,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 103716,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 202

Page 203: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /0352-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 361,8Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 362Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 267Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 171Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 104Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,38Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,32Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,181

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 88,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 103716,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 203

Page 204: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /0352-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 361,8Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 362Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 267Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 171Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 104Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,43Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,45Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,59

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,102

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 88,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 103716,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 204

Page 205: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /0402-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 399,0Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 399Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 294Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 189Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 114Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,26Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,32Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,04Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 89,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 103716,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 205

Page 206: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /0402-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 399,0Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 399Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 294Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 189Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 114Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,26Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,32Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,04Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 89,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 103716,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 206

Page 207: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /0402-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 399,0Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 399Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 294Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 189Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 114Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,44Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,23Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,56

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,124

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 89,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 103716,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 207

Page 208: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /0402-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 399,0Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 399Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 294Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 189Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 114Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,26Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,32Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,04Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,25

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 89,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 103716,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 208

Page 209: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /0402-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 399,0Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 399Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 294Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 189Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 114Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,44Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,23Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,56

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,124

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 89,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 103716,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 209

Page 210: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /0452-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 445,2Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 445Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 328Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 211Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 126Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,10Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,45

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 89,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 138276,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 210

Page 211: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /0452-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 445,2Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 445Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 328Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 211Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 126Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,10Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,45

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 89,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 138276,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 211

Page 212: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /0452-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 445,2Seasonal energy efficiency of the space cooling ηs,c [%] 191,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 445Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 328Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 211Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 126Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,38Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,50Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,31Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,75

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,130

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 89,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 138276,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 212

Page 213: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /0452-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 445,2Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 445Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 328Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 211Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 126Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,32Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,10Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,45

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 89,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 138276,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 213

Page 214: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /0452-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 445,2Seasonal energy efficiency of the space cooling ηs,c [%] 191,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 445Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 328Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 211Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 126Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,38Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,50Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,31Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,75

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,203Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,130

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 89,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 138276,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 214

Page 215: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /0512-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 512,0Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 512Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 377Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 243Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,29Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,46

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 89,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 138276,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 215

Page 216: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /0512-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 512,0Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 512Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 377Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 243Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,29Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,46

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 89,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 138276,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 216

Page 217: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /0512-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 512,0Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 512Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 377Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 243Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,41Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,14Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,71

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,130

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 89,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 138276,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 217

Page 218: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /0512-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 512,0Seasonal energy efficiency of the space cooling ηs,c [%] 179,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 512Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 377Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 243Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,29Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,46

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 89,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 138276,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 218

Page 219: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /0512-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 512,0Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 512Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 377Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 243Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,41Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,14Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,71

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,130

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 89,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 138276,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 219

Page 220: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /0572-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 567,2Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 567Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 418Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 269Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 164Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 90,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 138276,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 220

Page 221: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /0572-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 567,2Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 567Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 418Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 269Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 164Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 90,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 138276,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 221

Page 222: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /0572-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 567,2Seasonal energy efficiency of the space cooling ηs,c [%] 188,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 567Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 418Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 269Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 164Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,41Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,20Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,130

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 90,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 138276,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 222

Page 223: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /0572-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 567,2Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 567Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 418Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 269Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 164Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 90,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 138276,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 223

Page 224: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /0572-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 567,2Seasonal energy efficiency of the space cooling ηs,c [%] 188,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 567Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 418Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 269Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 164Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,41Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,20Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,514Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,130

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 90,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 138276,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 224

Page 225: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /0652-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 668,9Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 669Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 493Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 317Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 192Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,43

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,454Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 91,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 172872,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 225

Page 226: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /0652-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 668,9Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 669Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 493Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 317Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 192Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,43

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,454Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 91,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 172872,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 226

Page 227: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /0652-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 668,9Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 669Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 493Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 317Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 192Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,40Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,21Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,72

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,454Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,136

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 91,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 172872,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 227

Page 228: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /0652-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 668,9Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 669Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 493Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 317Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 192Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,03Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,43

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,454Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,258

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 91,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 172872,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 228

Page 229: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /0652-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 668,9Seasonal energy efficiency of the space cooling ηs,c [%] 187,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 669Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 493Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 317Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 192Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,40Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,21Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,72

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,454Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,136

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 91,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 172872,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 229

Page 230: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /0772-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 771,1Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 771Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 568Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 365Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 222Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,26Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,08Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,486Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,309

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 92,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 207432,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 230

Page 231: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /0772-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 771,1Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 771Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 568Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 365Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 222Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,26Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,08Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,486Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,309

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 92,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 207432,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 231

Page 232: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /0772-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 771,1Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 771Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 568Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 365Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 222Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,38Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,25Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,486Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,142

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 92,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 207432,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 232

Page 233: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /0772-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 771,1Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 771Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 568Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 365Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 222Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,26Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,08Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,486Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,309

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 92,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 207432,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 233

Page 234: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /0772-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 771,1Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 771Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 568Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 365Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 222Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,38Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,25Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,84

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,486Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,142

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 92,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 207432,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 234

Page 235: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /0902-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 892,6Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 893Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 658Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 423Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 257Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,33Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,34Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,05Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,39

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,369

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 241992,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 235

Page 236: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /0902-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 892,6Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 893Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 658Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 423Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 257Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,33Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,34Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,05Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,39

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,369

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 241992,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 236

Page 237: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /0902-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 892,6Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 893Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 658Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 423Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 257Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,38Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,47Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,23Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,68

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,148

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 241992,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 237

Page 238: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /0902-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 892,6Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 893Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 658Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 423Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 257Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,33Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,34Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,05Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,39

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,369

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 241992,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 238

Page 239: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /0902-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 892,6Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 893Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 658Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 423Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 257Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,38Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,47Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,23Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,68

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,148

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 93,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 241992,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 239

Page 240: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /0972-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 958,2Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 958Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 706Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 454Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 276Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,08Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,369

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 241992,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 240

Page 241: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /0972-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 958,2Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 958Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 706Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 454Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 276Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,08Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,369

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 241992,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 241

Page 242: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /0972-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 958,2Seasonal energy efficiency of the space cooling ηs,c [%] 190,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 958Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 706Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 454Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 276Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,34Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,36Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,27Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,86

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,148

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 241992,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 242

Page 243: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /0972-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 958,2Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 958Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 706Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 454Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 276Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,08Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,58

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,369

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 241992,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 243

Page 244: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /0972-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 958,2Seasonal energy efficiency of the space cooling ηs,c [%] 190,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 958Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 706Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 454Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 276Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,34Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,36Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,27Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,86

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,406Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,148

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 241992,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 244

Page 245: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /1052-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1043,0Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1043Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 769Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 494Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 302Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,08Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,680Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 276588,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 245

Page 246: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /1052-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1043,0Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1043Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 769Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 494Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 302Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,08Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,680Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 276588,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 246

Page 247: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /1052-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1043,0Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1043Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 769Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 494Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 302Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,42Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,25Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,86

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,680Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,174

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 276588,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 247

Page 248: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /1052-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1043,0Seasonal energy efficiency of the space cooling ηs,c [%] 183,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1043Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 769Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 494Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 302Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,08Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,680Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 276588,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 248

Page 249: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /1052-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1043,0Seasonal energy efficiency of the space cooling ηs,c [%] 189,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1043Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 769Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 494Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 302Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,42Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,25Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,86

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,680Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,174

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 276588,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 249

Page 250: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /1152-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1133,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1133Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 835Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 537Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,15Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,73

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,640Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 276588,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 250

Page 251: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /1152-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1133,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1133Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 835Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 537Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,15Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,73

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,640Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 276588,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 251

Page 252: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /1152-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1133,0Seasonal energy efficiency of the space cooling ηs,c [%] 191,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1133Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 835Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 537Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,39Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,32Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,98

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,640Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,174

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 276588,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 252

Page 253: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /1152-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1133,0Seasonal energy efficiency of the space cooling ηs,c [%] 185,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1133Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 835Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 537Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,15Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,73

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,640Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,389

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 276588,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 253

Page 254: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /1152-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1133,0Seasonal energy efficiency of the space cooling ηs,c [%] 191,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1133Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 835Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 537Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 328Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,39Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,32Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,98

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,640Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,174

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 276588,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 254

Page 255: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /1243-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1221,0Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1221Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 900Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 578Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 257Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,26Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,95Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,827Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,451

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 311148,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 255

Page 256: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /1243-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1221,0Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1221Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 900Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 578Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 257Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,26Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,95Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,827Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,451

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 311148,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 256

Page 257: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /1243-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1221,0Seasonal energy efficiency of the space cooling ηs,c [%] 188,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1221Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 900Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 578Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 257Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,37Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,12Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,82

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,827Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,203

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 311148,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 257

Page 258: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /1243-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1221,0Seasonal energy efficiency of the space cooling ηs,c [%] 182,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1221Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 900Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 578Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 257Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,24Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,26Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,95Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,60

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,827Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,451

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 311148,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 258

Page 259: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /1243-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1221,0Seasonal energy efficiency of the space cooling ηs,c [%] 188,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1221Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 900Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 578Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 257Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,37Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,12Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,82

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 0,827Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,203

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 311148,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 259

Page 260: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /1373-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1351,0Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1351Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 995Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 640Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 284Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,92Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,46

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,510

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 328428,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 260

Page 261: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /1373-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1351,0Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1351Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 995Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 640Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 284Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,92Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,46

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,510

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 328428,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 261

Page 262: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /1373-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1351,0Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1351Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 995Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 640Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 284Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,42Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,07Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,65

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,206

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 328428,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 262

Page 263: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /1373-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1351,0Seasonal energy efficiency of the space cooling ηs,c [%] 181,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1351Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 995Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 640Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 284Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,92Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,46

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,510

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 328428,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 263

Page 264: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /1373-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1351,0Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1351Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 995Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 640Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 284Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,42Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,07Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,65

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,206

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 94,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 328428,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 264

Page 265: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /1503-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1481,0Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1481Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1091Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 702Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 312Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,07Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,77

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,511

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 345708,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 265

Page 266: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /1503-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1481,0Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1481Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1091Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 702Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 312Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,07Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,77

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,511

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 345708,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 266

Page 267: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /1503-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1481,0Seasonal energy efficiency of the space cooling ηs,c [%] 192,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1481Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1091Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 702Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 312Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,35Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,41Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,25Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,97

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,209

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 345708,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 267

Page 268: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /1503-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1481,0Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1481Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1091Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 702Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 312Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,07Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,77

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,511

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 345708,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 268

Page 269: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /1503-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1481,0Seasonal energy efficiency of the space cooling ηs,c [%] 192,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1481Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1091Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 702Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 312Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,35Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,41Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,25Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,97

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,374Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,209

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 345708,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 269

Page 270: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /HT /1593-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1572,0Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1572Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1158Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 745Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 331Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,07Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,89

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,383Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,511

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 345708,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 270

Page 271: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /1593-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1572,0Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1572Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1158Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 745Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 331Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,07Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,89

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,383Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,511

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 345708,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 271

Page 272: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /SL-A /EC /1593-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1572,0Seasonal energy efficiency of the space cooling ηs,c [%] 192,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1572Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1158Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 745Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 331Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,40Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,22Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,08

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,383Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,209

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 345708,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 272

Page 273: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /1593-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1572,0Seasonal energy efficiency of the space cooling ηs,c [%] 186,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1572Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1158Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 745Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 331Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,30Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,07Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,89

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,383Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,511

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 345708,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 273

Page 274: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

FX2-G04 /D /SL-A /EC /1593-

Outdoor side heat exchanger of chiller air or water/brine AirIndoor side heat exchanger chiller water WaterType compressor driven vapour compression or sorption

processCompressor driven

vapour compressionDriver of compressor electric motor or fuel driven, gaseous or liquid fuel,

internal or external combustion engineElectric motor

Rated cooling capacity Prated,c [kW] 1572,0Seasonal energy efficiency of the space cooling ηs,c [%] 192,0

Declared cooling capacity for part load at given outdoor temperatures TjDeclared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1572Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1158Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 745Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 331Degradation coefficient for chillers Cdc 0,9

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures TjDeclared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,29Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,40Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,22Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,08

Power consumption in modes other than "active mode"Off mode POFF [kW] 0,000Thermostat-off mode PTO [kW] 1,383Crankcase heater mode PCK [kW] 0,000Standby mode PSB [kW] 0,209

Other itemsCapacity control fixed/staged/variable VariableSound power level, outdoor LWA [dB(A)] 95,0GWP of the refrigerant [Kg CO2eq] 7,00For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 345708,00For water/brine-to-water chillers: Rated brine or water flow rate, outdoor sideheat exchanger

[m³/h] -

Standard rating conditions used: low temperature application/medium temperatureapplication

Low temperatureapplication

Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

FX2-G04<<< BACK INDEX UNITS

FX2-G04_0252_1593_202008_ENELCA_Engine ver. 4.4.4.0 - DB ver. 0.0.0.0 274

Page 275: REGULATION (EU) N. 2016/2281 FOR COMFORT CHILLERS...For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 91476,00 For water/brine-to-water chillers: Rated brine

Tel (+39) 0424 509 500 - Fax (+39) 0424 509 509