reducing information Technology's ever-increasing carbon
footprintTom Raftery
Blog: cix.ie / tomrafteryit.netPodcast: www.podleaders.com
Email: [email protected]
![Page 2: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/2.jpg)
CIX
• Cork Internet eXchange - CIX• First professional data centre outside
Dublin• Opening Oct ’07• Not a sales pitch (unless your based in
Cork!!!)
![Page 3: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/3.jpg)
CIX.ie
![Page 4: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/4.jpg)
CIX.ie
![Page 5: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/5.jpg)
CIX.ie
![Page 6: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/6.jpg)
CIX.ie
![Page 7: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/7.jpg)
CIX.ie
![Page 8: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/8.jpg)
Lingo
• Watts = Voltage x Amps
• 1000 Watts for 1 hour = 1kWh
• 1U = 1 rack unit = 44.45 mm (1.75 in) high
• 1U servers -> 1A = 220W or .22kW
• Blade Servers/SAN = 500W per 1 U
• A large server might take 1kW
• 40U rack could use 20kW of power
![Page 9: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/9.jpg)
CIX Vision
• Carbon neutral data centre• Why?• How?
![Page 10: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/10.jpg)
Why? Climate change
![Page 11: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/11.jpg)
Why?
• DC running costs• Staffing - reasonable controllable• Connectivity - decreasing• Energy - increasing
![Page 12: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/12.jpg)
Increasing Energy requirements
• Rack of equipment typically used• 1.5 kW 7 years ago• 4.5 kW 4 years ago and• 15 kW in 2006!• SL Avatar consumes 1.75 kWh p.a.!
![Page 13: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/13.jpg)
Watts per $1000 server spend
• Price to fill a rack has gone down• Power consumption has gone up• => Increasing Watts per $1000 of
server spend
![Page 14: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/14.jpg)
Watts per $1000
![Page 15: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/15.jpg)
Carbon Neutrality
• How?• Using Pure Plant Oil (PPO) as an
energy source
![Page 16: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/16.jpg)
Background
• Data Centres:• Consume a lot of electricity • At roughly a constant rate• Have generating capacity at 2x
requirements• Connected to grid through high
voltage substations
![Page 17: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/17.jpg)
Background
• Electricity Supply:• Cannot be stored • Seasonal & diurnal demands• ESB offers Max Demand (MD)
discounts• Wind generates 0-30% of demand
but is highly unstable
![Page 18: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/18.jpg)
The Strategy
• Create a Data Centre power grid
• Powered by diesel generators burning PPO
• Grid generates power for ESB by day and pulls surplus power from ESB by night
• Give control of grid to ESB
• ESB can now buy more wind power
![Page 19: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/19.jpg)
Requirements
• Political will• Buy in from ESB• Buy in from other DCs• Buy in from farmers!• Time!
![Page 20: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/20.jpg)
In the meantime
• CIX are innovating to maximise• Energy efficiency and • Minimise carbon footprint
![Page 21: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/21.jpg)
Optimal DC environment
![Page 22: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/22.jpg)
DC Energy Flow
![Page 23: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/23.jpg)
Innovations
• Utilise free cooling
• Dynamically maximise chilled water temperature
• Eliminate water mixing
• Minimise humidification
• Eliminate air mixing
• Utilise low resistance, slow speed air paths
![Page 24: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/24.jpg)
Free Cooling
• Mean temp in Cork is 10.5˚C• Optimum inlet temp for servers is
21˚C• Exhaust air from servers is 30˚C to
40˚C• Use ambient temp to cool the warm
air and return water
![Page 25: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/25.jpg)
Maximise Chilled Water Temp
• Chillers have a fixed set point• CIX developed dynamic chiller
control system• Maximises temp of chilled water• Reduces energy required to chill it
![Page 26: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/26.jpg)
Eliminate Water Mixing
• Fixed chiller set-point • If CRAHs get overly cold water• => mix with warm water -
extremely wasteful• Dynamic set point eliminates water
mixing
![Page 27: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/27.jpg)
Minimise Humidification
• Low temperature water CRAHs => condensation • reduces the relative humidity• Steam (energy and cooling
implications) required to humidify• Dynamic chiller set point => less
condensation
![Page 28: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/28.jpg)
Typical DC
![Page 29: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/29.jpg)
Eliminate Air mixing
• Mixing hot and cold air - v wasteful• Most DCs - hot aisle/cold aisle
separation• CIX - cold aisle containment - most
energy efficient rack layout
![Page 30: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/30.jpg)
Low Resistance, Slow Speed Air
• Large unobstructed under-floor cavities
• Large overhead spaces for return air flows
• Fans require less energy to move air• Also, using thyristor controlled
direct drive fans to reduce belt resistance losses
![Page 31: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/31.jpg)
Server Supplied Heating
• Dimplex heat exchange unit• Servers heat the CIX offices• Servers heat water for CIX
![Page 32: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/32.jpg)
Power
• 10kv low impedence looped connection to the national grid
• Using GE Super ECO UPS’s offering >98% efficiency
![Page 33: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/33.jpg)
Power
•Normal mode• The output voltage is newly generated,
independently from the input voltage• Heat losses are present in rectifier and
inverter
•Super Eco Mode• Load is supplied via the bypass• UPS rectifier keeps the battery charged• UPS inverter switched off
(no heat losses)
Super Eco Mode
Normal mode
Inverter
DC
Battery bank
AC
AC
DC
Static bypass
Rectifier
Bypass supply
LoadRectifier
supply
Inverter
DC
Battery bank
AC
AC
DC
Static bypass
Rectifier
Bypass supply
LoadRectifier
supply
Transf.
![Page 34: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/34.jpg)
Typical DC
![Page 35: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/35.jpg)
End Result
Standard DC CIXChiller
HumidifierCRAC
IT EquipmentPDUUPS
LightingSwitch Gear
33% 12%3% <1%9% 4%30% 80%5% 0.01%18% <2%1% <1%1% 1%
![Page 36: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/36.jpg)
Conclusion
• Carbon neutrality• many stakeholders • Political will• time to roll out
• Extreme energy efficiency• Being built-in!
![Page 37: Reducing Information Technologies ever-increasing carbon footprint](https://reader033.vdocuments.mx/reader033/viewer/2022042606/54567752b1af9fb66e8b4f4a/html5/thumbnails/37.jpg)
References
• Uptime Institute - www.upsite.com
• APC - www.apc.com
• GE - www.ge.com
• CIX Energy Efficiency White Paper - www.cix.ie/air-conditioning-efficiency-at-the-cix-data-centre
• Second Life Avatar Power consumption - www.roughtype.com/archives/2006/12/avatars_consume.php