recloser joslyn.pdf
TRANSCRIPT
-
Raising the Standard Across the LineRaising the Standard Across the Line DB 707-101November 2000
JOSLYNHi-Voltage Corporation
Experience Leads to Innovation
TRIMOD 100 SERIES Single Phase Vacuum RecloserTRIMOD 100 SERIES Single Phase Vacuum Recloser
-
FEATURES / BENEFITSThe Singular Preference in RecloserPerformance and ReliabilityThe new TRIMOD 100 Series Vacuum Recloser raises thestandard of recloser performance by incorporating state-of-the-art vacuum interrupter technology with Joslyns fieldproven Joslyte solid foam insulating system and a long-lifesolenoid operating mechanism.
The following unique, field-proven features make theTRIMOD 100 Series the long-life, easy-to-use solutionfor utility recloser needs.
Long Operating LifeLong-life solenoid operating mechanism provides a minimumof 10,000 operations with no maintenance requirement.
Vacuum InterruptingAdvanced vacuum interrupter technology provides two dutycycle interruption life.
Manual Operating HandlesConvenient operating handles are located on the recloser. Theyellow handle permits mechanical opening and mechanicallyactuated, electrical closing of the recloser. The non-reclosinglever provides the capability of blocking reclosing after thefirst trip operation regardless of the number of reclosespreprogrammed in the control.
No Oil or GasThe TRIMOD 100 contains NO OIL or GAS for interruption orinsulation! The 30 year, field proven Joslyte solid insulationsystem provides dielectric strength around the vacuuminterrupter without concerns for leaks or environmental hazards.
Mounting VersatilityTRIMOD can be mounted to a wood pole, crossarms,or cluster mounting frame. Control can be mounteddirectly to TRIMOD or remotely.
Mechanical Position IndicatorThe position indicator is located on the bottom of the recloser.The large, reflective Open (Green) / Closed (Red) indicators arevisible from ground level.
Increased AccuracyTraditional single-phase reclosers withhydraulic controls have difficultymaintaining accuracy over time,particularly through temperaturevariations. This can affect coordination
and limit protection flexibility.Conversely, the PowerMAXcontrol is microprocessor-basedand its accuracy does not changeover time or with temperaturevariations, thus enabling betterand more reliable protectioncoordination.
FEATURES / BENEFITS
Non-ReclosingLever
Manual Trippingand ClosingHandle
Direct Control Mounting Shown(Remote Control Mounting Optional)
MountingFrame
Removable PolymerBushing; Cable ElbowConnection Compatible
Porcelain Housing SurroundingVacuum Interrupter with JoslyteSolid Dielectric Foam Insulation
Externally MountedCurrent Transformers(Underneath Metal Cover)
Environmental CableConnector
Manual OperatingHandles
RemovableAccess Panel
-
BOTTOMVIEW
JOSLYTE: No Oil or Gas
Removable CurrentTransformer
Long-LifeMechanism
Porcelain Housing
VacuumInterrupter
Joslyte SolidDielectric Foam
CurrentTransfer Block
Metal CurrentTransformer Cover
Pull RodAssembly
Open Solenoid
CloseSolenoid
Limit Switch
Toggle LinkageSelf-Lubricated
386 Bushing ForCable Elbow Connection
Standard NEMA2 Hole Connection
Removable Polymer Bushing,Cable Elbow Connection Compatible
AluminumCasting
Pull RodConnection
PositionIndicator
VACUUM INTERRUPTINGJOSLYTE SOLID DIELECTRIC INSULATION MATERIALJoslyn Hi-Voltage has been a leader in solid dielectric insulation for over30 years. The patented and field proven Joslyte solid dielectric foamhas been successfully used in other industry leading products such asthe VerSaVac and VarMaster vacuum switches and the TRIMOD3 phase recloser. This special, closed-cell, high voltage solid dielectricfoam has excelled in field applications in the most rugged climates anddemanding applications.
Bladder(no internalheaters)
JOSLYTE: No Oil or Gas
-
115-6 4-17.1 630 or 800 6 110115-10 4-17.1 630 or 800 10 110
115-12.5 4-17.1 630 or 800 12.5 110
127-6 17-29.3 630 or 800 6 125
127-10 17-29.3 630 or 800 10 125
127-12.5 17-29.3 630 or 800 12.5 125
TRIMOD 100 Series Vacuum Recloser
Recloser Ratings
Voltage Range(kV)
ContinuousCurrent (AMPS)
Interrupting Current(kA RMS Symmetrical)
Bil(kV)
ModelNo.
Nominal System Voltage (kV, RMS) 14.4 25
Rated Maximum Voltage (kV,RMS) 17.1 29.3
Nominal Frequency (Hz) 50 or 60 50 or 60
Number of Phases 1 1
BIL (kV) 110 125
Power Frequency Withstand - Dry (kV) 50 60
Power Frequency Withstand - Wet (kV) 45 50
Continuous Current (A RMS) 630 or 800 630 or 800
8-Hour Overload Current (A RMS) 800 800
Interrupting Current (kA RMS Symmetrical) 6,10 or 12.5 6, 10 or 12.5
Making Current (kA Asym Peak) 33 33
Arc Extinction Medium Vacuum Vacuum
Insulating Medium Solid High Solid HighDielectric Foam Dielectric Foam
Mechanical Operations 10,000 10,000
Recloser Ratings and Specifications
Description 15kV 27kV
Ordering and SpecifyingInformation Specify TRIMOD 100 Vacuum
Reclosers by selecting voltage class,continuous current, and interruptingcurrent rating from the ratings table.Each TRIMOD 100 includes: PowerMAX microprocessor
based recloser control mounted tothe TRIMOD. (Remote mountingof the control is available as anoption.)
Mounting Frame that can mountthe TRIMOD to a wood pole,crossarms, or a cluster mountingbracket.
Options Remote mounting control package
including:
Pole-mounting bracket for the control
Shielded control cable withconnectors on both ends. Specifylength up to 40 feet.
Arrester mounting provision.
Example: TRIMOD 115-12.5-630 Vacuum
Recloser
Remote Mounting Control Packagewith a 35 foot control cable
Arrester mounting provision
Recloser Ratings and Specifications
Model ExampleTRIMOD 115 - 12.5 - 630
# OfPhases
NominalVoltage
(kV)
InterruptingCurrent (kA)
ContinuousCurrent (A)
-
PowerMAXThe PowerMAX microprocessor-based controllerprovides unprecedented application flexibility and datarecording capabilities. All protection settings arechangeable from theintegrated keypad, withoutthe need to change orstock any components.
Remote monitoring andoperation is available viadry contacts or the RS-232communications port.
Enhanced FeaturesThe PowerMAXmicroprocessor-basedcontrol offers features thattraditionally have only beenavailable with three-phaserecloser controls. Thecontrol contains only asmall Lithium clock batteryfor maintaining accuratetime and date stamping.No other batteries are usedin the operation of thecontrol, thus eliminating costly battery maintenancenormally associated with electronic controls! All settingsand stored information are retained without the use ofbatteries even in the absence of line voltage. The controlcan be mounted directly to the recloser or convenientlylocated at a remote location.
Programmable SettingsProgramming of the PowerMAX is easily accomplished
by using the self-explanatory keypad. No dip switches oradditional components are required to make any settingchanges. A large LCD display allows for viewing settingchanges and stored information without the need for acomputer, although settings can be changed and storedinformation downloaded via a computer.
Time-Current CurvesAll traditional single-phase recloser curves plus ANSIinverse curves are selectable without the need tochange any components.
Voltage ProtectionThe PowerMAX has the ability to be programmedto trip on over-voltage or under-voltage conditions.
Single-Phase Trip, Three-Phase LockoutThe PowerMAX has the ability to be connected to otherPowerMAX controls to provide single-phase trippingand three-phase lockout.
Event RecordingThe event recorder stores the most recent 20 eventsenabling fast troubleshooting of problematic feeders. Eachtime and date stamped event includes the cause of theevent and any data associated with it. The events can beretrieved locally by using the keypad and display or remotelyvia the RS-232 port.
Lockout IndicatorThe control indicates lockout by illuminating the lockoutLED on the front panel as well as a high powered LED onthe bottom of the control enclosure. This enables quickand accurate determination from ground level as to whichTRIMOD has operated to lockout.
Low Voltage Testing CapabilityThe PowerMAX control is powered from 120 Vac or240 Vac. This, along with the fact that the TRIMOD doesnot use a high voltage closing solenoid, enables safe andconvenient testing of the recloser system.
PowerMAX 100: Control UnitPowerMAX 100: Control Unit
-
The Fisher Pierce Smartlink cellular monitoring and reporting systemprovides economical 2-way status and control capability. The systemutilizes Cellemetry and the existing cellular network. Applicationsinclude recloser monitoring, alarm monitoring, capacitor control, loadmonitoring, fault locating, and switch control. For more information,refer to Joslyn Bulletin Series 2700.
SMARTLINK MONITOR & CONTROL SYSTEM
Joslyn sectionalizers are used to improve reliability on distribution systems.Distribution sectionalizers isolate faults and outages with automaticsectionalizing, or remote-supervisory controls. For more information,refer to Joslyn Bulletin DB 750-202.
DISTRIBUTION SECTIONALIZERS
Three phase vacuum recloser using state-of-the-art technology withJoslyte solid dielectric foam insulation. TRIMOD vacuum interruptersprovide a long, maintenance-free operating life. TRIMOD reclosers areavailable with full featured microprocessor based controls. For moreinformation, refer to Joslyn Bulletin DB 706-301.
TRIMOD 300
USA (800) 621-58754000 East 116th StreetCleveland, OH 44105
(216) 271-6600 Fax: (216) 341-3615
CANADA (800) 363-8110Lachine, Quebec
Fax: (514) 631-1215
CHINA (86-21) 63543124Shanghai
Fax: (86-21) 63545852
www.joslynhivoltage.com
Copyright 2000, Joslyn Hi-Voltage CorporationAll other brand and product names
are trademarks or registered trademarksof their respective companies. Printed in USA.
JOSLYNHi-Voltage Corporation
Experience Leads to Innovation
Other Joslyn Distribution ProductsOther Joslyn Distribution Products