recapp facility evaluation report · report run on: march 6, 2007 7:36 am page 2 of 34 building id:...

41
Report run on: March 6, 2007 7:36 AM RECAPP Facility Evaluation Report Ardrossan Jr. / Sr. High School B2410A Ardrossan Elk Island Pub Sch Reg Div #14

Upload: others

Post on 30-Jun-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Report run on: March 6, 2007 7:36 AM

RECAPP Facility Evaluation Report

Ardrossan Jr. / Sr. High School

B2410AArdrossan

Elk Island Pub Sch Reg Div #14

Report run on: March 6, 2007 7:36 AM Page 2 of 34

B2410ABuilding Id:

Ardrossan Jr. / Sr. High SchoBuilding Name:

ArdrossanLocation:53129 R. R. 222 Address:

0.00Gross Area (sq. m): $17,078,613Replacement Cost:0Construction Year:

Evaluation Date: July 28 2006

Wade Engineering Ltd.Evaluation Company:

Ron ShannonEvaluator Name:

Located in the Town of Ardrossan, AB, with a student enrollment of 810. Gross area of 11060m2. School was originallyconstructed 1958 with several additions over a number of years. A community theater and new classroom wing wereconstructed in 1968, portables were added in 1977, two sections added in 1980. A major renovation with 2 moreadditions and replacement of the west 1958 wing with a 2 story section with architectural upgrades and modernization ofthe entire school was completed in 1989. Subsequent renovations with a small addition in 1995 to complete thecommunity theater and a small addition in 2001.

General Summary:

Structural Summary:School constructed over various years with three changes in elevations on main floor areas with both ramps and stairs tothese areas . Primarily single story block construction with a two story wing replacing the west section of the originalbuilding added in 1989. School includes tiered structural concrete seating in the theater. Some sections constructed withHSS steel columns, girders and OWSJ, large gym has glulam beams supporting the roof deck. Overall condition is acceptable.

Envelope Summary:Rock dash stucco on all exterior walls, one building section has a 700mm wide band of steel siding around top of wall.Windows include; pre-finished steel, anodized aluminum, PVC and a sloped curtain wall skylight over the main entry.The paint finish on the steel windows is starting to fail; the windows will require re-painting in 5-7 years. Exteriorsealants primarily around window/door frames are beginning to fail and will require replacement shortly. Roofing consists of BUR, SBS and inverted BUR assemblies and are well maintained, oldest remaining roof sectionsfrom 1992. Two areas scheduled for replacement in 3 years. Overall condition is acceptable.

Interior Summary:Flooring primarily sheet linoleum with some carpeting and ceramic tile in washrooms, majority of architectural finishesand hardware were upgraded and 1989 modernization. Overall interior finishes are in good condition.

Mechanical Summary:Most of the air systems were installed after 1989. Although the boiler, pumps, piping distribution and valves are original,various upgrading has been completed recently. The mechanical systems are sufficient to maintain optimumenvironmental conditions for teaching and learning environment. In general, the whole mechanical system is in goodcondition and works well.

Electrical Summary:Incoming service is 1200 amp, 120/208V, 3 phase in good condition. Branch circuit panelboards are located throughoutthe facility and are reaching capacity. The interior lighting has been completely retrofit with T8 fluorescent lamps andelectronic ballasts. The gym has new metal halide fixtures installed and all exit lights are LED. Fire alarm system hasbeen upgraded to a new addressable Mircom FX-2000 system. Overall, the building is in good condition.

6.60%5 year Facility Condition Index (FCI):

Facility Details Evaluation Details

Total Maintenance Events Next 5 years: $1,127,900

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Report run on: March 6, 2007 7:36 AM Page 3 of 34

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Condition Rating Performance1 - Critical Unsafe, high risk of injury or critical system failure.2 - Poor Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs.

3 - Marginal Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs.4 - Acceptable Meets present requirements, minor deficiencies. Average operating/maintenance costs.

Rating Guide

5 - Good Meets all present requirements. No deficiencies.6 - Excellent As new/state of the art, meets present and foreseeable requirements.

Report run on: March 6, 2007 7:36 AM Page 4 of 34

A1010 Standard Foundations*

A1030 Slab on Grade*

B1010.01 Floor Structural Frame*(Building Frame)

B1010.02 Structural Interior Walls Supporting Floors (or Roof)*

B1010.03 Floor Decks, Slabs, and Toppings*

B1010.05 Mezzanine Construction*

B1010.07 Exterior Stairs**

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

Rating

0

0

0

0

0

0

0

Installed

Installed

Installed

Installed

Installed

Installed

Installed

100

100

100

100

100

80

40

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

S1 STRUCTURAL

Grade beam and standard foundations.

Slab on grade throughout.

Masonry block construction.

Masonry block construction.

Cast in place concrete floor (2 story wing).

Concrete deck on masonry block for mechanical rooms in 1968 and 1958 sections.

Steel stairs and railing to mezzanine on 1958 section (Rm 214).

Report run on: March 6, 2007 7:36 AM Page 5 of 34

B1010.09 Floor Construction Fireproofing*

B1020.01 Roof Structural Frame*

B1020.04 Canopies*

B1020.06 Roof Construction Fireproofing*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

0

0

0

0

Installed

Installed

Installed

Installed

50

100

50

50

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Non-combustible construction.

Masonry bock with OWSJ and glulam beams, structural steel and OWSJ. Steel Q-deck and structural wood decking.

Steel frame on HSS columns at main and athletic wing entry, precast concrete decks and beams on HSS steel over exits.

Report run on: March 6, 2007 7:36 AM Page 6 of 34

B2010.01.06.03 Metal Siding**

B2010.01.08 Cement Plaster (Stucco): Ext. Wall*

B2010.01.09 Expansion Control: Exterior Wall Skin*

B2010.01.11 Joint Sealers (caulking): Ext. Wall**

B2010.02.03 Masonry Units: Ext. Wall Const.*

4 - Acceptable

4 - Acceptable

4 - Acceptable

3 - Marginal

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

1989

0

0

0

0

Installed

Installed

Installed

Installed

Installed

40

75

75

20

100

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Sealant replacement (1100m)

Failure Replacement 2008 $25,000 Medium

Sealant failures on steel and aluminum windows and doorsConcern:

Cut out failed sealant and install new urethane caulkingRecommendation:

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

S2 ENVELOPE

Event:

Type Year Cost Priority

Updated: MAR-07

Horizontal prefinished metal siding band on upper wall on single story east wing.

All wall areas - rock dash stucco. Some random wall damage to be repaired under maintenance.

Metal stucco expansion joints.

Windows, doors and penetrations.

All areas

Report run on: March 6, 2007 7:36 AM Page 7 of 34

B2010.02.05 Wood Framing*: Ext. Wall Const.

B2010.06 Exterior Louvers, Grilles, and Screens*

B2010.09 Exterior Soffits*

B2020.01.01.01 Steel Windows (Glass & Frame)**

B2020.01.01.02 Aluminum Windows (Glass & Frame)**

4 - Acceptable

4 - Acceptable

4 - Acceptable

3 - Marginal

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

0

0

0

0

1989

Installed

Installed

Installed

Installed

Installed

100

30

30

40

40

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Repaint steel windows

Preventative Maintenance 2007 $6,500 Medium

Factory paint finishes are corroding and flaking off on steelwindows (Approx. 16 windows).

Concern:

Remove rust and loose paint, prime and paint with zinc richcorrosion resistant paint.

Recommendation:

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Event:

Type Year Cost Priority

Updated: MAR-07

Remaining 1958 sections.

Air intake and exhaust grilles.

Canopy soffits - metal siding and concrete.

1989 two story wing and community theater.

Anodized and painted finish various locations.

Report run on: March 6, 2007 7:36 AM Page 8 of 34

B2020.01.01.06 Vinyl, Fibreglass &Plastic Windows**

B2030.01.01 Aluminum-Framed Storefronts**

B2030.01.02 Steel-Framed Storefronts**

B2030.01.10 Wood Entrance Door**

B2030.03 Large Exterior Special Doors (Overhead)*

B2030.05 Other Exterior Doors**

B3010.02.01.01 Asphalt Shingles**

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

Rating

1989

1989

1988

0

0

0

1989

Installed

Installed

Installed

Installed

Installed

Installed

Installed

40

30

30

30

30

30

30

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Various locations

Anodized frame and doors- main entry and athletic center.

1988 two story and theater.

At link to 1977 portables

Metal sectional door to vehicle bay.

Steel doors single leaf and double leaf at fire exits.

Two story wing

Report run on: March 6, 2007 7:36 AM Page 9 of 34

B3010.04.01 Built-up Bituminous Roofing (Asphalt & Gravel)**

B3010.04.04 Modified Bituminous Membrane Roofing (SBS)**

B3010.04.08 Membrane Roofing (Inverted/ Protected)**

B3010.07 Sheet Metal Roofing**

B3010.08.02 Metal Gutters and Downspouts**

3 - Marginal

5 - Good

5 - Good

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

1992

1989

1992

1989

1989

Installed

Installed

Installed

Installed

Installed

25

25

30

40

30

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Replace roofing (1320m2)

Failure Replacement 2010 $170,000 High

Roofs are showing signs of deteriorationConcern:

Replacement with SBS membrane is recommendedRecommendation:

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Event:

Type Year Cost Priority

Updated: MAR-07

Various roof areas. Most roof areas have been previously replaced with the oldest section from 1992; roof on east wing totheater was re-roofed in July 2006.

Various roof sections, no concerns.

Various roof sections, no concerns.

Canopy roof

Gutters and downspouts on two story wing.

Report run on: March 6, 2007 7:36 AM Page 10 of 34

B3020.01 Skylights**

B3020.02 Other Roofing Openings (Hatch,Vent, etc)*

B3020.02.03 Roof Windows (Clearstory)

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1989

1989

1989

Installed

Installed

Installed

20

25

0

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Replace skylight glazing (26m2)

Lifecycle Replacement 2010 $20,000 Low

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Event:

Type Year Cost Priority

Updated: MAR-07

Sloped curtain wall assembly on green house over main entry.

Exhaust vents, chimneys and mechanical/electrical penetrations.

Anodized aluminum windows above art room (Rm 150).

Report run on: March 6, 2007 7:36 AM Page 11 of 34

C1010.01 Interior Fixed Partitions*

C1010.01.01 Cast-in-place Concrete

C1010.02 Interior Demountable Partitions*

C1010.03 Interior Operable Folding Panel Partitions**

C1010.05 Interior Windows*

C1010.06 Interior Glazed Partitions and Storefronts*

C1010.07 Interior Partition Firestopping*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

5 - Good

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

Rating

0

0

0

1989

0

0

0

Installed

Installed

Installed

Installed

Installed

Installed

Installed

50

0

30

30

40

30

50

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

S3 INTERIOR

Concrete block, steel and wood frame with gypsum board.

Theater lobby walls

Steel stud with gypsum finish in classroom dividers

Vinyl accordion shutter

Steel with single glazing in offices.

Steel framed single glazed with wired safety glass in library and CTS.

Report run on: March 6, 2007 7:36 AM Page 12 of 34

C1020.01 Interior Swinging Doors**

C1020.03 Interior Fire Doors*

C1020.05.01 Coiling Doors and Grilles

C1030.01 Visual Display Boards**

C1030.02 Fabricated Compartments(Toilets/Showers)**

C1030.08 Interior Identifying Devices*

4 - Acceptable

4 - Acceptable

5 - Good

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

1989

0

0

1989

1989

0

Installed

Installed

Installed

Installed

Installed

Installed

40

50

40

20

30

20

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Replace Visual Display Boards (50 classrooms)

Lifecycle Replacement 2010 $75,000 Low

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Event:

Type Year Cost Priority

Updated: MAR-07

Steel frame with wood and steel doors.

Hallway doors on magnetic release, storage rooms.

Steel roll shutter in canteen

White boards, green boards and tack boards.

Standard painted steel enclosures

Directional signage, room identification, exits and general information boards.

Report run on: March 6, 2007 7:36 AM Page 13 of 34

C1030.10 Lockers**

C1030.12 Storage Shelving*

C1030.14 Toilet, Bath, and Laundry Accessories*

C2010 Stair Construction*

C2010.03 Metal Stair Construction

C2020.02 Terrazzo Stair Finishes*

5 - Good

4 - Acceptable

4 - Acceptable

4 - Acceptable

5 - Good

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

1989

0

0

0

0

0

Installed

Installed

Installed

Installed

Installed

Installed

30

20

20

100

0

60

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Full size in hallways, double stack and small stacked lockers in change rooms.

Wood and steel adjustable shelving throughout.

Steel/plastic toilet paper, soap, paper towel dispensers, built-in waste receptacles, sanitary napkin.

Concrete stairs to CTS, gym, library and second story, wood stair to mezzanine (Rm 214).

Steel access ladders to mezzanine in CTS and Rm 213.

Stairs to two story wing and gym.

Report run on: March 6, 2007 7:36 AM Page 14 of 34

C2020.05 Resilient Stair Finishes**

C2020.08 Stair Railings and Balustrades*

C2030.01 Ramp Construction*

C2030.02 Ramp Finishes*

C2030.03 Ramp Railings*

C3010.01 Concrete Wall Finishes*

4 - Acceptable

4 - Acceptable

5 - Good

4 - Acceptable

5 - Good

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

1989

0

0

0

0

0

Installed

Installed

Installed

Installed

Installed

Installed

20

50

100

0

50

100

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Replace CTS stair tread

Lifecycle Replacement 2010 $1,000 Low

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Event:

Type Year Cost Priority

Updated: MAR-07

Rubber tread and nosing on wood stairs and CTS.

Steel railings on concrete steps, wood railings to mezzanine

Concrete ramp with exposed aggregate.

Sheet linoleum

Handicap ramp - steel with plexiglass panels and painted wire safety screen Steel handrail on hallway

Theater lobby

Report run on: March 6, 2007 7:36 AM Page 15 of 34

C3010.02 Wall Paneling - gym**

C3010.02 Wall Paneling**

C3010.04 Gypsum Board Wall Finishes*

C3010.06 Tile Wall Finishes**

C3010.09 Acoustical Wall Treatment**

4 - Acceptable

5 - Good

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

1989

1989

0

1989

1989

Installed

Installed

Installed

Installed

Installed

30

30

60

40

20

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Replace Acoustic Baffles - FS 122 (475m2)

Lifecycle Replacement 2010 $9,000 Low

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Event:

Type Year Cost Priority

Updated: MAR-07

2.1m high varnished wood paneling

Fiberglass panel (3mm) for wall protection with batten strips

Partition walls

Ceramic tile in washrooms, change rooms, and backsplash on slop sinks

Fabric covered foam baffles in music room

Report run on: March 6, 2007 7:36 AM Page 16 of 34

C3010.11 Interior Wall Painting**

C3010.11 Interior Wall Painting**

C3010.14 Other Wall Finishes**

C3020.01.02 Paint Concrete Floor Finishes**

C3020.02 Tile Floor Finishes**

4 - Acceptable

4 - Acceptable

5 - Good

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

1989

0

1989

1989

1989

Installed

Installed

Installed

Installed

Installed

10

10

20

10

50

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Repaint interior walls (2500m2)

Repaint CTS and Mech. Room (800m2)

Lifecycle Replacement

Lifecycle Replacement

2010

2010

$29,000

$21,000

Low

Low

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-07

MAR-07

Latex paint throughout

Acrylic enamel textured finish (hardcoat) on block and gypsum in various locations to 2 meter height.

SS corner guards in high traffic areas.

Clear sealer in mechanical rooms and CTS

Wash rooms and change rooms.

Report run on: March 6, 2007 7:36 AM Page 17 of 34

C3020.04 Wood Flooring**

C3020.07 Resilient Flooring - weight room**

C3020.07 Resilient Flooring**

C3020.08 Carpet Flooring**

C3030.02 Ceiling Paneling (Wood)*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

1989

1989

1989

0

1989

Installed

Installed

Installed

Installed

Installed

30

20

20

15

60

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Replace Resilient Flooring (9000m2)

Replace carpet (72m2)

Lifecycle Replacement

Lifecycle Replacement

2010

2010

$365,000

$5,500

Low

Medium

Install new high traffic carpeting in FS 160 and FS 191.Recommendation:

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-07

MAR-07

Hardwood sports floor - large gym 1989, small gym (age unknown)

25mm high density rubber floor mat

Sheet linoleum, VC tile throughout.

High traffic carpet in various locations throughout the school, most carpet has been replaced in the last 5 -10 years.

Architectural wood trim on fluorescent fixtures hung between wood beams east wing. Art room has stained, exposed woodroof deck.

Report run on: March 6, 2007 7:36 AM Page 18 of 34

C3030.04 Gypsum Board Ceiling Finishes*

C3030.06 Acoustic Ceiling Treatment (Susp.T-Bar)**

C3030.07 Interior Ceiling Painting**

C3030.09 Other Ceiling Finishes*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

0

1989

1989

0

Installed

Installed

Installed

Installed

50

25

20

50

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Washrooms, change rooms and various locations throughout.

T bar ceiling throughout.

Storage rooms, washrooms and various locations.

Spray applied stipple finish, fabric covered acoustic baffles in music room.

Report run on: March 6, 2007 7:36 AM Page 19 of 34

D2010.01 Water Closets**

D2010.02 Urinals**

D2010.03 Lavatories**

D2010.04 Sinks**

D2010.05 Showers**

D2010.08 Drinking Fountains / Coolers**

D2020.01.01 Pipes and Tubes: Domestic Water*

5 - Good

5 - Good

5 - Good

5 - Good

5 - Good

5 - Good

5 - Good

Rating

Rating

Rating

Rating

Rating

Rating

Rating

1989

0

1989

1989

1989

1989

2004

Installed

Installed

Installed

Installed

Installed

Installed

Installed

35

35

35

30

30

35

40

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

S4 MECHANICAL

Floor mounted, flush valve, open front seat, regular and elongated rim bowl.

Wall and stall urinals, installed after 2000s, electronic controlled.

Porcelain steel bowl.

Stainless steel which vary in size and function.

Mixing box, control valve and showerhead

Vitreous china semi recessed. No refrigeration.

All the domestic hot, cold and recirculation piping insulated.

Report run on: March 6, 2007 7:36 AM Page 20 of 34

D2020.01.02 Valves: Domestic Water**

D2020.02.06 Domestic Water Heaters**

D2020.03 Water Supply Insulation: Domestic*

D2030.01 Waste and Vent Piping*

D2030.02 Waste Piping Specialties*

D2030.03 Waste Piping Equipment*

D2040.01 Rain Water Drainage Piping Systems*

5 - Good

5 - Good

5 - Good

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

Rating

1989

0

0

0

0

0

0

Installed

Installed

Installed

Installed

Installed

Installed

Installed

40

20

30

50

50

30

50

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

The domestic hot water and cold water valves work well, no leaking.

There are six (6) domestic hot water tanks. One State Heater domestic hot water tank (model: SBD65365, capacity 65 gal,input 328,500 btu/h, recovery 318.54 gal/h) was installed in 2004. The A.O.Smith domestic hot water tank (model:BTRC365110, capacity 65 Gal, Input: 328,500 btu/h, recovery 318.54 gal/h) was installed in 2005. Two Rheem Canadadomestic hot water tanks ( model: GL75-360-4A, input 324,000 btu/h, capacity 272,2 Gal) were installed originally and twoJETGLAS tanks (model: M100-210-TSR-3N, input 225,000 btu/h, 189.2 Gals) were installed originally.

All the domestic hot water tanks and pipes are insulated.

The waste and vent piping system is underground sanitary sewer system and connected to town's system.

Grease interceptor installed in kitchen. Dishwasher in kitchen

The waste piping is connected to the town's sanitary system.

Building site drainage, parking and general school site drainage are surface drainage system.

Report run on: March 6, 2007 7:36 AM Page 21 of 34

D2040.02.04 Roof Drains**

D3010.02 Gas Supply Systems*

D3020.02.01 Heating Boilers and Accessories: H.W.**

D3020.02.02 Chimneys (&Comb. Air): H.W. Boiler**

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

0

2005

0

0

Installed

Installed

Installed

Installed

40

60

35

30

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Replace Raytherm boilers (2)

Chimney Replacement

Lifecycle Replacement

Lifecycle Replacement

2010

2010

$54,900

$8,800

Low

Low

Replace the chimneys for the Raytherm Boilers (2).Recommendation:

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-07

MAR-07

All the roof drains were installed in 1958, 1968, 1973, 1980 and 1988. Some of the old roof drains had been replaced whenthe roofs were upgraded.

New gas meter was installed in 2005. Most of the pipe systems were installed originally during the different constructionperiods.

Three Weil-Mclain (1980) cast iron sectional boilers and two Raytherm water (1955) tube boilers (model: 1020T, max input918,000 Btu/h) heat the school. Boilers, valves and heating pipes are insulated.

All chimneys for H.W boilers were installed during the different construction periods and work well. But the two chimneys forthe two old Raytherm boilers were installed in 1955.

Report run on: March 6, 2007 7:36 AM Page 22 of 34

D3020.03.01 Furnaces**

D3020.03.02 Chimneys (&Comb. Air): Furnace*

D3020.04.01 Fuel-Fired Duct Heaters**

D3020.04.04 Chimney (&Comb.Air):Fuel-Fired Heater*

D3030.06.02 Refrigerant Condensing Units**

5 - Good

5 - Good

5 - Good

5 - Good

5 - Good

Rating

Rating

Rating

Rating

Rating

2005

2005

2001

0

1990

Installed

Installed

Installed

Installed

Installed

25

30

30

30

25

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Furnaces heat the portable buildings. Some of the furnaces have economizers.

Three Engineered Air roof top indirect fired makeup air units service the Beauty Culture and other areas.

The chimneys were installed associated with the indirect fired makeup air units.

An Engineered Air (model: CU251-1) unit provides cooling for the theater.

Report run on: March 6, 2007 7:36 AM Page 23 of 34

D3040.01.01 Air Handling Units: Air Distribution**

D3040.01.02 Fans: Air Distribution*

D3040.01.03 Air Cleaning Devices:Air Distribution*

D3040.01.04 Ducts: Air Distribution*

D3040.01.07 Air Outlets & Inlets:Air Distribution*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

0

0

0

0

0

Installed

Installed

Installed

Installed

Installed

30

30

30

50

30

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Air handling units including supply fans and return fans make up the building central air ventilation system to provide thesufficient capacity to effectively ventilate the school. AHU-1 ( Engineered Air LM-4), including supply fan and return fan, was installed in 1989. AHU-2 (Engineered Air LM-4), including supply fan and return fan, was installed in 1989. AH12 (PENN Ventilation ZCC-10), including supply fan and return fan, was installed in 1996. AH5 (Engineered Air LM-3), including supply fan and return fan, services the CTS area. RTU-1 ( Engineered Air DG-180-D), including supply fan, services the welding area. RTU-2 ( Engineered Air DJ-100-D), Including supply fan and return fan, services the classroom. RTU-3 ( Engineered Air ), makeup air unit, services the Beauty Culture area. AHU-4 ( Engineered Air LM-6), including supply fan and return fan, was installed in 1989. AHU-6 ( Engineered Air LM-8), including supply fan and return fan, services the classrooms. AHU-7 ( Engineered Air LM-8), including supply fan and return fan, services the gyms. AHU-8 ( Engineered Air LM-4), including supply fan and return fan, services the gyms. AHU-10 ( Engineered Air LM-10) includes supply fan and return fan. AHU-11 ( Recold of Canada, Model: AHB-340), includes supply fan and return fan. HF-7 was installed in 2003. HF-12 for music room.

The supply fans, return fans and exhaust fans provide school the ventilation at near 6 AC per hour and the portable systemsventilate air to about 4 AC per hour.

Air filtration of the central building systems with 2" medium efficiency, replaceable media filters and 1" similar filters forportable classroom system.

All the air ducts are insulated and no leakage.

The air outlets and inlets include stamped louvered diffusers, round diffusers, adjustable registers and grilles.

Report run on: March 6, 2007 7:36 AM Page 24 of 34

D3040.03.01 Hot Water Distribution Systems**

D3040.04.01 Fans: Exhaust**

D3040.04.03 Ducts: Exhaust*

D3040.04.05 Air Outlets and Inlets: Exhaust*

D3050.01.01 Computer Room Air Conditioning Units**

4 - Acceptable

5 - Good

4 - Acceptable

5 - Good

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

0

2001

0

2001

1990

Installed

Installed

Installed

Installed

Installed

40

30

50

30

30

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Hot Water Distribution System Replacement

Lifecycle Replacement 2010 $300,000 Low

Replace the 1968 hot water distribution system.Recommendation:

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Event:

Type Year Cost Priority

Updated: MAR-07

The heating hot water is delivered to the building perimeter radiation system and the terminal reheat coils by the heatingpumps. The school was built in 1958 and expanded in 1968, 1973, 1980 and 1988, the distribution systems were installedand upgraded in different years.

Building exhaust fans ventilate the washrooms effectively.

The exhaust ducts were installed in different construction periods and work effectively, no leakage.

Roof top ventilator exhaust fans provide the building effective ventilation.

A Mitsubishi refrigerant condensing unit (model: PU42EK7) provides cooling for the computer lab.

Report run on: March 6, 2007 7:36 AM Page 25 of 34

D3050.01.02 Packaged Rooftop Air Conditioning Units (& Heating Units)**

D3050.05.03 Finned Tube Radiation**

D3050.05.06 Unit Heaters**

D3060.02.02 Pneumatic Controls**

D3060.02.05 Building Systems Controls (BMCS, EMCS)**

D4010 Sprinklers: Fire Protection*

D4030.01 Fire Extinguisher, Cabinets and Accessories**

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

5 - Good

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

Rating

1989

1989

1989

1989

2004

1989

1989

Installed

Installed

Installed

Installed

Installed

Installed

Installed

30

40

30

40

25

60

30

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

One Carrier DX A/C unit provides cooling and heating for the lobby area of the 300 Wing building.

The building is mainly heated by the perimeter finned tube radiation and the terminal reheat coils.

Unit heaters service mechanical rooms and provide heat for the combustion air.

The fan coils, radiators and unit heaters are controlled by thermostats.

The new building DDC control system was installed in 2004

There is the sprinklers fire protection system in the school.

Portable wall mounted extinguishers were mounted in corridors.

Report run on: March 6, 2007 7:36 AM Page 26 of 34

D5010.03 Main Electrical Switchboards (Main Distribution)**

D5010.05 Electrical Branch Circuit Panelboards (Secondary Distribution)**

D5010.07.02 Motor Starters and Accessories**

4 - Acceptable

4 - Acceptable

3 - Marginal

Rating

Rating

Rating

1980

1988

1988

Installed

Installed

Installed

40

30

30

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Replace Motor Starters

Operating Efficiency Upgrade 2008 $6,000 Unassigned

The replacement parts for the Canadian Controllers in North300 are impossible to find and the maintenance costs are high.

Concern:

Replace all Canadian Controller motor controlsRecommendation:

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

S5 ELECTRICAL

Event:

Type Year Cost Priority

Updated: MAR-07

1200A, 120/208 V, 3 phase, 4 wire main distribution panel complete with 1200A main breaker. Main distribution is reachingcapacity. Main distribution will limit any future school additions or enhancements. Main distribution was redone andupgraded approximately 1980.

Branch circuit panels located throughout school are reaching capacity. Year of installation for panels varies due to multipleschool expansions and upgrades over the years. Future classroom receptacle upgrade will require some additional circuits.

Loose hardwired controls in various mechanical rooms. Most have been redone over the years through a rollingmaintenance and replacement program, with the exception of the Canadian controllers located in North 300 Wing.

1200Capacity Size

ampsCapacity Unit

Report run on: March 6, 2007 7:36 AM Page 27 of 34

D5020.01 Electrical Branch Wiring*

D5020.02.02.02 Interior Florescent Fixtures**

D5020.02.02.03 Interior Metal Halide Fixture*

4 - Acceptable

5 - Good

5 - Good

Rating

Rating

Rating

1958

2000

2000

Installed

Installed

Installed

50

30

30

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Power upgrade

Program Functional Upgrade 2009 $32,800 Medium

Classrooms obtaining increasingly more electric equipmentthat require addition power requirements. Inadequate amountof receptacles per classroom.

Concern:

Add 2 or 3 receptacles per classroom on new circuits toclassrooms with less than 4 receptacles per room. Existingclassroom circuits and panels are at capacity and thereforeproceeding with this power upgrade will also require a panelupgrade (D5010.05) to be implemented with this event. Pricingassumes approximately 10 rooms to undergo power upgrade.

Recommendation:

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Event:

Type Year Cost Priority

Updated: MAR-07

Conduit and BX throughout. Some surface wiremold for computer wiring and additional receptacles. Classroom receptaclesare being upgraded as needed with classrooms ranging from 2 to 4 plugs each.

Fluorescent fixtures used as primary lighting source throughout the school. All existing fixtures have been recently retrofitwith T8 lamps and electronic ballasts in early 2000s. Good lighting levels and quality throughout.

New 400W metal halide fixtures have been installed in the gymnasium. Installation was done with retrofit of fluorescentlighting.

Report run on: March 6, 2007 7:36 AM Page 28 of 34

D5020.02.03.02 Emergency Lighting Battery Packs**

D5020.02.03.03 Exit Signs*

D5020.03.01.04 Exterior H.P. Sodium Fixtures*

D5020.03.02 Lighting Accessories: Exterior (Lighting Controls)*

D5030.01 Detection and Fire Alarm**

D5030.02.02 Intrusion Detection**

4 - Acceptable

5 - Good

4 - Acceptable

4 - Acceptable

5 - Good

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

1988

2000

1988

1988

2006

1988

Installed

Installed

Installed

Installed

Installed

Installed

20

30

30

30

25

25

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Lifecycle Repalcement

Lifecycle Replacement 2010 $30,000 Low

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Event:

Type Year Cost Priority

Updated: MAR-07

Emergency battery packs complete with remote heads located throughout school

All exit signs have been retrofit with new LED lamps

Exterior 60-120W HPS lighting used on perimeter of school and parking lot. Fixtures have been added in an attempt toreduce vandalism and increase safety.

All exterior lights are on photocell control

Fire alarm system was recently upgraded with new addressable Mircom FX-2000 fire alarm system. Pull stations locatedat exits and heat detectors located in mechanical and storage rooms.

DCS Power 864 security system with door contacts and PIR motion detectors. User interface DSC keypad is located atfront entrance.

Report run on: March 6, 2007 7:36 AM Page 29 of 34

D5030.02.04 Video Surveillance**

D5030.03 Clock and Program Systems**

D5030.04.01 Telephone Systems**

D5030.04.04 Data Systems**

D5030.05 Public Address and Music Systems**

D5090.01 Uninterruptible Power Supply Systems**

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

1995

1988

1990

1988

1995

1988

Installed

Installed

Installed

Installed

Installed

Installed

25

25

25

25

20

30

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Video surveillance cameras located throughout the school and along exterior perimeter. Video signal feeds into the DigitalSentry System located in both the vice principal's and principals office for recording and monitoring.

Rauland master clock system located in office controls digital clocks in classrooms and hallways. Clocks mounted fromceiling are susceptible to vandalism and are being replaced with less obtrusive wall mounts.

Nitsuko phone system with handsets in office, staff and instructional areas.

Cat 5 cable throughout and supernet connected. Dell poweredge tower servers and dedicated rack housing 3COMswitching and AMP Netconnect patch panels located in dedicated server closet.

Dukane P/A system tied to phone system

Two stand alone APC UPS (Smart-UPS 1000 & 2200) backup power for network server system.

Report run on: March 6, 2007 7:36 AM Page 30 of 34

E1020.02 Library Equipment*

E1020.03 Theater and Stage Equipment*

E1020.07 Laboratory Equipment*

E1030.01 Vehicle Service Equipment*

E1090 Other Equipment (CTS)

E1090.03 Food Service Equipment*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

0

0

0

0

0

0

Installed

Installed

Installed

Installed

Installed

Installed

25

25

25

25

0

25

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

S6 EQUIPMENT, FURNISHINGS AND SPECIAL CONSTRUCTION

Electronic book scanner, circulation desk, wood and steel shelving, audio visual equipment and computer carrels.

Stage lighting and panel, stage drapes, sound equipment, control booth, props and wardrobe racks.

Upper and lower glass faced cabinets with chemical resistant laminate finishes, natural gas fittings, SS steel sinks,chemical fume hood, first aid and eye wash station, hazardous chemical storage cabinet, fire blankets, assorted chemicalsand equipment and SS carts for prep.

CTS shop; block stands, tool carts and engine hoist.

CTS - welding booths (3) with safety curtain and exhaust fans, wood working and metal working tools and equipment,graphics printing equipment, dark room with revolving door and photographic chemicals and equipment.

Canteen - gas fired SS fryer and griddle with overhead hood with fire suppression. SS wash sinks.

Report run on: March 6, 2007 7:36 AM Page 31 of 34

E1090.04 Residential Equipment*

E1090.07 Athletic, Recreational, and Therapeutic Equipment*

E2010.02 Fixed Casework**

E2010.03.01 Blinds**

E2010.05 Fixed Multiple Seating**

E2020 Moveable Furnishings*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

5 - Good

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

0

1989

0

1989

1989

0

Installed

Installed

Installed

Installed

Installed

Installed

25

15

35

30

35

20

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

electric ranges, microwaves, fridges, freezers, toaster ovens in canteen, staff lunch room and FS 167 (HEC). Washer anddryer (HEC). Upper and lower cabinets with laminate surfaces.

Gym - electric scoreboards and clocks (2), basketball hoops - (6) fixed, (6) mechanical, standard gym fittings. Weight room - free weights and dedicated weight equipment, stationary bikes, treadmills, cross trainer, stair climbers, etc.

Upper and lower cabinetry in offices and classrooms throughout. Wall mounted and built-in display cases in hallways,computer carrels in labs. Large storage cabinets in music, art and CTS rooms.

Vertical fabric in administration and some classrooms. Horizontal aluminum and vinyl in various locations.

Fabric covered theater seating with steel backs. Wood and steel benches, steel and laminate fixed picnic tables.

Standard classroom desks, chairs, office desks, filing cabinets, cafeteria tables and folding chairs.

Report run on: March 6, 2007 7:36 AM Page 32 of 34

F1010.02.04 Portable and Mobile Buildings*

F1010.02.05 Grandstands and Bleachers**

F1020.02 Special Purpose Rooms*(Language Lab)

F2020.01 Asbestos*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

1977

1989

0

0

Installed

Installed

Installed

Installed

25

50

50

0

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Replace portable windows (6)

Failure Replacement 2007 $7,200 High

Hardware failed, broken parts with no replacement partsavailable

Concern:

Install new PVC windows.Recommendation:

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Event:

Type Year Cost Priority

Updated: MAR-07

6 - portables added in 1977. Wood frame construction on concrete piles with vented crawlspace (dirt) with exposed glulamroof beams, with rock-dash stucco, metal fascia and aluminum windows (dual pane). SBS roofing (1995) on sloped wooddeck. Exterior wood stairs. Interior finishes consist of sheet linoleum, painted gypsum board on walls and ceiling, 19mm hardboard wall protection inhallways with textured acrylic enamel coating. White boards, tack boards, roll down screen and standard furnishings. Linkhas wood ramp with linoleum and heavy duty dimpled rubber flooring and full size lockers. Portables equipped with new forced air furnaces (install date 2000). Overall portable condition is acceptable.

5 tier folding bleachers in large gym (6)

Listening carrels equipped with built-in audio equipment and master console.

No asbestos known or reported.

Report run on: March 6, 2007 7:36 AM Page 33 of 34

F2020.09 Other Hazardous Materials*

4 - AcceptableRating

0Installed

0Design Life

MAR-07Updated

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

Various chemicals, acetylene tanks, cleaning solvents and lubricants

Report run on: March 6, 2007 7:36 AM Page 34 of 34

K4010.01 Barrier Free Route: Parking to Entrance

K4010.02 Barrier Free Entrances

K4010.03 Barrier Free Interior Circulation

K4010.04 Barrier Free Washrooms

4 - Acceptable

3 - Marginal

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

0

0

0

0

Installed

Installed

Installed

Installed

0

0

0

0

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Install power assist

Barrier Free Access Upgrade 2009 $10,600 Medium

School does not have power assist on any doors.Concern:

Install paddle activated power assists on front door.Recommendation:

Ardrossan - Ardrossan Jr. / Sr. High School (B2410A)

S8 FUNCTIONAL ASSESSMENT

Event:

Type Year Cost Priority

Updated: MAR-07

No restrictions, good access.

No power assists

Barrier free compliant

Barrier free washrooms provided

Report run on: March 6, 2007 9:11 AM

RECAPP Facility Evaluation Report

Ardrossan Jr. / Sr. High School

S2410Ardrossan

Report run on: March 6, 2007 9:11 AM Page 2 of 7

S2410Building Id:

Ardrossan Jr. / Sr. High SchoBuilding Name:

ArdrossanLocation:Address:

0.00Gross Area (sq. m): $0Replacement Cost:0Construction Year:

Evaluation Date:

Evaluation Company:

Evaluator Name:

Original site 1958, with major site upgrades in 1989. Site borders range road on west elevation. Asphalt parking on eastand west elevations, bus lane on west elevation, asphalt driveway and parking on south elevation. Mature grassed sitewith evergreen trees on west elevation. Landscaped courtyard on east elevation with assorted seating, benches andplanters. Site grading is acceptable with positive slope at the foundations The parking areas are equipped with exterior plugs and signage. Site is barrier free compliant with curb cuts andunrestricted access to entry doors. Overall condition is acceptable.

General Summary:

Structural Summary:

Envelope Summary:

Interior Summary:

Mechanical Summary:

Electrical Summary:

0%5 year Facility Condition Index (FCI):

Facility Details Evaluation Details

Total Maintenance Events Next 5 years: $9,000

Ardrossan - Ardrossan Jr. / Sr. High School (S2410)

Condition Rating Performance1 - Critical Unsafe, high risk of injury or critical system failure.2 - Poor Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs.

3 - Marginal Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs.4 - Acceptable Meets present requirements, minor deficiencies. Average operating/maintenance costs.

Rating Guide

5 - Good Meets all present requirements. No deficiencies.6 - Excellent As new/state of the art, meets present and foreseeable requirements.

Report run on: March 6, 2007 9:11 AM Page 3 of 7

G1030 Site Earthwork (Site Grading)*

G2010.02.01 Aggregate Roadway (Gravel)**

G2020.02.02 Flexible Paving Parking Lots(Asphalt)**

G2020.05 Parking Lot Curbs and Gutters*

G2020.06.02 Parking Bumpers*

G2020.06.03 Parking Lot Signs*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

5 - Good

Rating

Rating

Rating

Rating

Rating

Rating

0

1989

1989

0

0

0

Installed

Installed

Installed

Installed

Installed

Installed

50

15

25

25

25

25

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Re-surface fire lane (185m2)

Lifecycle Replacement 2010 $3,000 Low

Ardrossan - Ardrossan Jr. / Sr. High School (S2410)

S7 SITE

Event:

Type Year Cost Priority

Updated: MAR-07

School building sits slightly elevated to surrounding grounds with positive slope throughout. Some localized settlingrequiring maintenance to add soils.

Fire lane on north elevation

Extensive parking surrounding school, except north elevation, lot is regularly maintained.

Standard curb detail throughout.

Pre-cast curb stops, steel bollards by overhead door.

Directional, school bus, staff and visitor signage etc.

Report run on: March 6, 2007 9:11 AM Page 4 of 7

G2030.04 Rigid Pedestrian Pavement (Concrete)**

G2040.02 Fences and Gates**

G2040.03 Athletic and Recreational Surfaces**

G2040.05 Site and Street Furnishings*

3 - Marginal

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

1989

1989

1989

0

Installed

Installed

Installed

Installed

35

30

25

15

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Sidewalk repair (70m2)

Sidewalk replacement (100m2)

Repair

Lifecycle Replacement

2008

2024

$3,500

$15,000

Medium

Low

Sidewalk along south elevation of small gym 1988 addition hassettled.

Replace sidewalks in various locations.

Concern:

Concern:

Mudjack to restore proper elevations.Recommendation:

Ardrossan - Ardrossan Jr. / Sr. High School (S2410)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-07

MAR-07

Exterior walkways and landings, various ages.

Chain link fencing and gates around communication tower, dust collector (CTS) and property line (south elevation) Steel pipe railing bordering parking lots and various locations, there is a traffic gate on the fire lane. 1.8m high wood fence around dumpsters and barrier fence north end of 1958 wing

Paved court surface by 1977 portables

Steel benches in courtyard, pre-cast and steel waste bins and boot scrapers

Report run on: March 6, 2007 9:11 AM Page 5 of 7

G2040.06 Exterior Signs*

G2040.08 Flagpoles*

G2050.04 Lawns and Grasses*

G2050.05 Trees, Plants and Ground Covers*

G2050.07 Planting Accessories*

G3010.02 Site Domestic Water Distribution*

G3010.03 Site Fire Protection Water Distribution*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

Rating

0

0

0

0

0

0

0

Installed

Installed

Installed

Installed

Installed

Installed

Installed

25

30

15

10

10

50

50

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (S2410)

Raised block lettering for school identification.

One flagpole

Large grassed site

Various trees and shrubs on site.

Precast planters with small shrubs in courtyard.

Municipal service

Stand-pipes (2), fire hydrants (2)

Report run on: March 6, 2007 9:11 AM Page 6 of 7

G3020.01 Sanitary Sewage Collection*

G3030.01 Storm Water Collection*

G3060.01 Gas Distribution*

G4010.01 Electrical Substations*

G4010.02 Electrical Power Distribution Lines*

4 - Acceptable

3 - Marginal

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

0

0

0

0

0

Installed

Installed

Installed

Installed

Installed

50

50

50

50

50

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Install concrete splash pads.

Repair 2007 $2,500 High

Missing splash pads are causing localized soil erosion atfoundation.

Concern:

Install 1200mm splash pads at 6 locations along east elevationof NE corner, add soil and re-sod.

Recommendation:

Ardrossan - Ardrossan Jr. / Sr. High School (S2410)

Event:

Type Year Cost Priority

Updated: MAR-07

Municipal service

Concrete splash pads, storm drains on curbs and in parking lots, earthen drainage swale along east elevation to direct run-off to adjacent field.

Municipal service - natural gas

Pad mounted transformer located on the west side of school. Incoming electrical service is not original and was upgradedduring a recent renovation (approx. 1989). No surge protection provided.

Underground service

Report run on: March 6, 2007 9:11 AM Page 7 of 7

G4010.04 Car Plugs-ins*

G4020.01 Area Lighting*

G9090 Other Site Systems*

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

0

0

0

Installed

Installed

Installed

25

25

20

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Ardrossan - Ardrossan Jr. / Sr. High School (S2410)

Exterior plug-ins provided

HPS pole mounted lighting in parking lots.

Communication tower for internet service. Prefab steel utility shed with overhead and man door on skids.