Report run on: July 23, 2008 2:42 PM
RECAPP Facility Evaluation Report
St. Thomas Aquinas Elementary School
B2827ACalgary
Calgary RCSSD #1
Report run on: July 23, 2008 2:42 PM Page 2 of 40
B2827ABuilding Id:
St. Thomas Aquinas ElementBuilding Name:
CalgaryLocation:4540 - 26 Avenue S. W. Address:
1,349.36Gross Area (sq. m): $3,087,938Replacement Cost:1959Construction Year:
Evaluation Date: October 13 2007
Quinn Young Architects Ltd.Evaluation Company:
Barry McCallumEvaluator Name:
Constructed in 1959 this one-storey 4 room school had an original area of 584 s.m. In 1961 two additional classroomswere added with an additional area of 202 s.m. In 1963 a gymnasium and gym storage room comprising of 200 s.m. wasadded to the west end of the building. There are 4 portables attached to the building via a link and storage room on thenorth side. Total building area is currently 1350 s.m.
General Summary:
Structural Summary:Foundations consist of concrete piles and grade beams. HSS steel posts support a parallel chord sloping roofjoists/trusses over the classrooms. Roof is a metal Q-deck. The gymnasium has grade beams between concrete pierssupporting precast columns and an precast concrete roof 'T' system. The structure is in acceptable condition.
Envelope Summary:The building consists of exterior brick walls and stone cladding throughout. In 1990 the classroom exterior walls we5rereplaced with new aluminum windows and brick cladding. The exterior precast columns at the gymnasium are exposedand painted brown. The original BUR roof has been replaced with an SBS membrane and new prefinished metal capflashing and metal downspouts.The envelope is in acceptable condition
Interior Summary:The interior has brick clad walls around the classrooms. Original clerestorey windows at the corridor have been coveredwith drywall. Drywall partitions occur in the office area. Classrooms have sloped suspended ceiling tiles and oldercarpeting. The washrooms have their original ceramic floor and wall tiles which are in good condition. The interior is inoverall acceptable condition.
Mechanical Summary:The school has 2 Supper Hot boilers 720,000 each replaced in 2004, 1 large air handling unit, 4 fan coils and onedomestic hot water tank. The building is serviced with municipal sanitary sewer, storm sewer, domestic water andnatural gas. Heating is supplied through piping from the boilers to fan coils, and heating coils in the air handling unit.Classrooms and common areas get supply air from perimeter heat boxes with door and upper wall return. The grill inroom # 102 is blocked off and needs to be cleared. The systems are working satisfactorily with no major concerns atthis time.
Electrical Summary:120/240 V, 200A 1 phase 3 wire main distribution, underground feeders. Panels from various manufacturers at locatedthroughout the building. Interior lighting is mainly florescent with metal halide on the exterior. Emergency Battery Packsare located as required as well as incandescent exit lights. The fire alarm system is an Edwards 6500 and there is aSilent Knight Security system utilizing motion detectors. The phone system is Nortel and the PA system is a Raulandproduct requiring replacement. Cat5 data links are available throughout. Overall the electrical system is in acceptable condition.
15.93%5 year Facility Condition Index (FCI):
Facility Details Evaluation Details
Total Maintenance Events Next 5 years: $492,000
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Condition Rating Performance1 - Critical Unsafe, high risk of injury or critical system failure.2 - Poor Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs.
3 - Marginal Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs.4 - Acceptable Meets present requirements, minor deficiencies. Average operating/maintenance costs.
Rating Guide
5 - Good Meets all present requirements. No deficiencies.6 - Excellent As new/state of the art, meets present and foreseeable requirements.
Report run on: July 23, 2008 2:42 PM Page 3 of 40
A1010 Standard Foundations - 1959 Section*
A1010 Standard Foundations - 1961 Section*
A1010 Standard Foundations - 1963 Section*
A1030 Slab on Grade - 1959 Section*
A1030 Slab on Grade - 1961 Section*
A1030 Slab on Grade - 1963 Section*
B1010.01 Floor Structural Frame (Building Frame) - 1959 Section*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
Rating
1959
1961
1963
1959
1961
1963
1959
Installed
Installed
Installed
Installed
Installed
Installed
Installed
0
0
0
0
0
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Calgary - St. Thomas Aquinas Elementary School (B2827A)
S1 STRUCTURAL
Concrete piles and concrete grade beams
Concrete piles and concrete grade beams
Reinforced cip concrete grade beams between concrete piers and concrete footings
102mm reinforced concrete slab on grade
102mm reinforced concrete slab on grade
102mm reinforced concrete slab on grade over 102mm gravel on 4mil vapour barrier
102mm Reinforced concrete slab on grade with grade beams. 64 dia. Steel columns at pile locations supporting parallelchord steel trusses
Report run on: July 23, 2008 2:42 PM Page 4 of 40
B1010.01 Floor Structural Frame (Building Frame) - 1961 Section*
B1010.01 Floor Structural Frame (Building Frame) - 1963 Section*
B1010.07 Exterior Stairs - 1993 Section*
B1010.09 Floor Construction Fireproofing - 1959 Section*
B1010.09 Floor Construction Fireproofing - 1961 Section*
B1010.09 Floor Construction Fireproofing - 1963 Section*
B1010.10 Floor Construction Firestopping - 1959 Section*
4 - Acceptable
4 - Acceptable
3 - Marginal
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
Rating
1961
1963
1993
1959
1961
1963
1959
Installed
Installed
Installed
Installed
Installed
Installed
Installed
0
0
40
0
0
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Calgary - St. Thomas Aquinas Elementary School (B2827A)
102mm reinforced concrete slab on grade with grade beams. 64 dia. Steel columns at pile locations supporting parallelchord steel trusses
102mm reinforced concrete slab on grade . Precast concrete columns on reinforced cip concrete piers to 1675mm belowgrade on 1200x1200mm reinforced cip concrete footings. Columns support precast 'T' roofing structure
Wood framed stair case with metal safety tread stair treads on north side of school to play area with large deck/landing atgrade. Refer to G2030.06 for event and costs
Concrete slab on grade
Concrete slab on grade
Concrete slab on grade
Concrete slab
Report run on: July 23, 2008 2:42 PM Page 5 of 40
B1010.10 Floor Construction Firestopping - 1961 Section*
B1010.10 Floor Construction Firestopping - 1963 Section*
B1020.01 Roof Structural Frame - 1959 Section*
B1020.01 Roof Structural Frame - 1961 Section*
B1020.01 Roof Structural Frame - 1963 Section*
B1020.04 Canopies - 1959 Section*
B1020.06 Roof Construction Fireproofing - 1959 Section*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
Rating
1961
1963
1959
1961
1963
1959
1959
Installed
Installed
Installed
Installed
Installed
Installed
Installed
0
0
0
0
0
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Concrete slab
Under-slab duct penetrates floor at classroom mechanical. Construction assumed to meet code at time of installation. Noissue reported.
Steel deck on 450mm parallel chord steel truss/joists supported on 64 diameter steel columns
Steel deck on 450mm parallel chord steel truss/joists supported on 64 diameter steel columns
Precast concrete 'T' system supported on precats concrete columns
Exposed painted steel framing forming canopy at main entrance and overhangs at classrooms
Not required for non-combustible construction
Report run on: July 23, 2008 2:42 PM Page 6 of 40
B1020.06 Roof Construction Fireproofing - 1961 Section*
B1020.06 Roof Construction Fireproofing - 1963 Section*
4 - Acceptable
4 - Acceptable
Rating
Rating
1961
1963
Installed
Installed
0
0
Design Life
Design Life
MAR-08
MAR-08
Updated
Updated
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Not required for non-combustible construction
Not required for non-combustible construction
Report run on: July 23, 2008 2:42 PM Page 7 of 40
B2010.01.02.01 Brick Masonry: Ext. Wall Skin - 1959 Section*
B2010.01.02.01 Brick Masonry: Ext. Wall Skin - 1961 Section*
B2010.01.02.01 Brick Masonry: Ext. Wall Skin - 1963 Section*
B2010.01.03 Stone Assemblies: Exterior Wall Skin - 1959 Section*
B2010.01.03 Stone Assemblies: Exterior Wall Skin - 1963 Section*
B2010.01.09 Expansion Control: Exterior Wall Skin - 1959 Section*
B2010.01.09 Expansion Control: Exterior Wall Skin - 1961 Section*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
Rating
1959
1961
1963
1959
1963
1959
1961
Installed
Installed
Installed
Installed
Installed
Installed
Installed
75
75
75
75
75
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Calgary - St. Thomas Aquinas Elementary School (B2827A)
S2 ENVELOPE
Norman Tweed pressed bricks. Bricks to match were added to exterior wall with window replacement program in 1990
Norman Tweed pressed bricks. Bricks to match were added to exterior wall with window replacement program in 1990
Norman Tweed Pressed brick to match existing school
Random, broken, course and range jointed ashlar stone masonry veneer at main entrance on west corner and corner ofoffice area
Random, broken, course and range jointed ashlar stone masonry veneer at two central panel on South gym wall face
Brick pilasters on exterior face break wall panels into small panels
Brick pilasters on exterior face break wall panels into small panels
Report run on: July 23, 2008 2:42 PM Page 8 of 40
B2010.01.09 Expansion Control: Exterior Wall Skin - 1963 Section*
B2010.01.11 Joint Sealers (caulking): Ext. Wall - 1959 Section**
B2010.01.11 Joint Sealers (caulking): Ext. Wall - 1961 Section**
B2010.01.11 Joint Sealers (caulking): Ext. Wall - 1963 Section**
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
1963
1990
1990
1990
Installed
Installed
Installed
Installed
0
20
20
20
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Replace Joint Caulking
Replace Caulking
Replace Caulking
Lifecycle Replacement
Lifecycle Replacement
Lifecycle Replacement
2012
2012
2012
$5,720
$2,288
$2,288
Unassigned
Unassigned
Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Event:
Type
Type
Type
Year
Year
Year
Cost
Cost
Cost
Priority
Priority
Priority
Updated:
Updated:
Updated:
APR-08
APR-08
APR-08
Brick wall face broken by structure into small panels
Exterior joint caulking around windows was replaced when windows were upgraded
Exterior joint caulking around windows was replaced when windows were upgraded
Exterior joint caulking was replaced when windows were upgraded
Report run on: July 23, 2008 2:42 PM Page 9 of 40
B2010.01.13 Paints (& Stains): Exterior Wall - 1959 Section**
B2010.01.13 Paints (& Stains): Exterior Wall - 1961 Section**
B2010.01.13 Paints (& Stains): Exterior Wall - 1963 Section**
B2010.02.03 Masonry Units: Ext. Wall Const. - 1959 Section*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
1959
1961
1963
1959
Installed
Installed
Installed
Installed
15
15
15
0
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Repaint Soffit
Repaint Soffit
Repaint soffit
Lifecycle Replacement
Lifecycle Replacement
Lifecycle Replacement
2012
2012
2012
$5,720
$2,288
$1,144
Unassigned
Unassigned
Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Event:
Type
Type
Type
Year
Year
Year
Cost
Cost
Cost
Priority
Priority
Priority
Updated:
Updated:
Updated:
APR-08
APR-08
APR-08
Painted exposed metal deck @ soffit
Painted exposed metal deck @ soffit
Painted metal soffit at serated fascia profile
Pressed brick exterior walls
Report run on: July 23, 2008 2:42 PM Page 10 of 40
B2010.02.03 Masonry Units: Ext. Wall Const. - 1961 Section*
B2010.02.03 Masonry Units: Ext. Wall Const. - 1963 Section*
B2010.03 Exterior Wall Vapor Retarders, Air Barriers, and Insulation - 1959 Section*
B2010.03 Exterior Wall Vapor Retarders, Air Barriers, and Insulation - 1961 Section*
B2010.03 Exterior Wall Vapor Retarders, Air Barriers, and Insulation - 1963 Section*
B2010.06 Exterior Louvers, Grilles, and Screens - 1959 Section*
B2010.06 Exterior Louvers, Grilles, and Screens - 1961 Section*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
Rating
1961
1963
1959
1961
1963
1959
1961
Installed
Installed
Installed
Installed
Installed
Installed
Installed
0
0
0
0
0
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Pressed brick exterior walls
102mm painted concrete block walls
Undetermined. Assumed it was upgraded in 1990 at window locations where walls were rebuilt
Undetermined. Assumed it was upgraded in 1990 at window locations where walls were rebuilt
Unknown. Assumed to be as per industry standards in 1963
Prefinished brown metal fresh air grilles at each classroom
Prefinished brown metal fresh air grilles at each classroom
Report run on: July 23, 2008 2:42 PM Page 11 of 40
B2010.06 Exterior Louvers, Grilles, and Screens - 1963 Section*
B2010.09 Exterior Soffits - 1959 Section*
B2010.09 Exterior Soffits - 1961 Section*
B2010.09 Exterior Soffits - 1963 Section*
B2020.01.01.02 Aluminum Windows (Glass & Frame) - 1959 Section**
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
5 - Good
Rating
Rating
Rating
Rating
Rating
1963
1959
1961
1963
1990
Installed
Installed
Installed
Installed
Installed
0
0
0
0
40
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Replace Aluminum Windows
Lifecycle Replacement 2030 $22,880 Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Type Year Cost Priority
Updated: APR-08
Clear anodized wall mounted exhasut cap and wall grilles on upper gym wall. Mushroom Caps are slightly dented(vandalism)
Exposed metal roof pan and steel angles forming overhang
Exposed metal roof pan and steel angles forming overhang
Exposed bottom of precast structural 'T's formin saw-toothed pattern on south and north roof edges.
Original windows were replace in 1990 with dark bronze anodized aluminum double glazed windows with upper awningvented units
Report run on: July 23, 2008 2:42 PM Page 12 of 40
B2020.01.01.02 Aluminum Windows (Glass & Frame) - 1961 Section**
B2030.01 Exterior Entrance Doors - 1959 Section
B2030.01 Exterior Entrance Doors - 1961 Section
5 - Good
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
1990
1959
1961
Installed
Installed
Installed
40
30
30
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Replace Aluminum Windows
Replace Exterior Entrance Doors
Replace Entrance Doors
Lifecycle Replacement
Lifecycle Replacement
Lifecycle Replacement
2030
2012
2012
$8,008
$11,440
$4,576
Unassigned
Unassigned
Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Event:
Type
Type
Type
Year
Year
Year
Cost
Cost
Cost
Priority
Priority
Priority
Updated:
Updated:
Updated:
APR-08
APR-08
APR-08
Original windows were replace in 1990 with dark bronze anodized aluminum double glazed windows with upper awningvented units
Double painted metal doors and frames at main entrance and at mudroom. Both doors have upper borrowed lites. The Mainentrance also has borrowed side-lites
Double painted metal doors and frame with small vision lites now lead into connecting link to portables
Report run on: July 23, 2008 2:42 PM Page 13 of 40
B2030.01 Exterior Entrance Doors - 1963 Section
B3010.01 Deck Vapor Retarder and Insulation - 1959 Section*
B3010.01 Deck Vapor Retarder and Insulation - 1961 Section*
B3010.01 Deck Vapor Retarder and Insulation - 1963 Section*
B3010.04.04 Modified Bituminous Membrane Roofing (SBS) - 1959 Section**
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
1963
1959
1961
1963
1990
Installed
Installed
Installed
Installed
Installed
30
0
0
0
25
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Replace Exterior Entrance Doors
Replace SBS Roofing
Lifecycle Replacement
Lifecycle Replacement
2012
2015
$3,432
$81,111
Unassigned
Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
APR-08
APR-08
Double painted metal doors and frame exiting towards parking lot
Drawings indicate 50mm Stramit insulation over Q-deck may have been replaced when SBS membrane was installed. Notverified
Drawings indicate 50mm Stramit Insulation over Q-deck may have been replaced when SBS membrane was installed. Notverified
Not verified
BUR replaced with SBS roofing membrane
Report run on: July 23, 2008 2:42 PM Page 14 of 40
B3010.04.04 Modified Bituminous Membrane Roofing (SBS) - 1961 Section**
B3010.04.04 Modified Bituminous Membrane Roofing (SBS) - 1963 Section**
B3010.08.02 Metal Gutters and Downspouts - 1959 Section**
B3010.08.02 Metal Gutters and Downspouts - 1961 Section**
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
1990
1990
1990
1990
Installed
Installed
Installed
Installed
25
25
30
30
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Replace SBS Roofing
Replace SBS Roofing
Replace Gutters & Downspouts
Replace Gutters and Downspouts
Lifecycle Replacement
Lifecycle Replacement
Lifecycle Replacement
Lifecycle Replacement
2015
2015
2020
2020
$28,180
$27,653
$7,543
$3,409
Unassigned
Unassigned
Unassigned
Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Event:
Event:
Type
Type
Type
Type
Year
Year
Year
Year
Cost
Cost
Cost
Cost
Priority
Priority
Priority
Priority
Updated:
Updated:
Updated:
Updated:
APR-08
APR-08
APR-08
APR-08
Metal downspouts from sloped roofing to splash pads at grade
Metal downspouts from sloped roofing to splash pads at grade
Report run on: July 23, 2008 2:42 PM Page 15 of 40
B3010.08.02 Metal Gutters and Downspouts - 1963 Section**
B3020.02 Other Roofing Openings (Hatch,Vent, etc) - 1959 Section*
B3020.02 Other Roofing Openings (Hatch,Vent, etc) - 1961 Section*
B3020.02 Other Roofing Openings (Hatch,Vent, etc) - 1963 Section*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
1990
1959
1961
1963
Installed
Installed
Installed
Installed
30
0
0
0
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Replace Gutters and Downspouts
Lifecycle Replacement 2020 $3,409 Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Type Year Cost Priority
Updated: APR-08
Metal scupper & downspouts from roof to asphalt hard surface
Original skylights capped over, plumbing vents from washrooms,
Original skylights capped over
Original skylights capped off and roofed over
Report run on: July 23, 2008 2:42 PM Page 16 of 40
C1010.01.03 Unit Masonry Assemblies: Partitions -
C1010.01.07 Framed Partitions (Stud) -
C1010.07 Interior Partition Firestopping - *
C1020.01 Interior Swinging Doors (& Hardware) - *
4 - Acceptable
4 - Acceptable
2 - Poor
4 - Acceptable
Rating
Rating
Rating
Rating
1959
1959
1959
1959
Installed
Installed
Installed
Installed
0
0
0
40
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Install fire rated partition
Code Repair 2008 $3,432 Medium
Remove existing partition around mechanical unit Concern:
Install new rated partition. See C1020.01 for new door Recommendation:
Calgary - St. Thomas Aquinas Elementary School (B2827A)
S3 INTERIOR
Event:
Type Year Cost Priority
Updated: MAR-08
SCR brick walls between classrooms, between classrooms and corridor, and around storage rooms in classrooms
Principals office, upper walls of classrooms at corridor wall and around furnace in staff room
Furnace in staffroom is enclosed in wood framed and wood panelled wall with no ratings
Painted wood Doors in metal frames with half glass lites and transfer grilles leading to classrooms. Original satin chromefinish orbit locksets on interior doors Solid wood doors in metal frames to storage cupboards in classrooms Hollow metal doors in metal frames in hallway with hold-open devices Hollow metal doors and frames to mechanical and meter room
Report run on: July 23, 2008 2:42 PM Page 17 of 40
C1020.03 Interior Fire Doors - *
C1020.05.01 Coiling Doors and Grilles
C1020.07.01 Access Doors and Panels
C1030.01 Visual Display Boards - **
2 - Poor
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
1959
0
1959
1959
Installed
Installed
Installed
Installed
0
0
0
20
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Replace doors & frames
Replace Chalkboards and tackboards
Code Repair
Lifecycle Replacement
2008
2012
$4,576
$22,880
Medium
Unassigned
Unrated door and frame separating staff room form HVAC unitand frame to mechanical room has large section missing inorder to install new equipment
Concern:
Replace doors and frames with new rated doors & frames .Install new hardware
Recommendation:
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
MAR-08
APR-08
Unrated wood door and frame in wood partition at Gymnasium HVAC unit Metal door & frame at mechanical room, meter room and storage room
1963: Fire rated painted vertical metal shutters between gymnasium and mudroom 1995:Fire rated stainless Steel vertical metal shutter between office and main entrance
Access floor with quarry tile finish at main entrance outside mechanical room
Chalkboards & tackboards throughout
Report run on: July 23, 2008 2:42 PM Page 18 of 40
C1030.02 Fabricated Compartments(Toilets/Showers) - **
C1030.08 Interior Identifying Devices - *
C1030.10 Lockers - **
C1030.12 Storage Shelving - *
C1030.14 Toilet, Bath, and Laundry Accessories - *
5 - Good
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
1959
1959
1959
1961
1959
Installed
Installed
Installed
Installed
Installed
30
0
30
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Replace Fabricated Toilet Compartments
Replace wood cubbies/cabinets
Lifecycle Replacement
Lifecycle Replacement
2012
2012
$5,720
$28,600
Unassigned
Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
APR-08
APR-08
Painted metal toilet compartments
Black lamacoid signs above doors to classrooms. Becasue of the small size of the school directions are readily evident
Wood mounted cubbies with coat hooks and upper cabinets mounted in classrooms
A combination of metal and wood storage shelving in storage room
Wall mounted mirrors, soap dispensers and paper towel holders. Toilet paper holders and metal garbage cans inwashrooms
Report run on: July 23, 2008 2:42 PM Page 19 of 40
C2010 Stair Construction*
C3010.06 Tile Wall Finishes - **
C3010.11 Interior Wall Painting - *
C3020.01.01 Epoxy Concrete Floor Finishes - *
C3020.01.02 Paint Concrete Floor Finishes - *
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
3 - Marginal
Rating
Rating
Rating
Rating
Rating
1989
1959
1959
1995
1990
Installed
Installed
Installed
Installed
Installed
100
40
10
0
10
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Replace Tile Wall Finish
Refinish floor with industrial epoxy coating
Lifecycle Replacement
Failure Replacement
2012
2009
$14,872
$2,288
Unassigned
Medium
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
APR-08
MAR-08
Refer to F1030.05 for connecting link stair & ramp information
102x102mm glazed ceramic wall tile from floor to 1810mm AFF in washrooms
Painted drywall on upper walls in classrooms and around windows
Gym floor replaced in early 90's with pulastic epoxy floor finish
Painted concrete floor in mechanical room
Report run on: July 23, 2008 2:42 PM Page 20 of 40
C3020.02 Tile Floor Finishes - **
C3020.07 Resilient Flooring - **
C3020.08 Carpet Flooring - Administration Area & 105**
4 - Acceptable
4 - Acceptable
3 - Marginal
Rating
Rating
Rating
1959
1995
1995
Installed
Installed
Installed
50
20
15
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Replace Tile Floor Finish
Replace Resilient Flooring
Replace Carpet Flooring
Lifecycle Replacement
Lifecycle Replacement
Lifecycle Replacement
2012
2012
2012
$11,440
$17,160
$9,152
Unassigned
Unassigned
Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Event:
Type
Type
Type
Year
Year
Year
Cost
Cost
Cost
Priority
Priority
Priority
Updated:
Updated:
Updated:
APR-08
APR-08
MAR-08
25mm X 25mm unglazed floor tiles in washrooms 102x204mm quarry tiles at mudroom and main entrance
Original VAT flooring was replaced with sheet vinyl in the early 1990's. Sheet vinyl in corridors, part of room 105 and staffroom
1995: Carpet replaced in Administration area and room 105
Report run on: July 23, 2008 2:42 PM Page 21 of 40
C3020.08 Carpet Flooring - Classrooms**
C3030.06 Acoustic Ceiling Treatment (Susp.T-Bar) - **
C3030.07 Interior Ceiling Painting - *
3 - Marginal
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
1980
1959
1959
Installed
Installed
Installed
15
25
20
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Replace capet in classrooms
Replace Acoustic Ceiling Tiles
Preventative Maintenance
Lifecycle Replacement
2009
2012
$36,608
$24,024
Medium
Unassigned
Carpet floors are heavily worn and won't last 5 more yearsConcern:
Replace with sheet vinyl flooringRecommendation:
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
MAR-08
APR-08
Low level loop carpet
Suspended ceiling grid system and non-directional fissured mineral fibre ceiling tiles throughout classrooms, corridors andoffice areas
Painted metal pan in meter room, custodial room and mud room
Report run on: July 23, 2008 2:42 PM Page 22 of 40
D2010.04 Sinks**
D2010.08 Drinking Fountains / Coolers**
D2010.10 Washroom Fixtures (WC, Lav, Urnl)**
D2020.01.01 Pipes and Tubes: Domestic Water*
4 - Acceptable
5 - Good
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
1959
2004
1959
1959
Installed
Installed
Installed
Installed
30
35
30
0
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Replace Sinks
Replace Drinking Fountains / Coolers
Replace Washroom Fixtures (WC, Lav, Urnl)
Lifecycle Replacement
Lifecycle Replacement
Lifecycle Replacement
2012
2031
2012
$2,465
$2,467
$19,229
Unassigned
Unassigned
Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
S4 MECHANICAL
Event:
Event:
Event:
Type
Type
Type
Year
Year
Year
Cost
Cost
Cost
Priority
Priority
Priority
Updated:
Updated:
Updated:
APR-08
APR-08
APR-08
There is one stainless steal sinks in the staff room, and a porcelain on steel mop sink
There are several newer stainless steel drinking fountains.
The wash room fixtures are wall hung basins, With Crane faucets. The toilets are wall mounted with flush valves , theurinals are floor mounted with flush tanks. The staff and infirmary have tank type toilets that have been replaced recently.
The municipal water service is 2" copper. This branches to 1 1/4" for domestic water and 1 1/4 for lawn services.
Report run on: July 23, 2008 2:42 PM Page 23 of 40
D2020.01.02 Valves: Domestic Water**
D2020.01.03 Piping Specialties (Backflow Preventors)**
D2020.02.06 Domestic Water Heaters**
D2020.03 Water Supply Insulation: Domestic*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
1999
1999
2002
1959
Installed
Installed
Installed
Installed
40
20
20
0
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Replace Valves: Domestic Water
Replace Piping Specialties (Backflow Preventors)
Replace Domestic Water Heaters
Lifecycle Replacement
Lifecycle Replacement
Lifecycle Replacement
2039
2019
2022
$7,488
$6,818
$6,818
Unassigned
Unassigned
Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Event:
Type
Type
Type
Year
Year
Year
Cost
Cost
Cost
Priority
Priority
Priority
Updated:
Updated:
Updated:
APR-08
APR-08
APR-08
There are key operated frost free hose bibs with vacuum breakers.
There is a 1 1/4 Back flow preventor for the domestic water, one 1 1/4" for the lawn services and one 3/4" for the boiler feed.
One Bradford White hot water tank 36,000 BTU, 40 U.S. Gallon capacity.
The water lines have rigid fiberglass insulation, with a canvas covering in exposed areas.
Report run on: July 23, 2008 2:42 PM Page 24 of 40
D2030.01 Waste and Vent Piping*
D2040.02.04 Roof Drains*
D3010.02 Gas Supply Systems*
D3020.02.01 Heating Boilers and Accessories: H.W.**
D3020.02.02 Chimneys (&Comb. Air): H.W. Boiler**
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
1959
1959
1959
2004
2004
Installed
Installed
Installed
Installed
Installed
0
40
60
35
30
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Replace Heating Boilers and Accessories: H.W.
Replace Chimneys (&Comb. Air): H.W. Boiler
Lifecycle Replacement
Lifecycle Replacement
2039
2034
$27,440
$5,882
Unassigned
Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
APR-08
APR-08
Piping is cast underground, with cast and copper above ground.
Roof drains come down through the roof into eaves trough type piping, on to the surface.
There is a 1 1/4" municipal under ground natural gas supply for the school. The pressure is reduced in side the school andthe line size increased to 2 " to feed the school.
There are 2 Super hot boilers, they are 720,000 BTU's each. A horizon expansion tank and 2 Pumps service the boilers.
Ducted combustion air supplies the natural gas equipment in the boiler room. The boilers and hot water tank tie into metalbestos chimneys.
Report run on: July 23, 2008 2:42 PM Page 25 of 40
D3020.02.03 Water Treatment: H. W. Boiler*
D3040.01.01 Air Handling Units: Air Distribution**
D3040.01.02 Fans: Air Distribution (Remote from AHU)*
D3040.01.04 Ducts: Air Distribution*
D3040.01.07 Air Outlets & Inlets:Air Distribution*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
2004
1959
1959
1959
1959
Installed
Installed
Installed
Installed
Installed
0
30
0
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Replace Air Handling Units: Air Distribution
Lifecycle Replacement 2012 $18,776 Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Type Year Cost Priority
Updated: APR-08
There is a pot feeder with a by pass filter and sight glass. The chemical treatment is logged.
There is an air handling unit with a heating coil in the mechanical room. A circ pump circulates the water through the coil.
There are Lennox air distribution units in each class room. They pull heated air from under ground duct work when heat isrequired or out side air when ventilation is required.
The supply and return air ducts are square and round galvanized metal through out the school. The supply air for the classrooms is in under ground ducts. The gym is supplied through cabinets along the wall.
There are square diffusers for the air supply in metal cabinets along the wall, with upper wall grills for return air and doorgrills to return through the hall ways.
Report run on: July 23, 2008 2:42 PM Page 26 of 40
D3040.03.01 Hot Water Distribution Systems**
D3040.04.01 Fans: Exhaust**
D3040.04.03 Ducts: Exhaust*
D3040.04.05 Air Outlets and Inlets: Exhaust*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
2004
1959
1959
1959
Installed
Installed
Installed
Installed
40
30
0
0
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Replace Hot Water Distribution Systems
Replace Fans: Exhaust
Lifecycle Replacement
Lifecycle Replacement
2044
2012
$24,082
$3,869
Unassigned
Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
APR-08
APR-08
Hot water is distributed through welded and screwed steel piping and fittings, from the boilers to the heat transfer unitslocated in the mechanical room.
The school is serviced with exhaust fans for the wash rooms and two for the gym to outside bell type fans on the wall.
The exhaust ducts are square and round galvanized sheet metal.
Exhaust grills are egg crate type.
Report run on: July 23, 2008 2:42 PM Page 27 of 40
D3050.05.02 Fan Coil Units**
D3060.02.01 Electric and Electronic Controls**
D4030.01 Fire Extinguisher, Cabinets and Accessories*
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
2004
1959
1999
Installed
Installed
Installed
30
30
30
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Replace Fan Coil Units
Replace Electric and Electronic Controls
Lifecycle Replacement
Lifecycle Replacement
2034
2012
$21,984
$22,880
Unassigned
Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
APR-08
APR-08
There are 2 fan coil units with duct work under the floor to each room. There are also 2 units to supply the gym.
There are low voltage controls for the heating and ventilation equipment.
There are ABC hand held fire extinguishers through out the school.
Report run on: July 23, 2008 2:42 PM Page 28 of 40
D5010.03 Main Electrical Switchboards (Main Distribution)**
D5010.05 Electrical Branch Circuit Panelboards (Secondary Distribution)**
D5010.07.02 Motor Starters and Accessories**
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
1959
1959
1959
Installed
Installed
Installed
40
30
30
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Replace Main Electrical Switchboards (MainDistribution)
Replace Branch Circuit Panelboards
Replace Motor Starters
Lifecycle Replacement
Lifecycle Replacement
Lifecycle Replacement
2012
2012
2012
$20,284
$10,205
$1,759
Unassigned
Unassigned
Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
S5 ELECTRICAL
Event:
Event:
Event:
Type
Type
Type
Year
Year
Year
Cost
Cost
Cost
Priority
Priority
Priority
Updated:
Updated:
Updated:
APR-08
APR-08
APR-08
120/240 V, 200A 1 phase 3 wire main distribution, underground feeders; it works fine and, based on visual inspection, itseems to be in good condition, although the equipment has exceeded its life cycle. Not enough margin for futureupgrades/additional loads, therefore the upgrade of the main service and main distribution will be required at that time.
Various manufacturers. Some panels have been added in the past upgrades. the amount of spare circuits is very limited.Any upgrades/additions will require additional panels.
No MCC. Individual motor starters, feeding the mechanical loads.
Consequences of Deferral:
200Capacity Size
ampsCapacity Unit
Report run on: July 23, 2008 2:42 PM Page 29 of 40
D5020.01 Electrical Branch Wiring*
D5020.02.01 Lighting Accessories (Lighting Controls)*
D5020.02.02.02 Interior Florescent Fixtures**
D5020.02.03.02 Emergency Lighting Battery Packs**
D5020.02.03.03 Exit Signs*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
1959
1959
1959
1959
1959
Installed
Installed
Installed
Installed
Installed
0
0
30
20
0
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Replace Interior Florescent Fixtures
Replace Emergency Lighting Battery Packs**
Lifecycle Replacement
Lifecycle Replacement
2012
2012
$60,687
$4,323
Unassigned
Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
APR-08
APR-08
Where accessible for visual inspection, wiring is in conduit. There are no visible signs of overheating or electric arcs.
Individual switches, placed in various locations; some are key operated.. No LV controls.
Although functional, the maintenance may become costly (lamp replacement and power bill) . When replaced, thefluorescent lighting should be upgraded to T-8 technology.
Battery packs have been replaced since the construction. The emergency lighting has been tested yearly and it has beenfound functional.
Exit signs installed throughout the building, indicating in a clearly manner the egress pathways. Connected to line voltageand to emergency DC power.
Report run on: July 23, 2008 2:42 PM Page 30 of 40
D5020.03.01.03 Exterior Metal Halide Fixtures*
D5030.01 Detection and Fire Alarm**
D5030.02.02 Intrusion Detection**
D5030.03 Clock and Program Systems*
D5030.04.01 Telephone Systems*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
1959
1959
1959
1959
1959
Installed
Installed
Installed
Installed
Installed
0
25
25
25
25
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Replace Fire Alarm System
Replace Intrusion Detection**
Lifecycle Replacement
Lifecycle Replacement
2012
2012
$18,938
$11,139
Unassigned
Unassigned
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
APR-08
APR-08
Lights at access doors. Preferably, for safety, more lights along the perimeter should be installed (in the portableclassrooms area).
Edwards 6500 panel, 3 spare zones; remote annunciator at entrance. Pull stations and smoke detectors as required. Gongs in corridors and gym (no strobe lights). Magnetic door holders at corridor doors.
Silent Knight, with motion sensors strategically placed. The sensors cover the corridors and the access points.
Battery operated clocks. Bells through PA system.
Nortel system, with telephone sets in office area; no phone sets in classroom (paging via PA system).
Report run on: July 23, 2008 2:42 PM Page 31 of 40
D5030.04.05 Local Area Network Systems*
D5030.05 Public Address and Music Systems**
3 - Marginal
3 - Marginal
Rating
Rating
1959
1959
Installed
Installed
0
20
Design Life
Design Life
MAR-08
MAR-08
Updated
Updated
Replace Public Address and Music Systems
Failure Replacement 2011 $4,580 Medium
The existing system is not reliable, the staff and caretakerscomplaining about frequent failures. The system is obsolete.
Concern:
Replace with newer equipment.Recommendation:
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Type Year Cost Priority
Updated: APR-08
CAT 5 network; some classrooms are not connected, or they have insufficient connections (more than one computer, butonly one CAT 5 cable). Inadequate terminations at some locations (cables terminated with male connectors, pluggedstraight into the computer).
Raulands, located in the office area. Unreliable and difficult to operate.
Consequences of Deferral:Inconvenience for users and excessive maintenance costs.
Report run on: July 23, 2008 2:42 PM Page 32 of 40
E1020.02 Library Equipment - *
E1090.04 Residential Equipment - *
E1090.07 Athletic, Recreational, and Therapeutic Equipment - *
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
1959
1959
1959
Installed
Installed
Installed
0
0
0
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Repair plastic laminate top of charging desk
Repair 2008 $2,288 Medium
Plastic laminate is damaged at corner of librarians deskConcern:
Replace plastic laminate topRecommendation:
Calgary - St. Thomas Aquinas Elementary School (B2827A)
S6 EQUIPMENT, FURNISHINGS AND SPECIAL CONSTRUCTION
Event:
Type Year Cost Priority
Updated: MAR-08
Central charging desk with book drop, AV and Computers present
Refrigerator, Stove and microwave in staff room
Wall mounted basketball hoops in gymnasium, floor mats, and floor hockey nets
Report run on: July 23, 2008 2:42 PM Page 33 of 40
E2010.02 Fixed Casework - **
E2010.03.06 Curtains and Drapes**
3 - Marginal
4 - Acceptable
Rating
Rating
1959
1990
Installed
Installed
35
30
Design Life
Design Life
MAR-08
MAR-08
Updated
Updated
Replace Fixed Casework
Replace Drapes
Failure Replacement
Lifecycle Replacement
2009
2020
$68,640
$16,016
Medium
Unassigned
Painted millwork and upper cupboards are worn and will requireincreased repairs and maintenance
Concern:
Replace fixed cabinets in classrooms throughoutRecommendation:
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
MAR-08
APR-08
Painted plywood shelving and cupboards throughout classrooms. Light stained fir plywood shelving in library
Blackout drapes in all classrooms and sheer drapes in office area and staff room
Report run on: July 23, 2008 2:42 PM Page 34 of 40
F1010.02.04 Portable and Mobile Buildings - C84CS30*
4 - AcceptableRating
1989Installed
0Design Life
MAR-08Updated
Replace Lighting with T-8 Fixtures
Energy Efficiency Upgrade 2010 $2,288 Low
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Type Year Cost Priority
Updated: MAR-08
Architectural Floor: Sheet Vinyl flooring along coat hook area adjacent to corridor wall and low pile carpet throughout the rest of theroom over 16mm T&G GIS plywood flooring on 13mm fibre board on 6 mil poly vapour barrier over 16mm T&G plywoodsubfloor supported on 38x235 floor joist @ 400 o.c. Cavity filled with RSI 5.4 batt insulation 13mm plywood under sheathing Walls: Horizontal prefinished Metro Brown metal cladding upper wall and cedar brown plywood vertical board pattern overair barrier on 13mm plywood sheathing over 38x140 wood studs @ 400 o.c. Cavity filled with RSI 3.5 batt insulation 6 milpoly vapour barrier and 16mm Type 'X' GWB with paint finish Ceiling: T-bar grid system with Acoustic fibreboard lay in ceiling tiles Roof: 2ply elastomeric membrane on 13mm plywood wood deck supported on roof joists @ 400 o,c, cavity filled with RSI61. Batt insulation with 6 mil poly vapour barrier below and 16mm Type 'X' GWB ceiling taped and mudded There is a small painted drywall wood framed storage room in one corner of the room adjacent to the corridor. Technical Condition : Acceptable Recommendations: None. Mechanical Gas fired Lennox furnace for heating and ventilation rated at approx. 75,000 BTU. Air is supplied through rectangle diffusersin the top corner of the room and returned through a corner duct. The unit is controlled with its own stand aloneprogrammable thermostat. Technical Condition: acceptable. Recommendations: None. Electrical Life safety: smoke detection devices; Exit signs, emergency lighting, manual pull stations and F.A. gongs in the adjacentcorridor. Lighting: T-12 fluorescent; lighting levels satisfactory. Power receptacles - adequate; Data: 1 run; Phone: paging via PA system only; Technical Condition: acceptable. Recommendations: upgrade lighting from T-12 to T-8 technology
Report run on: July 23, 2008 2:42 PM Page 35 of 40
F1010.02.04 Portable and Mobile Buildings C81CS63*
4 - AcceptableRating
0Installed
30Design Life
MAR-08Updated
INstall new ceiling & Replace Lighting
Repair Battens & Caps
Energy Efficiency Upgrade 2008 $3,432 Unassigned
Metal battens have not been replaced where coat hooks wereremoved from the wall. There is minor vinyl damage to the wallin the northeast corner and vinyl caps are missing in a numberof locations
Concern:
Replace metal battens and PVC caps. Repair damaged vinylRecommendation:
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Event:
Type Year Cost Priority
Updated: MAR-08
Architectural (circa 1981: interior has been refurbished) Floor: Sheet Vinyl flooring throughout over 16mm T&G GIS plywood flooring on 13mm fibre board on 6 mil poly vapour barrierover 16mm T&G plywood subfloor supported on 38x235 floor joist @ 400 o.c. Cavity filled with RSI 5.4 batt insulation 13mmplywood under sheathing. Sheet Vinyl in the main corridor Walls: Horizontal prefinished Metro Brown metal cladding upper wall and cedar brown plywood vertical board pattern over airbarrier on 13mm plywood sheathing over 38x140 wood studs @ 400 o.c. Cavity filled with RSI 3.5 batt insulation 6 mil polyvapour barrier and vinyl clad gypsum board panels secured with metal battens and pvc covers (some battens/caps aremissing) Ceiling: Stipple ceiling finish directly applied to gypsum roof board Roof: 2ply elastomeric membrane on 13mm plywood wood deck supported on roof joists @ 400 o,c, cavity filled with RSI61. Batt insulation with 6 mil poly vapour barrier below and 16mm Type 'X' GWB ceiling taped and mudded There is a small painted drywall wood framed storage room in one corner of the room adjacent to the corridor. Technical Condition : acceptable except for missing battens Recommendations: Repair battens and caps Mechanical Gas fired Lennox furnace for heating and ventilation rated at approx. 75,000 BTU. Air is supplied through rectangle diffusersin the top corner of the room and returned through a corner duct. The unit is controlled with its own stand aloneprogrammable thermostat. Technical Condition: acceptable. Recommendations: None. Electrical Life safety: smoke detection devices; Exit signs, emergency lighting, manual pull stations and F.A. gongs in the adjacentcorridor. Lighting: T-12 fluorescent; lighting levels satisfactory. Power receptacles - adequate; Data: 1 run; Phone: paging via PA system only; Technical Condition: acceptable. Recommendations: upgrade lighting from T-12 to T-8 technology
Report run on: July 23, 2008 2:42 PM Page 36 of 40
F1010.02.04 Portable and Mobile Buildings C92CS11*
4 - AcceptableRating
1993Installed
30Design Life
MAR-08Updated
Repair 2008 $1,144 Medium
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Type Year Cost Priority
Updated: MAR-08
Architectural (circa 1992) Floor: Sheet Vinyl flooring along coat hook area adjacent to corridor wall and low pile carpet throughout the rest of theroom over 16mm T&G GIS plywood flooring on 13mm fibre board on 6 mil poly vapour barrier over 16mm T&G plywoodsubfloor supported on 38x235 floor joist @ 400 o.c. Cavity filled with RSI 5.4 batt insulation 13mm plywood under sheathing. Sheet Vinyl also in the main corridor Walls: Horizontal prefinished Metro Brown metal cladding upper wall and cedar brown plywood vertical board pattern overair barrier on 13mm plywood sheathing over 38x140 wood studs @ 400 o.c. Cavity filled with RSI 3.5 batt insulation 6 milpoly vapour barrier and 16mm Type 'X' GWB with paint finish Ceiling: T-bar grid system with Acoustic fibreboard lay in ceiling tiles . There is a painted gypsum bulkhead along the wallfrom the furnace room Roof: 2ply elastomeric membrane on 13mm plywood wood deck supported on roof joists @ 400 o,c, cavity filled with RSI61. Batt insulation with 6 mil poly vapour barrier below and 16mm Type 'X' GWB ceiling taped and mudded There is a small painted drywall wood framed storage room in one corner of the room adjacent to the corridor. Technical Condition : Acceptable Recommendations : None Mechanical Gas fired Carrier furnace for heating and ventilation rated at approx. 99,000 BTU. Air is supplied through rectangle diffusersin the top corner of the room and returned through a corner duct. The unit is controlled with its own stand aloneprogrammable thermostat. Technical Condition: acceptable. Recommendations: None. Electrical Life safety: smoke detection devices; Exit signs, emergency lighting, manual pull stations and F.A. gongs in the adjacentcorridor. Lighting: T-8 fluorescent; lighting levels satisfactory. Power receptacles - adequate; Data: 1 run; Phone: paging via PA system only; Technical Condition: acceptable. Recommendations: None.
Report run on: July 23, 2008 2:42 PM Page 37 of 40
F1010.02.04 Portable and Mobile Buildings C96CS34*
4 - AcceptableRating
1996Installed
30Design Life
MAR-08Updated
Reseal around roof drain
Repair 2008 $1,144 Medium
Stained ceiling tile indicates roof leakConcern:
Leak is located near roof drain. Inspect roof drain and resealbetween drain assembly and roof membrane
Recommendation:
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Type Year Cost Priority
Updated: MAR-08
Architectural Floor: Sheet Vinyl flooring along coat hook area adjacent to corridor wall and low pile carpet throughout the rest of theroom over 16mm T&G GIS plywood flooring on 13mm fibre board on 6 mil poly vapour barrier over 16mm T&G plywoodsubfloor supported on 38x235 floor joist @ 400 o.c. Cavity filled with RSI 5.4 batt insulation 13mm plywood under sheathing Walls: Horizontal prefinished Metro Brown metal cladding upper wall and cedar brown plywood vertical board pattern overair barrier on 13mm plywood sheathing over 38x140 wood studs @ 400 o.c. Cavity filled with RSI 3.5 batt insulation 6 milpoly vapour barrier and 16mm Type 'X' GWB with paint finish. Ceiling: T-bar grid system with Acoustic fibreboard lay in ceiling tiles . There is an exposed painted gypsum bulkhead alongthe wall from the furnace room Roof: 2ply elastomeric membrane on 13mm plywood wood deck supported on roof joists @ 400 o,c, cavity filled with RSI61. Batt insulation with 6 mil poly vapour barrier below and 16mm Type 'X' GWB ceiling taped and mudded There is a small painted drywall wood framed storage room in one corner of the room adjacent to the corridor. Technical Condition : acceptable - carpet has minor seam and one pull. There is a stained ceiling tile approximately wherethe roof drain is located Recommendations: Repair Leak and replace ceiling tile Mechanical Gas fired Manufactured Air System furnace for heating and ventilation rated at approx. 90,000 BTU. Air is supplied throughrectangle diffusers in the top corner of the room and returned through a corner duct. The unit is controlled with its own standalone programmable thermostat. Technical Condition: acceptable. Recommendations: None. Electrical Life safety: smoke detection devices; Exit signs, emergency lighting, manual pull stations and F.A. gongs in the adjacentcorridor. Lighting: T-8 fluorescent; lighting levels satisfactory. Power receptacles - adequate; Data: 1 run; Phone: paging via PA system only; Technical Condition: acceptable. Recommendations: None.
Report run on: July 23, 2008 2:42 PM Page 38 of 40
F1030.05 Other Special Construction Systems*
F2020.01 Asbestos - *
F2020.04 Mould - *
F2020.09 Other Hazardous Materials - *
4 - Acceptable
3 - Marginal
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
1989
1959
1959
1959
Installed
Installed
Installed
Installed
0
0
0
0
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Replace VAT tiles & Study Perforated ceiling tiles
Hazardous MaterialManagement Upgrade
2010 $8,008 Low
VAT tiles are still present in the storage rooms. Damagededges are visible at door openings. Damaged perforated ceilingtile in gym storage room
Concern:
Replace with sheet vinyl or VCT tiles. Test preforated ceilingtiles to see if replacement program in gym and gym storageroom should be undertaken.
Recommendation:
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Type Year Cost Priority
Updated: MAR-08
Internal corridor/link to portables complete with storage room. (construction similar to portables) West side has a concrete slab on grade with sloped floor for ramp to exit doors and a wood framed ramp with slip resistantAltro-20 Walkway sheet vinyl surface and painted metal tube railings to corridor level of portables. There is a wood framedstaircase with rubber treads and risers in the centre corridor area. On the east end a painted drywall wood framed (with battinsulation) storage room has been created for art supplies. The room has a painted gypsum ceiling, fire detector and has afire rated door & frame. There is a vented crawl space below the storage area east of the central corridor.
VAT tiles still present in storage cupboards in classrooms. There is minor damage to the edges of the tiles at the door.Perforated ceiling tiles in gymnasium may contain asbestos fibres (if original)
No mould visible . None reported
No other Hazardous materials visible. None reported
Report run on: July 23, 2008 2:42 PM Page 39 of 40
K3010 Building Services -
K3020 Indoor Environment -
K4010.01 Barrier Free Route: Parking to Entrance - *
K4010.02 Barrier Free Entrances - *
K4010.03 Barrier Free Interior Circulation - *
4 - Acceptable
4 - Acceptable
4 - Acceptable
3 - Marginal
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
1959
1959
1959
1959
1959
Installed
Installed
Installed
Installed
Installed
0
0
0
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Install New Door with Auto-Operator
Barrier Free Access Upgrade 2009 $17,160 Low
No auto-operator. A disabled student requires assistance toenter school
Concern:
Calgary - St. Thomas Aquinas Elementary School (B2827A)
S8 FUNCTIONAL ASSESSMENT
Event:
Type Year Cost Priority
Updated: MAR-08
Most services are acceptable except that the caretakers area is shared with computer data racks which should have beenlocated in a separate area.
The indoor environment is generally acceptable except for barrier free concerns.
At grade asphalt with asphalt walkway to front entrance
Painted Steel door in pressed steel frames. No Auto-operators
Ramp to portables all other rooms and washrooms at the same level
Report run on: July 23, 2008 2:42 PM Page 40 of 40
K4010.04 Barrier Free Washrooms - *
K4020 Building Code -
3 - Marginal
4 - Acceptable
Rating
Rating
1959
1959
Installed
Installed
0
0
Design Life
Design Life
MAR-08
MAR-08
Updated
Updated
Create Accessible Washroom
Barrier Free Access Upgrade 2009 $22,880 Low
No disabled water closet or sink.Concern:
Replace storage room (adjacent to office area - now an officewith an accessible washroom/infirmary) convert infirmary tosmall office/storage room
Recommendation:
Calgary - St. Thomas Aquinas Elementary School (B2827A)
Event:
Type Year Cost Priority
Updated: MAR-08
Washrooms are not accessible
Building appears to meet current code requirements except for the fire ratings around the mechanical equipment asidentified in C1010.07 and C1020.03
Report run on: July 24, 2008 2:54 PM
RECAPP Facility Evaluation Report
St. Thomas Aquinas School
S2827Calgary
Report run on: July 24, 2008 2:54 PM Page 2 of 8
S2827Building Id:
St. Thomas Aquinas SchoolBuilding Name:
CalgaryLocation:Address:
0.00Gross Area (sq. m): $0Replacement Cost:0Construction Year:
Evaluation Date: October 13 2007
Quinn Young Architects Ltd.Evaluation Company:
Barry McCallumEvaluator Name:
The site is approximately 1.1 ha and the main school entrance is located in the southeast corner of the site and faces26th Ave SW. There is a paved parking lot located on the south side at the intersection of 45th Street and 26th AvenueSW. A grassed playing field with ball diamond is located on the north side. The playing fields and parking area areseparated by a creative play area and asphalt play surfaces for the students. There is a chain link fence between theparking area and the student areas. Buses drop off students on Garland Street on the east side of the school site. Thesite is almost flat with a slight slope from the northwest to southeast. Sloped roofs are drained via gutters and rain waterleaders to splash pads around the perimeter of the building. Overall the site is in acceptable condition
General Summary:
Structural Summary:
Envelope Summary:
Interior Summary:
Mechanical Summary:
Electrical Summary:
0%5 year Facility Condition Index (FCI):
Facility Details Evaluation Details
Total Maintenance Events Next 5 years: $96,668
Calgary - St. Thomas Aquinas School (S2827)
Condition Rating Performance1 - Critical Unsafe, high risk of injury or critical system failure.2 - Poor Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs.
3 - Marginal Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs.4 - Acceptable Meets present requirements, minor deficiencies. Average operating/maintenance costs.
Rating Guide
5 - Good Meets all present requirements. No deficiencies.6 - Excellent As new/state of the art, meets present and foreseeable requirements.
Report run on: July 24, 2008 2:54 PM Page 3 of 8
G2010.02.02 Flexible Pavement Roadway (Asphalt) - **
G2010.05 Roadway Curbs and Gutters - *
G2020.02.02 Flexible Paving Parking Lots(Asphalt) - **
G2020.06.01 Traffic Barriers - *
G2020.06.02 Parking Bumpers - *
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
1959
1959
1959
1959
1959
Installed
Installed
Installed
Installed
Installed
25
0
25
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Replace Asphalt Roadway
Replace Asphalt Parking Lot
Lifecycle Replacement
Lifecycle Replacement
2012
2012
$3,432
$62,920
Unassigned
Unassigned
Calgary - St. Thomas Aquinas School (S2827)
S7 SITE
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
APR-08
APR-08
Asphalt driveway to parking lot from 45th street
Concrete curbs from 45th Street to parking lot
Asphalt parking lot
Chain link gate between parking lot and hard play area
Precast concrete parking bumpers used as curbs at perimeter of parking
Report run on: July 24, 2008 2:54 PM Page 4 of 8
G2020.06.03 Parking Lot Signs - *
G2020.06.04 Pavement Markings - *
G2030.02.02 Asphalt Pedestrain Pavement**
G2030.04 Rigid Pedestrian Pavement (Concrete) - **
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
1959
1959
1959
1959
Installed
Installed
Installed
Installed
0
0
20
25
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Replace Asphalt walkways
Replace concrete sidewalk
Lifecycle Replacement
Lifecycle Replacement
2012
2012
$2,288
$2,860
Unassigned
Unassigned
Calgary - St. Thomas Aquinas School (S2827)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
MAR-08
APR-08
Typical parking signs attached to chain link fence
Yellow stall lines
Asphalt walkways adjacent to building from parking lot to main entrance and from Garland Street to main entrance. Wideasphalt walkway from Garland Street to old north entrance area (now blocked off by portables)
Concrete sidewalk form 26th Avenue to main school entrance
Report run on: July 24, 2008 2:54 PM Page 5 of 8
G2030.06 Exterior Steps and Ramps - *
G2040.02.01 Chain Link Fences and Gates*
3 - Marginal
4 - Acceptable
Rating
Rating
1959
1959
Installed
Installed
0
30
Design Life
Design Life
MAR-08
MAR-08
Updated
Updated
Repair
Repair 2009 $3,432 Medium
Stair guards and deck are worn. Notyh end of deck has brokenboards
Concern:
Repair railings/ guards on staircase. Replace wood deck withasphalt paving
Recommendation:
Calgary - St. Thomas Aquinas School (S2827)
Event:
Type Year Cost Priority
Updated: MAR-08
Wood Stair case with metal safety tread stair treads on north side of school to play area large wood landing at grade
Chain Link fence around playing fields and between playing area and parking
Report run on: July 24, 2008 2:54 PM Page 6 of 8
G2040.03 Athletic and Recreational Surfaces - **
G2040.05 Site and Street Furnishings - *
G2040.06 Exterior Signs - *
G2040.08 Flagpoles - *
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
1959
1959
1959
1959
Installed
Installed
Installed
Installed
25
0
0
0
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Repair Asphalt Play surface
Replace Asphalt Recreational Surface
Repair
Lifecycle Replacement
2009
2012
$4,576
$17,160
Low
Unassigned
Weeds are growing in cracks Play surface markings are fadingConcern:
Remove weeds and repair asphalt cracks. Paint new playmarkings
Recommendation:
Calgary - St. Thomas Aquinas School (S2827)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
MAR-08
APR-08
Large grass playing fields and asphalt hard play area adjacent to school
A couple of steel framed benches with wood seats by the creative play area
Large lettering on backing panel located on upper gym wall facing 26th Avenue SW
Painted metal flagpole at main entrance
Report run on: July 24, 2008 2:54 PM Page 7 of 8
G2050.01 Irrigation Systems*
G2050.04 Lawns and Grasses - *
G2050.05 Trees, Plants and Ground Covers - *
G3010.02 Site Domestic Water Distribution*
G3010.03 Site Fire Protection Water Distribution*
G3020.01 Sanitary Sewage Collection*
G3030.01 Storm Water Collection*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
Rating
1959
1959
1959
1959
1959
1959
1959
Installed
Installed
Installed
Installed
Installed
Installed
Installed
0
0
0
0
0
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Calgary - St. Thomas Aquinas School (S2827)
The school has lawn services with no under ground irrigation.
Large elm in front of school and large poplars along Garland Street
The school has a 50mm copper water service.
There is a fire hydrant 15m from the school on the S.W. corner.
A 152mm sanitary line is connected to a 204mm municipal service in Garland Street
The storm water from the school site runs on the surface to the street. Drawings indicate that Internal roof drains from flatroof over washroom/office area go to drywell in front yard facing 26th Avenue.
Report run on: July 24, 2008 2:54 PM Page 8 of 8
G3060.01 Gas Distribution*
G4010.02 Electrical Power Distribution Lines - *
G4010.03 Electrical Power Distribution Equipment - *
G4010.04 Car Plugs-ins - *
G4020.01 Area Lighting - *
4 - Acceptable
3 - Marginal
4 - Acceptable
4 - Acceptable
3 - Marginal
Rating
Rating
Rating
Rating
Rating
1959
1959
1959
1959
1959
Installed
Installed
Installed
Installed
Installed
0
0
0
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
MAR-08
MAR-08
MAR-08
MAR-08
MAR-08
Updated
Updated
Updated
Updated
Updated
Calgary - St. Thomas Aquinas School (S2827)
There is an under ground natural gas service to the school.
Underground 200 amp, 120/240V, 1 phase, Canadian Westinghouse no provision for future service
Utility company supplied Pole mounted transformer down to grade with 3 #250 MCM conducters in 102mm fibre duct
18 stalls with 16 plug-ins encased in concrete posts
Wall mounted HID at upper gym wall and at exit doors. Soffit mounted lighting at main entrance.