reading a ge pslf *.epc into pws tracy rolstad avista system planning wecc pwsug, 14 march 2012
TRANSCRIPT
![Page 1: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/1.jpg)
Reading a GE PSLF *.epc into PWS
Tracy Rolstad
Avista System Planning
WECC PWSUG, 14 March 2012
![Page 2: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/2.jpg)
Open Case, Select <GE EPC format (with options)>
![Page 3: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/3.jpg)
What Options (these are defaults)?
![Page 4: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/4.jpg)
Start with GE
• Nothing is sacred about the GE defaults. Change them!
• Solve the case, multiple times…
• GE uses an estimated mismatch
• So, solve in GE three times or so
• Save the solved case as an *.epc file
![Page 5: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/5.jpg)
Read into PWS and Solve
• Read in case, note mismatches, understand them
• Lock all controls down, solve in PWS (set gen voltage control)
Check Interface flows against GE…
– GE allows double counting the same line
• PWS does NOT allow double counting
• Note Mismatch resolution in log
PWS Zero Impedance Line is very, very small
– GE uses X=0.00029 (0.725 ohms @ 500 kV)
– PWS uses X=0.00001 (0.025 ohms @ 500 kV)
![Page 6: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/6.jpg)
Mismatch Table
![Page 7: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/7.jpg)
Mismatches in State Variable View
![Page 8: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/8.jpg)
Mismatches in Input Data View
![Page 9: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/9.jpg)
![Page 10: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/10.jpg)
After Fixing GE Bface Error
• Errors after removing extra BFACE entry
Total MW Error (i.e. sum) = -19.5
Max MW Error = 3.7 (North to South California, Path 24)
Min MW Error = -4
![Page 11: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/11.jpg)
Read the Log, Understand and Take Action
![Page 12: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/12.jpg)
Read into PWS and Solve
• Unlock all controls, solve in PWS
Check log for AGC movement
– May need to “Zero out transactions”
• If GE transaction table isn’t manually updated by WECC staff
Check Interface flows against GE…
– Should get pretty much the same answer on path flows
Check for multiple islands
![Page 13: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/13.jpg)
Zeroing Out Transactions
![Page 14: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/14.jpg)
Voltage Control for Generators
• Allocate across buses using the user-specified remote regulation percentages. This option is what is used by default and most closely matches the sharing seen in RAW files.
• Allocate so all generators are at same relative point in their [min .. max] var range. This option most closely matches the sharing seen in a few EMS solutions PowerWorld has seen.
• Allocate across buses using the SUM OF user-specified remote regulation percentages. This option most closely matches the sharing seen in EPC files.
• Note: Generators at the same bus always allocate vars so they are at the same relative point in their [min…max] range
![Page 15: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/15.jpg)
Var Sharing
Bus: CABGOR12 (48061)
Nom kV: 13.80
Area: NORTHWEST (40)Zone: AVA: Coeur D'Alene (441)
System State
ID 1 ID 2
CAB GORG
CKT 1
81%
A
MVA
CABGOR12
1.0046 pu
13.86 KV
81.26 Deg 0.00 $/MWh
55.000 MW
22.299 Mvar
65.000 MW
8.714 Mvar
0.00 MW
0.00 Mvar
1.0716 tap
120.0 MW
31.0 Mvar
123.9 MVA
48059
1.0478 pu
240.99 KV
![Page 16: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/16.jpg)
Comparing PWS to GE VAr “Answer”
CABGOR12
55 MW 22 Mvar
65 MW 9 Mvar
CABGOR12 #1
VAr % across range-CE
1.00
0.00
76.61%
CABGOR12 #2
VAr % across range-CE
1.00
0.00
76.61%
31.7 Mvar -8.5 Mvar
18.7 Mvar -24.0 Mvar
CABGOR12
55 MW 16 Mvar
65 MW 16 Mvar
CABGOR12 #1
VAr % across range-CE
1.00
0.00
60.95%
CABGOR12 #2
VAr % across range-CE
1.00
0.00
93.68%
31.7 Mvar -8.5 Mvar
18.7 Mvar -24.0 Mvar
![Page 17: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/17.jpg)
Check Case Summary and Slack Bus Generator
Quantity GE PWS
Load MW 169427.5 169427.5
Gen MW 175697.1 175693.0
Losses MW 6269.8 6263.5
Buses count 18205 18585
Load MVAr 31767.3(t_area)
31718.3
Load MVAr* 32291.53 31718.3
Slack MW 538.0 543.01
* Summed directly from load record
![Page 18: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/18.jpg)
Look for Places to Establish “Test Flows”
![Page 19: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/19.jpg)
Check Performance in Contingent Environment
Bus: BENEWAH (48037)
Nom kV: 230.00
Area: NORTHWEST (40)
Zone: AVA: Palouse (446)
System State
ID s
MOSCOW
CKT 1
PINE CRK
CKT 1
SHAWNEE
CKT 1
BOULDER
CKT 1
BENEWAH
CKT 1
A
MVA
A
Amps
A
Amps
A
Amps
BENEWAH
1.0158 pu
233.64 KV
58.54 Deg
0.00 $/MWh
0.000 Mvar
0.00 MW
0.00 Mvar
61.0 MW
-18.7 Mvar
63.8 MVA
48249
1.0200 pu
234.61 KV
0.0 MW
0.0 Mvar
0.0 MVA
48317
1.0397 pu
239.14 KV
67.1 MW
-16.1 Mvar
69.0 MVA
48385
1.0181 pu
234.16 KV
166.3 MW
20.1 Mvar
167.6 MVA
48524
1.0156 pu
233.59 KV
1.0059 tap
38.3 MW
14.8 Mvar
41.0 MVA
48035
1.0015 pu
115.17 KV
![Page 20: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/20.jpg)
Participation Factor Note (Added Post Meeting)
• During the second WECC PWS Users Group we noticed that PWS was parsing the Gen MVA field of the *.epc file and setting Participation Factors on that field. In many cases this value is merely set to 100 MVA (for example the large units located in the third power house at Grand Coulee).
• Users should be alert to this behavior and manually set Participation Factors to be based on Pmax
Typically setting Participation Factors to Pmax is the desired setting for dispatching make-up power during contingency analysis, etc.
![Page 21: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/21.jpg)
Setting Participation Factors
![Page 22: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/22.jpg)
Questions?
• PWS will provide similar, but not exact results when compared to GE (or PTI)
• Heuristics abound…
What is “right?” Good reason to use multiple tools
• VAr dispatch of generation has an impact, especially on the initialization point for transient stability
• Zero impedance line representations have some impact
• Recommendation
• Presume that both software provide reasonably accurate possible solution points
• Take five minutes to understand the case read!!!
![Page 23: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012](https://reader035.vdocuments.mx/reader035/viewer/2022062307/551b241c550346cf5a8b59dd/html5/thumbnails/23.jpg)