Latest Technologies in Refrigeration and Air Conditioning - XVI European Conference Milano, 12th - 13th June 2015
General Gas
HONEYWELL - CONFIDENTIAL 1
R404A replacements in Commercial
refrigeration.
Latest Technologies in Refrigeration and Air Conditioning - XVI European Conference Milano, 12th - 13th June 2015
General Gas
HONEYWELL - CONFIDENTIAL 2
Agenda
Introduction to HFOs and Solstice® family
R404A replacement:
R407F Solstice® N40 (R-448A) HDR110
F-Gas: business consequences
Latest Technologies in Refrigeration and Air Conditioning - XVI European Conference Milano, 12th - 13th June 2015
General Gas
HONEYWELL - CONFIDENTIAL 3
F-Gas – Control of Use in Commercial Refrigeration
2015 2016 2017 2018 2019 2020 2022 2025 2028 2030
New Installation
Bans* (only main bans affecting Refrigeration shown
here)
Maintenance & Service
Bans* (only those affecting Refrigeration shown here)
Stationary Refrigeration
Equipment requiring HFC
>2500 GWP
Centralised multipack
systems >40kW capacity
using HFC >150 GWP /
except primary circuit
(not distributed) of
cascade system where
<1500 GWP is acceptable
New Commercial
Refrigerators / Freezers
(hermetically sealed
systems) >2500 GWP
New Commercial
Refrigerators / Freezers
(hermetically sealed
systems) >150 GWP
Domestic refrigerators
and freezers using
HFC’s >150 GWP
Virgin F-gases >2500 GWP
for servicing ref equip. With charge size of >40 T CO₂-eq (~10kg R404A)
Recycled and reclaimed F-
gases with >2500 GWP for
servicing ref equip with a charge size of >40 T CO₂-eq
RAC & H/Pump equip. pre-
charged with F-gases must be
included in a registered Quota system beginning 2017
Exemptions include Military
equipment and refrigeration
applications below -50 Deg C
NOTE: R407F (<1825 GWP) repl. for
R404A - can be used for servicing
without end date (beyond 2030...)
Phase-Down of HFC’s will have the Greatest Impact
Latest Technologies in Refrigeration and Air Conditioning - XVI European Conference Milano, 12th - 13th June 2015
General Gas
HONEYWELL - CONFIDENTIAL 4
F-Gas – Phase Down
Phase Down Mechanism
• What is your Strategy for Change? It should include...
• Refrigerant leak / charge reduction
• Educate your team and your customers on this change
• Improve your understanding of the low GWP alternatives to R404A
• Understand the minor differences in ‘how they are applied’
F-gas Regulations will
Challenge our Industry
Opportunities
• Become more comfortable with the differences glide / flammability / high pressures / different system technologies etc..
• Refrigerant choice – STOP using R404A wherever possible
• Mindset - Change provides Opportunities for your business
Latest Technologies in Refrigeration and Air Conditioning - XVI European Conference Milano, 12th - 13th June 2015
General Gas
HONEYWELL - CONFIDENTIAL 5
Introduction to Solstice® family
Solstice® HFO molecules Low and medium pressure applications
Nonflammable
(ASHRAE A1)
Mildly flammable
(ASHRAE A2L)
Examples of potential
applications
R-134a GWP=1430
Solstice® yf GWP* < 1
Auto A/C, Vending,
Refrigerators
Solstice® ze GWP* < 1
Chillers, CO2 Cascades
Refrigerators
R-123 GWP= 77
Solstice® zd GWP* =1
Centrifugal Chillers
*IPPC5
Latest Technologies in Refrigeration and Air Conditioning - XVI European Conference Milano, 12th - 13th June 2015
General Gas
HONEYWELL - CONFIDENTIAL 6
Introduction to Solstice® family
Solstice® Blends
Non Flammable
(ASHRAE A1)
Mildly Flammable
(ASHRAE A2L)
Examples of potential
applications
R-134a GWP=1430
Solstice® N13 (R-450A) GWP* = 547
Chillers, Med-temp
Refrigeration
R-404A
GWP=3922
Solstice® N40 (R-448A) GWP* = 1273
Solstice® HDR 110 GWP* < 150
Low-Temp
Refrigeration
R-22 GWP=1810
Solstice® N20
GWP* = 891
Solstice® L20 (R444B) GWP* = 295
Stationary A/C,
Refrigeration
R-410A GWP=2088
Solstice® L41 (R-447A) GWP* = 572
Stationary A/C
Applications
*IPPC5
Latest Technologies in Refrigeration and Air Conditioning - XVI European Conference Milano, 12th - 13th June 2015
General Gas
HONEYWELL - CONFIDENTIAL 7
R407F: Independent Measured Performance Comparison
Efficiency comparisons (Independent verification)
• Important improvements in MT applications ~ 10%
• Climate / system specific / optimisation during retro-fit
• Still large improvements at LT conditions ~ 6%
• Clear overall improvement in Energy Efficiency shown by R407F
Considerable
reduction in
operational / running
costs
0
10
20
30
40
50
60
70
80
90
100
110
120
103%
Bit
zer
Test
AS
DA
106%
Tew
is S
tud
y 108%
Sch
reze
nm
aier
Mo
rris
on
s
113%
Sa
fric
lim
107%
10
0%
110%
AS
DA
113%
Bit
zer
Test
115%
R40
4A
Efficiency
@ Medium Temp Efficiency
@ Low Temp
R407F (Measured Results) R404A
Baseline
Latest Technologies in Refrigeration and Air Conditioning - XVI European Conference Milano, 12th - 13th June 2015
General Gas
HONEYWELL - CONFIDENTIAL 8
MT
60%
70%
80%
90%
100%
110%
120%
-10°C / 45°C -30°C / 45°C
Cap
acit
y %
wit
h R
esp
ect
to
R4
04
A
Introducing N40 (R448A): Capacity & COP
Under system-like conditions, both R407F and N40 (R448A) provide capacity above 95% of R404A in low and medium temp applications
Under medium temp system conditions, R407F and N40 (R448A) provide the best efficiency (COP) Under low temp system conditions, N40 (R448A) provides the highest COP
Mean Pressures / Suct. Temp = -4°C (LT); 20°C (MT) / Useful Superheat = 5K / Subcooling = 0K
R4
04
A
R4
07
A
R4
07
F
R4
49
A
N4
0 (
R4
48
A)
R4
04
A
R4
07
A
R4
07
F
R4
49
A
N4
0 (
R4
48
A)
80%
85%
90%
95%
100%
105%
110%
115%
120%
-10°C / 45°C -30°C / 45°C
CO
P %
wit
h R
esp
ect
to
R4
04
A
R4
04
A
R4
07
A
R4
07
F
R4
49
A
N4
0 (
R4
48
A)
R4
04
A
R4
07
A
R4
07
F
R4
49
A
N4
0 (
R4
48
A)
BITZER Software: semi-hermetic compressor (4GE-23Y)
LT MT LT
Latest Technologies in Refrigeration and Air Conditioning - XVI European Conference Milano, 12th - 13th June 2015
General Gas
HONEYWELL - CONFIDENTIAL 9
90%
95%
100%
105%
110%
115%
120%
LT (-30°C) and MT (-10°C) @ 45°C Cond. Temp
% w
ith
Re
spe
ct t
o R
40
4A
Combined* LT and MT Energy Efficiency
70
80
90
100
110
120
130
140
150
-10°C / 45°C -30°C / 45°C
Dis
char
ge T
em
pe
ratu
re (
de
g C
)
Discharge Temperature
R4
04
A
R4
07
A
R4
07
F
R4
49
A
N4
0 (
R4
48
A)
R4
04
A
R4
07
A**
R4
07
F**
R4
49
A
R4
48
A (
R4
48
A)
R4
04
A
R4
07
A
R4
07
F
R4
49
A
N4
0 (
R4
48
A)
Bitzer Performance: Combined LT/MT & Tdischarge
R448A (best) and R407F (better) provide the highest combined energy efficiency
Due to lower discharge temperature, R448A is less likely than R407A or R407F to require liquid injection** **Requirements will vary depending on the actual operating conditions.
* 33% of total load from low temp and 67% from medium temp **Liquid injection required
Semi-Hermetic Compressor (4GE-23Y)
MT LT
Latest Technologies in Refrigeration and Air Conditioning - XVI European Conference Milano, 12th - 13th June 2015
General Gas
HONEYWELL - CONFIDENTIAL 10
Emerson Performance: Solstice® N40 (R-448A)
• Copeland Liquid and EVI Scroll
• Medium and Low Temperature
0.00
1.00
2.00
3.00
4.00
5.00
6.00
COP
COPARI/Dew Performance
0.0
1.0
2.0
3.0
4.0
5.0
6.0
COP
COP(Midpoint/SH 5K Peformance)
0.0
3.0
6.0
9.0
12.0
15.0
Cap
acit
y [k
W]
Capacity(ARI/Dew Performance)
0.0
3.0
6.0
9.0
12.0
15.0
Cap
acit
y [k
W]
Capacity(Midpoint/SH 5K Performance)
Scroll System Analysis @ -6.7°C / 48.9°C
R404A N40
Baseline 17%
>R404A
N40
11% >R404A
R404A
Baseline
• Copeland S/Hermetic Reciprocating
• Medium and Low Temperature
0.0
5.0
10.0
15.0
20.0
25.0
Cap
acit
y (k
W)
Capacity ARI/Dew Performance
0.0
5.0
10.0
15.0
20.0
25.0
Cap
acit
y (k
W)
CapacityMidpoint/SH 5K Performance
0.0
0.4
0.8
1.2
1.6
2.0
2.4
COP
COPARI/Dew Performance
0.0
0.4
0.8
1.2
1.6
2.0
2.4
COP
COPMidpoint/SH 5K Performance
15% >R404A
10% >R404A
N40
N40
R404A
R404A
Baseline
Baseline
Semi-Hermetic System Analysis @ -31.6°C / 43.3°C
Qualified for Use
‘N40 provides
superior
Energy
Efficiency to
that of R-404A
with reduced
GWP’
Latest Technologies in Refrigeration and Air Conditioning - XVI European Conference Milano, 12th - 13th June 2015
General Gas
HONEYWELL - CONFIDENTIAL 11
3rd Party evaluations: Solstice® N40 (R-448A)
Oak Ridge National Laboratory (US) Supermarket System Evaluation
Reduced compressor power by 3.7%
Increased refrigeration capacity by 7.5% Increased system COP by 11.6%
Baseline
R404
11% >R404A
Tewis Smart Systems Laboratory Test in Simulated Supermarket set-up
vs R-404A
Latest Technologies in Refrigeration and Air Conditioning - XVI European Conference Milano, 12th - 13th June 2015
General Gas
HONEYWELL - CONFIDENTIAL 12
3rd Party evaluations: Solstice® N40 (R-448A)
Toshiba Refrigeration (Japan) Condensing Unit Performance trial
Ambient tests at 32º & 43º C to JIS 8623 (std)
N40 showed 4-16%higher COP and excellent
match in capacity
ASDA (UK) Successful >14 months trial store comparison
Improved capacity and efficiency vs. R404A Simple retro-fit with minimal system adjustment Discharge Temp close to R404A level (no liq injection
required on LT)
90%
95%
100%
105%
110%
115%
120%
125%
130%
To=32℃ To=43℃ To=32℃ To=43℃
Ca
pa
city
,CO
P [
%(v
s.R
40
4A
)]
Capacity COP
Evaporating
temperature -5°CEvaporating
temperature -30°C
108%110%
107%
116%
104% 102%
109%
98%
(JIS B 8623) (JIS B 8623)
‘Solstice N40 is well
engineered refrigerant
to meet requirement as
an alternative to
R404A’
Refrigerants roadmap: R-404A
Medium temperature and low temperature stationary refrigeration
Performax LT (R-407F)
Baseline R-404A (A1, 3922 / 3943)
GWP 4th
/ 5th 1824 / 1764
Class. A1
Potential app. MT and LT stationary refrigeration
Use New/Retrofit
Drop-in (1)
Cap. Similar
Drop-in (1)
Eff. 5% to 10% higher
Compressor (2) Recip, Scroll, Screw
CommentsNo TXV change
Higher Tdis in LT
Status Commercial
Solstice® N40 (R-448A)
Baseline R-404A (A1, 3922 / 3943)
GWP 4th
/ 5th 1386 / 1273
Class. A1
Potential app. MT and LT stationary refrigeration
Use New/Retrofit
Drop-in (1)
Cap. Similar
Drop-in (1)
Eff. 5% to 10% higher
Compressor (2) Recip, Scroll, Screw
CommentsNo TXV change
Good compressor envelope coverage
Status Available for sampling. Commercial 2015
(1) Drop-in test in a non-optimized system
(2) Suitable compressor technology, check with Honeywell technical department for qualified models
BETTER BEST
Performax LT (R-407F) is preferred option • Already commercial • Homologated by most components
manufacturers • Proven experience in commercial, industrial and
food service applications over Europe • Closer cost to R-404A than Solstice N40
Solstice N40 (R-448A) could be interesting if: • Further GWP reduction is desired
Environmental goal Tax country
• Slight improvement of Tdis vs R-407F is required Solstice N40: Tdis still higher than R-404A Solstice N40: Tdis still lower than R-22
Latest Technologies in Refrigeration and Air Conditioning - XVI European Conference Milano, 12th - 13th June 2015
General Gas
HONEYWELL - CONFIDENTIAL 14
HDR110 (GWP<150): Self-Contained System Evaluation
ASHRAE 72 standard test: 3/4 HP Reach-in R404A Freezer placed in a chamber at 25°C Cabinet volume filed with glycol/water test simulators and frozen food
Near drop-in test of HDR-110: TXV was slightly adjusted to provide appropriate superheat No oil change required. Typical charge optimization carried out Evaporator position inverted to get counter-flow configuration
Latest Technologies in Refrigeration and Air Conditioning - XVI European Conference Milano, 12th - 13th June 2015
General Gas
HONEYWELL - CONFIDENTIAL 15
24h Freezer Performance: HDR-110 vs R404A
Capacity within 5% of R404A
Efficiency increased by 6%
Maximum discharge temperature (108°C) within compressor limits
HDR-110 under Evaluation by Major Equipment Manufacturers
80%
85%
90%
95%
100%
105%
110%
Capacity Efficiency
Pe
rfo
rman
ce [
% o
f R
40
4A
]
R404A HDR-110