r-type fire alarm system - ホーチキ株式会社 · versatile gr-type fire alarm system...
TRANSCRIPT
![Page 1: R-TYPE FIRE ALARM SYSTEM - ホーチキ株式会社 · Versatile GR-type Fire Alarm system (capacity: about 5,000m2 ~ 70,000m2) 2 types: wall-mounted and freestanding 8 models Simple](https://reader035.vdocuments.mx/reader035/viewer/2022062917/5ed29f779c816a0c4332660b/html5/thumbnails/1.jpg)
Equipped withAutomatic Test
Function
HRK-TYPE
GR-TYPECONTROL PANEL
R-TYPE FIREALARM SYSTEM
R-TYPE FIREALARM SYSTEM
Weare
concernedwith
"BasicFunctions"
Small • Medium ScaleGR-Type Control Panel
![Page 2: R-TYPE FIRE ALARM SYSTEM - ホーチキ株式会社 · Versatile GR-type Fire Alarm system (capacity: about 5,000m2 ~ 70,000m2) 2 types: wall-mounted and freestanding 8 models Simple](https://reader035.vdocuments.mx/reader035/viewer/2022062917/5ed29f779c816a0c4332660b/html5/thumbnails/2.jpg)
1
HRK
1
It provides security for office buildings, apartments, mansions,hotels, departmental stores, hospitals, schools and factories.It has thoroughly explored the fundamental functions of the R-typesystem. More buildings than ever are installed with the R-type FireAlarm system.
Addresses Addresses
Compatible with
Versatile GR-type Fire Alarmsystem (capacity: about 5,000m2
~ 70,000m2)2 types: wall-mounted andfreestanding 8 modelsSimple applicability andoperabilityLow-cost and automatic testfunction-equippedClear LCD and warning alertComform to new specificationfor public addressStandard installation withsmoke control • gas leakagewarning functionConnect up to 39 units of R-type display panel (can connectup to 15 units of annuciators)Enhanced function for signaltransfer at serial port.
Handles 2 system 254 addresses ~16 system 2032 system (1 system 127 addresses)
Highly versatileConnectable with annuciator
Standard installation with monthly log function • Flexible transmission
Standard installation with fire alarm function and analog monitor function
![Page 3: R-TYPE FIRE ALARM SYSTEM - ホーチキ株式会社 · Versatile GR-type Fire Alarm system (capacity: about 5,000m2 ~ 70,000m2) 2 types: wall-mounted and freestanding 8 models Simple](https://reader035.vdocuments.mx/reader035/viewer/2022062917/5ed29f779c816a0c4332660b/html5/thumbnails/3.jpg)
2
Total extension distance: system km
Comfortable Multiple System MethodComfortable Multiple System Method
R-type
Making
full
use
of
the
basic
functions
of
the
system
The R-type system ofHOCHIKI is not easilyaffected by the noiseinterference generated bymobile phones
Positioning R-type System
Dispersedtype
Centralisedtype
MULTIPLE SYSTEM METHOD(1 SYSTEM 127 ADDRESSES)If the transmission route for the R-type FireAlarm system uses a single system, a singlefailure may affect the entire system. Thus,based on the risk diversification philosophy,HOCHIKI incorporated a multiple-systemdesign, which reduces the impact on thesystem to its minimum should a failure occurs.
TOTAL EXTENSION DISTANCE :2.4KMTo monitor scattered buildings at a site, suchas a factory, for instance, the transmissiondistance will be insufficient on the singlesystem method and multiple control panelsbecome necessary. With the multiple systemdesigned by HOCHIKI, however, a singlesystem can accommodate 2.4km of totalextension distance. Thus, a single unit of thecontrol panel can handle all the monitoringactivities. This method provides much moreroom than the single system method.
HRF III
HRH
HRK
HRG II
HRJ
HRJ
P
No. of addresses (No. of lines) 254 508 762(1,016) 2,032 16,000
Intergrated Control Panel
Analog
GR
-type
Addressable A
nalog Function
Fire Alarm
& Sm
oke Control
PanelFire A
larm C
ontrol PanelR-type
Signal systemR-type Central Panel
Multiple system
Each system
R-type system (single system method)
R-type system (multiple system method)
1 unit of control panel
Insecure Ease ofmind
Relia-bility
Appli-cabi-lity
Cost-efficient
HRK
![Page 4: R-TYPE FIRE ALARM SYSTEM - ホーチキ株式会社 · Versatile GR-type Fire Alarm system (capacity: about 5,000m2 ~ 70,000m2) 2 types: wall-mounted and freestanding 8 models Simple](https://reader035.vdocuments.mx/reader035/viewer/2022062917/5ed29f779c816a0c4332660b/html5/thumbnails/4.jpg)
HRK
3
Low-cost, clear displayand user-friendy. Thedisplay and operationarea features easilydistinguishable design,colors and big buttonsfor easy operation.“User-friendliness” isthe key idea here.
Display and operation functionsconcentrated in the
L350mm x W420mmWide display and operation area
The reliable
Dual check functionStandard installation (automatic testfunction + self-diagnosis function)
Besides the automatic test function required by the Japan FireService Law, implemented via the use of the automatic testfunction-equipped detector, its standard installation includesthe unique self-diagnosis function which executes “ detectoroperation test”, “detector contamination test” and “standbypower test”. It cuts back on the running cost required bycontrol and operation as well as improves the reliability.
Easy monitoring and control bymeans of
Detector data(analog value)
Log functionstandard installation
Equipped with monthly loggingfunction for automatic testfunction-equipped detector data(analog value). When necessary,analog values of up to a monthcan be generated for displayand printing. A more accuratecontrol and operation (detailedknowledge of indoor environment condition) is achieved withlower unwanted alarm and appropriate sensitivity check.
VARIOUS WARNING DISPLAY
ANALOG MONITOR
WARNING DISPLAY
![Page 5: R-TYPE FIRE ALARM SYSTEM - ホーチキ株式会社 · Versatile GR-type Fire Alarm system (capacity: about 5,000m2 ~ 70,000m2) 2 types: wall-mounted and freestanding 8 models Simple](https://reader035.vdocuments.mx/reader035/viewer/2022062917/5ed29f779c816a0c4332660b/html5/thumbnails/5.jpg)
4
The user-friendliness of the R-typesystem taken into consideration.
Flexible system building
Multi-line modulesand monitormodules
The system’s flexible setupallows various combinations ofterminal devices via the use ofvarious modules. For example,to install a conventionaldetector or connect anIntruder detection sensor, usethe multi-line modules ormonitor modules which allowsthe connection of 1 addressand 4 lines. This arrangementprovides the building with adelicate system.
A wide scope of uses
Used for various purposes5 display lamps
The standard installation includes 5 display lamps whichcan display the fire hydrant, sprinkler, smoke controland air-condition, etc., individually. The condition ofthe equipment to bemonitored can beconstantly displayedwithout switching over tothe LCD. Direct input can beexecuted from the contact orinput can be executed from therelay.
Easy to understand
5.6 inch LCD
With the bright back-lit screen, the display is highlyvisible and easy to undestand. 16 characters of“English, numeric, Kana, Kanji” or 13 characters+ line number are adopted forthe message display. Theseparate function furthersplits the screen into upperand lower part for fastchecking and operation.
Conform to current needs
Conform to the newspecification forPublic AddressStandard installation
This system conforms to the newJapanese public address standardsuch as the signal transfer for fireverification (2nd fire alarm • ManualCall Point • fire identification).
Early detection of fire
Pre-Alarm functionStandard installation
Aggressive adoption of handyfunctions
Built-in printerwhich records systemoperation data
This function is handy as it recordsand prints detail data for eachoperation, including fire alarm,operation records of automatic testresult, and manual inspection. It isuseful for control and operation.
Design with theadministrator in mind
Illustratedoperation display
This system also conforms to the evaluationcriteria for the comprehensive control panel(operation console). It is further integratedwith the CRT display and can be used fordetailed management of equipmentinformation for the entire building.
Easy to understand
Compatible with thelatest comprehensivecontrol panel.
Easily understood illustrations are usedfor daily operations as well as emergency.The adminstrator needs not panic in anemergency.
The pre-alarm functionconstantly monitors thesignals received from theanalog function-equippeddetector. It issues warning(pre-alarm) before thesituation develops into afire.
Multi-line modules
Smoke detector x 17
Heat detector x 30 ormore
x 4 lines
* Screen Display may differ according to the version of the system.
![Page 6: R-TYPE FIRE ALARM SYSTEM - ホーチキ株式会社 · Versatile GR-type Fire Alarm system (capacity: about 5,000m2 ~ 70,000m2) 2 types: wall-mounted and freestanding 8 models Simple](https://reader035.vdocuments.mx/reader035/viewer/2022062917/5ed29f779c816a0c4332660b/html5/thumbnails/6.jpg)
5
AddressableManual Call
Point
Photoelectricbeam
type detector
Fixed-temperature
spot-typedetector
Rate of Risespot-typedetector
Photoelectricspot-typedetector
Fire monitormodule
Map • lamp display
Annuciator
R-type display panel+ annuciatorUp to 39 units
Bell module
Gas leakage module
Standard contactmonitor module
Smoke control module
RS-485 x 1 chR-type display panel
Fire monitor module1 system 127addresses Upto 16 systems2032 addresses
RS-232 x 2 ch
HRK control panel
CRT system
Centralised monitorpanel, etc.
PC (data setup etc.) Addressprogrammer
: Automatic test function device
HRK
![Page 7: R-TYPE FIRE ALARM SYSTEM - ホーチキ株式会社 · Versatile GR-type Fire Alarm system (capacity: about 5,000m2 ~ 70,000m2) 2 types: wall-mounted and freestanding 8 models Simple](https://reader035.vdocuments.mx/reader035/viewer/2022062917/5ed29f779c816a0c4332660b/html5/thumbnails/7.jpg)
6
The system handles differenttypes, scales, purposes anduses of building with ease.
This system provides flexible setup using moduleswhich matches the types of equipment information,such as automatic fire alarm, gas leakage, SmokeControl and general monitor equipment, etc., andallows flexible combination of connection withterminals. When combined with other facilities, itprovides the base for building a complete Fire Alarmenvironment which caters to the specific conditionsof buildings.
The system is useful for buildings of various scalesand uses, include areas where an indefinite numberof guests may visit, staff areas and parking spaces,etc. It helps to minimize confusion, which may ariseduring a fire, by its interlocked operations, such asthe administrator emergency guidance feature andsmoke control devices, etc.
This system caters to various types of buildingenvironment, uses and management systems (madepossible via the automatic test function using devicessuch as indoor detectors which operate when theoccupants are not around), such as the location andscale of buildings from a single block of high-risemansion to multiple-block apartments. It is a FireAlarm system designed with cost-effectiveness inmind.
The automatic test function allows the heat andsmoke tests to be omitted during the inspection,which allows a more comfortable environment forpatients. In addition, R-type display panel, whichprovides identification information on locations faraway from the control room, and annuciators, whichdisplay maps or lamps, can be installed in the nursecentres on every floor. As such, every floor will havea monitor system which runs 24-hours a day.
With the combined use of multi-signal detectorsand fire monitor modules, etc., a flexible monitorsystem can be built for guest rooms and publicrooms, etc. The privacy of your guests will bemaintained with the use of the automatic testfunction.
In the case of schools and factories, where variousfacilities are scattered around in the estates, acomfortably wide area monitor system can beconstructed with the R-type system characterisedby the multiple-system method, or the single-systemmethod characterised by its extension distance of2.4km/ system. It can also incorporate a centralisedcontrol using the CRT system.
Office Building •Tenant Building
Mansion •Apartment
Departmental Store• Shopping Centres
Hospital • Research Institute
School • FactoryHotel •Resort
![Page 8: R-TYPE FIRE ALARM SYSTEM - ホーチキ株式会社 · Versatile GR-type Fire Alarm system (capacity: about 5,000m2 ~ 70,000m2) 2 types: wall-mounted and freestanding 8 models Simple](https://reader035.vdocuments.mx/reader035/viewer/2022062917/5ed29f779c816a0c4332660b/html5/thumbnails/8.jpg)
7
2000
600450
1100
550160
WALL-MOUNTED TYPE
Flexible system configuration,with free incorporation of
variable modules that are...
(Unit : mm)
FREESTANDING TYPE
(Unit : mm)
Type Product code No. of No. of Capacity of External dimension Weightsystem address standby W x H x D kg
powerHRK- 2 254 3.5AH Approx.
ACW254FGA 34Wall HRK- 4 508 550 x 1100 x 160 Approx.
mounted ACW508FGA 38type HRK- 8 1016 6.0AH Approx.
ACW1016FGA 40HRK- 8 1016 6.0AH Approx.
Free- ACS1016FGA 127standing HRK- 12 1524 600 x 2000 x 450 Approx.
type ACS1524FGA 10.0AH 133HRK- 16 2032 Approx.
ACS2032FGA 135
Type GR-type Control Panel (Time Delay) with automatictest function
Product code HRK-ACW FGA HRK-ACS FGA(Wall-mounted type) (Freestanding type)
Main Power AC 220V 50/60HzPower consumption Maximum 6AStandby power DC24V Nickel Cadmium batteryNo. of main lines System line : HP 1.2-4C/system
Control line : HP 1.2-10PTransmission Polling • selecting (with interrupt function)systemLength of main Total extension distance 2.4kmsignal line Max distance 1.56km/systemAllowable line Main signal line : 30ΩresistanceDisplay Digital display LED 7 segment display
Fire : 6 digits x 2 windowsGas leakage : 6 digits x 2 windows
Message display Back-lit LCD (5.6 inch)Message : 16 characters or 13characters + lines number(JIS 1” and 2nd level Kanji)
Operation Section Menu, keypad, switchesRecord Built-in printerSignal transfer Various representative signal transfer : 10
Individual signal transfer : 15 (in-board : up to 60 points<option>)Serial port signal transfer : RS-232C (2 ch)
RS-485 (1 ch)Nominal time delay 50 seconds (smoke detector : 50 seconds;
heat detector : 20 seconds)Gas leakage time 40 secondsdelayMain sound • Synthetic sound, electronic sound and buzzerfailure soundMaterial Steel plate (1.6mm thick) baking paintColor Door, main set, : color closed to Munsell value :
2.5Y9/1 (100% glossy available)Operation, display panel : color closed to Munsell value5Y6/0.5 (30% glossy available)
![Page 9: R-TYPE FIRE ALARM SYSTEM - ホーチキ株式会社 · Versatile GR-type Fire Alarm system (capacity: about 5,000m2 ~ 70,000m2) 2 types: wall-mounted and freestanding 8 models Simple](https://reader035.vdocuments.mx/reader035/viewer/2022062917/5ed29f779c816a0c4332660b/html5/thumbnails/9.jpg)
8
PHOTOELECTRIC SPOT-TYPESMOKE DETECTOR (multi- signal)
...compatible with the variousinformation needs.
RATE OF RISE SPOT-TYPEHEAT DETECTOR
FIXED-TEMPERATURE SPOT-TYPEHEAT DETECTOR
MODULE
* Fire monitor modules (CHT-K4)
R-TYPE DISPLAY PANEL
Product code HEX-1PETransmission Up to 1km (from control panel)distanceDisplay Back-lit LCDAlarm Buzzer (option : synthetic sound)External (W) 300 x (H) 380 x (D) 70mmdimensionWeight Approx. 6kg (including battery)
SYSTEM DEVICES
Product name (type) Productcode
Fire monitor 4 lines CHT-K4
1 line CHP-KL
Gas leakage 4 lines CHT-G4
Standard 4 lines CHT-S4
contact monitor
Smoke Control 4 lines CHT-R4
(without
reset)
2 lines CHT-D2
(with reset)
Bell (with auto- 1 line CHT-BY
test function)
Addressable PRF-1
manual call point
R-type display HEX-1PE
panel
Annuciator * main units HEX-1PD
* Power, input/output and display units arerequired separately.
M Please refer to Hochik i main productcatalogue for exact requirement.
Modules
Manualcall point
DisplayPanel
Product code ALG-123LYRated power DC 39.5V 30mA
Product code ASA-2RLYRated power DC 26V 30mA
Product code ATG-TA60LYRated power DC 26V 30mA
SERVICE DEVICES
Product name Product code
Photoelectricspot-type smoke ALG-123LY
detector (multi-signal)
Photoelectricbeam-type smoke ABB-12Y
detector (dual-signal)
Rate of risespot-type ASA-2RLY
heat detector
Fixed-Temperaturespot-type ATG-TA60LY
heat detector
Photoelectricspot-type SLR-M
smoke detector
Ionisationspot-type SIJ-M
smoke detector
Fixed-Temperaturespot-type DFJ-M
heat detector
Combinedspot-type DCD-M
heat detector
Rate of risespot-type DSC-M
heat detector
Aut
o-te
st fu
nctio
neq
uipp
ed d
etec
tor
(with
ana
log
func
tion)
Purpose Fire monitor Leakage Standard contact Smoke control Bell
monitor monitor control
Product CHT-K4 CHT-G4 CHT-S4 CHT-R4 CHT-D2 CHT-BY
Current 620µA 270µA Contact a:320µA 280µA 220µA
consumption Contact b:680µA
Applicable wire ø0.8mm ~ ø1.6mm (single line)
Temperature -10˚C ~ 50˚C (for indoor)
range
Material Self-extinguish resin
Color Grey
External (W) 30 x (H) 200 x (D) 72mm
dimension
Weight Approx. 160g Approx. 140g Approx. 140g Approx. 170g Approx. 140g
Con
vent
iona
l Det
ecto
r
![Page 10: R-TYPE FIRE ALARM SYSTEM - ホーチキ株式会社 · Versatile GR-type Fire Alarm system (capacity: about 5,000m2 ~ 70,000m2) 2 types: wall-mounted and freestanding 8 models Simple](https://reader035.vdocuments.mx/reader035/viewer/2022062917/5ed29f779c816a0c4332660b/html5/thumbnails/10.jpg)
HOCHIKI CORPORATIONHEAD OFFICE2-10-43, Kamiosaki,Shinagawa-ku,Tokyo 141-8660, JAPANTelephone : 81-3-3444-4116Facsimile : 81-3-3444-4167
SINGAPOREBRANCH OFFICE629 Aljunied Road, #03-16Cititech Industrial BuildingSingapore 389838Telephone : 65-6841-9728Facsimile : 65-6841-9781Email : [email protected]
HOCHIKI AMERICA CORPORATIONTelephone : 1-714-898-0795Facsimile : 1-714-892-2809
HOCHIKI EUROPE (U.K.) LIMITEDTelephone : 44-1634-260133Facsimile : 44-1634-260132