PXIE RFQ Resonance Controller System modeling and controller design Jonathan Edelen and Auralee Edelen August 4, 2015 J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 1 / 20

Upload: dangdang

Post on 10-Apr-2018

220 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

PXIE RFQ Resonance ControllerSystem modeling and controller design

Jonathan Edelen and Auralee Edelen

August 4, 2015

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 1 / 20

Page 2: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Overview

• Control system requirements

• Control system architecture

• Review of LBL modeling of the RFQ

• Overview of the water cooling system

• Modeling of the water cooling system

• Initial controls simulations

• Way forward

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 2 / 20

Page 3: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Control system requirements

• Keep reflected power below 20% in order to maintain cavity fieldwith RF amplifiers

• Trip recovery time• Baseline: Recover in less then 10 times interruption time• Goal: Recover in less then 2 times interruption time

• Maximum recovery time (startup time)• Baseline: 30 minutes• Goal: 10 minutes

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 3 / 20

Page 4: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Control system architecture

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 4 / 20

Page 5: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

State machine

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 5 / 20

Page 6: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Modeling and Simulation Effort

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 6 / 20

Page 7: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Review of LBL modeling of the thermal properties ofthe RFQ

Figure: 2-D Electro-Thermal simulation (Andrew Lambert at LBL)

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 7 / 20

Page 8: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Review of LBL modeling of the thermal properties ofthe RFQ

Figure: RF transient response due to different vane and wall response times,(Andrew Lambert LBL)

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 8 / 20

Page 9: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Water cooling system overview

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 9 / 20

Page 10: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Model of the water cooling system

• Use model to understand general system behavior and underlyingdynamics

• Initial model (good for developing a general understanding)• RFQ is treated as two lumps of copper (vane and wall)• Vane and wall temperatures are coupled• Return temperature is mixed with cooler supply temperature• Pipe losses are modeled• Non-linear flow curve from valve is modeled• Pump heating is modeled• High degree of flexibility for additional complexity

• Higher fidelity numerical models (improved understanding oftransient behavior: in progress)

• Use to benchmark initial model• Possibly used later on for higher-fidelity control simulations

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 10 / 20

Page 11: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Model of the water cooling system

• Use model to understand general system behavior and underlyingdynamics

• Initial model (good for developing a general understanding)• RFQ is treated as two lumps of copper (vane and wall)• Vane and wall temperatures are coupled• Return temperature is mixed with cooler supply temperature• Pipe losses are modeled• Non-linear flow curve from valve is modeled• Pump heating is modeled• High degree of flexibility for additional complexity

• Higher fidelity numerical models (improved understanding oftransient behavior: in progress)

• Use to benchmark initial model• Possibly used later on for higher-fidelity control simulations

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 10 / 20

Page 12: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Model of the water cooling system

• Use model to understand general system behavior and underlyingdynamics

• Initial model (good for developing a general understanding)• RFQ is treated as two lumps of copper (vane and wall)• Vane and wall temperatures are coupled• Return temperature is mixed with cooler supply temperature• Pipe losses are modeled• Non-linear flow curve from valve is modeled• Pump heating is modeled• High degree of flexibility for additional complexity

• Higher fidelity numerical models (improved understanding oftransient behavior: in progress)

• Use to benchmark initial model• Possibly used later on for higher-fidelity control simulations

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 10 / 20

Page 13: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Comparison of initial model with LBL simulations

o Attempt to compare RFQcomponent of the cooling systemmodel to the 2-D ANSYSsimulations done by LBL

o Transient behavior is not wellmatched

o Steady state behavior is adequatelymatched

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 11 / 20

Page 14: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Initial model characterization with simple PI control(Step Response)

o At t = 0 the RF power increases by2%

o Step response of the RFQ thermalmodel only (blue line)

o Step response of the whole watersystem (red line)

o Step response with a simple PIloop modulating the vane FCV onthe resonant frequency error(yellow line)

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 12 / 20

Page 15: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Initial model characterization with simple PI control(Step Response)

- Closed loop time constant longerthen open loop

- A PI loop modulating just the vaneFCV can keep the RFQ onresonance but the response time istoo slow (need some sort of MPC)

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 13 / 20

Page 16: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Initial model characterization with simple PI control

o At t = 0 the RF power trips of for10s

o Trip response of the RFQ thermalmodel only (blue line)

o Trip response of the whole watersystem (red line)

o Trip response with a simple PIloop modulating the vane FCV onthe resonant frequency error(yellow line)

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 14 / 20

Page 17: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Initial model characterization with simple PI control

- Closed loop time constant longerthen open loop

- Ripples in the trip response aredue to temperature fluctuations inrecirculating water

- A PI loop modulating just the vaneFCV can keep the RFQ onresonance but the response time istoo slow (need some sort of MPC)

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 15 / 20

Page 18: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Implementation Effort

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 16 / 20

Page 19: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Overview

• Data acquisition (communicate with Cryo-con 18i over Ethernet)• Program can request data using SCPI commands through a TCP

socket• Archive of data is stored based on control algorithm needs

• Control system interfaces• LLRF system (SEL/GDR and cavity resonance information)• PLC (control actions to flow valve)• ACNET (general communication for high level control)

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 17 / 20

Page 20: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Overview

• Data acquisition (communicate with Cryo-con 18i over Ethernet)• Program can request data using SCPI commands through a TCP

socket• Archive of data is stored based on control algorithm needs

• Control system interfaces• LLRF system (SEL/GDR and cavity resonance information)• PLC (control actions to flow valve)• ACNET (general communication for high level control)

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 17 / 20

Page 21: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Cryo-con 18i temperature monitor

o Connects to up to 8temperature sensorssimultaneously

o Precision better than 0.01C

o Data available over Ethernetat a rate of 7.5 Hz

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 18 / 20

Page 22: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Data acquisition test over Ethernet

Figure: Sample data from RTD using Ethernet-CryoCon interface. Usingpython code and SCPI commands to communicate with the cryo-con overEthernet we confirmed our ability to reliably communicate with this device

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 19 / 20

Page 23: PXIE RFQ Resonance Controllerpxie.fnal.gov/PIPIImeetings/RCS_Presentation_4Aug2015.pdf · PXIE RFQ Resonance Controller ... model to the 2-D ANSYS simulations done by LBL oTransient

Way forward

• Initial development: from now until the RFQ water system isinstalled and operational

• Assemble control system hardware• Develop and test communication to the PLC• Develop and test interface between control system and ACNET• Develop test plan for gathering data on the RFQ• Develop initial control algorithm based on system model

• Milestone: RFQ water system installed and operational• Test initial control system• Study water system for full design of resonance control system• Iterate on control algorithm using test data

• Milestone: Final resonance control system implemented

J. Edelen and A. Edelen (CSU) PXIE RFQ Resonance Controller August 4, 2015 20 / 20