NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Inspection Type Last EditedTime InInspectionId
P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE, STATEN ISLAND, NY, 10304School:
4546 2020-03-24 07:20AM 2020-08-23 05:45PMARCHITECTURAL - SENIOR
4555 2020-03-24 10:33AM 2020-03-24 02:41PMARCHITECTURAL - ASSOCIATE
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? No
Shower Rooms (No key/storage)Comments on Inaccessible Inspection
Principal(s) Information
Principal Name Kristin Mchugh
Principal Organization R721 SPED - Staten Island
Meeting with Principal? No
Principal Feedback The Principal returned the questionnaire with the following
comment: The Elevators break down and need maintenance.
Custodian Was not present
Fireman Anthony Chickara
Building Square Footage 69,000
Comments on the Area (Square Feet) N/A
Comments on the Stories (Floors) plus Basements 3+B
Comments on the Year Built 1979
Comments on the Student Population 225
Comments on the Staff Population 193
Comments on the Number of Classrooms 29
Weather Fair
Facade Photo
Tompkins Avenue- North View
Main Entrance Photo
Facade A - 155 Tompkins Avenue
Page 1 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural InspectionRoof Photo
Roof 1 - Northeast View
Have any Systems/Major Building Components been upgraded? Systems: New Elevator addition
Years: 1992
Systems: Exterior Wall repointing (partial )
Years: 2003
Systems: New Exterior Doors(partial- Facade B),Parking Lot
repaved, New Fire Window
Years: 2009
Systems: Parapet repointing (partial)
Years: 2012
Systems: Nurse’ s Office relocated to Room 211, Chimney
repointing, repairs
Years: 2013
Have there been any New Building Additions? No New Construction
Tandem No Tandem
Leased Space? No
Priority ConditionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Accessibility
Accessibility Status Question Response
Is the Primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are All floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes
If the following spaces exist, are they ALL accessible? Art Room, Auditorium,
Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
Physical Breakdown Structure Exists Complies Required DeficiencyAudio
Induction
System
Fire
Alarm
Strobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
YesExterior Entrances & Exits
NoNoExterior H/C Lifts
Page 2 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Physical Breakdown Structure Exists Complies Required DeficiencyAudio
Induction
System
Fire
Alarm
Strobe
NoNoExterior Ramps and Railings
Interior Routes
NoNoCorridor and Lobby H/C Lifts
YesYesInterior Corridor Doors And
Hardware
YesInterior Corridors & Lobbies
YesYesInterior Elevators
YesInterior Lobby Doors And Hardware
NoInterior Ramps
Rooms & Spaces
NoArt Rooms
NoAuditorium
Cafeteria
Yes YesBasement Yes Yes
Classrooms
Yes Yes1st - 3rd Floors
NoComputer Rooms
NoGymnasium
NoLibrary
Main Office
Yes YesRoom 131
NoMulti-purpose Room
Nurse's Office
Yes YesRoom 211
NoPool
NoScience Lab
Toilet Rooms (boys)
Yes Yes1st - 3rd Floors
Toilet Rooms (girls)
Yes Yes1st - 3rd Floors
Toilet Rooms (staff)
Yes Yes1st Floor - Men’s and
Women’s
Page 3 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
EXTERIOR Inspected
InspectedAREAWAY
Instance on AW1 - AW3 Inspected
3- FairInstance Condition
Instance Quantity 3
Instance Quantity Uom EACH
AREAWAY GRATINGS:MINOR RUSTINGDeficiency
Deficiency Location/Instance
80Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
AW2
Violations No violations recorded
AREAWAY SLAB:CRACKS AND SPALLINGDeficiency
Page 4 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
EXTERIOR
AREAWAY
Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
AW1
Violations No violations recorded
Does not existAWNINGS AND CANOPIES
InspectedCHIMNEY
MasonryMaterial Type(s)
Condition 3- Fair
BRICK:MINOR CRACKS AND SPALLINGDeficiency
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action RESTITCH
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Chimney
Violations No violations recorded
BRICK:OPEN JOINTSDeficiency
Page 5 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
EXTERIOR
CHIMNEY
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Chimney
Violations No violations recorded
InspectedCOPING
Condition 3- Fair
CAST STONE:OPEN TRANSVERSE JOINTS WITH
DAMAGED CAULKING
Deficiency
Deficiency Location/Instance
50Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade C
Violations No violations recorded
Does not existCORNICE
InspectedDOORS
InspectedDOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Page 6 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Condition 3- Fair
METAL CLAD:DETERIORATED DOOR AND FRAME -
MINOR DETERIORATION
Deficiency
Deficiency Location/Instance
2Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade B - Exit 3
Violations No violations recorded
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTRANSOM/SIDE LIGHT
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedEXTERIOR SOFFITS
Condition 4- Between Fair and Poor
METAL:DETERIORATION/DAMAGED/MISSING PIECESDeficiency
Roof Plan Reference
Elevation
260Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Page 7 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
EXTERIOR
EXTERIOR SOFFITS
Deficiency Photo 1
Facade D
Deficiency Photo 2
Facade A
Violations No violations recorded
InspectedEXTERIOR WALLS
MasonryMaterial Type(s)
15,000Replacement Quantity
Replacement Uom S.F.
Instance on All Facades Inspected
4- Between Fair and PoorInstance Condition
Instance Quantity 15,000
Instance Quantity Uom S.F.
BRICK:WATER INFILTRATION IN INSTRUCTIONAL SPACEDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade D
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 5Urgency of Action
LEVEL 4Purpose of Action
Page 8 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo 1
Staircase B/4 - 3rd Floor shown, similar 2nd Floor and 1st Floor
Violations 35346987N
BRICK:MAJOR / THRU CRACKSDeficiency
Roof Plan Reference
Elevation
Elevation Reference All Facades
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade D
Violations No violations recorded
BRICK:OPEN JOINTSDeficiency
Roof Plan Reference
Page 9 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Elevation Reference All Facades
600Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
Does not existLOADING DOCK
InspectedLOUVER
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedPARAPETS
MasonryMaterial Type(s)
4,000Replacement Quantity
Replacement Uom C.F.
Instance on All Facades Inspected
3- FairInstance Condition
Instance Quantity 4,000
Instance Quantity Uom CF
BRICK:MINOR CRACKS, SPALLINGDeficiency
Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 10 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
EXTERIOR
PARAPETS
Deficiency Photo 1
Facade C
Violations No violations recorded
BRICK:OPEN JOINTSDeficiency
Deficiency Location/Instance
80Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade E
Violations No violations recorded
Does not existPLAZA DECK
InspectedROOF
InspectedROOFING
Replacement Quantity 19,000
Replacement Uom S.F.
Does not existLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
Does not existROOF BARRIER
Does not existROOF CAGE
Does not existROOF FENCE
Does not existROOF HATCH/SMOKE HATCH
InspectedROOFING
Instance on IRMA:Roofs 1 and 2 Inspected
3- FairInstance Condition
Instance Quantity 19,000
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 1979
Source of Installation Year Custodial Staff
IRMA:ROOFING:LOSS OF GRAVELDeficiency
Page 11 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
Deficiency Location/Instance
400Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1
Violations No violations recorded
IRMA:ROOFING:DAMAGED INSULATIONDeficiency
Deficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1
Violations No violations recorded
IRMA:ROOFING:MAJOR ACTIVE ROOF LEAKS IN
INSTRUCTIONAL SPACE
Deficiency
Page 12 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENT
REMOVAL
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Staircase C - 3rd Floor
Violations No violations recorded
InspectedROOFING DRAINS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedSPECIALTIES
InspectedBULKHEAD/PENTHOUSE
3- FairCondition
BULKHEAD/PENTHOUSE CEILING:PLASTER
DAMAGED/DETERIORATED
Deficiency
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Bulkhead
Page 13 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
EXTERIOR
ROOF
SPECIALTIES
BULKHEAD/PENTHOUSE
Violations No violations recorded
BULKHEAD/PENTHOUSE WALLS/EXTERIOR:OPEN
JOINTS
Deficiency
Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Bulkhead
Violations No violations recorded
Does not existCUPOLA/ SPIRES/ TOWERS
Does not existDORMER
InspectedDUNNAGE STEEL
3- FairCondition
MAJOR RUSTINGDeficiency
Deficiency Location/Instance
50Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1
Violations No violations recorded
Page 14 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
EXTERIOR
ROOF
SPECIALTIES
Does not existROOF/GRAVITY TANK
Does not existSKYLIGHT/ROOF VENT
Does not existSTAIRS/RAMPS: EXTERIOR
InspectedWINDOWS
6,000Replacement Quantity
Replacement Uom S.F.
InspectedEXTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedLINTELS
Condition 3- Fair
STEEL:MINOR RUSTINGDeficiency
Roof Plan Reference
Elevation
300Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
InspectedWINDOWS
Material Type(s) Aluminum
Instance on Aluminum - Other:All Facades Inspected
5- PoorInstance Condition
Instance Quantity 6,000
Instance Quantity Uom S.F.
Installation Year 1979
Source of Installation Year Custodial Staff
ALUMINUM - OTHER:INOPERABLEDeficiency
Page 15 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
EXTERIOR
WINDOWS
WINDOWS
Roof Plan Reference
Elevation
Elevation Reference All Facades
1,200Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE WINDOW
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Violations No violations recorded
ALUMINUM - OTHER:AIR AND WATER INFILTRATION,
OPEN JOINTS WITH DAMAGED CAULKING
Deficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A
100Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
1st Floor-Elevator Wing shown, similar 2nd and 3rd Floors
Violations No violations recorded
INTERIOR Inspected
Page 16 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
INTERIOR
Does not existAUDITORIUM
CAFETERIA
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
ACOUSTIC TILES:DAMAGED/MISSINGDeficiency
Center, South Sides of RoomDeficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
South Side of Room
Violations No violations recorded
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on Basement Does not exist
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
East Side of RoomDeficiency Location/Instance
110Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
East Side of Room
Violations No violations recorded
Sliding-folding Partition
Instance on Basement Inspected
3- FairInstance Condition
MOVABLE PANELS:DAMAGEDDeficiency
East Side of RoomDeficiency Location/Instance
Page 17 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
INTERIOR
CAFETERIA
Sliding-folding Partition
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
East Side of Room
Violations No violations recorded
Stage
Instance on Basement Does not exist
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on Basement Does not exist
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 2- Between Good and Fair
ACOUSTIC TILES:DAMAGED/MISSINGDeficiency
Rooms 301, 325, Corridor near Rooms 105, 119, 319 and other
locations
Deficiency Location/Instance
250Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Room 105
Violations No violations recorded
ACOUSTIC TILES:DAMAGED/MISSING - ACTIVE LEAKDeficiency
Room C19Deficiency Location/Instance
35Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Page 18 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo 1
Room C19
Violations No violations recorded
InspectedDoor(s)
Condition 5- Poor
WOOD:DETERIORATED DOORDeficiency
Rooms 117, 127, 226, 331Deficiency Location/Instance
4Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 117
Violations No violations recorded
InspectedFloor Finish
Condition 2- Between Good and Fair
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
Rooms 105, C9, Corridor near Rooms C20, 201Deficiency Location/Instance
60Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 105
Violations No violations recorded
Does not existSpecialties
InspectedWalls
Condition 2- Between Good and Fair
GLAZED BLOCK:CRACKS/SPALLINGDeficiency
Page 19 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Corridor near Rooms 106, 115, 123, 201, 317 and other locationsDeficiency Location/Instance
45Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Room 115
Violations No violations recorded
MASONRY:CRACKS/SPALLINGDeficiency
Rooms 105, 114, 303Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 105
Violations No violations recorded
Does not existGYMNASIUM
InspectedINTERIOR DOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedINTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
KITCHEN
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Basement Inspected
3- FairInstance Condition
METAL:DETERIORATED DOOR AND FRAMEDeficiency
Room C17Deficiency Location/Instance
1Deficiency Quantity
Page 20 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
INTERIOR
KITCHEN
Door(s)
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room C17
Violations No violations recorded
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
CONCRETE:CRACKSDeficiency
Room C11Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room C11
Violations No violations recorded
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
Near EntranceDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Entrance
Violations No violations recorded
Walls
Page 21 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
INTERIOR
KITCHEN
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
MASONRY:CRACKS/SPALLINGDeficiency
Corridor near Room C11, Rooms C11, Near WindowsDeficiency Location/Instance
25Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Room C11
Violations No violations recorded
Does not existLIBRARY
Does not existLOCKER ROOM
Does not existMULTI-PURPOSE ROOM
Does not existPOOLS
Does not existSCIENCE DEMO ROOM
Does not existSCIENCE LAB
Does not existSCIENCE PREP ROOM
SHOWER ROOM
Instance on Room 106 - Boys Inaccessible
Instance on Room 114 - Girls Inaccessible
Instance on Room 228 Inaccessible
InspectedSTAIRS/RAMPS: INTERIOR
Do Letter Stair Signs Exist? Yes
InspectedCeiling
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLING - ACTIVE LEAKDeficiency
Stair C/3Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair C/3
Violations No violations recorded
InspectedDoor(s)
Page 22 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Door(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existPartition
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStairs and Landings
Condition 3- Fair
STONE:BROKEN/MISSINGDeficiency
Stairs C/1, D/1Deficiency Location/Instance
180Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair D/1
Violations No violations recorded
InspectedWalls
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLING - ACTIVE LEAKDeficiency
Stair B/2Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 4Purpose of Action
Deficiency Photo 1
Stair B/2
Violations 35346987N
GLAZED BLOCK:CRACKS/SPALLINGDeficiency
Stairs A/3, B/2, C/2, 3Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 23 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Deficiency Photo 1
Stair B/2
Violations No violations recorded
InspectedSTRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFLOOR STRUCTURE
Condition 3- Fair
CONCRETE SLAB ON GRADE:MINOR CRACKSDeficiency
BasementDeficiency Location/Instance
80Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Elevator Room (C1)
Violations No violations recorded
InspectedFOUNDATION WALLS
Material Type(s) Concrete
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedROOF STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedVAULTS-BUNKERS
InaccessibleFoundation Walls
InaccessibleSlab Structure
InspectedVault/Ash Hoist Doors and Framing
3- FairCondition
MINOR RUSTINGDeficiency
Facade DDeficiency Location/Instance
2Deficiency Quantity
Quantity Uom EACH
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 24 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
VAULTS-BUNKERS
Vault/Ash Hoist Doors and Framing
Deficiency Photo 1
Facade D
Violations No violations recorded
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 5- Poor
WOOD:DETERIORATED DOORDeficiency
Rooms 111, 113, 220Deficiency Location/Instance
3Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 111
Violations No violations recorded
InspectedFloor Finish
Condition 2- Between Good and Fair
CERAMIC TILE:BROKEN/MISSING TILESDeficiency
Rooms C8, 113Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 113
Page 25 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STAFF
Floor Finish
Violations No violations recorded
InspectedStalls
Condition 4- Between Fair and Poor
RUST - MAJORDeficiency
Room 220Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 220
Violations No violations recorded
InspectedWalls
Condition 2- Between Good and Fair
CERAMIC TILE:BROKEN/ MISSINGDeficiency
Rooms 113Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 113
Violations No violations recorded
InspectedTOILET ROOMS - STUDENTS
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 5- Poor
WOOD:DAMAGED LOUVERDeficiency
Rooms C12, 306, Basement-GirlsDeficiency Location/Instance
3Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 26 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Door(s)
Deficiency Photo 1
Room 306
Violations No violations recorded
InspectedFloor Finish
Condition 2- Between Good and Fair
CERAMIC TILE:BROKEN/MISSING TILESDeficiency
Rooms C12, 218, 306Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 306
Violations No violations recorded
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
CERAMIC TILE:BROKEN/ MISSINGDeficiency
Rooms C12, 306Deficiency Location/Instance
15Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 306
Violations No violations recorded
LIFE SAFETY Inspected
Page 27 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
LIFE SAFETY
Does not existF.D. HOLDING AREA
Does not existSTEEL STAIRS
SITE Inspected
InspectedCONTAINERIZATION
Condition 5- Poor
CONTAINER DAMAGEDDeficiency
Parking LotDeficiency Location/Instance
4Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Parking Lot
Violations No violations recorded
CONCRETE PAD MISSINGDeficiency
Parking LotDeficiency Location/Instance
500Deficiency Quantity
Quantity Uom S.F.
Potential Action INSTALL NEW
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Parking Lot
Violations No violations recorded
InspectedDRAINAGE SYSTEM FOR ASPHALT
InspectedCatch Basins/Manhole - Surrounded by Asphalt
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Asphalt Covering
Does not existDRAINAGE SYSTEM FOR CONCRETE
Does not existDRAINAGE SYSTEM FOR SOIL
Does not existDRINKING FOUNTAINS
InspectedFENCES
Condition 3- Fair
WROUGHT IRON:DAMAGED/DETERIORATEDDeficiency
Along Tompkins AvenueDeficiency Location/Instance
120Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
Page 28 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
SITE
FENCES
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Tompkins Avenue
Violations No violations recorded
Does not existIRRIGATION SYSTEM
InspectedPAVING
InspectedDOT Sidewalk
Does not existAsphalt
InspectedConcrete
3- FairCondition
DAMAGED CURBSDeficiency
Along Tompkins AvenueDeficiency Location/Instance
50Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Tompkins Avenue
Violations No violations recorded
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
Along Tompkins AvenueDeficiency Location/Instance
200Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Tompkins Avenue
Violations No violations recorded
HEAVINGDeficiency
Page 29 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Along Tompkins AvenueDeficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Tompkins Avenue
Violations No violations recorded
Does not existPavers
InspectedSite Sidewalks & Walkways
Does not existAsphalt
InspectedConcrete
3- FairCondition
CRACKS - MAJORDeficiency
Along Tompkins Avenue, Near Exit 4Deficiency Location/Instance
125Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Tompkins Avenue
Violations No violations recorded
HEAVINGDeficiency
Near Exit 4Deficiency Location/Instance
25Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 30 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Concrete
Deficiency Photo 1
Near Exit 4
Violations No violations recorded
Does not existPavers
InspectedStudent Non-Use
Gravel Exists? No
InspectedAsphalt
3- FairCondition
CRACKS - MAJORDeficiency
Parking LotDeficiency Location/Instance
250Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Parking Lot
Violations No violations recorded
POTHOLESDeficiency
Parking LotDeficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Parking Lot
Violations No violations recorded
Does not existConcrete
Does not existPavers
Page 31 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R722Architectural Inspection
Question Response
SITE
PAVING
InspectedStudent Use
Gravel Exists? No
Does not existAsphalt
InspectedConcrete
2- Between Good and FairCondition
CRACKS - MAJORDeficiency
SchoolyardDeficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Schoolyard
Violations No violations recorded
Does not existPavers
Does not existPLAYGROUNDS
Does not existPLAYING SURFACE
InspectedRETAINING WALLS
Condition 2- Between Good and Fair
Are there any Retaining Walls 6' OR higher facing public street/sidewalk? No
No deficiencies recordedDeficiency
Does not existSEATING
Does not existSITE WALLS (NOT RETAINING WALLS)
Does not existSTAIRS/RAMPS: EXTERIOR