NYC Department of Education Building Condition Assessment Survey 2019-2020 R722 Architectural Inspection Inspection Type Last Edited Time In InspectionId P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE, STATEN ISLAND, NY, 10304 School: 4546 2020-03-24 07:20AM 2020-08-23 05:45PM ARCHITECTURAL - SENIOR 4555 2020-03-24 10:33AM 2020-03-24 02:41PM ARCHITECTURAL - ASSOCIATE Asset Data Question Answer Was the Building Fully Accessible for Inspection? No Shower Rooms (No key/storage) Comments on Inaccessible Inspection Principal(s) Information Principal Name Kristin Mchugh Principal Organization R721 SPED - Staten Island Meeting with Principal? No Principal Feedback The Principal returned the questionnaire with the following comment: The Elevators break down and need maintenance. Custodian Was not present Fireman Anthony Chickara Building Square Footage 69,000 Comments on the Area (Square Feet) N/A Comments on the Stories (Floors) plus Basements 3+B Comments on the Year Built 1979 Comments on the Student Population 225 Comments on the Staff Population 193 Comments on the Number of Classrooms 29 Weather Fair Facade Photo Tompkins Avenue- North View Main Entrance Photo Facade A - 155 Tompkins Avenue Page 1 of 32 Print Date: 9/11/2020 Mobile Validity Version 2.0 (P)

Upload: others

Post on 26-Sep-2020

23 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Inspection Type Last EditedTime InInspectionId

P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE, STATEN ISLAND, NY, 10304School:

4546 2020-03-24 07:20AM 2020-08-23 05:45PMARCHITECTURAL - SENIOR

4555 2020-03-24 10:33AM 2020-03-24 02:41PMARCHITECTURAL - ASSOCIATE

Asset DataQuestion Answer

Was the Building Fully Accessible for Inspection? No

Shower Rooms (No key/storage)Comments on Inaccessible Inspection

Principal(s) Information

Principal Name Kristin Mchugh

Principal Organization R721 SPED - Staten Island

Meeting with Principal? No

Principal Feedback The Principal returned the questionnaire with the following

comment: The Elevators break down and need maintenance.

Custodian Was not present

Fireman Anthony Chickara

Building Square Footage 69,000

Comments on the Area (Square Feet) N/A

Comments on the Stories (Floors) plus Basements 3+B

Comments on the Year Built 1979

Comments on the Student Population 225

Comments on the Staff Population 193

Comments on the Number of Classrooms 29

Weather Fair

Facade Photo

Tompkins Avenue- North View

Main Entrance Photo

Facade A - 155 Tompkins Avenue

Page 1 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 2: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural InspectionRoof Photo

Roof 1 - Northeast View

Have any Systems/Major Building Components been upgraded? Systems: New Elevator addition

Years: 1992

Systems: Exterior Wall repointing (partial )

Years: 2003

Systems: New Exterior Doors(partial- Facade B),Parking Lot

repaved, New Fire Window

Years: 2009

Systems: Parapet repointing (partial)

Years: 2012

Systems: Nurse’ s Office relocated to Room 211, Chimney

repointing, repairs

Years: 2013

Have there been any New Building Additions? No New Construction

Tandem No Tandem

Leased Space? No

Priority ConditionExist

Last Year?

Priority

Category

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Structural Engineer Required

Structural

Condition Type

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Accessibility

Accessibility Status Question Response

Is the Primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are All floors of the building accessible through compliant means? Yes

Accessible classrooms exists on each floor? Yes

Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes

If the following spaces exist, are they ALL accessible? Art Room, Auditorium,

Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

Yes

Physical Breakdown Structure Exists Complies Required DeficiencyAudio

Induction

System

Fire

Alarm

Strobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

YesExterior Entrances & Exits

NoNoExterior H/C Lifts

Page 2 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 3: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Physical Breakdown Structure Exists Complies Required DeficiencyAudio

Induction

System

Fire

Alarm

Strobe

NoNoExterior Ramps and Railings

Interior Routes

NoNoCorridor and Lobby H/C Lifts

YesYesInterior Corridor Doors And

Hardware

YesInterior Corridors & Lobbies

YesYesInterior Elevators

YesInterior Lobby Doors And Hardware

NoInterior Ramps

Rooms & Spaces

NoArt Rooms

NoAuditorium

Cafeteria

Yes YesBasement Yes Yes

Classrooms

Yes Yes1st - 3rd Floors

NoComputer Rooms

NoGymnasium

NoLibrary

Main Office

Yes YesRoom 131

NoMulti-purpose Room

Nurse's Office

Yes YesRoom 211

NoPool

NoScience Lab

Toilet Rooms (boys)

Yes Yes1st - 3rd Floors

Toilet Rooms (girls)

Yes Yes1st - 3rd Floors

Toilet Rooms (staff)

Yes Yes1st Floor - Men’s and

Women’s

Page 3 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 4: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Building Template

Inspection

Question Response

Architectural

ATHLETIC FIELDS Does not exist

EXTERIOR Inspected

InspectedAREAWAY

Instance on AW1 - AW3 Inspected

3- FairInstance Condition

Instance Quantity 3

Instance Quantity Uom EACH

AREAWAY GRATINGS:MINOR RUSTINGDeficiency

Deficiency Location/Instance

80Deficiency Quantity

Quantity Uom S.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

AW2

Violations No violations recorded

AREAWAY SLAB:CRACKS AND SPALLINGDeficiency

Page 4 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 5: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

EXTERIOR

AREAWAY

Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

AW1

Violations No violations recorded

Does not existAWNINGS AND CANOPIES

InspectedCHIMNEY

MasonryMaterial Type(s)

Condition 3- Fair

BRICK:MINOR CRACKS AND SPALLINGDeficiency

Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action RESTITCH

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Chimney

Violations No violations recorded

BRICK:OPEN JOINTSDeficiency

Page 5 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 6: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

EXTERIOR

CHIMNEY

Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Chimney

Violations No violations recorded

InspectedCOPING

Condition 3- Fair

CAST STONE:OPEN TRANSVERSE JOINTS WITH

DAMAGED CAULKING

Deficiency

Deficiency Location/Instance

50Deficiency Quantity

Quantity Uom L.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade C

Violations No violations recorded

Does not existCORNICE

InspectedDOORS

InspectedDOOR HARDWARE

Condition 3- Fair

No deficiencies recordedDeficiency

InspectedDOORS AND FRAMES

Page 6 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 7: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Condition 3- Fair

METAL CLAD:DETERIORATED DOOR AND FRAME -

MINOR DETERIORATION

Deficiency

Deficiency Location/Instance

2Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade B - Exit 3

Violations No violations recorded

InspectedLINTELS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedTRANSOM/SIDE LIGHT

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedEXTERIOR SOFFITS

Condition 4- Between Fair and Poor

METAL:DETERIORATION/DAMAGED/MISSING PIECESDeficiency

Roof Plan Reference

Elevation

260Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Page 7 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 8: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

EXTERIOR

EXTERIOR SOFFITS

Deficiency Photo 1

Facade D

Deficiency Photo 2

Facade A

Violations No violations recorded

InspectedEXTERIOR WALLS

MasonryMaterial Type(s)

15,000Replacement Quantity

Replacement Uom S.F.

Instance on All Facades Inspected

4- Between Fair and PoorInstance Condition

Instance Quantity 15,000

Instance Quantity Uom S.F.

BRICK:WATER INFILTRATION IN INSTRUCTIONAL SPACEDeficiency

Roof Plan Reference

Elevation

Elevation Reference Facade D

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 5Urgency of Action

LEVEL 4Purpose of Action

Page 8 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 9: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Deficiency Photo 1

Staircase B/4 - 3rd Floor shown, similar 2nd Floor and 1st Floor

Violations 35346987N

BRICK:MAJOR / THRU CRACKSDeficiency

Roof Plan Reference

Elevation

Elevation Reference All Facades

100Deficiency Quantity

Quantity Uom S.F.

Potential Action REMOVE AND REBUILD

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade D

Violations No violations recorded

BRICK:OPEN JOINTSDeficiency

Roof Plan Reference

Page 9 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 10: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Elevation Reference All Facades

600Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A

Violations No violations recorded

Does not existLOADING DOCK

InspectedLOUVER

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedPARAPETS

MasonryMaterial Type(s)

4,000Replacement Quantity

Replacement Uom C.F.

Instance on All Facades Inspected

3- FairInstance Condition

Instance Quantity 4,000

Instance Quantity Uom CF

BRICK:MINOR CRACKS, SPALLINGDeficiency

Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 10 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 11: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

EXTERIOR

PARAPETS

Deficiency Photo 1

Facade C

Violations No violations recorded

BRICK:OPEN JOINTSDeficiency

Deficiency Location/Instance

80Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade E

Violations No violations recorded

Does not existPLAZA DECK

InspectedROOF

InspectedROOFING

Replacement Quantity 19,000

Replacement Uom S.F.

Does not existLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS

Does not existROOF BARRIER

Does not existROOF CAGE

Does not existROOF FENCE

Does not existROOF HATCH/SMOKE HATCH

InspectedROOFING

Instance on IRMA:Roofs 1 and 2 Inspected

3- FairInstance Condition

Instance Quantity 19,000

Instance Quantity Uom S.F.

“Does the roof have major mechanical equipment sitting on Dunnage

Steel less than 18" above the Roofing?"

No

Installation Year 1979

Source of Installation Year Custodial Staff

IRMA:ROOFING:LOSS OF GRAVELDeficiency

Page 11 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 12: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

EXTERIOR

ROOF

ROOFING

ROOFING

Deficiency Location/Instance

400Deficiency Quantity

Quantity Uom S.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Roof 1

Violations No violations recorded

IRMA:ROOFING:DAMAGED INSULATIONDeficiency

Deficiency Location/Instance

100Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Roof 1

Violations No violations recorded

IRMA:ROOFING:MAJOR ACTIVE ROOF LEAKS IN

INSTRUCTIONAL SPACE

Deficiency

Page 12 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 13: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

EXTERIOR

ROOF

ROOFING

ROOFING

Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENT

REMOVAL

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Staircase C - 3rd Floor

Violations No violations recorded

InspectedROOFING DRAINS

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedSPECIALTIES

InspectedBULKHEAD/PENTHOUSE

3- FairCondition

BULKHEAD/PENTHOUSE CEILING:PLASTER

DAMAGED/DETERIORATED

Deficiency

Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action MAINTENANCE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Bulkhead

Page 13 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 14: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

EXTERIOR

ROOF

SPECIALTIES

BULKHEAD/PENTHOUSE

Violations No violations recorded

BULKHEAD/PENTHOUSE WALLS/EXTERIOR:OPEN

JOINTS

Deficiency

Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Bulkhead

Violations No violations recorded

Does not existCUPOLA/ SPIRES/ TOWERS

Does not existDORMER

InspectedDUNNAGE STEEL

3- FairCondition

MAJOR RUSTINGDeficiency

Deficiency Location/Instance

50Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Roof 1

Violations No violations recorded

Page 14 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 15: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

EXTERIOR

ROOF

SPECIALTIES

Does not existROOF/GRAVITY TANK

Does not existSKYLIGHT/ROOF VENT

Does not existSTAIRS/RAMPS: EXTERIOR

InspectedWINDOWS

6,000Replacement Quantity

Replacement Uom S.F.

InspectedEXTERIOR GUARDS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedLINTELS

Condition 3- Fair

STEEL:MINOR RUSTINGDeficiency

Roof Plan Reference

Elevation

300Deficiency Quantity

Quantity Uom L.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A

Violations No violations recorded

InspectedWINDOWS

Material Type(s) Aluminum

Instance on Aluminum - Other:All Facades Inspected

5- PoorInstance Condition

Instance Quantity 6,000

Instance Quantity Uom S.F.

Installation Year 1979

Source of Installation Year Custodial Staff

ALUMINUM - OTHER:INOPERABLEDeficiency

Page 15 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 16: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

EXTERIOR

WINDOWS

WINDOWS

Roof Plan Reference

Elevation

Elevation Reference All Facades

1,200Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE WINDOW

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Violations No violations recorded

ALUMINUM - OTHER:AIR AND WATER INFILTRATION,

OPEN JOINTS WITH DAMAGED CAULKING

Deficiency

Roof Plan Reference

Elevation

Elevation Reference Facade A

100Deficiency Quantity

Quantity Uom L.F.

Potential Action MAINTENANCE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

1st Floor-Elevator Wing shown, similar 2nd and 3rd Floors

Violations No violations recorded

INTERIOR Inspected

Page 16 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 17: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

INTERIOR

Does not existAUDITORIUM

CAFETERIA

Instance on Basement Inspected

Ceiling

Instance on Basement Inspected

2- Between Good and FairInstance Condition

ACOUSTIC TILES:DAMAGED/MISSINGDeficiency

Center, South Sides of RoomDeficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

South Side of Room

Violations No violations recorded

Door(s)

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on Basement Does not exist

Floor Finish

Instance on Basement Inspected

2- Between Good and FairInstance Condition

VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency

East Side of RoomDeficiency Location/Instance

110Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

East Side of Room

Violations No violations recorded

Sliding-folding Partition

Instance on Basement Inspected

3- FairInstance Condition

MOVABLE PANELS:DAMAGEDDeficiency

East Side of RoomDeficiency Location/Instance

Page 17 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 18: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

INTERIOR

CAFETERIA

Sliding-folding Partition

40Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

East Side of Room

Violations No violations recorded

Stage

Instance on Basement Does not exist

Walls

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on Basement Does not exist

InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES

InspectedCeiling

Condition 2- Between Good and Fair

ACOUSTIC TILES:DAMAGED/MISSINGDeficiency

Rooms 301, 325, Corridor near Rooms 105, 119, 319 and other

locations

Deficiency Location/Instance

250Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Corridor near Room 105

Violations No violations recorded

ACOUSTIC TILES:DAMAGED/MISSING - ACTIVE LEAKDeficiency

Room C19Deficiency Location/Instance

35Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Page 18 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 19: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

Deficiency Photo 1

Room C19

Violations No violations recorded

InspectedDoor(s)

Condition 5- Poor

WOOD:DETERIORATED DOORDeficiency

Rooms 117, 127, 226, 331Deficiency Location/Instance

4Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 117

Violations No violations recorded

InspectedFloor Finish

Condition 2- Between Good and Fair

VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency

Rooms 105, C9, Corridor near Rooms C20, 201Deficiency Location/Instance

60Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 105

Violations No violations recorded

Does not existSpecialties

InspectedWalls

Condition 2- Between Good and Fair

GLAZED BLOCK:CRACKS/SPALLINGDeficiency

Page 19 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 20: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls

Corridor near Rooms 106, 115, 123, 201, 317 and other locationsDeficiency Location/Instance

45Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Corridor near Room 115

Violations No violations recorded

MASONRY:CRACKS/SPALLINGDeficiency

Rooms 105, 114, 303Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 105

Violations No violations recorded

Does not existGYMNASIUM

InspectedINTERIOR DOOR HARDWARE

Condition 3- Fair

No deficiencies recordedDeficiency

InspectedINTERIOR GUARDS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

KITCHEN

Instance on Basement Inspected

Ceiling

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Basement Inspected

3- FairInstance Condition

METAL:DETERIORATED DOOR AND FRAMEDeficiency

Room C17Deficiency Location/Instance

1Deficiency Quantity

Page 20 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 21: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

INTERIOR

KITCHEN

Door(s)

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room C17

Violations No violations recorded

Floor Finish

Instance on Basement Inspected

2- Between Good and FairInstance Condition

CONCRETE:CRACKSDeficiency

Room C11Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room C11

Violations No violations recorded

VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency

Near EntranceDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Entrance

Violations No violations recorded

Walls

Page 21 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 22: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

INTERIOR

KITCHEN

Walls

Instance on Basement Inspected

2- Between Good and FairInstance Condition

MASONRY:CRACKS/SPALLINGDeficiency

Corridor near Room C11, Rooms C11, Near WindowsDeficiency Location/Instance

25Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Corridor near Room C11

Violations No violations recorded

Does not existLIBRARY

Does not existLOCKER ROOM

Does not existMULTI-PURPOSE ROOM

Does not existPOOLS

Does not existSCIENCE DEMO ROOM

Does not existSCIENCE LAB

Does not existSCIENCE PREP ROOM

SHOWER ROOM

Instance on Room 106 - Boys Inaccessible

Instance on Room 114 - Girls Inaccessible

Instance on Room 228 Inaccessible

InspectedSTAIRS/RAMPS: INTERIOR

Do Letter Stair Signs Exist? Yes

InspectedCeiling

Condition 2- Between Good and Fair

PLASTER:CRACKS/SPALLING - ACTIVE LEAKDeficiency

Stair C/3Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair C/3

Violations No violations recorded

InspectedDoor(s)

Page 22 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 23: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Door(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existPartition

InspectedRailings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStairs and Landings

Condition 3- Fair

STONE:BROKEN/MISSINGDeficiency

Stairs C/1, D/1Deficiency Location/Instance

180Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair D/1

Violations No violations recorded

InspectedWalls

Condition 2- Between Good and Fair

PLASTER:CRACKS/SPALLING - ACTIVE LEAKDeficiency

Stair B/2Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 4Purpose of Action

Deficiency Photo 1

Stair B/2

Violations 35346987N

GLAZED BLOCK:CRACKS/SPALLINGDeficiency

Stairs A/3, B/2, C/2, 3Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 23 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 24: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Walls

Deficiency Photo 1

Stair B/2

Violations No violations recorded

InspectedSTRUCTURAL

InspectedCOLUMNS/BEAMS/BEARING WALLS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFLOOR STRUCTURE

Condition 3- Fair

CONCRETE SLAB ON GRADE:MINOR CRACKSDeficiency

BasementDeficiency Location/Instance

80Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Elevator Room (C1)

Violations No violations recorded

InspectedFOUNDATION WALLS

Material Type(s) Concrete

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedROOF STRUCTURE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedVAULTS-BUNKERS

InaccessibleFoundation Walls

InaccessibleSlab Structure

InspectedVault/Ash Hoist Doors and Framing

3- FairCondition

MINOR RUSTINGDeficiency

Facade DDeficiency Location/Instance

2Deficiency Quantity

Quantity Uom EACH

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 24 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 25: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

INTERIOR

STRUCTURAL

VAULTS-BUNKERS

Vault/Ash Hoist Doors and Framing

Deficiency Photo 1

Facade D

Violations No violations recorded

InspectedTOILET ROOMS - STAFF

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 5- Poor

WOOD:DETERIORATED DOORDeficiency

Rooms 111, 113, 220Deficiency Location/Instance

3Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 111

Violations No violations recorded

InspectedFloor Finish

Condition 2- Between Good and Fair

CERAMIC TILE:BROKEN/MISSING TILESDeficiency

Rooms C8, 113Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 113

Page 25 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 26: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

INTERIOR

TOILET ROOMS - STAFF

Floor Finish

Violations No violations recorded

InspectedStalls

Condition 4- Between Fair and Poor

RUST - MAJORDeficiency

Room 220Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 220

Violations No violations recorded

InspectedWalls

Condition 2- Between Good and Fair

CERAMIC TILE:BROKEN/ MISSINGDeficiency

Rooms 113Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 113

Violations No violations recorded

InspectedTOILET ROOMS - STUDENTS

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 5- Poor

WOOD:DAMAGED LOUVERDeficiency

Rooms C12, 306, Basement-GirlsDeficiency Location/Instance

3Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 26 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 27: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Door(s)

Deficiency Photo 1

Room 306

Violations No violations recorded

InspectedFloor Finish

Condition 2- Between Good and Fair

CERAMIC TILE:BROKEN/MISSING TILESDeficiency

Rooms C12, 218, 306Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 306

Violations No violations recorded

InspectedStalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

CERAMIC TILE:BROKEN/ MISSINGDeficiency

Rooms C12, 306Deficiency Location/Instance

15Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 306

Violations No violations recorded

LIFE SAFETY Inspected

Page 27 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 28: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

LIFE SAFETY

Does not existF.D. HOLDING AREA

Does not existSTEEL STAIRS

SITE Inspected

InspectedCONTAINERIZATION

Condition 5- Poor

CONTAINER DAMAGEDDeficiency

Parking LotDeficiency Location/Instance

4Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Parking Lot

Violations No violations recorded

CONCRETE PAD MISSINGDeficiency

Parking LotDeficiency Location/Instance

500Deficiency Quantity

Quantity Uom S.F.

Potential Action INSTALL NEW

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Parking Lot

Violations No violations recorded

InspectedDRAINAGE SYSTEM FOR ASPHALT

InspectedCatch Basins/Manhole - Surrounded by Asphalt

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existCulverts - Asphalt Covering

Does not existDRAINAGE SYSTEM FOR CONCRETE

Does not existDRAINAGE SYSTEM FOR SOIL

Does not existDRINKING FOUNTAINS

InspectedFENCES

Condition 3- Fair

WROUGHT IRON:DAMAGED/DETERIORATEDDeficiency

Along Tompkins AvenueDeficiency Location/Instance

120Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

Page 28 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 29: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

SITE

FENCES

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along Tompkins Avenue

Violations No violations recorded

Does not existIRRIGATION SYSTEM

InspectedPAVING

InspectedDOT Sidewalk

Does not existAsphalt

InspectedConcrete

3- FairCondition

DAMAGED CURBSDeficiency

Along Tompkins AvenueDeficiency Location/Instance

50Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along Tompkins Avenue

Violations No violations recorded

DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency

Along Tompkins AvenueDeficiency Location/Instance

200Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along Tompkins Avenue

Violations No violations recorded

HEAVINGDeficiency

Page 29 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 30: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Along Tompkins AvenueDeficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along Tompkins Avenue

Violations No violations recorded

Does not existPavers

InspectedSite Sidewalks & Walkways

Does not existAsphalt

InspectedConcrete

3- FairCondition

CRACKS - MAJORDeficiency

Along Tompkins Avenue, Near Exit 4Deficiency Location/Instance

125Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along Tompkins Avenue

Violations No violations recorded

HEAVINGDeficiency

Near Exit 4Deficiency Location/Instance

25Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 30 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 31: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

SITE

PAVING

Site Sidewalks & Walkways

Concrete

Deficiency Photo 1

Near Exit 4

Violations No violations recorded

Does not existPavers

InspectedStudent Non-Use

Gravel Exists? No

InspectedAsphalt

3- FairCondition

CRACKS - MAJORDeficiency

Parking LotDeficiency Location/Instance

250Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Parking Lot

Violations No violations recorded

POTHOLESDeficiency

Parking LotDeficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Parking Lot

Violations No violations recorded

Does not existConcrete

Does not existPavers

Page 31 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 32: P.S. 722 (OTC) - STATEN ISLAND, 155 TOMPKINS AVENUE ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R722 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R722Architectural Inspection

Question Response

SITE

PAVING

InspectedStudent Use

Gravel Exists? No

Does not existAsphalt

InspectedConcrete

2- Between Good and FairCondition

CRACKS - MAJORDeficiency

SchoolyardDeficiency Location/Instance

100Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Schoolyard

Violations No violations recorded

Does not existPavers

Does not existPLAYGROUNDS

Does not existPLAYING SURFACE

InspectedRETAINING WALLS

Condition 2- Between Good and Fair

Are there any Retaining Walls 6' OR higher facing public street/sidewalk? No

No deficiencies recordedDeficiency

Does not existSEATING

Does not existSITE WALLS (NOT RETAINING WALLS)

Does not existSTAIRS/RAMPS: EXTERIOR

Page 32 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)