protection and control ied manager pcm600 … · 1. description the protection and control ied...
TRANSCRIPT
Contents
1. Description...........................................................3
2. Tool variants.........................................................4
3. Connectivity packages.........................................4
4. Graphical application configuration.....................4
5. Signal matrix.........................................................5
6. Graphical display editor.......................................6
7. Hardware configuration........................................6
8. Parameter setting.................................................6
9. Signal monitoring.................................................7
10. Event viewer........................................................7
11. Disturbance handling..........................................7
12. Communication configuration.............................7
13. Project explorer...................................................7
14. User management...............................................8
15. Integrated help menus........................................8
16. Data transfer........................................................8
17. System requirements..........................................8
18. Selection table and ordering data.....................10
19. Document revision history.................................10
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumesno responsibility for any errors that may appear in this document.
© Copyright 2009 ABB Oy.
All rights reserved.
Trademarks
ABB is a registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.
Protection and Control IED Manager 1MRS756448 DPCM600Product version: 2.1 Issued: 06.07.2009
2 ABB
1. Description
The Protection and Control IED ManagerPCM600 tool provides versatile functionalities
for the entire life-cycle of all Relion®
protection and control IED applications, at allvoltage levels. This easy-to-handle tool helpsthe user to manage your protection andcontrol equipment all the way fromapplication and communication configurationto disturbance handling, including automaticdisturbance reporting.
Designed to communicate, PCM600 interactswith IEDs over the fast and reliable TCP/IPvia corporate LAN or WAN, or alternatively
directly through the communication port atthe front of the IED. PCM600 tool is able toread and write all configuration and settingdata of an IED with a single command.
The user interface, workflow and the IEC61850-based data model in PCM600 aredesigned according to the same philosophy
as the Relion® protection and control IEDs,ensuring smooth and seamless integrationbetween the tool and the IEDs.
PCM600 also secures the projects and datacreated with earlier versions of the PCM600tool, which enables full backwardscompatibility.
GUID-BC9474F6-E579-4326-99E8-433B8A3FEB99 V1 EN
Figure 1. PCM600 connected locally or remotely to IEDs
Protection and Control IED Manager 1MRS756448 DPCM600Product version: 2.1 Issued: 06.07.2009
Revision: D
ABB 3
2. Tool variants
PCM600 is available in three variants:PCM600, PCM600 Engineering and PCM600
Engineering Pro. PCM600 Engineering Proincludes PCM600 Engineering functionality,which again includes PCM600 functionality.
Table 1. Supported functions per tool variant
Function PCM600 PCM600Engineering
PCM600Engineering
Pro
Signal matrix ● ● ●
Parameter setting ● ● ●
Communication management ● ● ●
Disturbance handling ● ● ●
Signal monitoring ● ● ●
Event viewer ● ● ●
Creating/Handling projects ● ● ●
IED user management ● ● ●
Graphical display editor ● ● ●
Hardware configuration ● ● ●
User management ● ● ●
Graphical application configuration - ● ●
IEC 61850 communication configuration,incl. GOOSE
- - ●
3. Connectivitypackages
PCM600 incorporates ABB’s connectivitypackage concept, which simplifies protectionengineering and reduces the risk of errors.The Connectivity Packages, which aredownloadable from ABB’s web portal oravailable on CDs, make configurations andIED data readily available to the PCM600tool. The packages further contain acomprehensive description of the IED,
including data signals, parameters, protocoladdresses and IED documentation.
4. Graphical applicationconfiguration
The state-of-the-art graphical applicationconfiguration functionality offers powerfulways to create, adapt and modify applicationconfigurations, which also can be made astemplates for later re-use. PCM600alsoenables presentation of the whole signal flow
Protection and Control IED Manager 1MRS756448 DPCM600Product version: 2.1 Issued: 06.07.2009
4 ABB
from input to output. It also assists the userduring the creation of applicationconfiguration through colour indications ofthe function blocks to ensure that themandatory inputs have been correctlyconnected. Before writing the configurationto an IED, the tool offers validation of thecomplete IED configuration which ensuresthat the configuration does not contain errors.
Additionally, the user can compare theconfiguration in the tool to the one in theIED. Further, the signal status on-linemonitoring functionality helps to verify thereal-time processes in the IED, which isextremely useful for troubleshooting.
GUID-62510AC1-D402-425C-A00D-FD0B97138922 V1 EN
Figure 2. Application configuration, Onlinemonitoring
GUID-A565A681-95ED-4CEC-B721-DD119BEBE400 V1 EN
Figure 3. Application configuration, visualindication of the configuration
5. Signal matrix
The graphical signal matrix of PCM600 allowsthe user to efficiently connect CTs, VTs,binary input and output signals to theconfiguration. The configuration can also bechanged from here. The tool can also be usedfor connecting the LEDs on the IED as wellas for connection of the GOOSE signalsbetween the IEDs.
In addition to the standard functions ofPCM600, the Engineering Pro variant offersmeans to connect the GOOSE (GenericObject Oriented Substation Events) signalsbetween the IEDs. In a system based on IEC61850, GOOSE messaging is used for timecritical messages.
Once the IEDs have been configured andparameterized, PCM600 enables theconfiguration of the horizontal bay-to-baycommunication for station-wide interlocking,and sends the complete IED description to asystem engineering tool.
GUID-ADD28079-AE48-4C38-BA28-138FDEE21977 V1 EN
Figure 4. Signal matrix tool view
Protection and Control IED Manager 1MRS756448 DPCM600Product version: 2.1 Issued: 06.07.2009
ABB 5
6. Graphical displayeditor
The graphical display editor is used forconfiguring the display of an IED. Thegraphical display consists of one or morepages. A display page contains the drawingarea where the actual display configuration ismade. A display is configured by draggingpredefined graphical symbols from a libraryonto the drawing area. The directed link toolcan be used to draw connections betweensymbols. Every symbol type has acorresponding representation in both theANSI and the IEC symbol palettes. Symbolscan be connected to the applicationconfiguration.
GUID-3248B496-F627-44AD-9261-ABB812508CAA V1 EN
Figure 5. Graphical display editor,configuring the display of an IED
7. Hardwareconfiguration
The hardware configuration can be used toget a quick overview of an IED and to add orchange hardware modules. It is possible toview the front and back of the IED includingcard information and their slot position.Furthermore it is possible to compare thehardware configuration used in the tool tothe actual one in the IED.
8. Parameter setting
The parameter setting of PCM600 allows theuser to view and set IED parameters offline(stored in the tool) and online (stored inboth, tool and IED). The parameters can beread from the IED to PCM600 or written fromPCM600 to the IED while the IED is in service.
The parameter setting function can be usedin two different modes. The normal modeallows the IED protection engineer to quicklyview and change the most commonly usedparameters, whereas the advanced modeunveils all parameters that can be set.
PCM600 further offers a filtering functionallowing the user to view all IED parametersor the parameters related to a specificfunction block. In addition, the user canchoose to only view parameters that havebeen changed or parameters with valuesdeviating from the IED’s setting. Changedparameters with different values in the tooland in the IED are clearly indicated.
GUID-C054605B-7CC8-431C-A4F2-07797F7B5518 V1 EN
Figure 6. Parameter setting view
Protection and Control IED Manager 1MRS756448 DPCM600Product version: 2.1 Issued: 06.07.2009
6 ABB
9. Signal monitoring
The signal monitoring function provides theuser with online information about themeasured values and displays the status ofbinary input and output signals of an IED.Furthermore, PCM600 facilitatescommissioning and testing of physicalconnections via the signal monitoring tool(forcing of signals).
10. Event viewer
The event viewer of PCM600 enables the userto view the IEDs’ sequence of eventsinformation including timestamps. The eventlog facilitates detailed post-fault analyses offaults and disturbances.
11. Disturbance handling
PCM600 offers effective handling andmonitoring of disturbance records from theIEDs. The disturbance files stored in thestandard COMTRADE format allow the userto view the disturbance record usingWavewin™ software or any commerciallyavailable disturbance analyzer supporting theCOMTRADE format. If required, the reportlayout and contents can be adapted to user-specific needs.
By means of the task scheduler of PCM600,the records can be set to be automaticallyread from the IED. The task scheduler is anindependent process and does not requirePCM600 to be activated. After receiving thefile, PCM600 automatically creates adisturbance report, which can immediately beforwarded to subscribers by e-mail. Such anotification shortens the time fromdisturbance detection to corrective action.
12. Communicationconfiguration
PCM600 incorporates two communicationtools: the communication management tooland the communication configuration tool.
The communication management tool is usedto configure the following protocols for an
IED: DNP3, IEC 60870-5-103 or Modbus®.The communication configuration tool,available in PCM600 Engineering Pro, is usedfor configuring the IEC 61850 substationcontrol or inter-bay communication.
13. Project explorer
The project explorer can be used to navigateto the used IEDs within a project / substationand furthermore within an IED to navigate tothe different functionality of an IED. The useris able to create a plant structure with asubstation, voltage levels, bays and IEDs.
New IEDs can also be created by use of IEDtemplates. This enables the reuse of existingIED configurations. IEDs, bays, voltage levelsor a whole substation can be copied andpasted in the plant structure. Selection of aspecific IED in the project explorer givesaccess to the IED’s tools. The function ofimporting and exporting descriptions of IEC61850 substation configurations, configureddevices and device functionality allowsinformation to be shared with otherengineering and system integration tools. Byusing the filtering feature of the projectexplorer the user can filter information ofother tools according to the selection made.
Protection and Control IED Manager 1MRS756448 DPCM600Product version: 2.1 Issued: 06.07.2009
ABB 7
14. User management
PCPCM600 tool supports access managementboth for the tool and the IEDs. The useraccounts in PCM600 can be linked toWindows user accounts or be defined asseparate user accounts for PCM600. The usermanagement feature allows the administratorto create user groups with different accessrights and profiles.
The access management for the IEDs can beenabled or disabled with the IED usermanagement tool in PCM600. This tool is alsoused for setting and changing passwords forthe IED’s different user levels.
15. Integrated helpmenus
All the necessary instructions for using thetool are integrated in PCM600. Context
sensitive help menus and tool tips providethe user with information about the selectedtools. The IED documentation and guidesavailable from the connectivity package canbe directly accessed from the help menus.
16. Data transfer
PCM600 offers improved data transferbetween the IEDs and the IED managementtool. The IEDs can be accessed remotelyusing the TCP/IP protocol via a local areanetwork (LAN) and standard Ethernet cables,a secured wide area network (WAN), asecured wireless network (WLAN) or, locally,using the IEDs’ front communication port.
Protection and Control IED Manager 1MRS756448 DPCM600Product version: 2.1 Issued: 06.07.2009
8 ABB
17. System requirements
Table 2. Hardware requirements
Hardware Minimum Recommended
CPU 1.0 GHz 2.0 GHz
RAM 1 GB 3 GB
Free hard disk space 500 MB 5 GB
Monitor 1024 x 768 1280 x 1024
Ethernet port required required
Table 3. Supported operating systems
Operating system Version
Microsoft Windows 2000 SP4 or later
Microsoft XP Professional Edition SP2 or later
Microsoft Windows Server 2003
Microsoft Windows Server 2003 R2
Microsoft Windows Vista Business SP1
Table 4. Communication
Protocols
TCP/IP via LAN or WLAN
Serial Port (RS-232) or USB/RS-232 converter if SPA based communication is used
Opto/electrical (RS-232) cable for front communication if SPA based communication is used
Protection and Control IED Manager 1MRS756448 DPCM600Product version: 2.1 Issued: 06.07.2009
ABB 9
18. Selection table andordering data
The selection table can be used to choose theright tool variant for an IED – for the latest
supported IEDs please visit www.abb.com/substationautomation
To order PCM600, PCM600 Engineering orPCM600 Engineering Pro use the orderingdata in the ordering code table.
Sig
nal
mat
rix
Par
amet
er s
etti
ng
Com
munic
atio
n m
anag
emen
t
Dis
turb
ance
han
dli
ng
Sig
nal
monit
ori
ng
Even
t vie
wer
Cre
atin
g/H
andli
ng p
roje
cts
IED
use
r m
anag
emen
t
Gra
phic
al d
ispla
y e
dit
or
Har
dw
are
confi
gura
tion
Gra
phic
al a
ppli
cati
on c
onfi
gu
-
rati
on
IEC
61850 c
om
munic
atio
n
confi
gura
tion, in
cl. G
OO
SE
670 series ● ● ● ● ● ● ● ● ● ● ● ●
650 series ● ● ● ● ● ● ● ● ● ● ● ●
630 series ● ● ● ● ● ● ● ● ● ● ● ●
615 series ● ● ● ● ● - ● ● - - - ●
610 series - ● - ● ● - ● ● - - - -
RE_541/543/545 - ● - ● ● ● ● - - - - -
REF 542plus - ● - ● - - ● - - - - -
REX 521 - ● - ● ● ● ● - - - - -
SPACOM series 1) - ● - - ● - ● - - - - -
PCM600
PCM600 Engineering
PCM600 Engineering Pro
1) SPAD 346 C, SPAJ 140 C, SPAJ 141 C, SPAJ 142 C, SPAJ 144 C, SACO 16D1, SACO 16D3 and SACO 64D4GUID-7C235241-02C5-4F43-A0D4-F3F0D1812EEE V1 EN
Figure 7. Selection table
Table 5. Ordering codes
Product Order number
PCM600 2.1 PCM600-21
PCM600 Engineering 2.1 PCM600E-21
PCM600 Engineering 2.1 Company 1) PCM600E-21-C
PCM600 Engineering Pro 2.1 PCM600EP-21
PCM600 Engineering Pro Company 2) PCM600EP-21-C
1) Includes 10 PCM600 Engineering 2.1 licenses2) Includes 10 PCM600 Engineering Pro 2.1 licenses
Protection and Control IED Manager 1MRS756448 DPCM600Product version: 2.1 Issued: 06.07.2009
10 ABB
19. Document revision history
Document revision/date Product version History
A/20.12.2007 2.0 First release
B/30.05.2008 2.0 SP1 Content updated
C/03.03.2009 2.0 SP2 Content updated
D/06.07.2009 2.1 Content updated tocorrespond to the productversion
Protection and Control IED Manager 1MRS756448 DPCM600Product version: 2.1 Issued: 06.07.2009
ABB 11
Contact us
ABB OyDistribution AutomationP.O. Box 699FI-65101 VAASA, FinlandPhone +358 10 22 11Fax +358 10 22 41094
ABB ABSubstation Automation ProductsSE-721 59 Västerås, SwedenPhone +48 (0) 21 34 20 00Fax +48 (0) 21 14 69 18
www.abb.com/substationautomation
1MR
S75
6448
D©
Cop
yrig
ht 2
009
AB
B. A
ll rig
hts
rese
rved
.