protecting life, environment and property… 1 autroflame detectors id: aflame_x33_1_intro 09-2003
TRANSCRIPT
1
Protecting life, environment and property…
AutroFlameDetectors
AutroFlameDetectors
ID: AFLAME_X33_1_intro 09-2003
2
Protecting life, environment and property…
The New Flame Detectors FamilyThe New Flame Detectors Family
3
Protecting life, environment and property…
Massive Regulatory Changes Massive Regulatory Changes
• Factory Mutual 3260-2000
• DNV
• EN54 part-10
4
Protecting life, environment and property…
New Universal Features New Universal Features
• Dedicated Class I Div. I, EEx de wiring box
• Common housing for all technologies• More outputs options
– 2 Alarm relays– 1 Fault relay– 4-20 mA and relay– Modbus / RS485– Data logger– Addressable modules installed– Magnetic manual Oi activation switch
5
Protecting life, environment and property…
New Universal FeaturesNew Universal Features
• Temperature compensated heated optics– Heater will boost heat on cold startup and when the
detector temperature is below zero• Data event logger will record the detectors operating
temperature– Record of over-temperature events in turbine
enclosures
6
Protecting life, environment and property…
AutroFlame X33/1 Multispectrum IR
AutroFlame X33/1 Multispectrum IR
7
Protecting life, environment and property…
New CapabilitiesNew Capabilities
• Same extended performance as the X33• Configurable auxiliary relay • Form C alarm relay• PowerLoop direct connection
8
Protecting life, environment and property…
AutroFlame X33/1 & Q9033B MountAutroFlame X33/1 & Q9033B Mount
9
Protecting life, environment and property…
AutroFlame X33/1 Optical Integrity
AutroFlame X33/1 Optical Integrity
• New sensor and Oi ring orientation• Built in weather visor for improved water resistance• Optical integrity ring modified to keep water off the check surfaces
using a plastic metal bonded design• Optical integrity consecutive check time adjustable for improved
water and rain resistance
10
Protecting life, environment and property…
AutroSafe X33/1 Optical Integrity
AutroSafe X33/1 Optical Integrity
• Automatic optical integrity test monitors for both loss of, and increased sensitivity in each sensor
• Manual optical integrity test verified to perform a calibrated test of the detector and system
• Like a Genie, magnetic Oi, no test lamp required!
11
Protecting life, environment and property…
AutroFlame X52 Ultraviolet/Infrared Detector
AutroFlame X52 Ultraviolet/Infrared Detector
12
Protecting life, environment and property…
New CapabilitiesNew Capabilities
• New high speed capability- 30 ms• The best false alarm rejection for any UVIR detector• Heated optics
13
Protecting life, environment and property…
AutroFlame X98 Infrared Detector
AutroFlame X98 Infrared Detector
14
Protecting life, environment and property…
New CapabilitiesNew Capabilities
• Heated optics • Auxiliary relay
15
Protecting life, environment and property…
AutroFlame X22 Ultraviolet DetectorAutroFlame X22 Ultraviolet Detector
16
Protecting life, environment and property…
New CapabilitiesNew Capabilities
• Same high level signal processing • The best false alarm rejection for any UV detector• Heated optics
17
Protecting life, environment and property…
New Vibration Free MountNew Vibration Free Mount• Q9033B Mounting swivel with angle indicators
18
Protecting life, environment and property…
Weather Visor Flame PlatformWeather Visor Flame Platform
20
Protecting life, environment and property…
AutroFlame X33/1 Replacement Module
AutroFlame X33/1 Replacement Module
21
Protecting life, environment and property…
Protect•ir Laser Aimer Q1201CProtect•ir Laser Aimer Q1201C
22
Protecting life, environment and property…
Connection to AutroSafeConnection to AutroSafe
6 5
4
3
2
1
9
7
8
6
4
5
3
1
2
19
17
18
16
14
15
13
11
12
Com Fire
N.O. Fire
N.O. Fault
Com Fault2K
BN-300
X33/1 Detector
5861-011.4341 AutroFlame SS Exd w/built in BNB-3005861-011.4361 AutroFlame Alu Exd w/built in BNB-300
23
Protecting life, environment and property…
Typical Flame Detector Mounting
Typical Flame Detector Mounting
Conduit Seal Fitting
Minimum 10o down
mounting angle
24
Protecting life, environment and property…
Detector PositioningDetector Positioning
25
Protecting life, environment and property…
Flame Detector TestingFlame Detector Testing
• Only method to confirm system performance is an actual fire test
• Not practical or allowable at most jobsites
• Videotape recording common
• High-speed UV system response timer available
26
Protecting life, environment and property…
Flame Detector TestingFlame Detector Testing
• Complete system check-out with manual Oi is recommended (Calibrated System Check)
• Hand-held test lamp often required by customer• Test lamps do not confirm detection system
performance
27
Protecting life, environment and property…
New ApplicationsNew Applications
• Longer detection range requirements• New false alarm requirements• Class A fire materials• Nasty environments• Extreme cold environments