protect 3.m 15 – 120kva. protect 3.m the new generation of uninterruptible power supplies (ups)...
Post on 18-Dec-2015
216 views
TRANSCRIPT
PROTECT 3.M
15 – 120kVA
PROTECT 3.M
the new generation ofuninterruptible power supplies (UPS) with3-phase Mains input and 3-phase Mains output
PROTECT 3.M General data
PROTECT 3.M will be offered in two cubicle variances.
Variance 1:Cubicle dimensions: (W x H x D) 600mm x 1600mm x 1000mmMaximum 6 modules each 15kVA = 90kVA per cubicleVariance 2:Cubicle dimensions: (W x H x D) 600mm x 2000mm x 1000mmMaximum 8 modules each 15kVA = 120kVA per cubicle
15kVA per Modul (hot-swappable)Degree of redundancy selectable via DisplayEach Modul is independent , Controllcard/Display are just for Communication and Indication.Integrated Distribution with up to 36 breakers as an optionLCD DisplayCommunication via RS232, RS485, SNMP & AS400
PROTECT 3.M General data
1.6 m cubicleMB at the bottom
2.0 m cubicleMB at the top
PROTECT 3.M
High MTBF ability
Each UPS module in the Protect 3.M is the full function UPS. There is no additional controlling module to the parallel application and load sharing. Regarding to the serious calculation on the system MTBF, if you have two more UPS modules for parallel redundancy, the system ability is above 99.999% and the MTBF will be close to 15 Million Hours.
MTTR
Once the system has one more UPS module for parallel redundancy, the system will still keepworking if one of the UPS modules fails. If the failed modules exceed the parallel redundancy modules, the module replacement procedure only need 5 minutes for system recover.
PROTECT 3.M Battery
Battery
+/- 240Volt DC (20 bloc for each string)Integrated batteriecharger in each Module (2700W / 4.5A)
Battery Management in two stepsStep 1) up to 90% battery capacity constant currentStep 2) above 90% capacity constant voltage
PROTECT 3.M Technical data part I
Classification VFI SS 111 acc. to IEC 62040-3 Protect 3.M 1.6m rack Protect 3.M 2.0m rack
Type power 90 kVA 120kVA
72 kW 96 kW
max. modules per rack 6 8
UPS-input
Input voltage 400 / 230Vac (3/N/PE~)
Input voltage range without battery mode 277 - 520Vac(3ph~)
Frequency 50 Hz / 60Hz
Current consumption (max.) 120A with 6 modules 160A with 8 modules
Power factor > 0.99 at 100% Load
THD(i) <=5%
UPS-output
Rated output voltage 400V ± 2%
Frequency in battery mode 50 Hz ± 0.5%
Output current22 A / per module 132A with 6 modules
22 A / per module 176A with 8 modules
Transfer time at mains outage 0 ms ( zero transfer )
Voltage waveform Sinusoidal
Overload response (online mode) 130% for 10min / 150% for 1min
Crest factor 3
PROTECT 3.M Technical data part II
Battery
Nominal voltage
240VDC (40pcs for each set in series connection.One battery neutral wire from the central)
Autonomy time Free to choose runtime extension with scalable external battery.Available configurations with 24,38 or 65 Ah)
Overload / deep discharge protection Yes
Communication
Interfaces RS232 / RS485 for status and measurement values, Communication slot ( for pot.-free contacts or SNMP adapter)
Shutdown software (on CD) Included for all typical operating systems (e.g. MS-Windows,Novell Netware,Mac OS,Linux,Unix derivates, etc.)
Failure indicators (acoustic/optical) LCD with digital information of input and output parameters (voltage,frequency,power etc.) battery parameter incl. failure diagnosis by password protect level, LED for status and main failures.
PROTECT 3.M Technical data part III
General data
Efficiency total > 90%
Audible noise (1m distance) <62 dB
Operating temperature range 0º - 40 ºC
Humidity 20% - 90%
Installation height up to 1000m, at nominal load
Equipment colour RAL 7035
Size approx.W x H x D (mm) 600 x 1600 x 1000 600 x 2000 x 1000
Weight appr. (kg)
250kg rack +35kg per module
300kg rack + 35kg per module
Certification CE
PROTECT 3.M · Applications
Single - and multi-user systems
( Workstations, FileServer, Application Server, ... )
Network protection (client / server architecture)
e.g. intranet / internet application
EDP - equipment (CAD - systems, ...)
Communication equipment (IT - sector)
Component protection of telecommunication
Cash systems (trade)
Other user-critical applicationen
(process systems (stored-program contoller, ... ))
PROTECT 3.M · conceptual highlights
Modularity with UPS plug-in modules
in VFI (double-conversion) technology
n + x technology
free choice of redundancy level
scalable design for flexible
power- / autonomy time requirements
central simplified management
more efficient service
independent UPS - modules
(without any central control logic)
PROTECT 1.M · UPS classes
Publication by ZV
EI: U
PS
Guide
........... by additional lightning arrestors
Voltage Phenomenon Time e. g. IEC UPS solution 62040-3
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Outage - blackouts
Sags / brownouts
Dynamic overvoltage
Undervoltage
Overvoltage
Lightning
Transients (Surge)
Frequency variations
Voltage distortion (Burst)
Voltage harmonics
> 10 ms
continuous
continuous
sporadic
< 4 ms
sporadic
periodic
continuous
VFD
Voltage +FrequencyDependent
VIVoltage
Independent
VFI
Voltage +Frequency
Independent
Classification 3
Offline
Classification 2
LineInteractive
Classification 1
(true) Online
real Double-Conversion
Protect 3.M System architecture
Integrated Distribution with up to 36 breakers as an option
Communication module incl. communication port
LCD-Display
UPS-modules each 15kVA
PROTECT 3.M · UPS module design
Inverter
Battery system
Rectifier
Load
Mains
Electronicstatic bypass
~
~
Battery charger
~
PFC
Filter
Mains
filter
DSP / CanBus
control logic unit
RS232
SNMP
DC/DC Booster
High power reserves as a result of a max. 24 kVAtotal output
High safety reserves asa result of n+x technology
Independent UPS modules (no central control) slide-in types; suitable for rackmount
Diagram of an UPS PROTECT module :
PROTECT 3.M · n + x technology · redundancy level
n + x technology
advantage
n + x technology
advantage
Quantity of UPS modules 1 2 3 4 5 6 7 8
Load modul modules modules modules modules modules modules modules
15 kVA
noredundancy n + 1
(15 kVA)n + 2
(30 kVA)n + 3
(45 kVA)n + 4
(60 kVA)n + 5
(75 kVA)n + 6
(90 kVA)n + 7 (105 kVA)
30 kVA no
redundancyn + 1
(15 kVA)n + 2
(30 kVA)n + 3
(45 kVA)n + 4
(60 kVA)n + 5
(75 kVA)n + 6
(90 kVA)
45 kVA no
redundancyn + 1
(15 kVA)n + 2
(30 kVA)n + 3
(45 kVA)n + 4
(60 kVA)n + 5
(75 kVA)
60 kVA - - - no
redundancyn + 1
(15 kVA)n + 2
(30 kVA)n + 3
(45 kVA)n + 4
(60 kVA)
75 kVA - - - no
redundancyn + 1
(15 kVA)n + 2
(30 kVA)n + 3
(45 kVA)
90 kVA - - - no
redundancyn + 1
(15 kVA)n + 2
(30 kVA)
105 kVA - - - - - - - - -no
redundancyn + 1
(15 kVA)
120 kVA - - -no
redundancy
Higher reliability
Easy to increase overall capacity
Modules hot - swapable (without any interruption)
Protect 3.M Usage >> Delivery
Cubicle packing
Module packing
Protect 3.M - Mains connection
Mains Battery Load
PROTECT 3.M – LCD display
Appear „green light“
Appear „yellow light“
Appear „yellow light“
Appear „red light“and warning alarm
PROTECT 3.M Communication interface
“Dual monitoring“ interfacefrom left to the right:
- RS485- RS485- RS232- RS485
- Expansible
AS/400 card with potential-free contacts
SNMP / SNMP PRO card (with connector for additional temperature measurements)
PROTECT 3.M SNMP-Adapter
SNMP Slot-Adapter for UPS Features:
Agent for RFC1628 MIB UPS standard MIB
Embedded Web-Server Monitoring via Web
Configuration via Web
Embedded Event Manager Start of different Jobs
Net Broadcast
Monitoring of environmental conditions Temperature, Humidity, GenSet, Fire, Air
condition, Smoke shutter...
Support Software products Network Management Software „NMS“
NMS special for Power Supply Systems
Shutdown Software “CompuWatch”
Direct multi-server shutdown of different OS with communication modules
SNMP Adapter Pro: 6000001271SNMP Adapter: 6000004036
PROTECT 3.M AS/400 slotcard
Pin 1: UPS FaultBattery below cutoff voltage
Pin 2: Summary Alarm:UPS failure, Utility power failure, Battery low
Pin 3 and 4: Short from Pin 3 to 4 generates an UPS shutdown,e.g. by installing an external switch for EPO.
Pin 5: Common ground for relays (pins 1, 2, 6, 7, 8 und 9)Pin 6: Bypass active; mains operationPin 7: Battery low
Battery voltage is below the predetermined levelPin 8: UPS on; normal operation
(relay closed during normal operation)Pin 9: Utility Failure; battery operation
Attention ! Contact load rating: AC / DC 24 V / 0,5 A
Pin-assignment
Description
1 UPS Failure
2 Summary alarm (signal of pins 1, 7and 9)
3 Emergency shutdown, e.g. connection of an external switch for EPO (closer)
4
5 Common ground for pins 1, 2, 6, 7, 8 und 9
6 Bypass active
7 Battery low
8 UPS on
9 Utility Failure
UPS system: PROTECT 3.M
Graphical front-end of CompuWatch Normal operation
PROTECT 3.M